HomeMy WebLinkAboutFile Documents.210 W Main St.0056.2019 (49).ARBK■ Versatile combustion control systems ■ Made with Weil-McLain quality www.weil-mclain.com APPLICATIONS INCLUDE: Apartment Buildings Commercial Buildings Schools and Other Institutions Multiple Boilers Indirect-Fired Water Heating …And Much More COMMERCIAL GAS BOILER LGB COMMERCIAL GAS BOILER Series 2 | Gas | Water or Steam | MBH: 400-2,860 | Efficiency 85.1% Net Load Range: Hot Water 280-2,111 MBH / Steam 975-7,402 Sq. Ft. ™ ™BL-1 / BL-2 03/16/2019 Cast Iron Sections LGB™ sections are made of durable cast iron for long life. It’s not uncommon for Weil-McLain® cast iron boilers to last 35 years or more. Sections are not face ground; the tough outer skin is retained to protect against corrosion. The sections are studded with heat pins that cause the hot gases to swirl about, scrubbing the entire surface for greater heat transfer and maximum operating efficiency. Section Seal Modern elastomer sealing rings in the port openings assure a watertight seal. Because of the elasticity of the seals (unlike metal push nipples), they fill any gap caused by imperfections in the port openings, misalignment of sections, or expansion and contraction. Combined with short draw rods, sealing rings also permit faster section assembly. Lugs and sockets assure proper section alignment during assembly; the machined surfaces of the port openings control the compression ratio of the rings. Sealing Rope Sealing rope between the sections assures a permanent, gastight seal. When installed, the rope is visible between sections so the boiler can be checked for tightness. Sealing rope — a standard feature of Weil-McLain® commercial boilers — allows for expansion and contraction of the sections, is impervious to heat and moisture, will not crack and will last the life of the boiler. Rear Cleaning Removing the rear jacket panel and steel cleanout plates expose the flue passages for inspection and cleaning. Factory-Assembled Base and Burners The insulated, galvanized steel base houses the gas manifold and one-piece, high tempurature aluminized steel burners. These burners feature efficient performance, excellent flame characteristics, and quiet ignition and extinction. Burners provide fixed primary air — no adjustment required for approved gases. One burner/base assembly and one gas train are furnished for the LGB™-4 through 12, and two each for the LGB™-13 through 23. LGB™ DESIGN ADVANTAGES 2 03/16/2019 ■ 85.1% combustion efficiency saves energy. The LGB™ is the highest efficiency cast iron atmospheric gas boiler available. Exceeds efficiency requirements of ASHRAE 90.1. ■ Cast iron sections for corrosion resistance and long life. ■ Compact design saves valuable space…only 50⅜” high, allowing more headroom for piping and venting. ■ Patented section sealing method, short draw rods and sealing rope section speed assembly to reduce installation time. ■ Extra-large 9” top port opening forms an internal header for better water circulation. Large steaming area assures rapid generation of dry steam. ■ AGA design certified for natural and propoane gas. Ratings certified by Air-Conditioning, Heating and Refrigeration Institute (AHRI) for natural and propane gas. ■ Factory-assembled gas train located within the boiler jacket. (Except for all IRI boilers and LGB™-21 through 23 boilers with CSD-1/FM.) All LGB™-6 through 23 boilers (except for all IRI and LGB-21) are capable of low-high-low or staged firing with an additional operating limit control. ■ Factory-assembled base and burners reduce installation time. ■ Simplified piping. The largest LGB™ steam boiler requires only two risers. ■ Built-in air separator in water boilers. Air is diverted to the expansion tank through a 1” tapping next to supply outlet. ■ Steel jackets with durable powdercoat finish in Weil- McLain® blue…completely insulated…designed for fast installation. ■ 10 Year Limited Heat Exchanger Warranty. Covers cast iron sections. FEATURES…ADVANTAGES…BENEFITS 3 03/16/2019 PANEL FEATURES ■ Main flame failure lockout. ■ 4 indicator lamps: call for heat, pilot proven, main flame proven, and flame failure (8 lamps on WFFP™-2 panel). ■ Isolated alarm contact to indicate flame failure. ■ Power-on switch, fuse(s), and terminal strip. ■ Optional flame failure alarm bell. OPTIONAL WFFP™ CONTROL PANEL FOR STANDARD (AGA) AND CSD-1 SYSTEMS FOR LGB™ 6-23 LGB™ COMBUSTION CONTROL SYSTEM OPTIONS Manual Main Shutoff Valve —1 2 2 —1 2 1 1 1 Diaphragm Gas Valve w/Reg. & Pilot Takeoff 1 ———1 ————— Diaphragm Gas Valve —1 2 2 —1 2 ——— Diaphragm Gas Valve—2 Stage w/Regulator —1 2 2 —1 2 1 1 1 Motorized Gas Valve w/Actuator (On/Off)———————2 2 2 Low Gas Pressure Switch ———————1 1 1 High Gas Pressure Switch ———2 ———1 1 1 Normally Open Solenoid Vent Valve ————————1 1 Manual Leak Checking Gas Valve ————1 1 1 1 1 1 Leak Test Cock ————2 2 4 3 1 1 Pilot Shutoff Cock —1 2 2 1 1 2 2 1 2 Pilot Solenoid Valve —1 2 2 1 1 2 2 1 2 Pilot Regulator ————1 1 2 2 1 2 UCS Control Module 1 ————————— Flame Guardian® Control System —1 2 2 —————— CSD—1 Control Panel ————1 1 2 ——— WMBC™—1A Control Panel ————————1 — WMBC™—2A Control Panel ———————1 —1 For detailed information:Page 5 Page 6 Page 7 LG B ™ 4 - 5 AG A & F M De s c r i p t i o n of M a j o r Co m p o n e n t s LG B ™ 6 - 1 2 AG A & F M LG B ™ 13 - 2 0 AG A & F M LG B ™ 2 1 - 2 3 AG A LG B ™ 5 C S D - 1 LG B ™ 6 - 1 2 C S D - 1 LG B ™ 13 - 2 0 CS D - 1 LG B ™ 2 1 - 2 3 CS D - 1 & F M LG B ™ 5 - 1 2 I R I LG B ™ 13 - 2 3 I R I 4 03/16/2019 FACTORY-ASSEMBLED GAS TRAIN: The gas train allows for fast and easy installation. A slow- opening, soft ignition, high capacity, combination gas valve is used on the LGB™ 4-5 boilers. LOW-HIGH-LOW FIRING: LGB 6-23 boilers can provide low-high-low firing with the addition of a water temperature or steam pressure control. FACTORY-ASSEMBLED GAS TRAIN: The gas train allows for fast and easy installation. A dual gas valve train has an on/off diaphram valve and a low-high-low regulated gas valve. WFG FLAME GUARDIAN® CONTROL SYSTEM FEATURES: A pre-wired WFG® control system consisting of a mounting plate, two Weil-McLain® UCS control modules and terminal block are furnished as standard equipment with each base assembly. On a call for heat, the pilot proving control module provides a spark to ignite the pilot. When the pilot flame is proven, the first stage of the two-stage gas valve opens and all burners light on low fire. When the main flame sensor proves carryover, the second stage of the gas valve opens and the burners go to high fire. In the event the pilot or main flame is not proven during a timed trial for ignition, the WFG® control system will provide 100% shutoff. After a timed 5-minute delay, another ignition sequence will automatically be initiated. The control system provides multiple ignition trials. The control system design has been certified by AGA and all components are UL Listed. STANDARD (AGA) AND FM CONTROL SYSTEMS FOR LGB™ 4-5 STANDARD (AGA) CONTROL SYSTEMS FOR LGB™ 6-23 AND FM CONTROL SYSTEMS FOR LGB™ 6-20 STANDARD COMBUSTION CONTROL SYSTEMS UNIVERSAL CONTROL SYSTEM FEATURES: One Weil-McClain® UCS ignition control module and wire harness are furnished as standard equipment with each base assembly. On a call for heat, the UCS produces a spark to ignite the pilot. When the pilot flame is proven, the main gas valve opens with a built-in, slow opening soft ignition. In the event the pilot is not proven during a timed trial for ignition, the UCS control system will provide 100% shutoff. After a timed 5-minute delay, another ignition sequence will automatically be initiated. The control system has been certified by AGA and all components are UL Listed. 5 03/16/2019 CSD-1 SYSTEMS FOR LGB™ 5 ADDITIONAL COMBUSTION CONTROL SYSTEMS CONTROL SYSTEM FEATURES: A pre-wired control panel with one ignition control module, a manual reset relay with indicator light and a terminal block are furnished as standard equipment with each base assembly. On a call for heat, the control module produces a spark to ignite the pilot. When the pilot flame is proven, the combination gas valve opens with a built-in, slow opening soft ignition. Upon two consecutive pilot flame failures, the control module will trip the manual reset relay and illuminate the red lockout light. The lockout condition(s) should be corrected before pressing the red reset button to reset the boiler. The control system has been certified by AGA and all components are UL Listed. CSD-1 SYSTEMS FOR LGB™ 6-20 CONTROL SYSTEM FEATURES: A pre-wired control panel with one pilot-proving module, one main flame proving module, a manual reset relay with indicator light and a terminal block are furnished as standard equipment with each LGB™ 6-12 boiler. For LGB™ 13- 20, two pre-wired control panels are provided, one for each base. On a call for heat, the pilot-proving module, one main flame proving module, a manual reset relay with indicator light and a terminal block are furnished as standard equipment with each LGB™ 6-12 boilers. For LGB™ 13-20, two pre- wired control panels are provided, one for each base. Upon two consecutive pilot flame failures or on failure to sense main flame, the control module will trip the manual reset relay and illuminate the red lockout light. The lockout condition(s) should be corrected before pressing the red reset button to reset the boiler. For LGB™ 13-20, the control systems for each base will operate independently of each other. The control system has been certified by AGA and all components are UL Listed. 6 03/16/2019 CONTROL SYSTEM FEATURES: A pre-wired WMBC™ control panel is furnished as standard equipment. The gas train is located outside the boiler jacket. On a call for heat, the pilot control circuit produces a spark and opens the pilot solenoid allowing the pilot to ignite. For LGB™ 13-23, the universal ignition control then produces a spark to ignite the pilot on the second base. After the pilot(s) has been proven, the flame safeguard control energizes the main flame circuit allowing the main burners to ignite at low fire. The main pilot is then de-energized and the main flame sensor proves the main burner operation at low fire. For LGB™ 13-23, the pilot on the second base continues to burn during the boiler “on” cycle. The flame safeguard control then energizes the downstream gas valve allowing the boiler to fire at high fire. If the pilot or main flame are not proven during the start-up sequence, then the flame safeguard control will lock out on safety. A red indicator light and alarm bell will energize. The lockout condition should be corrected and then the red reset button should be pressed to restart the boiler. The control system will permit a normal start up after an automatic 5-minute delay. The control system has been certified by AGA and all components are UL Listed. CSD-1 AND FM CONTROL SYSTEMS FOR LGB™ 21-23 AND IRI CONTROL SYSTEMS FOR LGB™ 5-23 ■ Proven main flame with interrupted pilot for main base; pilot is extinguished after 10-second trial for ignition. For two-base boilers, the second base has an intermittent pilot; the pilot on second base continues to burn during boiler “on” cycle. ■ Pre-purge timer to provide 5-minute enforced wait after flame failure. ■ Flame failure alarm bell. ■ Five indicator lamps: power on, call for heat, pilot on, main flame on, and flame failure. ■ High-low fire control terminals. Low-high-low fire may be provided with a water temperature or steam pressure control. ■ Flame safeguard primary control. ■ Power-on switch, pilot-on switch, main-flame-on switch, alarm silencer switch, fuse and terminal strip. WMBC™ CONTROL PANEL FEATURES: 7 03/16/2019 PIPING CONNECTIONS WATER BOILERS PIPING NOTES: Alternative Piping-for LGB™-4 through 12 only: If desired, all three piping connections (supply, return and expansion tank) can be taken off same end of boiler. Supply and return sizes in table below for water boilers refer to minimum size of pipe connected to boiler for 20° or higher temperature drop between supply and return. Recommended Minimum Pipe Sizes (20° Rise Through Boiler) Boiler Model Pipe Size Supply and Return LGB™-4 2" LGB™-5 2½" LGB™-6 through 8 3" LGB™-9 through 16 4" LGB™-17 through 23 5" STEAM BOILERS Recommended Minimum Pipe Sizes For Single Risers Boiler Model Riser A Header H Equalizer J LGB™-4 through 8 4"4"2" LGB™-9 through 11 5"5"2½" LGB™-12 6"6"2½" Recommended Minimum Pipe Sizes For Dual Risers Boiler Model Riser A B Header H Equalizer J LGB™-13 through 15 4" 4"6"4" LGB™-16 through 19 5" 5"6"4" LGB™-20 through 23 6" 6"8"4" 8 03/16/2019 STANDARD, ADDITIONAL AND OPTIONAL EQUIPMENT STANDARD EQUIPMENT, ALL UNITS: ■ Cast iron sections ■ Insulated extended jacket ■ Aluminized steel collector hood(s) and draft hood(s) ■ Control transformer (120/24v) ■ Factory-assembled burner and base unit(s): – One-piece aluminized steel burners – Gas manifold – Aluminized steel base panels – Hi-temp insulated board ■ Wiring harness: junction box and pre-wired flexible conduit STANDARD EQUIPMENT, LGB™-6 thru 23: ■ Flame guardian® panel with flame rectification electronic control system for each base assembly: – Pre-wired control panel - Terminal block - Two ignition control modules having integral spark generators - Intermittent electronic ignition pilot system - Electronically supervised pilot burner with ignition electrode and flame rod - Main flame sensor rod STANDARD EQUIPMENT, WATER BOILERS: ■ Combination operating and high limit temperature control (LGB™-4 thu 20 only) ■ Operating temperature control (LGB™-21 thru 23 only) ■ High limit temperature control (LGB™-21 thru 23 only) ■ Combination pressure temperature gauge ■ 30 PSI ASME relief valve-side outlet ■ Built-in air eliminator in end sections ■ Probe-type low water cutoff, PS-851-120 (packaged only) STANDARD EQUIPMENT, STEAM BOILERS: ■ Operating pressure control ■ High limit pressure control ■ Compound presure-vacuum gauge ■ Gauge cocks, glass and guards ■ 15 PSI ASME relief valve-side outlet ■ Float-type low water cutoff, MM no. 61 LWCO STANDARD EQUIPMENT, LGB™-4 and 5: ■ Intermittent electronic ignition systems (UCS): – Intermittent ignition control module – Electronically supervised pilot burner with ignition electrode and flame rod – Wire Harness ADDITIONAL EQUIPMENT ■ WFFP™ control panels (LGB™-6 thru 23) ■ WMBC™ control panels (LGB™-5 thru 23) ■ Probe-type low water cutoff, ps-851-120 (non-packaged water only) ■ Factory-assembled sections (LGB™-4 thru 14 only) ■ Fire-tested packaged unit (LGB™-4 thru 14 only) ■ 1½" Inspection tappings with brass plugs — two for each section ■ 80 PSI working pressure test of sections ■ Water level controls and low water cutoffs ■ Low-high-low firing (LGB™-6 thru 12 only) ■ Stage firing (LGB™-13 thru 23 only) ■ Energy management control systems (BCP panels) ■ IRI, FM and CSD-1 control systems ■ Natural gas to propane gas conversion kit ■ W-M and PLUS indirect-fired water heaters ■ W-M Maxiflo® pool heaters ■ W-M brazed plate heat exchangers WFFP CONTROL PANEL EQUIPMENT STANDARD: ■ WFFP™-1 Panel (LGB™-6 Thru 12) ■ WFFP™-2 Panel (LGB™-13 Thru 23) – 30-second time delay relay (two on WFFP™-2) – Two 24-volt DPDT relays (four on WFFP™-2) – Terminal block – Fuse (two on WFFP™-2) – Toggle switch – Four Indicator lamps (eight on WFFP™-2) ADDITIONAL: ■ Alarm bell and transformer for remote indication of flame failure ■ Alarm bell – panel mounted WMBC™ CONTROL PANEL EQUIPMENT STANDARD: ■ WMBC™-1A panel (LGB™-5 thru 12) ■ WMBC™-2A panel (LGB™-13 thru 23) – Motorized gas train – Interruptible pilot (intermittent pilot for adjacent base and additional control module) – Pre-wired control panel: - Flame sefeguard primary control - Pre-purge control timer - Relay(s) - Terminal block - Fuse (two on WMBC™-2A) - Four toggle switches - Five indicator lamps - Alarm bell 9 03/16/2019 Left View Right View Front View LGB ™ DIMENSIONS Model Dimensions (inches)Draft Hood Outlet(s) Number & SizeABCW LGB™-4 18 9 —21 1-10" LGB™-5 23 11½—26 1-12" LGB™-6 28 14 —31 1-12" LGB™-7 33 16½—36 1-12" LGB™-8 38 19 —41 1-14" LGB™-9 43 21½—46 1-14" LGB™-10 48 24 —51 1-16" LGB™-11 53 26½—56 1-16" LGB™-12 58 29 —61 1-16" LGB™-13 63 16½30 66 2-12" LGB™-14 68 19 32½71 1-12"/ 1-14" LGB™-15 73 19 35 76 2-14" LGB™-16 78 21½37½81 2-14" LGB™-17 83 21½40 86 2-14" LGB™-18 88 24 42 91 1-14"/ 1-16" LGB™-19 93 24 45 96 2-16" LGB™-20 98 26½47½101 2-16" LGB™-21 103 26½60 106 2-16" LGB™-22 108 29 52½111 2-16" LGB™-23 113 29 55 116 2-16" (1) For LGB™ 4-23-return tapping size is 5" (qty. 2) and supply tapping size is 6" (qty. 2). (2) Gas trains on all IRI boilers and LGB™ 21-23 for CSD-1 & FM are located outside the boiler jacket. Allow additional clearances as required. Notes: 10 03/16/2019 Left View Right View (1) Rated pressure for LGB™ 21-23 CSD-1 & FM is 5.5" W.C. Notes: Boiler Model No. of Gas Trains Standard AGA No. of Gas Trains CSD-1 & FM No. of Gas Trains IRI 5" W.C.7" W.C 5" W.C.7" W.C 5.5" W.C.7" W.C. LGB™-4 1 1"——————— LGB™-5 1 1"1"1 1"1"1 1¼"1" LGB™-6 1 1¼"1"1 1¼"1"1 1¼"1" LGB™-7 1 1¼"1"1 1¼"1"1 1¼"1" LGB™-8 1 1¼"1"1 1¼"1"1 1½"1¼" LGB™-9 1 1¼"1"1 1¼"1"1 2"1¼" LGB™-10 1 1½"1¼"1 1½"1¼"1 2"1¼" LGB™-11 1 2"1¼"1 2"1¼"1 2"1½" LGB™-12 1 2"1¼"1 2"1¼"1 2"1½" LGB™-13 2 1¼"1"2 1¼"1"1 2"1½" LGB™-14 2 1¼"1"2 1¼"1"1 2"1½" LGB™-15 2 1¼"1"2 1¼"1"1 2"1½" LGB™-16 2 1¼"1"2 1¼"1"1 2"1½" LGB™-17 2 1¼"1"2 1¼"1"1 2"1½" LGB™-18 2 1½"/ 1¼"1¼"/ 1"2 1½"/ 1¼"1¼"/ 1"1 2½"1½" LGB™-19 2 1½"1¼"2 1½"1¼"1 2½"2" LGB™-20 2 1½"/ 2"1¼"2 1½"/ 2"2"1 2½"2" LGB™-21 2 2"1¼"1 3"2"1 3"2" LGB™-22 2 2"1¼"1 3"2"1 3"2" LGB™-23 2 2"1¼"1 3"2"1 3"2" CONTROL TAPPING TABLE (1) Available on special request only. (2) Must be on same side as supply to system. Notes: Location Size Steam Water (4)Left End Right End C1 C2 1¼"Boiler Drain Boiler Drain D1 & D2 D3 & D4 ½"Gauge Glass (3)— E1 & E2 E3 & E4 1"Low Water Cutoff (3)Optional Low Water Cutoff E1 E3 1"Pressure Operating & Limit Controls & Pressure Gauge Limit Control (2) F1 F2 1"—To Expansion Tank or Automatic Air Vent (2) G1 G2 3/4"—Operating Control (2) H1 & H2 (1)H3 & H4 (1)⅜"Tri-cock — J1 J2 2"Steam Relief Valve & Skim Tapping Water Relief Valve and Skim Tapping K1 K2 ½"—Combination Pressure & Temperature Gauge (2) M1 & M2 M3 & M4 1"Optional Low Water Cutoff (3)Optional Low Water Cutoff M1 M3 1"Firing Rate Control (when used)Firing Rate Control (when used) or Probe Low Water Cutoff (3) Must be on same side as steam equalizer piping. (4) Additional controls for water boilers may be placed in supply piping. 11 03/16/2019 RATINGS — STEAM Boiler Model Number (1) Heating Medium Input MBH (2) AHRI Certified Ratings (3) Boiler N.P.Sq. Ft. Steam Boiler Water Content Gallons Approx. Shipping Weight Lbs. Assembled Block Weight Complete Packaged Boiler Weight Chimney Breeching Size (I.D) (inches) (5) Gross Output MBH (2) Net Rating Steam MBH (2)Steam (to waterline)Water(gallons)Models PLGB (4) LGB-4-S Steam 400 312 234 9.7 975 23.2 36.5 1185 975 1600 10 LGB-5-S Steam 520 409 307 12.6 1279 28.9 45.6 1455 1200 1800 12 LGB-6-S Steam 650 514 386 15.7 1607 34.6 54.7 1725 1425 2000 12 LGB-7-S Steam 780 619 464 18.9 1936 40.3 63.9 2005 1650 2300 12 LGB-8-S Steam 910 724 543 22.0 2264 46.0 73.0 2290 1900 2500 14 LGB-9-S Steam 1040 829 622 25.2 2591 51.9 82.1 2560 2125 2800 14 LGB-10-S Steam 1170 934 701 28.3 2918 57.6 91.2 2800 2375 3100 16 LGB-11-S Steam 1300 1039 779 31.5 3246 63.4 100.4 3105 2600 3300 16 LGB-12-S Steam 1430 1144 858 34.6 3576 69.1 109.5 3365 2850 3500 16 LGB-13-S Steam 1560 1239 929 37.8 3868 74.9 118.6 3785 3100 4100 16 LGB-14-S Steam 1690 1344 1015 40.9 4228 80.7 127.7 4085 3330 4300 16 LGB-15-S Steam 1820 1449 1102 44.0 4592 86.4 136.9 4355 ——16 LGB-16-S Steam 1950 1552 1188 47.2 4950 92.2 146.0 4725 ——17 LGB-17-S Steam 2080 1658 1276 50.3 5316 98.0 155.1 4975 ——17 LGB-18-S Steam 2210 1764 1364 53.5 5682 103.6 164.2 5270 ——18 LGB-19-S Steam 2340 1867 1448 56.6 6034 109.5 173.4 5540 ——18 LGB-20-S Steam 2470 1974 1533 59.8 6384 115.3 182.5 5820 ——19 LGB-21-S Steam 2600 2077 1613 62.9 6720 121.0 191.6 6080 ——19 LGB-22-S Steam 2730 2184 1696 66.1 7065 126.8 201.2 6365 ——19 LGB-23-S Steam 2860 2288 1776 69.2 7402 132.5 209.8 6625 ——20 (1) Add to boiler number “S" for Steam, “W" for Water. (2) MBH = thousands of BTU/hour. (3) Net AHRI ratings are based on net installed radiation of sufficient quantity for building requirements. Do not add on for normal piping and pickup. Water boilers are rated at 80 psig maximum working pressure. Water ratings are based on piping and pickup allowance of 1.15. Additional allowance should be made for gravity hot water systems or unusual piping and pickup loads. Ratings shown are for elevations up to 2,000 feet. For ratings above 2,000 feet, reduce at rate of 4 percent per 1000 feet above sea level. (4) Sling length is 5 feet; 2 per boiler. (5) A twenty-foot (20') chimney height may be used in most cases, based on using a six-foot (6') length of connector for breeching of the size shown from the nearest draft hood outlet to the chimney or vent with not more than one (1) standard sloping-type 90° elbow. Consult the National Fuel Gas Code, ANSI Z223.1, for actual sizing. If individual vertical vents are to be used, each vent diameter should be the same size as the respective draft hood outlet and the height may be reduced to five feet (5') measured above the draft hood outlet. Notes: RATINGS — WATER Boiler Model Number (1) Heating Medium Input MBH (2) AHRI Certified Ratings (3) Boiler H.P. Boiler Water Content Gallons Approx. Shipping Weight Lbs. Assembled Block Weight Complete Packaged Boiler Weight Chimney Breeching Size (I.D.) Inches (5) Gross Output MBH (2) Net Rating Water MBH (2)Models PLGB (4) LGB-4-W Water 400 322 280 9.7 36.5 1185 975 1600 10 LGB-5-W Water 520 419 364 12.6 45.6 1455 1200 1800 12 LGB-6-W Water 650 523 455 15.7 54.7 1725 1425 2000 12 LGB-7-W Water 780 628 546 18.9 63.9 2005 1650 2300 12 LGB-8-W Water 910 737 641 22.0 73.0 2290 1900 2500 14 LGB-9-W Water 1040 843 733 25.2 82.1 2560 2125 2800 14 LGB-10-W Water 1170 950 826 28.3 91.2 2800 2375 3100 16 LGB-11-W Water 1300 1057 919 31.5 100.4 3105 2600 3300 16 LGB-12-W Water 1430 1165 1013 34.6 109.5 3365 2850 3500 16 LGB-13-W Water 1560 1273 1107 37.8 118.6 3785 3100 4100 16 LGB-14-W Water 1690 1381 1201 40.9 127.7 4085 3330 4300 16 LGB-15-W Water 1820 1489 1295 44.0 136.9 4355 ——16 LGB-16-W Water 1950 1597 1389 47.2 146.0 4725 ——17 LGB-17-W Water 2080 1708 1485 50.3 155.1 4975 ——17 LGB-18-W Water 2210 1817 1580 53.5 164.2 5270 ——18 LGB-19-W Water 2340 1926 1675 56.6 173.4 5540 ——18 LGB-20-W Water 2470 2035 1770 59.8 182.5 5820 ——19 LGB-21-W Water 2600 2207 1919 62.9 191.6 6080 ——19 LGB-22-W Water 2730 2318 2016 66.1 201.2 6365 ——19 LGB-23-W Water 2860 2428 2111 69.2 209.8 6625 ——20 WM1512_BRO_027 LGB 12 03/16/2019 RUNTAL BASEBOARD/OUTPUT OUTPUTS* CONTRACTOR SERIES In Stock:Take your order “To Go” Easy to Buy:Tell your wholesaler you want Runtal Baseboard or Wallpanels (they’re white): The other 9 standard colors take 2 weeks to manufacture. In Baseboard choose a height (6”, 9”, 12”) and a length (2’-14’). In Wallpanels choose a height (18”, 24”) in a 2’, 3’ or 4’ lengths. It’s that easy, and you can now take it with you! Easy to Install:Uniform fittings allow each radiator to be piped eight different ways. Continuous Mounting eliminates the need for backing. Simply wall mount (hardware included). All pipe fittings are 1/2” NPT with 1/8” NPT Vent Fittings (Manual Vent Included!). Standard Pipe Covers are also in stock. Easy to Sell:Whether it’s a one radiator renovation, or a whole house, using Runtal will impress your customer.Runtal is attractive, durable, healthy, and comfortable. Runtal may be used as a direct replacement for fin-tube or cast iron baseboard (see tips on installation), or it may be used with water temperatures as low as 140° F, (making it a perfect radiant alternative or complement to floor heating). Runtal Radiators carry a 5-year warranty. Runtal North America, Inc.PO Box 8278 187 Neck Road Ward Hill, MA 01835 TEL: 978-373-1666 FAX: 978-372-7140 WEBSITE: www.runtalnorthamerica.com Warmth by Design *Outputs shown are based on 180°F AWT at 70°F room temperature. Outputs at 140° are 350, 450, 550, 850 and 1050 Btu’s/Ft on UF-2, UF-3, UF-4, UF-6 and UF-8 respectively. For outputs at various temperatures, see the complete Runtal catalog. Length (Ft) UF-6 1430 BTUH/Ft* UF-4 930 BTUH/Ft* Contractor’s Baseboard and Wallpanel Series from Runtal! RADIATORS R 18” UF-3 770 BTUH/Ft* 9” UF-2 600 BTUH/Ft* 6” 12” UF-8 1810 BTUH/Ft* 24” 2 1,200 1,540 1,860 2,860 3,620 2.5 1,500 1,925 2,325 3 1,800 2,310 2,790 4,290 5,430 3.5 2,100 2,695 3,255 4 2,400 3,080 3,720 5,720 7,240 5 3,000 3,850 4,650 6 3,600 4,620 5,580 7 4,200 5,390 6,510 8 4,800 6,160 7,440 9 5,400 6,930 8,370 10 6,000 7,700 9,300 11 6,600 8,470 10,230 12 7,200 9,240 11,160 13 7,800 10,010 12,090 14 8,400 10,780 13,020 BB-1 03/16/2019 Vertical Covers CONTRACTOR SERIES Installation Tips for Runtal Baseboard/Wallpanels Roughing In: The rough in dimensions are the same for all 5 heights. Tips:Always plan to pipe directly into the radiator. “U” shapes should be avoided. Always check your piping scheme in advance to be sure of clearance from joists, etc. Piping: Each radiator may be piped eight different ways. This should allow for the most efficient and most attractive installation. Trim Covers: There are 2 types of standard trim covers: Vertical Covers and Horizontal Covers. Please refer to Runtal’s “Radiator Trim Sheet” for complete information. System: Runtal will work well in both High and Low temperature closed loop systems. Tips:Use all of the K-12 brackets provided with each radiator. Place 1 bracket 6” in from each end, and equally space the rest. Mount bracket on studs whenever possible (use appropriate method for non-stud mounting). Mount radiators 3” from the floor for optimum efficiency, ease of vacuuming, and proper trim cover fit. However a minimum of 1” between radiator and finished floor is permissible. Be sure to install leveling bolt (K-45) prior to piping radiator. Tips:Piping should be kept to a minimum and should be planned to match the standard trims. Always install the air vent (included) opposite the supply side of the radiator. Be sure to properly seal the flush plugs (included) in the unused fittings (3/8” and 3/16” hex wrenches required). Be sure to leave room for piping inside corners. You will need two to three inches plus working room, minimum. Tips:Horizontal trims require a minimum of 2” overlap on the radiator for proper fit. It may be easier to purchase trims after the radiators are installed, but care should be taken to ensure that all piping has been done with stan- dard trim configurations in mind. If you are unable to use standard trims on an installation, please call for custom trim options. Tips: Always test the system with air at a maximum pressure of 50 PSI prior to wet testing. Runtal baseboard may be used with fin-tube, but the fin-tube will perform better if the Runtal is at the end of the loop. Runtal is compatible with cast iron baseboard and cast iron radiators. In series installation: an individual loop should not exceed 30,000 Btuh or 7 radiators. Vertical Covers: These come standard in 3” and 10” heights and are designed to cover straight vertical pipe between the radiator and the floor. They can be easily field cut for heights other than 3” and 10”. Horizontal Covers: Standard trims simply snap into place. Straight Trims (used as End Trims & Center Trims) are 12” long. Inside Corners are 12” x 12” and End Cap Trims are either 6” x 2” (right hand) or 2” x 6” (left hand). Outside Corner Trims and other special trims are readily available on request. Mounting: The mounting system is identical on all 5 heights. Roughin-(L-2") UF-2 (1/8 NPT)(1/8 NPT) Height 5-3/4" 2 x (1/2" NPT)1" 3/4" 1" 2"1 5/8" Length-(L) 2 x (1/2"NPT) K-12 K-45 Horizontal Covers 03/16/2019 Wh i s p e r C o m f o r t ™ V e n t i l a t i o n F a n s ■ Spot balanced ventilation ■ Low-rate continuous run ideal for multi-family dwellings ■ Ideal for new air tight homes built to meet energy effi ciency standards ■ UL listed for ceiling or wall mount installation ■ Exchange capillary core recovers heat, energy and moisture ■ Balances air pressure inside the house Panasonic WhisperComfort Spot Energy Recovery Ventilator (ERV) offers a revolutionary way to provide balanced ventilation. Affordable and easy to install, WhisperComfort is energy effi cient and provides fresh ventilated air while maintaining Indoor Air Quality (IAQ). FV-04VE1 Two 4" Ducts HRV-1 03/16/2019 whole building ERV that requires connecting to the Central HVAC System. Ideal for: Home Office / Game Rooms / Family Rooms / Bonus Rooms This is an affordable way to add ERV to a specific room or a new addition. Whole House ERV WhisperComfort is also suitable to meet whole house ventilation requirements under ASHRAE 62.2. WhisperComfort is an ideal choice when partnered with mini-splits or VRF Heat Pumps for fresh, balanced air with energy recovery which makes it a very affordable, cost-effective IAQ solution. The sizing charts on the next page provide a guideline for number of bedrooms and square feet. Additionally, two or even three WhisperComfort ERV’s may be installed, often at a cost lower than a traditional whole house ERV. Ideal for: Condominiums / Apartments / Housing Authority properties / Hotels / Studio apartments ASHRAE 62.2 2010 Standard The American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE) set a standard for whole house ventilation, requiring that continuous mechanical ventilation be 7.5 CFM per bedroom (master bedroom X 2) plus 1 CFM per 100 square feet, with sone not to exceed 1.0. ASHRAE 62.2-2013 requires a ventilation rate of 7.5 CFM per person plus 3 CFM per 100 square feet. Please check with your local code to determine which ventilation standard you should follow. Panasonic WhisperComfort ERV is an affordable, efficient way to meet the ASHRAE 62.2 standard. FEATURES Balanced Ventilation Tightly built homes and buildings utilizing exhaust only fans can create negative pressure. WhisperComfort solves this by supplying air to replace exhausted air, helping to balance air pressure within the home. Panasonic WhisperComfort Spot ERV uses two 4 inch ducts – one to exhaust stale air and the other to supply fresh air from outdoors. Its low, continuous run ensures volatile organic compounds (VOC’s) are vented out and replaced with fresh air. WhisperComfort does not require connection to the Central HVAC or the addition of a condensation line. This 'Spot' ERV feature allows it to be installed in many places throughout the home to meet comfort, health and IAQ needs. Exchange Capillary Core Indoor and outdoor air passes through Panasonic’s patented capillary core technology designed to transfer heat energy and moisture. This process tempers supply air while transferring moisture. Motor Technology Panasonic uses a single AC condenser motor to run two highly efficient blower wheels. The motor is totally enclosed to ensure long-life and continuous quiet operation. Filters Two filters clean exhaust and supply air before passing through the ERV core, extending the life of the core. Grille Design The contemporary, low profile grille design incorporates spring clips for easy removal. Spot ERV WhisperComfort is a ceiling or wall-mount Energy Recovery Ventilator (ERV) that is ideal for a single large, open space room or for multistory homes' hallways. Two or even three WhisperComfort ERV's may be installed, often at a cost lower than a traditional Tight Home Air Pressure Without ERV With Spot ERV Spot ERV Technology OUTSIDECool Cool INSIDE WarmWarmHeat & Moisture Tr ansfer 03/16/2019 Frost Prevention Mode WhisperComfort incorporates built-in frost prevention technology to avoid core freeze up. • Above 32ºF both exhaust and supply are fully functional • From 32ºF to 20ºF the mechanical damper on the supply air closes for 30 minutes, then opens 1 hour at the set high/ low mode. The cycle repeats itself to avoid core freeze up. (Exhaust only 30 minutes per 90-minute cycle) • Below 20ºF the mechanical damper on the supply air remains closed for 1 hour and opens 10 minutes at low mode. After 10 minutes the cycle will repeat or change if the temperature has risen above 20ºF. (Exhaust only 60 minutes per 80-minute cycle) Settings WhisperComfort has two 2-speed CFM settings High Low __________________________________________________ Setting 1. 20 CFM 10 CFM Setting 2. 40 CFM 20 CFM factory preset The factory setting is 40/20 CFM. To change to optional 20/10 CFM setting, move the plug connector located in the junction box to the 20 CFM side of receptacle. This step must be completed prior to installation. Switches WhisperComfort operates in an on/off and high/low mode. When the switch is turned off, the unit does not operate. When the switch is turned on, the unit will operate at the high or low mode. A duplex switch, designed for a single gang box, may be selected for switch operation. Switch labels are provided for convenience to attach to the selected switches. Panasonic offers the FV-WCSW21-W/A(White/Almond) 2 function switch as part of the WhisperControl product line. This commercial grade on/off multiswitch can be used with the ERV, includes a designer wall plate and carries a 2-year limited warranty. This switch is sold separately. 32ºF Open 1 hr. Close 30 m. Open 1 hr. Open 10 m. 40 C F M 20 C F M Close 1 hr. Open 10 m. 19ºF -13ºF Balanced Ventilation With Spot ERV WINTER SUMMER Outside Inside OPERATION ON OFF HI LO Switch sold separately. 03/16/2019 Filters WhisperComfort has two air fi lters. One fi lter is located on the inside louver of the grille. The second fi lter is located in the unit held by a bracket with a handle. Pull the handle to remove the fi lter bracket and remove the fi lter from the bracket. Both fi lters should be vacuumed with a soft brush attachment. • Rust-proof paint treatment on galvanized housing • Thermal fuse protection • Meets Washington State Ventilation and Indoor Air Quality code and ASHRAE 62.2 - 2010 • 3 Year Warranty PRODUCT Exchange Capillary Core Supply Air Filter Exhaust Air Filter N/A=not applicable w.g.=water gauge S.P.=static pressure Specifications FV-04VE1 40 CFM 20 CFM 10 CFM Characteristics Static pressure in inches w. g. 0.1 0.1 0.1 Air Volume Exhaust (CFM) 40 20 10 Air Volume Supply (CFM) 30 20 10 Noise (sones) 0.8 <0.3 N/A Power Consumption (Watts) 23 21 17 Speed 1479 1292 1095 Current 0.15 0.10 0.09 Power Rating (V/Hz)120/60 Specifications Motor Type Condenser Type of Motor Bearing Ball Thermal Fuse Protection Yes Blower Wheel Type 2 x Sirocco Apparent Sensible Effectiveness Heating (%) 32 °F (0°C)66% at 30 CFM Total Recovery Efficiency Cooling (%) 95 °F (35°C)36% at 29 CFM Note: CFM and sones are tested and certifi ed in accordance with HVI testing standards. Energy effi ciency is tested in accordance with CSA-C439 standard. 22-1/2 i n . 5 in . 10-3/4 i n . 3-3/8 i n . 5-9/16 i n . 8-5/8 in. 8-1/2 in. 4-1/2 in. 20-3/4” 16-3/4” 18-1/2” 13-1/2” 7-7/8” 13-1/2” to 16” 22-1/8” 4” 4” 6-5/8” 13-1/2” to 16” 2 x 4" ducts FV-04VE1 Optional Exterior Wall Cap Optional Elbow FV-WC04VE1 FV-EB04VE1 0.00 0.10 0.20 0.30 0.40 0.50 0102030405060 Airflow(CFM) 20 Feet 40 Feet 60 Feet 80 Feet 100 Feet FV-04VE1(Exhaust) FV-04VE1(Supply) FV-04VE1 40/20 CFM or 20/10 CFM Two 4" ducts VF16013SSDesign and specifi cations subject to change without notice. Panasonic Eco Solutions of North America Eco Products Division Two Riverfront Plaza Newark, NJ 07102 us.panasonic.com/ventfans For Order Information PHONE: 866-292-7299 FAX: 888-553-0723 ventfans@us.panasonic.com03/16/2019 ER V JANUARY 2019 RENEWAIRE.COM | 800.627.4499 EV450 & HE SERIES COMMERCIAL ERV CATALOG HRV-2 03/16/2019 RENEWAIRE.COM 1.800.627.4499 4 EV - S E R I E S 7/ 8 " P o w e r I n 7/ 8 " C o n t r o l I n 10 " Ro u n d T y p . (O p t i o n a l 45 E V T 1 0 Tr a n s i t i o n Ki t S h o w n ) 25 1/4" 11 1/4" 5 1 / 4 " T y p . Di s c o n n e c t Sw i t c h 5 1 / 8 " T y p . 54 1 / 2 " O v e r a l l (w i t h R o u n d T r a n s i t i o n s ) CL 2 1 / 4 " C o n t r o l I n CL 14 1 / 4 " P o w e r I n EA OA FA RA Pr e s s u r e Po r t s ( 4 ) T y p . (2 ) 7/ 8 " H o l e s fo r W i r i n g i n Bo t t o m o f E - B o x 33 7/8" Case 15 7 / 8 " Ca s e 16 3 / 8 " Ov e r a l l 6 3 / 8 " 10 1/8" 26 1/4" 1 1 / 2 " T y p . 4 4 1 / 8 " C a s e 47 1 / 8 " O v e r a l l (w i t h F l a n g e s ) 14 1/4" Minimum Service Area (Doors can be Removed from Hinges) 44 1 / 2 " M i n i m u m Se r v i c e A r e a 24 3/4" TO P V I E W Do o r Sw i n g Do o r Sw i n g 4 1/4" Typ. 20 1/4" Typ. 7/ 8 " Ty p . CL 2 5 / 8 " Co n t r o l I n CL 4 1 / 8 " Po w e r I n 12 " X 8 " T y p . Du c t F l a n g e (O p t i o n a l 45 E V D F Ki t S h o w n ) 2 1 / 8 " Ty p . 36 3/8" Overall RI G H T V I E W FR O N T V I E W LE F T V I E W Mo d e l : E V 4 5 0 I N Dr a w i n g T y p e : U n i t D i m e n s i o n Ve r s i o n : M A Y 1 7 AB B R E V I A T I O N S EA : E x h a u s t A i r t o o u t s i d e OA : O u t s i d e A i r i n t a k e RA : R o o m A i r t o b e e x h a u s t e d FA : F r e s h A i r t o i n s i d e IN S T A L L A T I O N O R I E N T A T I O N Un i t m a y b e i n s t a l l e d i n a n y o r i e n t a t i o n . NO T E 1. U N L E S S O T H E R W I S E S P E C I F I E D , DI M E N S I O N S A R E R O U N D E D T O T H E NE A R E S T E I G H T H O F A N I N C H . 2. S P E C I F I C A T I O N S M A Y B E S U B J E C T TO C H A N G E W I T H O U T N O T I C E . EV 4 5 0 IN En e r g y R e c o v e r y V e n t i l a t o r St a n d a r d o r E C M o t o r O p t i o n AI R F L O W C O N F I G U R A T I O N Av a i l a b l e a s s h o w n i n d i m e n s i o n d r a w i n g . UN I T M O U N T I N G & A P P L I C A T I O N Ca n b e m o u n t e d i n a n y o r i e n t a t i o n . R A / E A a i r s t r e a m ca n b e s w i t c h e d w i t h O A / F A a i r s t r e a m . EV 4 5 0 IN En e r g y R e c o v e r y V e n t i l a t o r St a n d a r d SPECIFICATIONS & DIMENSIONS Specifi cations may be subject to change without notice. INDOOR UNIT SPECIFICATIONS Ventilation Type: Static plate, heat and humidity transfer Typical Airfl ow Range: 200-540 CFM AHRI 1060 Certifi ed Core: One L85-G5 Standard Features: Non-fused disconnect 24 VAC transformer/relay package Cross-core differential pressure ports Filters: Total qty. 2, MERV 8: 14" x 20" x 2" Unit Dimensions & Weight: 54 1/2" L x 16 3/8" W x 36 3/4" H 137-199 lbs., varies by option(s) Max. Shipping Dimensions & Weight (on pallet): 62" L x 42" W x 22" H 250 lbs. Motor(s), choice of: Qty. 1, 0.6 HP (standard single phase) Qty. 1, 0.5 HP (standard three phase) Options: Qty. 1, Variable Speed/ECM - Direct Drive Motors (see EV450IN EC Motor submittal) - 0.5 HP, 120V/1Ph/60HZ, 0.5 HP, 208-230V/1Ph/60HZ Fused disconnect Integrated programmable controls - enhanced, premium Qty. 2, Factory mounted fi lter alarms - both airstreams Double wall construction Exterior paint - white, custom colors Accessories: Filters - MERV 13, 2" (shipped loose) Backdraft damper 10" Wall cap 10" - galvanized, paintable galvanneal Vibration isolation kit Hanging bracket kit Transition kit 10" - round, qty. 2 Flange kit - rectangular 12" x 8", 2 fl anges Solid state speed control kit - 115V, qty. 1, 208-230V, qty. 1 Digital time clock - wall mount (TC7D-W), in exterior enclosure (TC7D-E) Carbon dioxide sensor/control - wall mount (CO2-W), duct mount (CO2-D) IAQ sensor - wall mount (IAQ-W), duct mount (IAQ-D) Motion occupancy sensor/control - ceiling mount (MC-C), wall mount (MC-W) Smoke detector - duct mount (SD-D) Louver with 10" round duct connection - 12" (W) x 12" (H) Electric duct heater - RH series (1-11.5 kW); EK series (1–175 kW); designed for indoor ductwork installation only HP Volts HZ Phase FLA Min. Cir. Amps Max. Overcurrent Protection Device 0.6 120 60 Single 7.2 9.0 15 0.6 208-230 60 Single 3.9-3.6 4.9 15 0.6 277 60 Single 3.5 4.4 15 0.5 208-230 60 Three 1.7-1.5 2.1 15 0.5 460 60 Three 0.8 1.0 15 UNIT PERFORMANCE Airfl ow CFM ESP in H20 Watts 1P 3P 225 1.25 335 181 375 0.89 464 333 420 0.75 518 394 480 0.50 584 472 500 0.43 600 491 540 0.25 640 540 575 0.00 690 610 ELECTRICAL DATA Note: Watts is for the entire unit. Note: Airfl ow performance includes effect of clean, standard fi lter supplied with unit. CORE PERFORMANCE Thermal Performance Ratings G5 2015.2.xlsx EV450 (IOM) 30% 50% 70% 90% 200 300 400 500 600 Ef f e c t i v e n e s s ( % ) Airflow (CFM) At AHRI 1060 standard conditions. See all AHRI certifi ed ratings at www.ahrinet.org. 450INEV Energy Recovery Ventilator Standard Download specification at: renewaire.com/specifications Note: Indirect Gas-Fired Duct Furnace is not available on the EV450IN. 03/16/2019 FOR THE MOST COMPLETE AND CURRENT INFORMATION VISIT RENEWAIRE.COM 5 EV - S E R I E S 7/ 8 " P o w e r I n 7/ 8 " C o n t r o l I n 10 " Ro u n d T y p . (O p t i o n a l 45 E V T 1 0 Tr a n s i t i o n Ki t S h o w n ) 25 1/4" 11 1/4" 5 1 / 4 " T y p . Di s c o n n e c t Sw i t c h 5 1 / 8 " T y p . 54 1 / 2 " O v e r a l l (w i t h R o u n d T r a n s i t i o n s ) CL 2 1 / 4 " C o n t r o l I n CL 14 1 / 4 " P o w e r I n EA OA FA RA Pr e s s u r e Po r t s ( 4 ) T y p . (2 ) 7/ 8 " H o l e s fo r W i r i n g i n Bo t t o m o f E - B o x 33 7/8" Case 15 7 / 8 " Ca s e 16 3 / 8 " Ov e r a l l 6 3 / 8 " 10 1/8" 26 1/4" 1 1 / 2 " T y p . 4 4 1 / 8 " C a s e 47 1 / 8 " O v e r a l l (w i t h F l a n g e s ) 14 1/4" Minimum Service Area (Doors can be Removed from Hinges) 44 1 / 2 " M i n i m u m Se r v i c e A r e a 24 3/4" TO P V I E W Do o r Sw i n g Do o r Sw i n g 4 1/4" Typ. 20 1/4" Typ. 7/ 8 " Ty p . CL 2 5 / 8 " Co n t r o l I n CL 4 1 / 8 " Po w e r I n 12 " X 8 " T y p . Du c t F l a n g e (O p t i o n a l 45 E V D F Ki t S h o w n ) 2 1 / 8 " Ty p . 36 3/8" Overall RI G H T V I E W FR O N T V I E W LE F T V I E W Mo d e l : E V 4 5 0 I N Dr a w i n g T y p e : U n i t D i m e n s i o n Ve r s i o n : M A Y 1 7 AB B R E V I A T I O N S EA : E x h a u s t A i r t o o u t s i d e OA : O u t s i d e A i r i n t a k e RA : R o o m A i r t o b e e x h a u s t e d FA : F r e s h A i r t o i n s i d e IN S T A L L A T I O N O R I E N T A T I O N Un i t m a y b e i n s t a l l e d i n a n y o r i e n t a t i o n . NO T E 1. U N L E S S O T H E R W I S E S P E C I F I E D , DI M E N S I O N S A R E R O U N D E D T O T H E NE A R E S T E I G H T H O F A N I N C H . 2. S P E C I F I C A T I O N S M A Y B E S U B J E C T TO C H A N G E W I T H O U T N O T I C E . EV 4 5 0 IN En e r g y R e c o v e r y V e n t i l a t o r St a n d a r d o r E C M o t o r O p t i o n AI R F L O W C O N F I G U R A T I O N Av a i l a b l e a s s h o w n i n d i m e n s i o n d r a w i n g . UN I T M O U N T I N G & A P P L I C A T I O N Ca n b e m o u n t e d i n a n y o r i e n t a t i o n . R A / E A a i r s t r e a m ca n b e s w i t c h e d w i t h O A / F A a i r s t r e a m . EV 4 5 0 IN En e r g y R e c o v e r y V e n t i l a t o r St a n d a r d SPECIFICATIONS & DIMENSIONS Specifi cations may be subject to change without notice. INDOOR UNITSPECIFICATIONS Ventilation Type: Static plate, heat and humidity transfer Typical Airfl ow Range: 200-540 CFM AHRI 1060 Certifi ed Core: One L85-G5 Standard Features: Non-fused disconnect 24 VAC transformer/relay package Cross-core differential pressure ports Filters: Total qty. 2, MERV 8: 14" x 20" x 2" Unit Dimensions & Weight: 54 1/2" L x 16 3/8" W x 36 3/4" H 137-199 lbs., varies by option(s) Max. Shipping Dimensions & Weight (on pallet): 62" L x 42" W x 22" H 250 lbs. Motor(s), choice of: Qty. 1, 0.6 HP (standard single phase) Qty. 1, 0.5 HP (standard three phase) Options: Qty. 1, Variable Speed/ECM - Direct Drive Motors (see EV450IN EC Motor submittal) - 0.5 HP, 120V/1Ph/60HZ, 0.5 HP, 208-230V/1Ph/60HZ Fused disconnect Integrated programmable controls - enhanced, premium Qty. 2, Factory mounted fi lter alarms - both airstreams Double wall construction Exterior paint - white, custom colors Accessories: Filters - MERV 13, 2" (shipped loose) Backdraft damper 10" Wall cap 10" - galvanized, paintable galvanneal Vibration isolation kit Hanging bracket kit Transition kit 10" - round, qty. 2 Flange kit - rectangular 12" x 8", 2 fl anges Solid state speed control kit - 115V, qty. 1, 208-230V, qty. 1 Digital time clock - wall mount (TC7D-W), in exterior enclosure (TC7D-E) Carbon dioxide sensor/control - wall mount (CO2-W), duct mount (CO2-D) IAQ sensor - wall mount (IAQ-W), duct mount (IAQ-D) Motion occupancy sensor/control - ceiling mount (MC-C), wall mount (MC-W) Smoke detector - duct mount (SD-D) Louver with 10" round duct connection - 12" (W) x 12" (H) Electric duct heater - RH series (1-11.5 kW); EK series (1–175 kW); designed for indoor ductwork installation only HP Volts HZ Phase FLA Min. Cir. Amps Max. Overcurrent Protection Device 0.6 120 60 Single 7.2 9.0 15 0.6 208-230 60 Single 3.9-3.6 4.9 15 0.6 277 60 Single 3.5 4.4 15 0.5 208-230 60 Three 1.7-1.5 2.1 15 0.5 460 60 Three 0.8 1.0 15 UNIT PERFORMANCE Airfl ow CFMESP in H20Watts 1P 3P 2251.25335181 3750.89464333 4200.75518394 4800.50584472 5000.43600491 5400.25640540 5750.00690610 ELECTRICAL DATA Note: Watts is for the entire unit. Note: Airfl ow performance includes effect of clean, standard fi lter supplied with unit. CORE PERFORMANCE Thermal Performance Ratings G5 2015.2.xlsxEV450 (IOM) 30% 50% 70% 90% 200 300 400 500 600 Ef f e c t i v e n e s s ( % ) Airflow (CFM) At AHRI 1060 standard conditions. See all AHRI certifi ed ratings at www.ahrinet.org. 450INEVEnergy Recovery Ventilator Standard Download specification at: renewaire.com/specifications Note: Indirect Gas-Fired Duct Furnace is not available on the EV450IN. 03/16/2019 M-SERIES PRODUCT CATALOG Zoned Comfort Solutions™ www.mitsubishicomfort.com AC-1 / HP-1,2 03/16/2019 ENERGY-EFFICIENT OPERATION ENERGY-EFFICIENT AND ENVIRONMENTALLY FRIENDLY Do you want to live in constant comfort or maintain a reasonable energy bill? You don’t have to choose. Zoned Comfort Solutions™ utilize green technologies and are up to 40% more efficient than central air. Don’t sacrifice comfort over worries about high energy costs. ▶▶INVERTER®-driven compressor technology results in substantial energy and utility savings ▶▶Zoned control for improved comfort and decreased energy usage ▶▶Many ENERGY STAR® certified systems ▶▶SEER ratings as high as 33.1—dramatically better than conventional systems ▶▶Local and state utility rebates and incentive opportunities ▶▶83% of system components are recyclable ▶▶Washable filters made from natural materials Let energy rebate programs work for you. Learn more at www.mitsubishicomfort.com and choose the Rebates & Financing tab. SAVINGS OPPORTUNITIES Mitsubishi Electric Zoned Comfort Solutions™ are so energy efficient that a majority of our INVERTER®-driven systems have received ENERGY STAR® certification. This can mean big savings. Add in the federal tax credit and local government and utility rebates, and you have an opportunity to enjoy comfort at substantial savings. These rebates come in many forms, from property and sales tax exemptions to loans and grants. There are thousands of such programs in the U.S., but they are often not widely promoted or publicized. With Mitsubishi Electric, you truly can Make Comfort Personal® (and save some money, too). For details on qualifying systems, go to www.mitsubishicomfort.com/taxcredit, or visit www.dsireusa.org for information on available local rebate opportunities from state governments or utility companies. 6 03/16/2019 ENERGY STAR ® CERTIFIED SYSTEMS Note: List is current as of this printing. RESIDENTIAL AIR CONDITIONER AHRI Reference #Outdoor Indoor EER SEER HSPF 8715778 MUY-GL09NA MSY-GL09NA 15.40 24.60 N/A 8715779 MUY-GL12NA MSY-GL12NA 13.00 23.10 N/A 8715780 MUY-GL15NA MSY-GL15NA 13.00 21.60 N/A 8715781 MUY-GL18NA MSY-GL18NA 13.40 20.50 N/A 8715782 MUY-GL24NA MSY-GL24NA 12.50 20.50 N/A RESIDENTIAL HEAT PUMP AHRI Reference #Outdoor Indoor EER SEER HSPF 8854557 MUFZ-KJ09NAHZ MFZ-KJ09NA 15.80 28.20 13.00 8849446 MUFZ-KJ12NAHZ MFZ-KJ12NA 13.60 25.50 12.00 8854558 MUFZ-KJ15NAHZ MFZ-KJ15NA 13.50 21.80 11.60 8854559 MUFZ-KJ18NAHZ MFZ-KJ18NA 12.60 21.00 11.30 8797130 MUZ-FH06NA(H)MSZ-FH06NA 19.10 33.10 13.50 7002062 MUZ-FH09NA(H)MSZ-FH09NA 16.10 30.50 13.50 7002063 MUZ-FH12NA(H)MSZ-FH12NA 13.80 26.10 12.50 7002444 MUZ-FH15NA(H)MSZ-FH15NA 12.50 22.00 12.00 8797133 MUZ-FH18NA(H)2 MSZ-FH18NA 12.50 21.00 12.00 8856678 MUZ-GL09NA MSZ-GL09NA 15.40 24.60 12.80 8715783 MUZ-GL12NA MSZ-GL12NA 13.00 23.10 12.50 8715784 MUZ-GL15NA MSZ-GL15NA 13.00 21.60 11.70 8715785 MUZ-GL18NA MSZ-GL18NA 13.40 20.50 11.20 8715786 MUZ-GL24NA MSZ-GL24NA 12.50 20.50 10.00 3589025 MXZ-2C20NA2 Non-ducted Indoor Units 12.70 20.00 10.00 7451974 MXZ-2C20NAHZ2 Non-ducted Indoor Units 13.50 17.00 9.80 7505787 MXZ-3C24NA2 Non-ducted Indoor Units 13.60 20.00 9.80 7451969 MXZ-3C24NAHZ2 Non-ducted Indoor Units 13.50 19.00 10.00 7451794 MXZ-3C30NAHZ2 Non-ducted Indoor Units 12.50 18.00 11.00 7434482 MXZ-4C36NAHZ Non-ducted Indoor Units 14.00 19.10 11.30 7434486 MXZ-4C36NAHZ Mixed Ducted and Non-ducted Indoor Units 12.65 17.45 10.70 7434477 MXZ-5C42NAHZ Non-ducted Indoor Units 13.40 19.00 11.00 MXZ-8C60NA Mixed Ducted and Non-ducted Indoor Units ENERGY STAR® MOST EFFICIENT 2017 (with kumo cloudTM controller) 7 03/16/2019