HomeMy WebLinkAboutFile Documents.427 Rio Grande Pl.0016.2019 (51).ACBKSpace Saver n 7.5 to 240 KW Std n 270 to 360 KW Tall n 25 to 1229 MBH n Section IV ASME up to 160 psi and 250º F Safe • Sure • Simple Lattner Space Saver Electric Hot Water Boilers 06/24/2019 Introduction The Lattner Space Saver - Electric hot water boiler is self- contained and UL Listed for closet and equipment room installation. It requires a minimum amount of floor space and is designed for extended life when used as the primary, supplemental, or standby hydronic heating source. Standard Features VeSSeL ConStruCtion - Vertical ASME section IV, “H” stamped vessel, rated to 160 psi and 250º F. Registered with National Board. enCLoSure - NEMA 1, ventilated control panel with hinged door, key lock and vessel enclosure with removable panels mounted on steel channel base. Heat resistant silicon acrylic enamel protects all surfaces to 180º F. inSuLation - To minimize heat loss, vessel is insulated with four inches of one pound per cubic foot density fiberglass. Safety PreSSure reLief - ASME rated pressure relief valve. HigH Limit Cutout - Manual reset high temperature cutout provides protection in the event of an over temperature condition. Low water Cutoff - Manual reset, probe-type cutout de-energizes boiler on low water condition. External test and manual reset pushbuttons provided to meet CSD-1. ControLS - Fused control transformer with on/off switch and indicator lamp provides control power. Steps ranging from 1 to 8 depending on the size of the boiler. Drain VaLVe - Provided for right side connection as standard, easily accessible from boiler front. gauge - Combination temperature/pressure-indicating gauge is factory installed for front visibility. main SuPPLy terminaLS - Furnished on all boilers for copper conductors. eLement BunDLe - Element bundle utilizes single bend in- coloy elements widely spaced for maximum heat dissipation to reduce lime build-up between passes. Element terminals are double sealed with epoxy and silicone rubber to ensure long life. Elements are individually replaceable. Incoloy will with- stand scaling and temperatures to approximately 1700º F. uL LiSteD - Under file No. E30432. Due to space limitations, some built-in features may not be available in combination with others; consult factory representative.  MODEL KW RANGE GALLONS INLET OUTLET W X D W X D OVERALL H H OVERALL F R                                                                                  46”06/24/2019 Steps and circuits based on 480 3 PH Power Boilers over 4 steps include progressive sequencer Standard controls are DIGITAL PID CONTROLLER For additional capacity, see Lattner Cabinet Series Capacities & Amps CAPACITY KW 7.5 10 15 20 22.5 30 35 37.5 45 50 55 60 67.5 70 75 80 85 90 95 100 105 120 135 150 165 180 195 210 225 240 25.6 34.1 51.2 68.3 76.8 102.4 119.5 128.0 153.6 170.7 187.7 204.8 230.4 238.9 256.0 273.0 290.1 307.2 324.2 341.3 358.4 409.6 460.8 512.0 563.1 614.3 665.5 716.7 767.9 819.1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 5 5 6 6 7 7 8 8 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 5 5 6 6 7 7 8 8 9.0 NA 18.0 NA 27.1 36.1 NA 45.1 54.1 NA NA 72.2 81.2 NA 90.2 NA NA 108.3 NA NA 126.3 144.3 162.4 180.4 198.5 216.5 234.5 252.6 270.6 288.7 31.3 41.7 62.5 83.3 93.8 125.0 145.8 156.3 187.5 208.3 229.2 250.0 281.3 291.7 312.5 333.3 354.2 375.0 395.8 416.7 437.5 500.0 562.5 625.0 687.5 750.0 812.5 875.0 937.5 1000.0 36.1 48.1 72.1 96.2 108.2 144.2 168.3 180.3 216.3 240.4 264.4 288.5 324.5 336.5 360.6 384.6 408.7 432.7 456.7 480.8 504.8 576.9 649.0 721.2 793.3 865.4 937.5 1009.6 1081.7 1153.8 480 490 490 500 500 500 510 530 530 540 540 550 550 560 570 600 600 600 610 625 650 650 760 760 800 950 1000 1120 1200 1300 18.0 NA 36.1 NA 54.1 72.2 NA 90.2 108.3 NA NA 144.3 162.4 NA 180.4 NA NA 216.5 NA NA 252.6 288.7 324.8 360.8 396.9 433.0 469.1 505.2 541.3 577.4 20.8 NA 41.6 NA 62.5 83.3 NA 104.1 124.9 NA NA 166.5 187.4 NA 208.2 NA NA 249.8 NA NA 291.5 333.1 374.7 416.4 458.0 499.6 541.3 582.9 624.5 666.2 MBH NO. STEPS*CIRCUIT(S)**480V, 3Ø 240V, 3Ø 208V, 3Ø 240V, 1Ø 208V, 1Ø AMPS APPROX. WEIGHT LBS. NOTE: * Steps and circuits based on standard 480V/3 phase power. Consult factory for single phase configurations. ** Boilers with 1 to 4 step will include a digital PID temperature controller and relay outputs. Boilers with over 4 steps will include a digital PID temperature controller and progressive sequencer Typical Boiler Piping Diagram SPACE SAVER BOILER Typical Boiler Piping Diagram Capacities & Amps KW MBH Vessel Diameter Inches Vessel Capacity Gallons Steps Circuits AMPs (600/3) AMPs (480/3) AMPs (240/3) AMPs (208/3) AMPs (240/1) Approx Operating Weight (Lbs) Approx Shipping Weight (Lbs) 7.5 26 8 7 1 1 7.2 9.0 18.0 31.3 538 480 15.0 51 8 7 1 1 14.4 18.0 36.1 41.6 62.5 548 490 22.5 77 8 7 1 1 21.7 27.1 54.1 93.8 558 500 30.0 102 8 7 1 1 28.9 36.1 72.2 83.3 125.0 558 500 37.5 128 8 7 2 2 36.1 45.1 90.2 156.3 568 510 45 154 8 7 2 2 43.3 54.1 108.3 124.9 187.5 588 530 52.5 179 8 7 2 2 50.5 63.1 126.3 218.8 598 540 60 205 8 7 2 2 57.7 72.2 144.3 166.5 250.0 598 550 75 256 8 7 3 3 72.2 90.2 180.4 208.2 312.5 628 570 90 307 8 7 3 3 86.6 108.3 216.5 249.8 375.0 658 600 105 358 8 7 4 4 101.0 126.3 252.6 291.5 437.5 708 650 120 410 8 7 4 4 115.5 144.3 288.7 333.1 500.0 708 650 135 461 10 11 4 5 129.9 162.4 324.8 374.7 851 760 150 512 10 11 4 5 144.3 180.4 360.8 416.4 851 760 165 563 10 11 4 6 158.8 198.5 396.9 458.0 891 800 180 614 12 18 4 6 173.2 216.5 433.0 499.6 1099 950 195 666 12 18 4 7 187.6 234.5 469.1 541.3 1149 1000 210 717 12 18 4 7 202.1 252.6 505.2 582.9 1269 1120 225 768 12 18 8 8 216.5 270.6 541.3 624.5 1349 1200 240 819 12 18 8 8 230.9 288.7 577.4 666.2 1449 1300 270 922 12 24 8 12 259.8 324.8 649.5 749.5 1550 1350 292.5 998 12 24 8 13 281.5 352.0 1650 1450 315 1075 12 24 8 14 303.1 379.0 1700 1500 337.5 1152 12 24 8 15 324.8 406.0 1750 1550 360 1229 12 24 8 16 346.4 433.0 1800 160006/24/2019 Sample Specifications 1. furnish and install uL listed Lattner Space Saver electric boiler(s) with capacity and voltage as scheduled, equipment with replaceable incoloy element(s) mounted on a single standard ASA flange. 2. Heating element(s) to be single bend, 75 w/in2 not exceed- ing .425” diameter. Elements to be widely spaced for maximum heat dissipation and individually replaceable from flange for servicing. 3. All control components to be prewired and functionally tested. Components to include: Heavy-duty adjustable controller(s) to maintain water temperature; spring reinforced fuse blocks with Class J or K fuses per 48 ampere circuit; disconnecting break magnetic contacts UL Listed for 200,000 cycles; fuse control transformer; on/off control switch with pilot light indication; indictor lamps for each control stop and safety circuit; properly sized lugs for incoming conductors with electrical knockouts located on right side of control panel; ASME rate pressure relief value; manual rest probe-type low water cutoff; temperature and pressure gauge; high temperature limit with manual reset, air eliminator; and factory mounted drain valve. 4. Pressure vessel to be constructed per aSme Section iV, designed for 160 psi and 250º F, registered with the National Board. Data reports are to be provided. Vessel to insulated for minimum heat loss with a 4” fiberglass blanket rated at 1 pound per cubic foot density and mounted on a 4” steel channel base. 5. unit to include cabinet style ventilated steel enclosure with prewired, ventilated control panel. All surfaces to be corrosion protected with non-oxidizing silicon acrylic enamel heat resistant to 180º F. Optional Features – Select as Required • Interlocking Disconnect • manual Load Limiter/energy Saver • Outdoor Air Reset (Electronically adjusts discharge set-point inversely with changes in outside temperature) • Ammeter (1 or 3 phase, please indicate) • Voltmeter • KWH Energy Meter • Demand Power Limiter • 7 Day Program Clock • ground fault monitor System • Audible alarm for fault annunciation • Interlocking Flow Switch • Building Management Interface packages • NSF approved liner with stainless steel fittings Lattner Boiler Manufacturing Co. Lattner Boiler Mfg. Co. 1411 9th St. S.W. Box 1527 Cedar Rapids, IA 52406 800-345-1527 • 319-366-0778 FA x 319-366-0770 www.lattner.com • e-mail: info@lattner.com Bulletin No. SB 115-17 HOW TO ORDER • model number • KW • Volts / Phase • operating temperature • maximum operating Pressure • gPm • Btu • Inlet and Outlet size (if not using Lattner standard) • optional features S 60 LW - 480 3 Kilowatts Space Saver High / Low Pressure (HW / LW) Voltage Phase model Designation 06/24/2019