HomeMy WebLinkAboutFile Documents.834 W Hallam St.0010.2018 (52).ARBKMarkup Summary 3-7-2018
Page: A-106 PROPOSED ROF PLAN
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Please clarify the style of the
gutter (half-round or K-style) and
downspouts, and the material.
Whether they are galvanized or
painted has to be reviewed and
approved by HPC staff and
monitor, not left as TBD on the
drawings. Same for flashing and
snow clips. Please specify the
exact proposed clip. Clips on
the historic house are to be
limited in number and extent to
minimum code requirement.
PermitSet.834WHallam.2018.02.pdf (22)
Page: A-108 PROPOSED MAIN LEVEL FINISH FLOR PLAN
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The east lightwells require
clarification and redesign. In
basement plans they are
depicted as attached to the
foundation wall, but in first floor
plans the southeast lightwell
appears to float away from the
foundation wall and the
northeast lightwell is obstructed
by the proposed bay window
above it (which must be
removed in any case.) The top
of the lightwells must be the
minimum height above grade
that is allowed by code. The
permit suggests that they would
project some 2’ above grade.
Page: A-201 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The permit must correctly depict
the water table that the
clapboard siding dies into, on all
sides of the house. The water
table sits directly below the
brackets on the bay window.
Page: A-201 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Please add a note to the
drawings clarifying that all
historic exterior trim will be
preserved.
GRID TO EXTERIOR FACE OF
PROPOSED WOOD FRAMING
G
Please clarify the style of the gutter (half-round
or K-style) and downspouts, and the material.
Whether they are galvanized or painted has to
be reviewed and approved by HPC staff and
monitor, not left as TBD on the drawings. Same
for flashing and snow clips. Please specify the
exact proposed clip. Clips on the historic house
are to be limited in number and extent to
minimum code requirement.
124
108
114
112
117
116
118
105A 105B
106B
111
113
103A
103D
128
120121122
115
103C
105
123
119
103B
106A
107X
104X103X
102X
106
127125126
104A
107A
66
7
B
B
D
D
101
T.O.PLY99'-11"
T.O.FF100'-0"
T.O.PLY99'-11"
T.O.FF100'-0"
T.O.CONC98'-1"
T.O.PLY98'-0"
T.O.FF98'-1"
T.O.PLY98'-0"
T.O.FF98'-1"
T.O.PLY99'-6"
T.O.FF99'-7"
T.O. SLAB97'-11"
T.O. SLAB97'-11"T.O. SLAB97'-11"
T.O. SLAB97'-11"
T.O. SLAB97'-11"T.O. SLAB97'-11"
T.O. SLAB97'-11"
T.O.PLY99'-6"
T.O.FF99'-7"
GRID TO EXTERIOR FACE OF
PROPOSED WOOD FRAMING
GRID TO EXTERIOR FACE OF
PROPOSED WOOD FRAMING
GRID TO EXTERIOR FACE OF
PROPOSED WOOD FRAMING
GRID TO INTERIOR FACE OF
PROPOSED WOOD FRAMING
GRID TO INTERIOR FACE OF
PROPOSED WOOD FRAMING
LIVINGUNIT 103
ENTRYUNIT 103
ENTRYUNIT 105
ENTRYUNIT 104 ENTRYUNIT 106
ENTRYUNIT 101
KITCHENUNIT 101
LIVINGUNIT 102
KITCHENUNIT 102
ENTRYUNIT 107
LIVINGUNIT 107
BATHROOM 1UNIT 103
KITCHENUNIT 103
LIVINGUNIT 101
FOYER
STORAGEUNIT 107 STORAGEUNIT 101
STORAGEUNIT 102
STORAGEUNIT 106
STORAGEUNIT 103
STORAGEUNIT 104
STORAGEUNIT 105
TRASH ENCLOSURE
LAUNDRYUNIT 103
POWDERUNIT 107
11
33
44
G
G
F
F
E
E
A
A
8
2
5
C
C
109 110
ENTRYUNIT 102
BEDROOM 1UNIT 103
The east lightwells require clarification
and redesign. In basement plans they
are depicted as attached to thefoundation wall, but in first floor plansthe southeast lightwell appears to float
away from the foundation wall and the
northeast lightwell is obstructed by the
proposed bay window above it (whichmust be removed in any case.) The topof the lightwells must be the minimum
height above grade that is allowed by
code. The permit suggests that they
would project some 2’ above grade.
9'-0"
101 2764
ELEVATION
The permit must correctly
depict the water table that
the clapboard siding dies
into, on all sides of the
house. The water table
sits directly below the
brackets on the bay
window.
2
SETBACK LINE
PROPERTY LINE
Please add a note to the drawings clarifying that all historic
exterior trim will be preserved.
FP Response: The foundation under building A has
been restructured, so the lightwells no longer appear
to float away from the foundation wall. We also removed
the bay window, so there is no interference with the
lightwell. Lightwells are shown at the minimum height
above grade. Reference sheet A-103 + A-206.
FP Response: Gutters, downspouts, flashing and
snow clips are all specified in the plans and elevations.
Gutters will be half-round painted aluminum, downspouts
round painted aluminum, flashing is painted aluminum,
and snow clips are painted aluminum, The specs for the
snow clips are also included. Reference sheet A-106 +
A-201 through A-207.
FP Response: The permit elevations now show
the water table that the clapboard siding dies into
on all sides of building A. Reference sheet A-201
through A-207.
FP Response: A note has been added to all
existing floor plans to preserve all historic exterior
trim. Refernce sheet A-103x.1 through A-106x.2.
04/13/2018
Page: A-201 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Is this a railing? This was not
approved by HPC.
Page: A-206 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Please relocate the downspout
which is attached to the front
porch post. It should discharge
somewhere further back along
the east wall.
Page: A-206 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
A detail of the reconstructed
chimney on the historic house is
required, and the reconstruction
must be correctly represented in
all drawings in the permit. This
was a condition of Final
approval.
Page: A-206 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The window currently in place at
this location is not historic.
Historic photographs show a
rectangular stained glass
window in this location. An
identical window appears to be
in place further to the north,
where the historic exterior wall is
now interior. The remaining
stained glass window is to be
salvaged and installed at 107x.
101
102X
27
Is this a railing? This
was not approved by
HPC.
B C
14'-10"
CA-303
107X
206X
205X
36
T.O PLY @ SECOND LEVEL
@ BUILDING A: 109'-9"
T.O RIDGE HEIGHT@ BUILDING A: 124'- 7"
SETBACK LINE
PROPERTY LINE
Please relocate the downspout
which is attached to the front
porch post. It should discharge
somewhere further back along
the east wall.
C DCA-303
36
A detail of the reconstructed
chimney on the historic house is
required, and the reconstruction
must be correctly represented in
all drawings in the permit. This
was a condition of Final
approval.
9'-0"
9'-10"
002001
104X
107X
206X
53
51
53
51
T.O PLY @ SECOND LEVEL@ BUILDING A: 109'-9"
T.O PLY @ MAIN LEVEL@ BUILDING A: 99'-11"
T.O SLAB @ LOWER LEVEL@ BUILDING A: 90'-11"
SGSG
SCALE: 1/4" = 1'-0"7 PROPOSED ELEVATION
The window currently in place at this location is
not historic. Historic photographs show a
rectangular stained glass window in this
location. An identical window appears to be in
place further to the north, where the historic
exterior wall is now interior. The remaining
stained glass window is to be salvaged and
installed at 107x.
FP Response: This is a heat pump, part of
the mechanical equipment. It will be shielded
from the roadway via plantings, and has now
been labeled in elevations. Reference sheet
A-201 through A-2017.
FP Response: This downspout has been
relocated further back along the east
wall. Reference sheet A-206.
FP Response: The reconstruction
of the chimney is now depicted in all
proposed drawings, and references
the detail which calls out the historic
materials on A-414. Reference A-206.
FP Response: We have added a note that
the stained glass window located presently
on an interior portion of the home be
salvaged and installed in this location.
Reference sheet A-206.
04/13/2018
Page: A-206 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Wall vents are not permitted on
the historic resource. Please
provide drawings indicating all
required exterior vents, placed at
the foundation level or through
the roof of the Victorian. Utilized
the historic chimney for a flue if
possible. The placement of all
vents requires review and
approval by staff and monitor.
Ideally roof vents should be
grouped together to the extent
possible and located towards the
north east corner of the building.
The proposed radon vent
should be moved away from the
historic chimney or be routed
through it.
Please provide information on
any panels or meters to be
installed on the exterior of the
Victorian.
Page: A-206 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
There are two windows labeled
104x. It appears this east facing
bay is supposed to be 106x.
Applicant is proposing to
relocate a historic window from
the demolished portion of the
building onto this façade. This
was not approved and is not
appropriate as it is a
misrepresentation of the design
of the house. If a double hung
window is desired in this
location, please propose a
design which is subtly
distinguishable from historic
windows in the building.
Page: A-206 ELEVATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The windows in the east and
west dormers are represented to
be casement windows now,
which is incorrect. The permit
indicates they will become
casements, which was not
allowed by the HPC Final
Resolution.
Page: A-502 EXTERIOR ONSTRUCTION DETAIL
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The foundation under the historic
resource is depicted as sitting
proud of the framed wall of the
Victorian. This must be revised.
The existing condition is not
historic. Please revisit all related
drawings to show the framed
wall resting on the concrete
foundation, with the sheathing
aligning with the outside face of
the foundation wall.
Please clarify the material for the
exposed foundation. Exposed
concrete or painted metal
flashing are permitted.
113
002
104X
05X
53
51
212 211
28
31
56
33
54
27
47
37
26
56
32
30
SG
Wall vents are not permitted on the historic resource.
Please provide drawings indicating all required exterior
vents, placed at the foundation level or through the roof
of the Victorian. Utilized the historic chimney for a flue if
possible. The placement of all vents requires review and
approval by staff and monitor. Ideally roof vents should
be grouped together to the extent possible and located
towards the north east corner of the building. The
proposed radon vent should be moved away from the
historic chimney or be routed through it.
Please provide information on any panels or meters to
be installed on the exterior of the Victorian.
002
104X
53
51
27
47
37
26
56
32
30
SG
There are two windows labeled 104x. It
appears this east facing bay is supposed to be
106x. Applicant is proposing to relocate a
historic window from the demolished portion of
the building onto this façade. This was not
approved and is not appropriate as it is a
misrepresentation of the design of the house. If
a double hung window is desired in this
location, please propose a design which is
subtly distinguishable from historic windows in
the building.
C D E DA-304
205X
212
56
32
36
The windows in the east and
west dormers are represented to
be casement windows now,
which is incorrect. The permit
indicates they will become
casements, which was not
allowed by the HPC Final
Resolution.
W-1
FOOTINGREF STRUCT
CONTINUOUSWATERPROOFING
RADON SYSTEMBY OTHERS
EXPANSION JOINTCOMPACTED FILL
GRAVEL FILLADJACENT TOFOUNDATION WALLTO EXTEND TOPERIMITERDRAINS; REF CIVIL
UNDISTRURBED SOIL
FOUNDATIONDRAIN; REF CIVIL
FILTER FABRIC
EXT
F-2
W-2,3
W-1
6" MIN
2"T.O.SHEATH
T.O.CONC
CONTINUOUS WATERPROOFING
CONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERS
BLOCKING
SILL PLATE
INTEXT
INT
F-2
W-4
W-1
6"
2"T.O.SHEATH
T.O.CONC
CONTINUOUS WATERPROOFING
CONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERS
SILL PLATE
BLOCKING
INTEXT
INT
F-2
W-2,3
W-1
2"T.O.SHEATH
T.O.CONC
CONTINUOUS WATERPROOFING
CONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERS
BLOCKING
MEMBER REF STRUCT
SILL PLATE
INTEXT
INT
W-4
W-1
F-5
2"
T.O.CONC
CC-J
MS
INTEXT
SLOPE PER PLAN
F-4
W-4
W-4
F-2
CONTINUOUS WATERPROOFING
CONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERS
MEMBER REF STRUCTSILL PLATE
BLOCKINGMEMBER REF STRUCT
WRB
INTEXT
INTEXT
R-3
W-4
W-4
F-2
2"CONTINUOUS WATERPROOFING
CONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERSMEMBER REF STRUCT
BLOCKING
CONTINUOUS WATERPROOFINGCONTINUOUS METAL FLASHING- FOLDED AND SOLDERED @JOINTS AND CORNERSSILL PLATEEXT
EXT
INT
INT
SLOPE PER PLAN
F-2,3W-2,3,4
W-2,3,4
MEMBER REF STRUCTSILL PLATECONTINUOUS WATERPROOFING
BLOCKING
INTEXT
INT
EXT
W-4
SOFFIT REF PLANBLOCKINGBLOCKING
ROOF OVERHANG BEYOND INTEXT
F-2
W-7
BLOCKING
SOUND CLIP
SCALE: 1 1/2"= 1'-0"1 TYP FDN @ FOOTINSCALE: 1 1/2"= 1'-0"2 HIST. MAIN LEVEL WALL TRANSSCALE: 1 1/2"= 1'-0"3 PROP. MAIN LEVEL WALL TRANSSCALE: 1 1/2"= 1'-0"4 HIST. WALL TRANS @ HARDSCAPE
SCALE: 1 1/2"= 1'-0"5 PROP. WALL TRANSSCALE: 1 1/2"= 1'-0"6 TRANS @ LIVING OVER EXTSCALE: 1 1/2"= 1'-0"7 TRANS @ EXT OVER LIVINGSCALE: 1 1/2"= 1'-0"8 TYP SLOPED ROOF OVERHANG
SCALE: 1 1/2"= 1'-0"9 TYP EAVE @ EXT W
SCALE: 1 1/2"= 1'-0"10 TYP ROOF INT
SCALE: 1 1/2"= 1'-0"11 TYP RAKE ROOF DETAIL
SCALE: 1 1/2"= 1'-0"12 FIRE-RATED INTERSECTION
The foundation under the historic resource is
depicted as sitting proud of the framed wall of theVictorian. This must be revised. The existingcondition is not historic. Please revisit all relateddrawings to show the framed wall resting on theconcrete foundation, with the sheathing aligning with
the outside face of the foundation wall.Please clarify the material for the exposed
foundation. Exposed concrete or painted metalflashing are permitted.
FP Response: This window has been removed
from our proposed design. Reference sheet
A-206.
FP Response: The windows have been revised to
show fixed windows and is clarified as such in the
window schedule. Reference sheet A-201 + A-206.
FP Response: The foundation has been revised
and the exterior of structures align. The material
over the exposed foundation is a painted metal
flashing as shown in intersection 2 on sheet A-502.
FP Response: Our mechanical engineer has
explained to me that the vents do not have
enough span to vent through the roof. They
have been relocated to the west facade between
building A and C. The exact location on this
facade can be worked out. Reference A-106
and A-206.
04/13/2018
Page: A-601 EXTERIOR DOR + WINDOW TYPES +
SCHEDULE
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Please submit shop drawings for
the new front door, porch trim
and posts on the Victorian. This
was a condition of Final
approval. Can the doors on the
new construction be a little
different, like one lower panel
instead of two? Please provide
a cut sheet for door hardware on
the Victorian front door.
Page: A-602 EXTERIOR DOR + WINDOW TYPES +
SCHEDULE
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Please update the window
schedule to be more clear that
windows you have labeled “x”
are existing historic windows to
be preserved. Please indicate
that historic glass will be
preserved.
Page: A-603 EXTERIOR DOR + WINDOW TYPES +
SCHEDULE
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Is window 204 a historic
window? Why is it called out for
replacement?
Page: G-02 LAND USE APROVALS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Prior to Round 2 submittal,
please provide HPC staff with a
memo clearly depicting
proposals for staff and monitor
review of:
•Gutter style, downspouts and
snow clips
•All walkway and porch deck
materials.
•Proposed landscape plan.
•All proposed vents, meters and
equipment on or directly next to
the historic resource.
Please do not submit for Round
2 until these topics have been
resolved.
Page: L-100 OVERALL MATERIALS PLAN
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The fence at the front of the
property is not historic and may
be removed. Some sheets show
the fence and others do not. No
information about gates has
been provided.
Please submit shop drawings for the new front door, porch trim
and posts on the Victorian. This was a condition of Final approval.
Can the doors on the new construction be a little different, like
one lower panel instead of two? Please provide a cut sheet for
door hardware on the Victorian front door.
121 122
CASEMENT CASEMENT
3'-0"x4'-6"3'-0"x4'-6"
------
ID
TYPE
W x H FRAME SIZE
W x H LEAF SIZE
NOTES
Please update the window schedule to be more clear that
windows you have labeled “x” are existing historic windows to be
preserved. Please indicate that historic glass will be preserved.
215 216
OW FIXED FIXED
Is window 204 a historic window? Why is it called out for
replacement?
Prior to Round 2 submittal, please provide HPC staff with a memo clearly
depicting proposals for staff and monitor review of:
•Gutter style, downspouts and snow clips
•All walkway and porch deck materials.
•Proposed landscape plan.
•All proposed vents, meters and equipment on or directly next to the
historic resource.
Please do not submit for Round 2 until these topics have been resolved.
The fence at the front of the property is not historic and
may be removed. Some sheets show the fence and
others do not. No information about gates has been
provided.
FP Response: In the notes of the window
schedule we have clarified for the historic
windows listed with an X that the historic
window and glass is to be preserved.
FP Response: As noted, the existing window
is not a double hung as the historic framing eludes
to being present here. So we are replacing
with a window to match the historic.
FP Response: In the preservation plan
memo, we clearly state the gutter style,
downspouts, and snow clips. We also
state walkway and porch deck materials,
We have included the proposed landscape
plan, and the elevations show vents, meters,
and equipment on and around Building A.
The fence is proposed to be removed and was
an oversight on the previous submittal plans.
Revised.
FP Response: Shop Drawings for the front
door are attached to the preservation plan.
Porch trim and posts will reconstructed by
Chris Thompson, and all drawings will be
submitted and approved by HP prior to
construction.
04/13/2018
Page: L-100 OVERALL MATERIALS PLAN
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The surface of the historic front
porch must be wood. This was
a condition of Final approval.
Please seek HPC staff and
monitor approval for the material
to be used for the porch decks
on the new structures. This was
not specified at Final review.
Page: L-100 OVERALL MATERIALS PLAN
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The walkway materials require
approval by HPC staff and
monitor. The front walk to the
Victorian is to be grey concrete,
brick or red sandstone, not
concrete pavers as indicated.
The center walk is to be a
different material than the
walkway to the Victorian porch.
Page: L-300 OVERALL LANDSCAPE PLAN & PLANT
SCHEDULE
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The landscape plan requires
review and approval by HPC
staff and monitor regarding
design, and review by Parks for
water use requirements.
Preliminarily, HPC staff
recommends less perennials
and more sod around the historic
structure. A final condition of
approval was that any sprinklers
be at least two feet away from
the building. A narrow,
unplanted border at the base of
the house may be appropriate.
The potentilla on the east have
the potential to damage the
resource by holding too much
moisture against the building.
The spruce trees at the
northwest and southeast corners
of the property were to be
revised to reduce the
appearance of a barrier. This
was a condition of Final
approval.
Page: S-001 ENERAL NOTES
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
The structural drawings do not
adequately address how the
original wall and roof framing,
sheathing, fascia and soffits will
be retained. This was a
condition of HPC Final approval.
The drawings indicate that
house wrap will be installed,
which would require removal of
the historic siding. This requires
further discussion.
The surface of the historic front porch must be wood.
This was a condition of Final approval. Please seek HPC
staff and monitor approval for the material to be used for
the porch decks on the new structures. This was not
specified at Final review.
The walkway materials require approval by HPC staff and
monitor. The front walk to the Victorian is to be grey
concrete, brick or red sandstone, not concrete pavers as
indicated. The center walk is to be a different material than
the walkway to the Victorian porch.
The landscape plan requires review and approval byHPC staff and monitor regarding design, and review byParks for water use requirements. Preliminarily, HPCstaff recommends less perennials and more sod aroundthe historic structure. A final condition of approval wasthat any sprinklers be at least two feet away from thebuilding. A narrow, unplanted border at the base of the
house may be appropriate. The potentilla on the east
have the potential to damage the resource by holding too
much moisture against the building. The spruce trees at
the northwest and southeast corners of the property
were to be revised to reduce the appearance of a barrier.
This was a condition of Final approval.
12. No structural modifications, alterations, or repairs shall be made without prior review by
Structural Engineer. Submit details and calculations prepared by a professional engineer
registered in state where project is located and employed by contractor.
N
1
2
3
4
5
6
The structural drawings do not adequately address how the original
wall and roof framing, sheathing, fascia and soffits will be retained.
This was a condition of HPC Final approval. The drawings indicate
that house wrap will be installed, which would require removal of the
historic siding. This requires further discussion.
Noted. Revised to indicate a wood material.
The proposed walk associated with the
historic Poppies building has been revised to
be a sand set, or previous, brick paver. All
other walkways are proposed to be gray
concrete.
This landscape plans have been revised to
indicate a 24” aggregate dripline with steel
edger. Aggregate was chosen in lieu of a
mulch product to minimize splash-back of dirt
during storm events. The spruce trees have
been omitted within the 8th Street ROW due
to the required sight triangle associated with
the alley and the Spruce trees located at the
southeast corner of the property have been
reduced in quantity, as well as staggered to
reduce the appearance of a barrier.
RE: S-001, Existing Construction, Note 6
04/13/2018
Page: Z-04 WAL DEMOLITION CALCULATIONS
Author: amyg
File Name: PermitSet.834WHallam.2018.02.pdf
Please add a note to the drawing
indicating an inspection by HPC
staff will occur following
demolition, prior to relocation of
the historic resource.Please add a note to the drawing indicating an inspection by
HPC staff will occur following demolition, prior to relocation of
the historic resource.FP Response: This note has been included onto
this drawing.
Additional Action Items:
House Moving Location
Electric Meter Location
FP Response: We have included the form from Bill Bailey describing his house moving
methodology. The house will be lifted in place on site while the foundation for Building A
is constructed, and then moved to that south east location.
FP Response: We will continue to work through the location of the electric meters on Building
A for the next round of responses. I will verify with the mechanical engineer if we create a
larger concrete wall for the stoop, if they would then have the clearance required to function.
04/13/2018