HomeMy WebLinkAboutFile Documents.834 W Hallam St.0010.2018 (54).ARBKChannel Report Hydraflow Express Extension for Autodesk® AutoCAD® Civil 3D® by Autodesk, Inc.Wednesday, Apr 4 2018 17031-Hallam Street Capacity (Q100 Offsite=1.35 cfs) Gutter Cross Sl, Sx (ft/ft)= 0.020 Cross Sl, Sw (ft/ft)= 0.083 Gutter Width (ft)= 2.00 Invert Elev (ft)= 7911.50 Slope (%)= 0.50 N-Value = 0.016 Calculations Compute by:Known Q Known Q (cfs)= 1.35 Highlighted Depth (ft)= 0.28 Q (cfs)= 1.350 Area (sqft)= 0.75 Velocity (ft/s)= 1.79 Wetted Perim (ft)= 8.21 Crit Depth, Yc (ft)= 0.29 Spread Width (ft)= 7.92 EGL (ft)= 0.33 0 2 4 6 8 10 12 14 16 18 20 22 24 Elev (ft)Depth (ft)Section 7911.00 -0.50 7911.50 0.00 7912.00 0.50 7912.50 1.00 7913.00 1.50 Reach (ft) You created this PDF from an application that is not licensed to print to novaPDF printer (http://www.novapdf.com) The estimates Q100 into Hallam Street above this site is 1.35 cfs. This analysis utilizes a longitudinal road slope of 0.5% since the roadway elevation peaks directing in front of the property. The data above and the graph below indicate that the peak flow for the Major Storm Event does not overtop the curb and therefore, the building finish floor elevations do not need to be 12" above the adjacent street curb flowline. 04/13/2018