HomeMy WebLinkAboutFile Documents.834 W Hallam St.0010.2018 (33).ARBK0010.2018.ARBK_ElectricalComments1
Page Label: 148
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
Coordinate with Utility for meter/
disconnect locations & service
wiring sizing -- no lighting plan
for exterior grade access or
stairway -- bathroom lighting
not on plan -Panel schedules are
generic & do not represent
plans, label for specific units &
have accurate calculations --
AFCI & GFI protection per
current adopted NEC --
PERMIT SET.834Hallam.2017.11.pdf (12)
Page Label: 148
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
Identify Panels & Meters to unit
#
Page Label: 149
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
225.30 allows 1 outside feeder
per structure - There are 3
structures on this site --please
describe the special condition
that requires allowance of more
than 1 feeder. Part of condition
is that such distribution is
permitted under the condition
that the distribution system is
under a single management.
Page Label: 149
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
How are branch circuits for
common areas supplied?
Page Label: 149
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Fuel Gas Code
Color:
Is there a house panel for the
storage units ?
Where is it located?
2[(4#900 MCM AL)4"C]
SHEET NUMBER:
DRAWN BY:
CHECKED BY:
PROJECT MANAGER:
SHEET TITLE:
PROJECT NUMBER:
SCALE:
of
170915-01
BW
ajs
BW
AS NOTED
Permit Documents
CITY STAMPS:
1 6
E.0.01
ELECTRICA
SCHEDULES,
LINE DIAGR
Coordinate with Utility for meter/ disconnect locations & service wiring sizing -- no lighting
plan for exterior grade access or stairway -- bathroom lighting not on plan -Panel
schedules are generic & do not represent plans, label for specific units & have accurate
calculations -- AFCI & GFI protection per current adopted NEC --
M
150/2
M
150/2
Identify Panels & Meters to unit #
C
A-303 DA-304
RE
C
2
3
1
F
D
W/D
DW
DW
E G
LIVING
UNIT 101-L2
MAIN LEVEL ENTRY
UNIT 107-L1
KITCHEN
UNIT 102-L1
LIVINGUNIT 102-L1
KITCHENUNIT 101-L1
F
BB
3BB
2.5
B
2
DFC (AC-1
1
DFC(AC-7)
STOVE
DW
GFIC
GFICSTOVE
GFIC GFICDW
DRYER
GFIC
PANEL
NEL
METER PAC
MAIN DISC
ROUGH-IN
225.30 allows 1 outside feeder per structure - There are 3 structures on this site
--please describe the special condition that requires allowance of more than 1
feeder. Part of condition is that such distribution is permitted under the condition
that the distribution system is under a single management.
F
DW
W/
D
C
E
RG
KITCHEN
UNIT 103-L1
LEVEL ENTRY
NIT 103-L1
LIVING
UNIT 103-L1
BB
3
BB
2.5
BB
2.5
4
DFC
(AC-3)
DRYER
DWGFIC GFIC
PANEL
How are branch circuits for common areas supplied?
UNIT 7
STORAGE
UNIT 2
STORAGE
UNIT 3
STORAGE
UNIT 1
STORAGE
UNIT 4
STORAGE
UNIT 5
STORAGE
UNIT 6
STORAGE
SE
T
B
A
C
K
L
I
N
E
F
AIN LEVEL ENTRY
UNIT 106-L1
IN LEVEL ENTRY
UNIT 105-L1
UH
1
UH
1
BB
2.5
BB
2.5
Is there a house panel
for the storage units ?
Where is it located?
Lighting design is not part of Peak Designs contract. New
panelboard schedules are included in this set.
Panelboard labels added in this set.
One "EZ" meter pak has been shown per building.
There is a "Public" panelboard to supply branch circuits to
those areas.
There is a new location as a part of this plan set.
04/13/2018
Page Label: 151
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
2 Appliance circuits required per
kitchen
Page Label: 151
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
sink GFI recept in bathtub??
cannnot be on bedroom circuit
-- no BB allowed in tub
Page Label: 151
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
Add receptacle
Page Label: 151
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
AFCI/GFCI per current NEC
Page Label: 152
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
Add receptacle
C
303
W/D
KITCHEN
UNIT 104-L2
LIVING
UNIT 104-L2
BB
3
BB
2.5
BB
2.5
2 (AC-4)
2
DFC (AC-4)
WH
1
G
D
FIC
DRYER
PANEL
2 Appliance circuits required per kitchen
5
4
F DW
F
6
BATH 2
UNIT 107-L2
KITCHEN
UNIT 106-L2
BB
3
BB
2.5
BB
2.5
DWGFIC
GFIC
PANEL
sink GFI recept in bathtub??
cannnot be on bedroom circuit
-- no BB allowed in tub
R
Add receptacle
E
AFCI/GFCI per current NEC
Add receptacle
Two circuits will be planed for within the panelboard
for each unit.
New locations as a part of this plan set.
can we get more direction on this comment.
can we get more direction on this comment.
Label have been added for GFIC recept. Arc fault will be
covered under the specs.
04/13/2018
Page Label: 152
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
AFCI/GFCI per current NEC
Page Label: 152
File Name: PERMIT SET.834Hallam.2017.11.pdf
Author: mitchm
Subject: Text Box
Color:
ok <4'
D
A-304F
LIVING
UNIT 105-L3
BATH 1
UNIT 105-L3
RD LEVEL
BB
2.5
BB
2.5
BB
3
AFCI/GFCI per current NEC
UNIT 105-L3
C
ok <4'
04/13/2018