Architectural Engineering Consultants, Inc.
`
An Office with LEED TTMM Accredited Professionals
40801 US Hwy 6 & 24, Suite 214, Eagle-Vail, CO 81620 Post Office Box 8489, Avon, CO 81620
phone: 970-748-8520 email: stan@aec-vail.com web: www.aec-vail.com
May 25, 2018
David Johnston
David Johnston Architects
119 South Spring Street, Suite 203
Aspen, CO 81611
Re: Aspen Affordable Housing – 802 West Main Street
Dear David,
This document is intended to show compliance of the new construction of the Aspen Affordable Housing
located at 802 West Main Street, Aspen, CO with the 2015 International Energy Conservation Code (2015
IECC). We propose to use a prescriptive approach per sections 402.1-402.3 and 403.2.1 of the 2015
IECC.
Project
The project at 802 West Main Street is the new construction of a multi-family residence with a floor area
of 10,874.19 sf. For heat load calculations, please refer to the Appendix. The heat load calculations are
performed using the Carrier Hourly Analysis Program and provides a more detailed and accurate load
than Manual J.
Building Envelope
The following table lists the mandatory minimum insulation and fenestration requirements for the project
climate zone (7). All new assemblies will meet the following requirements.
Fenestration
U-factor
Ceiling R-
value
Wood frame
wall R-value
Floor
R-value
Basement wall
R-value
Slab
R-value
Code Minimums 0.28 (1) 49 20+5 or 13+10 38 (2) 15/19 (3) 10 (4)
Notes: 1) Fenestration SHGC requirements do not apply in climate zone (7)
2) Or insulation sufficient to fill the framing cavity, R-19 minimum
3) R-15 continuous insulation on the interior or exterior or R-19 cavity insulation on the interior of
the basement wall. Can be satisfied with R-13 cavity plus R-5 continuous.
4) 4 ft deep and R-15 edge insulation for heated slabs
5) R-10 continuous insulation or R-13 cavity insulation.
Sincerely,
Dan Findley
Mechanical Engineer
06/15/2018
Zone Sizing Summary for Default System
Project Name: 802 W Main Street
Prepared by: AEC, Inc.
05/25/2018
07:53AM
Hourly Analysis Program v4.50 Page 1 of 2
Air System Information
Air System Name Default System
Equipment Class UNDEF
Air System Type SZCAV
Number of zones 1
Floor Area 5060.0 ft²
Location Aspen, Colorado
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM Individual peak space loads
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Sizing Data
Zone Name
Maximum
Cooling
Sensible
(MBH)
Design
Air
Flow
(CFM)
Minimum
Air
Flow
(CFM)
Time
of
Peak
Load
Maximum
Heating
Load
(MBH)
Zone
Floor
Area
(ft²)
Zone
CFM/ft²
Zone 1 86.3 5148 5148 Aug 1500 103.2 5060.0 1.02
Zone Terminal Sizing Data
Space Loads and Airflows
No Zone Terminal Sizing Data required for this system.
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time
of
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft²)
Space
CFM/ft²
Zone 1
001 MECHANICAL 1 1.7 Jul 1500 255 5.1 365.0 0.70
002 STORAGE 1 3.9 Aug 1500 657 13.2 785.0 0.84
102A LIVING ROOM 1 2.6 Aug 1600 113 2.3 155.0 0.73
102B DINING 1 5.8 Sep 1400 207 4.2 115.0 1.80
102C KITCHEN 1 1.5 Jul 1500 54 1.1 110.0 0.49
102D MUDROOM 1 0.6 Jul 1600 113 2.3 95.0 1.19
102E BEDROOM 1 1.8 Jul 1700 127 2.6 135.0 0.94
102F BATH 1 0.4 Jul 1500 15 0.3 60.0 0.24
103A LIVING ROOM 1 6.8 Sep 1400 257 5.1 125.0 2.05
103B DINING 1 2.2 Jul 1600 61 1.2 90.0 0.68
103C KITCHEN 1 2.4 Jul 1500 148 3.0 145.0 1.02
103D MUDROOM 1 0.3 Jul 1900 45 0.9 50.0 0.89
103E BEDROOM 1 2.4 Sep 1500 163 3.3 155.0 1.05
103F BATH 1 0.3 Jul 1500 12 0.2 50.0 0.24
105A LIVING ROOM 1 2.8 Jul 1500 154 3.1 175.0 0.88
105B DINING 1 5.0 Jul 1000 229 4.6 105.0 2.18
105C KITCHEN 1 1.4 Jul 1600 74 1.5 100.0 0.74
105D MUDROOM 1 0.8 Jul 1700 143 2.9 95.0 1.51
105E BEDROOM 1 3.0 Jul 1700 155 3.1 135.0 1.15
105F BATH 1 0.4 Jul 1500 18 0.4 60.0 0.30
201A LIVING ROOM 1 4.7 Oct 1400 156 3.1 155.0 1.00
201B DINING 1 6.1 Sep 1500 205 4.1 115.0 1.78
201C KITCHEN 1 1.7 Jul 1800 69 1.4 110.0 0.63
201D MUDROOM 1 0.7 Jul 1800 127 2.5 95.0 1.33
201E BEDROOM 1 1.9 Jul 1700 139 2.8 135.0 1.03
201F BATH 1 0.4 Jul 1600 24 0.5 60.0 0.39
203A LIVING ROOM 1 6.4 Sep 1400 239 4.8 125.0 1.91
203B DINING 1 3.2 Jul 1400 95 1.9 90.0 1.05
203C KITCHEN 1 2.6 Jul 1600 155 3.1 145.0 1.07
203D MUDROOM 1 0.4 Jul 1900 44 0.9 50.0 0.89
203E BEDROOM 1 2.5 Sep 1500 161 3.2 155.0 1.04
203F BATH 1 0.4 Jul 1600 20 0.4 50.0 0.39
205A LIVING ROOM 1 4.3 Jul 1400 161 3.2 175.0 0.92 06/15/2018
Zone Sizing Summary for Default System
Project Name: 802 W Main Street
Prepared by: AEC, Inc.
05/25/2018
07:53AM
Hourly Analysis Program v4.50 Page 2 of 2
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time
of
Load
Air
Flow
(CFM)
Heating
Load
(MBH)
Floor
Area
(ft²)
Space
CFM/ft²
205B DINING 1 4.6 Jul 1400 199 4.0 105.0 1.90
205C KITCHEN 1 1.6 Jul 1700 67 1.3 100.0 0.67
205D MUDROOM 1 0.8 Jul 1700 126 2.5 95.0 1.33
205E BEDROOM 1 3.1 Jul 1700 139 2.8 135.0 1.03
205F BATH 1 0.4 Jul 1700 24 0.5 60.0 0.39
Notes: Loads were calculated for three residences per level. Typical conditions exist for the remaining three residences per level.
MANUAL J DESIGN CONDITIONS
WINTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS
OUTDOOR TEMPERATURE -15 °F OUTDOOR TEMPERATURE 82 °F
INDOOR TEMPERATURE 70 °F INDOOR TEMPERATURE 75 °F
TOTAL HEAT LOSS 190,751 BTU/HR SENSIBLE HEAT GAIN 178,554 BTU/HR
LATENT HEAT GAIN 19,796 BTU/HR
TOTAL HEAT GAIN 198,350 BTU/HR
06/15/2018