HomeMy WebLinkAboutFile Documents.219 N Monarch St.0179.2017 (125).ARBK0179-2017-ARBK_BuildingComments_1
Page: 1
File Name: 1700-24 219 N. Monarch - Permit 7-25-17.pdf
Subject: PlanCheck
Author: nickt
Color:
The special inspection
agreement form must be signed
by the contractor.
1700-24 219 N. Monarch - Permit 7-25-17.pdf (3)
Page: 1
File Name: 1700-24 219 N. Monarch - Permit 7-25-17.pdf
Subject: PlanCheck
Author: nickt
Color:
Revise the special program
schedule on S1.0 to include the
epoxy anchors (2015 IBC
1705.1.1)
Page: 5
File Name: 1700-24 219 N. Monarch - Permit 7-25-17.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a design for the wood
trellis.
Page: [4] 17042-M1.0, M1.1-M1.0
File Name: 17042-Permit-072117.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide cutsheets and
installation instructions for the
dryer booster fan demonstrating
that it is listed to UL 705 and that
the proposed installation is in
compliance with the instructions.
2015 IMC 504.5
17042-Permit-072117.pdf (3)
Page: [4] 17042-M1.0, M1.1-M1.0
File Name: 17042-Permit-072117.pdf
Subject: PlanCheck
Author: nickt
Color:
Show your calculations used to
arrive at the CFM and
%continuous rate for the ERV.
Use this equation from
Ordinance 40, 2016:
Min vent rate = ((0.01 x floor
area) + [7.5 x (#bedrooms + 1)])
x 0.75
Revise control sequence note to
specify the number of hours it
will run for in each 4 hour period.
The special inspection agreement form
must be signed by the contractor.
Revise the specialprogram schedule onS1.0 to include theepoxy anchors (2015IBC 1705.1.1)
Provide a design forthe wood trellis.
7/21/17
Provide cutsheets andinstallation instructionsfor the dryer boosterfan demonstrating thatit is listed to UL 705and that the proposedinstallation is incompliance with theinstructions. 2015 IMC504.5
7/21/17
Show your calculations used to arrive at the CFM and %continuous rate for the ERV. Use thisequation from Ordinance 40, 2016:Min vent rate = ((0.01 x floor area) + [7.5 x (#bedrooms + 1)]) x 0.75Revise control sequence note to specify the number of hours it will run for in each 4 hour period.
SIGNED AND INCLUDED
INCLUDED ON SHEET 21.0
TRELLIS DESIGNED AND SHOWN ON SHEET S2.4 11/27/17
Page: [5] 17042-M1.0, M1.1-M1.1
File Name: 17042-Permit-072117.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a plumbing plan with
isometric (or flatometric)
showing which fixtures will drain
into the lift station sump. Only
those fixtures that cannot drain
to the sewer by gravity may
drain to the lift station. 2015 IPC
712.1
Page: 9
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Revise site plan to dimension
the building from the property
line and locate the building per
the line grade form.
219 N Monarch Permit Set.pdf (31)
Page: 10
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a state demo license
Page: 20
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Line grade form has a typo; 100'
should equal 7897' as shown on
civils.
Page: 31
File Name: 219 N Monarch Permit Set.pdf
Subject: Crawlspace access
Author: nickt
Color:
Provide access to the
crawlspace(s) per 2015 IRC
R408.4. If mechanical equipment
is located inside, access must be
sized and located per 2015 IMC
306. Pay attention to the
maximum distance from access
to equipment.
7/21/17
Provide a plumbingplan with isometric (orflatometric) showingwhich fixtures will draininto the lift stationsump. Only thosefixtures that cannotdrain to the sewer bygravity may drain tothe lift station. 2015IPC 712.1
ON GRADE GROUT SET
PATIO; IMPERVIOUS
PERVIOUS SODDED AREAS
EXIST. TREE; TYP.
789
6
78
9
6
789
PR
PR
O
P
E
R
T
Y
LIN
E
3,076 s
Revise site plan to dimension the
building from the property line
and locate the building per the
line grade form.
DEMO EXIST. STRUCTURE
Provide a state demolicense
Line grade form has atypo; 100' should
equal 7897' as shown
on civils.
004
004
011
010
5
4
2
G
G
F
F
1
3
22'-10"
8'-4"1'-0"3'-8"1'-0"
1'-31/2"
3'-
0
"
1'-
0
"
8'-4"4'-8"1'-0"
1'-
0
"
3'-
0
"
1'-31/2"
001
002
W1 TYP. U.N.O.
W4
W4
8.7
3
1
24
8.7
7
5
68
BEDROOM #4005
BEDROOM #5
001
CLOSET #5
002
CLOSET #4006
A5.1
C5.3
14.3
Provide access to the
crawlspace(s) per
2015 IRC R408.4. If
mechanical equipment
is located inside,
access must be sized
and located per 2015
IMC 306. Pay attention
to the maximum
distance from access
to equipment.
GARAGE DIMENSIONED AND PINNED
ASBESTOS ABATEMENT LICENSE # GAC:468
TYPO CORRECTED
CRAWLSPACE SHOWN ON MECH. PLANS
11/27/17
Page: 32
File Name: 219 N Monarch Permit Set.pdf
Subject: Door landings
Author: nickt
Color:
At all exterior doors, including
upper level decks, provide the
elevation of the landing on each
side of the door and the height of
the threshold above the landings
(this can be spot elevations
and/or details). Doors may not
swing over a greater than 1 1/2"
threshold. Distance from exterior
landing to top of threshold may
be a max of 7 3/4" if door does
not swing over the step. (2015
IRC R311.3)
Page: 32
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Show the location of the electric
panel.
Page: 32
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Revise floor plans to show
window callouts as shown on the
elevations.
Page: 32
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide spot elevations at all
changes in level.
Page: 33
File Name: 219 N Monarch Permit Set.pdf
Subject: Snowstops
Author: nickt
Color:
Provide snow stops at all
locations where roofs could shed
snow onto walkways, stairs,
alleys, decks, exits, utilities,
emergency escape and rescue
opening window wells, or
adjacent properties per
Ordinance 40, 2016.
101101b
5
6
7
4
DE
G F
10'-2"13
'-01/8"
3'-
0
"
51/2"
B5.2
X6.1
14.3
24.3
UP
W2
W5
W3
BREAKFAST
AREA
104
At all exterior doors, including upper level decks,
provide the elevation of the landing on each side
of the door and the height of the threshold above
the landings (this can be spot elevations and/or
details). Doors may not swing over a greater
than 1 1/2" threshold. Distance from exterior
landing to top of threshold may be a max of 7
3/4" if door does not swing over the step. (2015
IRC R311.3)
101
F
3'
-
0
"
51/2"
24.3
UP
W2
BREAKFAST
AREA
104
Show the location of the
electric panel.
AS
P
E
N
,
CO
21
9
MO
1703
ISSUE
PROJECT No:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGN
CORPS LLC. ALL RIGHTS RESERVED
MAIN LEVEL PLAN
04/17/2017SCHEMATIC I SET
05/09/2017SCHEMATIC II SET
05/15/2017RDS
06/28/2017PERMIT SET
5
6
7
4
4'-
6
"
7'
-
3
"
18
'
-
1
0
"
B5.2
TERRACE
110
Revise floor plans to show
window callouts as shown on
the elevations.
1
1 F
X6.1
UP
Provide spot elevations at
all changes in level.
DESIGN CORPSALIUS
DESIGN CORPSALIUS
ASP
E
N
, CO
21
9
MO
N
A
R
C
H
ST
R
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
UPPER LEVEL PLAN
3.3
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
N
201
208
207
204
202
203
205
206
209
210
A
A
55
66
77
44
B
B
C
C
D
D
E
E
22
G
G
F
F
11
33
A5.1A5.1
B5.2 B5.2
X6.1
C5.3C5.3
D5.4
D5.4 15.5
15.5
#DrgID#LayID
14.1
14.3
14.4
24.3
45'-0"
51/2"
6'-3"
51/2"
12'-0
"
51/2"
8'-101/2"
51/2"
12'-2"51/2"2'-1"51/2"4'-10"51/2"8'-7"51/2"14'-7"51/2"
51/2"5'-5"2'-10"8'-53/4"51/2"
51/2"3'-0"
6'-0"
3'-2"
FLATROOF BELOW
DECK201
PLA
T
E
HEIG
H
T
@ 113'-6"
DN
PLATE HEIGHT @ 108'-0"
W6
W5
ELEV.
W1TYP. U.N.O.
W2
W2
W2
PLAT
E
HEIG
H
T
@ 110'-5"
GUEST SUITE206
MASTER BEDROOM201
MASTER CLOSET203
MASTER BATHROOM202
DN
OWNERS CLOSET204
OPEN TOBELOW
GUESTBATHROOM207
GUEST CLOSET #1205
6:12
8:124:12 8:12
0 2'4'8'SCALE: 1/4" = 1'-0"1 UPPER LEVEL PLAN
Provide snow stops atall locations whereroofs could shed snowonto walkways, stairs,alleys, decks, exits,utilities, emergencyescape and rescueopening window wells,or adjacent propertiesper Ordinance 40,2016.
ELEVATIONS PROVIDED ON ALL PLANS
SHOWN IN GARAGE ON SHEET 3.2
NOT NECESSARY PER CONVERSATION WITH NICK
SHOWN ON FLOOR PLANS
SNOW STOPS SHOWN ON ROOF PLAN AND UPPER LEVEL PLAN
11/27/17
Page: 34
File Name: 219 N Monarch Permit Set.pdf
Subject: Fire Area
Author: nickt
Color:
Provide a fire area floor plan
measuring the fire area of the
building. Fire area, as defined by
2015 IBC section 202, is
measured to the inside of
exterior walls but also includes
exterior usable areas that are
covered. Include the area under
the trellis.
Page: 35
File Name: 219 N Monarch Permit Set.pdf
Subject: 75% high efficacy lamps
Author: nickt
Color:
A minimum of 75% of all lamps
installed in permanent light
fixtures must be high efficacy in
dwelling units. Note this
requirement on the plans. (2015
IECC R404.1 & C405.1)
Page: 41
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide a window and door
schedule listing U factors, size,
and which are safety glazed.
The following windows must be
safety glazed per 2015 IRC
R308.4:
104, 105-109, 116, 148, 149,
201-205, 206-210, 224, and 225.
Page: 43
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Window 224 will be unable to
open due to the guard.
Page: 45
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
This callout references 8/7.4
which is a detail at the garage
door. Create a detail for this
condition showing the wall.
E
2
G F
1
3
C5.3
TRELLIS BELOW
LINE OF DECK BELOW
LINE OF ROOF BELOW
4" HALF ROUND
COPPER GUTTER TYP.
PL
SNOW CLIPS
Provide a fire area floor plan
measuring the fire area of the
building. Fire area, as defined by
2015 IBC section 202, is
measured to the inside of exterior
walls but also includes exterior
usable areas that are covered.
Include the area under the trellis.
RR
R
R
R
R
R
R
G F WINE ROOM
010
BATHROOM #1
013
X6.1
A minimum of 75% of all lamps
installed in permanent light fixtures
must be high efficacy in dwelling
units. Note this requirement on the
plans. (2015 IECC R404.1 & C405.1)
DESIGN CO
ALIU
DESIGN CO
ALIU
CH
ST
R
E
E
T
122'-0"ROOF
VERTICAL T&G WOOD
SIDING
WOOD FASCIA
ROOF 217 215216
5 1432
Provide a window and door schedule listing U factors, size,
and which are safety glazed. The following windows must be
safety glazed per 2015 IRC R308.4:
104, 105-109, 116, 148, 149, 201-205, 206-210, 224, and 225.
DESIGN CORPSALIUS
DESIGN CORPSALIUS
AS
P
E
N
, CO
21
9
MO
N
A
R
C
H
ST
R
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
SOUTH ELEVATION
4.3
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
54 6
160 159
158 157
88'-10"LOWER LEVEL 88'-10"LOWER LEVEL
100'-0"MAIN LEVEL 100'-0"MAIN LEVEL
111'-0"UPPER LEVEL 111'-0"UPPER LEVEL
122'-0"ROOF 122'-0"ROOF
VERTICAL T&G WOODSIDING
WOOD FASCIA
DRYSTACK STONEVENEER
LINE OFFINISHED GRADE
229 228 226
150151
227
225
149
152
230231 224
153
154155156
222223
54 6 7213
0 2'4'8'SCALE: 1/4" = 1'-0"2 PARTIAL SOUTH ELEVATION
0 2'4'8'SCALE: 1/4" = 1'-0"1 SOUTH ELEVATION
Window 224 will beunable to open due tothe guard.
107.4
57.4
37.4
87.4
83'-4"
88'-10"
100'-0" ARCH = 7897
111'-0"
GARAGE
BEDROOM #4
UPPER FLOOR T.O. PLY
MAIN FLOOR T.O. PLY
LOWER LEVEL T.O. PLY
CRAWL SPACE T.O. CONC.
F4
F5
A SECTION 'A'
This callout references
8/7.4 which is a detail
at the garage door.
Create a detail for this
condition showing the
wall.
SEE GENERAL CODE NOTES ON
SHEET 1.2
WINDOW SCHEDULE ADJUSTED
ACCORDINGLY THOUGH I DISAGREE
WITH CERTAIN SAFETY NUMBERINGS
NOTED & CORRECTED
DETAIL REFERENCE ADJUSTED
PROVIDED ON SHEET 1.7
11/27/17
Page: 45
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
You have two crawlspaces. The
section drawings show the main
crawl to appear to be within the
thermal envelope but the vertical
crawl that connects two stories
appears to not be within the
thermal envelope. REScheck
shows the crawl as being not
part of the thermal envelope.
Pick an option below for each
crawlspace and coordinate all
drawings:
a.If it will not be part of the
thermal envelope, insulate the
floor and walls between the
crawl and living areas per 2015
IECC R401. Provide ventilation
per 2015 IRC R408.2. Currently
your mechanical plans show that
you provide ventilation to the
main crawlspace only.
b.If the crawl is to be part of the
thermal envelope, insulate the
walls separating the crawl from
the exterior per 2015 IECC
R401. Provide conditioned air to
the crawl per 2015 IRC R408.3
2.2 or ventilate per 2015 IRC
R408.3 2.1 or 2015 IMC 406.1.
Note: you must provide an air
barrier at the thermal envelope
per 2015 IECC table R402.4.1.1.
Also, provide crawlspace
access.
Page: 45
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Provide an air barrier at the
separation between the garage
and the rest of the house. 2015
IECC table R402.4.1.1
Page: 45
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
This callout references 3/7.4
which is a detail at the
foundation wall against grade.
Create a detail for this condition
showing the wall separating the
two crawlspaces.
DESIGN CORPSALIUS
DESIGN CORPSALIUS
ASP
E
N
, CO
21
9
MO
N
A
R
C
H
STR
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
SECTIONS
5.1
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
107.4
57.4
47.4
37.4
97.4
107.3
87.4
83'-4"
88'-10"
100'-0" ARCH = 7897
111'-0"
LINE OF EXISTING GRADE
LINE OF PROPOSED GRADE
GARAGE MUDROOM KITCHEN DINING ROOM POWDERROOM
GUEST SUITEMASTER CLOSETMASTER BEDROOM
GAME ROOMBEDROOM #4 HALL BEDROOM #3
UPPER FLOOR T.O. PLY
MAIN FLOOR T.O. PLY
LOWER LEVEL T.O. PLY
CRAWL SPACE T.O. CONC.
GUEST SUITECLOSET
CRAWLSPACE
AEDCBGF
F5
F2F4
F2
F6
F3F5
0 2'4'8'SCALE: 1/4" = 1'-0"A SECTION 'A'
You have two crawlspaces. The section drawings show the main crawl to appearto be within the thermal envelope but the vertical crawl that connects two storiesappears to not be within the thermal envelope. REScheck shows the crawl asbeing not part of the thermal envelope. Pick an option below for eachcrawlspace and coordinate all drawings: a.If it will not be part of the thermal envelope, insulate the floor and wallsbetween the crawl and living areas per 2015 IECC R401. Provide ventilation per2015 IRC R408.2. Currently your mechanical plans show that you provideventilation to the main crawlspace only.b.If the crawl is to be part of the thermal envelope, insulate the walls separatingthe crawl from the exterior per 2015 IECC R401. Provide conditioned air to thecrawl per 2015 IRC R408.3 2.2 or ventilate per 2015 IRC R408.3 2.1 or 2015IMC 406.1.Note: you must provide an air barrier at the thermal envelope per 2015 IECCtable R402.4.1.1.Also, provide crawlspace access.
107.4
57.4
47.4
37.4
107.3
87.4
83'-4"
88'-10"
100'-0" ARCH = 7897
111'-0"
GARAGE MUDROOM KITCHEN DINING ROOM POWDERROOM
GUEST SUITE
MASTER CLOSET
MASTER BEDROOM
GAME ROOMBEDROOM #4 HALL BEDROOM #3
UPPER FLOOR T.O. PLY
MAIN FLOOR T.O. PLY
LOWER LEVEL T.O. PLY
CRAWL SPACE T.O. CONC.
GUEST SUITECLOSET
CRAWLSPACE
AEDCBGF
F5
F2F4
F2
F6
F3F5
SCALE: 1/4" = 1'-0"A SECTION 'A'
Provide an air barrierat the separation
between the garageand the rest of thehouse. 2015 IECC
table R402.4.1.1
107.4
57.4
37.4
87.4
83'-4"
88'-10"
100'-0" ARCH = 7897
111'-0"
GARAGE
BEDROOM #4
UPPER FLOOR T.O. PLY
MAIN FLOOR T.O. PLY
LOWER LEVEL T.O. PLY
CRAWL SPACE T.O. CONC.
F4
F5
SCALE: 1/4" = 1'-0"A SECTION 'A'
This callout references
3/7.4 which is a detail
at the foundation wall
against grade. Create
a detail for this
condition showing the
wall separating the
two crawlspaces.
BACKFILLED VERTICAL CRAWLSPACE
REVISED
11/27/17
Page: 45
File Name: 219 N Monarch Permit Set.pdf
Subject: Air sealing general note
Author: nickt
Color:
Indicate in your sections and
details how you will accomplish
the air sealing requirements of
2015 IECC table R402.4.1.1.
Indicate the continuity of the air
barrier and where it is located
throughout the building. Note
locations that require caulking,
sealing, taping, etc. Note which
components are included in the
air barrier such as spray foam,
gypsum, housewrap, and/or
exterior insulation. You may
have all of the above but you
need to pick one continuous
barrier and stick to it. It needs to
follow the thermal barrier. The
better detail you provide, the
easier it will be for the contractor
and inspector to be successful.
This is a new 2015 code
requirement in lieu of a blower
door test. Contact me to discuss.
Page: 45
File Name: 219 N Monarch Permit Set.pdf
Subject: Attic access
Author: nickt
Color:
Provide access to all attics.
Show hatches on RCPs. 2015
IRC R807
Page: 48
File Name: 219 N Monarch Permit Set.pdf
Subject: Attic access
Author: nickt
Color:
Provide access to all attics.
Show hatches on RCPs. 2015
IRC R807
Page: 48
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Detail 9/7.4 does not appear on
sheet 7.4.
107.4
57.4
87.4
100'-0" ARCH = 7897
111'-0"
GARAGE
UPPER FLOOR T.O. PLY
MAIN FLOOR T.O. PLY
G F
F4
F5
Indicate in your sections and details how you will
accomplish the air sealing requirements of 2015 IECC
table R402.4.1.1. Indicate the continuity of the air barrier
and where it is located throughout the building. Note
locations that require caulking, sealing, taping, etc. Note
which components are included in the air barrier such as
spray foam, gypsum, housewrap, and/or exterior
insulation. You may have all of the above but you need to
pick one continuous barrier and stick to it. It needs to
follow the thermal barrier. The better detail you provide,
the easier it will be for the contractor and inspector to be
successful. This is a new 2015 code requirement in lieu
of a blower door test. Contact me to discuss.
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS
AS
P
E
N
,
CO
21
9
MO
N
A
R
C
H
ST
R
E
E
T
ISSUEDRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
04/17/2017SCHEMATIC I SET
05/09/2017SCHEMATIC II SET 05/15/2017RDS
06/28/2017PERMIT SET
57.4
47.4
97.4
107.3
LINE OF EXISTING GRADE
LINE OF PROPOSED GRADE
GARAGE MUDROOM KITCHEN DINING ROOM POWDERROOM
GUEST SUITE
MASTER CLOSET
MASTER BEDROOM
GAME ROOMBEDROOM #4 HALL BEDROOM #3
GUEST SUITECLOSET
AEDCBF
F5
F2F4
F2
F3F5
Provide access to allattics. Show hatcheson RCPs. 2015 IRCR807
567 4 2 13
97.4
137.3
97.3
77.3
117.3
88'-10"
100'-0"
MAIN LEVEL
111'-0"UPPER LEVEL
122'-0"ROOF
MASTER CLOSET
LIVING ROOM
DINING
LIVINIG ROOMFITNESS STAIR
MASTERFOYER
F2
F7
F2
Provide access to allattics. Show hatcheson RCPs. 2015 IRCR807
97.4
7.3
LIVING ROOM
FITNESS
Detail 9/7.4 does not
appear on sheet 7.4.
PROVIDED AND NOTED ON RCP'S
PROVIDED AND SHOWN ON RCP'S
LINKED TO THE RIGHT DETAIL
11/27/17
Page: 51
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Tyvek Thermawrap R5 is
compressible- this means that
when the wood siding is installed
over it, it will be flattened and
lose its R value. If you use
furring strips, it will only be
compressed at the strips-
making it cavity insulation (not
continuous). Revise details
and/or REScheck to work
together. (Also, won't you see
the white tyvek through the 1/4"
gaps in the siding?)
Page: 51
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Your above grade exterior walls
must have R-5 continuous
insulation in addition to the
cavity insulation to match your
REScheck. Revise all details as
necessary.
Page: 51
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
REScheck shows basement
walls with R-15 continuous
insulation. Revise all drawings to
match this or revise the
REScheck.
Page: 52
File Name: 219 N Monarch Permit Set.pdf
Subject: Class A Roof
Author: nickt
Color:
Provide documentation that the
roof assemblies are Class A.
This is typically either an ESR or
UL report. Revise you roof
details to match the reports.
(Ordinance 40, 2016)
Page: 53
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Include the wall separating the
crawl from the living space in the
REScheck.
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS
AS
P
E
N
, CO
21
9
MO
N
A
R
C
H
S
T
R
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
WALL ASSEMBLIES
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET
05/15/2017RDS
06/28/2017PERMIT SET
1 1/2"SEE PLAN 3 1/2"5/8"
1/2"5 1/2"5/8"
5/8"SEE PLAN5/8"
1/2" EXT. GRADE SHEATHING
WALL FRAMING W/ BLOCKING AS REQUIRED
R-28 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
TYVEK THERMAWRAP R-5 CONTINUOUSINSULATION
VERTICAL WOOD SIDING @ 5" O.C. - LEAVE 1/4" GAP
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
GROUT & JOINTS PER APPROVED MOCK-UP
BACKFILL W/ SCREENED GRAVEL
R-11 RIGID INSULATION
FIBERGLASS FILTER CLOTH
CONC. WALL RE: STRUCT.
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
FOUNDATION WATERPROOFING - CONTINUE TO BOTTOMOF FOOTING (SHOWN DASHED)
6" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
R-13 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
WALL FRAMING W/ BLOCKING AS REQUIRED
SOUND ATTENUATING INSULATION - REFER TO SPECS
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
GROUT & JOINTS PER APPROVED MOCK-UP
WALL FRAMING W/BLOCKING AS REQUIRED
1/2" EXT. GRADE SHEATHING
BUILDING WRAP/ PAPER
3" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
MIN. 1" AIR OR MORTAR SPACE
GROUT & JOINTS PER APPROVED MOCK-UP
3" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
TYVEK THERMAWRAP R-5 CONTINUOUSINSULATION
WALL DETAIL & ASSEMBLY TEMPLATE
1 ½" = 1'-0"INTERIOR WALL (TYPICAL)W1
1 ½" = 1'-0"W2
½" = 1'-0"NSULATED FOUNDATION WALL W/ FURRING
EXTERIOR STUD WALL W/ VERTICAL SIDING
GL
GL
GL
½" = 1'-0"
GL
GL
½" = 1'-0"EXTERIOR STUD WALL W/ STONE VENEER @ STAIR
GL
WALL FRAMING W/ BLOCKING AS REQUIRED
Tyvek Thermawrap R5 iscompressible- this means thatwhen the wood siding isinstalled over it, it will beflattened and lose its R value. Ifyou use furring strips, it will onlybe compressed at the strips-making it cavity insulation (notcontinuous). Revise detailsand/or REScheck to worktogether. (Also, won't you seethe white tyvek through the 1/4"gaps in the siding?)
DESIGN CORPSALIUS
DESIGN CORPSALIUS
ASP
E
N
, CO
21
9
MO
N
A
R
C
H
S
T
R
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
WALL ASSEMBLIES
7.2
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
1/2"5 1/2"5/8"
1 1/2"SEE PLAN 3 1/2"5/8"3"1/2"5 1/2"3"5/8"
1/2"5 1/2"5/8"
5/8"SEE PLAN5/8"
2"SEE PLAN
1/2" EXT. GRADE SHEATHING
WALL FRAMING W/ BLOCKING AS REQUIRED
R-28 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
TYVEK THERMAWRAP R-5 CONTINUOUSINSULATION
VERTICAL WOOD SIDING @ 5" O.C. - LEAVE 1/4" GAP
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
GROUT & JOINTS PER APPROVED MOCK-UP
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
WALL FRAMING W/BLOCKING AS REQUIRED
1/2" EXT. GRADE SHEATHING
BUILDING WRAP/ PAPER
R-28 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
BACKFILL W/ SCREENED GRAVEL
R-11 RIGID INSULATION
FIBERGLASS FILTER CLOTH
CONC. WALL RE: STRUCT.
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
FOUNDATION WATERPROOFING - CONTINUE TO BOTTOMOF FOOTING (SHOWN DASHED)
6" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
MIN. 1" AIR OR MORTAR SPACE
GROUT & JOINTS PER APPROVED MOCK-UP
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
WALL FRAMING W/BLOCKING AS REQUIRED
1/2" EXT. GRADE SHEATHING
BUILDING WRAP/ PAPER
R-24 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
3" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
MIN. 1" AIR OR MORTAR SPACE
3" FURRING
R-13 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
WALL FRAMING W/ BLOCKING AS REQUIRED
SOUND ATTENUATING INSULATION - REFER TO SPECS
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
GROUT & JOINTS PER APPROVED MOCK-UP
WALL FRAMING W/BLOCKING AS REQUIRED
1/2" EXT. GRADE SHEATHING
BUILDING WRAP/ PAPER
3" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
MIN. 1" AIR OR MORTAR SPACE
GROUT & JOINTS PER APPROVED MOCK-UP
WALL FRAMING W/BLOCKING AS REQUIRED
1/2" EXT. GRADE SHEATHING
BUILDING WRAP/ PAPER
3" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
MIN. 1" AIR OR MORTAR SPACE
VERTICAL WOOD SIDING @ 5" O.C. - LEAVE 1/4" GAP
FOUNDATION WATERPROOFINGCONTINUE TO BOTTOM OFFOOTING (SHOWN DASHED)4" DIAMETER A.B.S PERFORATEDFOUNDATION DRAIN
FIBERGLASS FILTER CLOTH
BACKFILL W/ SCREENED GRAVEL
R-11 RIGID INSULATION
CONC. WALL RE: STRUCT.
SLAB @ CRAWL SPACE RE: STRUCT.
TYVEK THERMAWRAP R-5 CONTINUOUSINSULATION
1 1/2" WALL DETAIL & ASSEMBLY TEMPLATE
1 ½" = 1'-0"INTERIOR WALL (TYPICAL)W1
1 ½" = 1'-0"W3 EXTERIOR STUD WALL W/ STONE VENEER
1 ½" = 1'-0"W2
1 ½" = 1'-0"INSULATED FOUNDATION WALL W/ FURRINGW4
EXTERIOR STUD WALL W/ VERTICAL SIDING
GL
GL
GL
1 ½" = 1'-0"1 ½" = 1'-0"W7EXTERIOR STUD WALL W/ STONE VENEER @ STAIRS
GL GL
GL
1 ½" = 1'-0"W5 EXTERIOR STUD WALL W/ STONE VENEER @ STAIR
GL
1 ½" = 1'-0"W6 EXTERIOR STUD WALL W/ STONE VENEER @ DECK
1 TYPICAL FOOTER CONDITION1 ½" = 1'-0"
GL
WALL FRAMING W/ BLOCKING AS REQUIRED
Your above gradeexterior walls musthave R-5 continuousinsulation in addition tothe cavity insulation tomatch your REScheck.Revise all details asnecessary.
DESIGN CORPS
ALIUS
DESIGN CORPS
ALIUS
AS
P
E
N
, CO
21
9
MO
N
A
R
C
H
S
T
R
E
E
T
ISSUEDRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
WALL ASSEMBLIES
04/17/2017SCHEMATIC I SET
05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
1 1/2"SEE PLAN 3 1/2"5/8"3"1/2"5 1/2"3"5/8"
1/2"5 1/2"5/8"
5/8"SEE PLAN5/8"
2"SEE PLAN
1/2" EXT. GRADE SHEATHING
WALL FRAMING W/ BLOCKING AS REQUIRED
R-28 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
TYVEK THERMAWRAP R-5 CONTINUOUSINSULATION
VERTICAL WOOD SIDING @ 5" O.C. - LEAVE 1/4" GAP
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
BACKFILL W/ SCREENED GRAVEL
R-11 RIGID INSULATION
FIBERGLASS FILTER CLOTH
CONC. WALL RE: STRUCT.
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
FOUNDATION WATERPROOFING - CONTINUE TO BOTTOMOF FOOTING (SHOWN DASHED)GROUT & JOINTS PER APPROVED MOCK-UP
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
WALL FRAMING W/BLOCKING AS REQUIRED
1/2" EXT. GRADE SHEATHING
BUILDING WRAP/ PAPER
R-24 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
3" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
MIN. 1" AIR OR MORTAR SPACE
3" FURRING
R-13 SPRAY-IN RIGID CLOSED-CELL INSULATION (ACTS ASVAPOR BARRIER)
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
WALL FRAMING W/ BLOCKING AS REQUIRED
SOUND ATTENUATING INSULATION - REFER TO SPECS
5/8" GYPSUM WALL BOARD OR OTHER INTERIOR FINISH -SEE SCHEDULE
GROUT & JOINTS PER APPROVED MOCK-UP
WALL FRAMING W/BLOCKING AS REQUIRED
1/2" EXT. GRADE SHEATHING
BUILDING WRAP/ PAPER
3" (NOMINAL) STONE VENEER
MTL. WALL TIES PER I.R.C. CHAPTER 7
MIN. 1" AIR OR MORTAR SPACE
FOUNDATION WATERPROOFINGCONTINUE TO BOTTOM OFFOOTING (SHOWN DASHED)4" DIAMETER A.B.S PERFORATEDFOUNDATION DRAIN
FIBERGLASS FILTER CLOTH
BACKFILL W/ SCREENED GRAVEL
R-11 RIGID INSULATION
CONC. WALL RE: STRUCT.
SLAB @ CRAWL SPACE RE: STRUCT.
1 1/2" WALL DETAIL & ASSEMBLY TEMPLATE
1 ½" = 1'-0"INTERIOR WALL (TYPICAL)W1
1 ½" = 1'-0"W2
1 ½" = 1'-0"INSULATED FOUNDATION WALL W/ FURRINGW4
EXTERIOR STUD WALL W/ VERTICAL SIDING
GL
GL
GL
1 ½" = 1'-0"1 ½" = 1'-0"W7 EXTERIOR STUD WALL W/ STONE VENEER @ STAIRS
GL GL
GL
1 ½" = 1'-0"W5 EXTERIOR STUD WALL W/ STONE VENEER @ STAIR
GL
1 TYPICAL FOOTER CONDITION1 ½" = 1'-0"
GL
WALL FRAMING W/ BLOCKING AS REQUIRED
REScheck showsbasement walls withR-15 continuousinsulation. Revise alldrawings to match thisor revise theREScheck.
DES
A
DR
COP
COR
RO
SC
SC
RD
PE
SEE INTERIOR SPECIFICATIONS FORFINISH MATERIAL
5/8" C/DX PLYWOOD SHEATHING
SYNTHETIC SHINGLES
5/8" GYP. BD. CEILING - TYP OVERHEATED SPACES
VAPOR BARRIER ATATTICE SPACE ONLY
8" R7/INCH BLOWN-IN POLY-ISO INSULATION(R-56 TOTAL)
RAFTER RE:STRUCTURAL
BITUMINOUS WATERPROOFMEMBRANE (FULL COVERAGE)- HIGH TEMPERATURE
TYPICAL FLAT MEMBRANE ROOFR11 ½" = 1'-0"
1 ½" = 1'-0"R2 TYPICAL ROOF W/ SHINGLES
Provide documentation that the roof
assemblies are Class A. This is typically
either an ESR or UL report. Revise you
roof details to match the reports.
(Ordinance 40, 2016)
DESIGN CORPSALIUS
DESIGN CORPSALIUS
AS
P
E
N
, CO
21
9
MO
N
A
R
C
H
ST
R
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
WALL ASSEMBLIES &DETAILS
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
2 63/64"SEE PLAN 2 63/64"
2"SEE PLAN3 1/2"5/8"
5 1/2"5/8"
5/8" GYPSUM WALL BOARD OR OTHERINTERIOR FINISH - SEE SCHEDULE
WALL FRAMING W/ BLOCKING ASREQUIRED
R-28 SPRAY-IN RIGID CLOSED-CELLINSULATION (ACTS AS VAPOR BARRIER)
CONC. WALL RE: STRUCT.
MTL. WALL TIES @ (1)PER 2 SQ. FT. MAX. -NON-CORRUGATED
GROUT & JOINTS PER APPROVED MOCK-UP
3" (NOMINAL) STONE VENEER
FOUNDATIONWATERPROOFINGCONTINUE TO BOTTOMOF FOOTING (SHOWNDASHED)4" DIAMETER A.B.SPERFORATEDFOUNDATION DRAIN
FIBERGLASS FILTER CLOTH
BACKFILL W/ SCREENEDGRAVEL
R-11 RIGID INSULATION
WALL FRAMING W/BLOCKING AS REQUIRED
CONC. WALL RE:STRUCT.
5/8" GYPSUM WALL BOARDOROTHER INTERIOR FINISH -SEE SCHEDULE
SEE PLAN FOR FLOORING TYPE
GRADE PER LANDSCAPE PLAN
.3
1 ½" = 1'-0"INTERIOR WALL @ CRAWLSPACEW13
1 ½" = 1'-0"W14 RETAINING WALL W/ STONE VENEER
1 1/2" WALL DETAIL & ASSEMBLY TEMPLATE
GL
GL
7 TYPICAL FOOTER CONDITION1 ½" = 1'-0"
GL
LIVING SPACECRAWLSPACE
Include the wallseparating the crawlfrom the living spacein the REScheck.
REMOVED FROM DETAIL AND
RESCHECK
NO LONGER REQUIRED PER RESCHECK
DRAWINGS SHOW R-15
NO LONGER APPLICABLE, BACKFILLED
11/27/17
Page: 53
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Details 1/7.2 and 7/7.4 show the
same footer condition differently.
One shows what appears to be
an insulated crawl, another a
non-insulated crawl. Coordinate
your drawings.
Page: 54
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Revise stone veneer details to
provide weeps per 2015 IRC
R703.8.5.
Page: 54
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
The roof plan suggests the roof
deck is sloped to a central drain.
How is the slope provided?
Revise 4/A7.4 to provide greater
detail on waterproofing and
drainage.
Page: 55
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
Window details on 7.5 reference
stucco that is not shown
anywhere else. If there is to be
stucco on this project, revise
elevations, wall sections, and
details. Label if it is EIFS or
cementitious. If using EIFS,
provide a drainage plane or it will
require special inspection (2015
IBC 1704). If no stucco, update
your window details.
Page: 72
File Name: 219 N Monarch Permit Set.pdf
Subject: PlanCheck
Author: nickt
Color:
The following windows must be
safety glazed per 2015 IRC
R308.4. Revise the window
schedule on 10.1.
104, 105-109, 116, 148, 149,
201-210, 224, 225.
DESIGN CORPSALIUS
DESIGN CORPSALIUS
AS
P
E
N
, CO
21
9
MO
N
A
R
C
H
ST
R
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
WALL ASSEMBLIES &DETAILS
7.4
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
2 63/64"SEE PLAN 2 63/64"
2"SEE PLAN3 1/2"5/8"
5 1/2"5/8"
5/8" GYPSUM WALL BOARD OR OTHERINTERIOR FINISH - SEE SCHEDULE
WALL FRAMING W/ BLOCKING ASREQUIRED
R-28 SPRAY-IN RIGID CLOSED-CELLINSULATION (ACTS AS VAPOR BARRIER)
CONC. WALL RE: STRUCT.
MTL. WALL TIES @ (1)PER 2 SQ. FT. MAX. -NON-CORRUGATED
GROUT & JOINTS PER APPROVED MOCK-UP
3" (NOMINAL) STONE VENEER
FOUNDATIONWATERPROOFINGCONTINUE TO BOTTOMOF FOOTING (SHOWNDASHED)4" DIAMETER A.B.SPERFORATEDFOUNDATION DRAIN
FIBERGLASS FILTER CLOTH
BACKFILL W/ SCREENEDGRAVEL
R-11 RIGID INSULATION
WALL FRAMING W/BLOCKING AS REQUIRED
CONC. WALL RE:STRUCT.
5/8" GYPSUM WALL BOARDOROTHER INTERIOR FINISH -SEE SCHEDULE
SEE PLAN FOR FLOORING TYPE
GRADE PER LANDSCAPE PLAN
7.3
1 ½" = 1'-0"INTERIOR WALL @ CRAWLSPACEW13
1 ½" = 1'-0"W14RETAINING WALL W/ STONE VENEER
1 1/2" WALL DETAIL & ASSEMBLY TEMPLATE
GL
GL
7 TYPICAL FOOTER CONDITION1 ½" = 1'-0"
GL
LIVING SPACECRAWLSPACE
Details 1/7.2 and 7/7.4 show thesame footer condition differently.One shows what appears to be aninsulated crawl, another anon-insulated crawl. Coordinateyour drawings.
2"SEE P
FOUNDATION WATERPROOFINGCONTINUE TO BOTTOM OFFOOTING (SHOWN DASHED)
4" DIAMETER A.B.S PERFORATEDFOUNDATION DRAIN
FINISH GRADE SLOPE AWAY
WATERPROOFING WRAPPEDUNDER CAP STONE(SHOWN DASHED)
MTL. WALL TIES @ (1) PER 2SQ. FT. MAX. - NON-CORRUGATED
3" (NOMINAL) STONEVENEER
METAL DRIP
GROUT & JOINTS PERAPPROVED MOCK-UP
WATERPROOFING
SHEATHING
METAL DRIP
7.4
7 TYPICAL FOOTER CON 1 ½" = 1'-0"
GL
GL
PLANTER DETAIL101 ½" = 1'-0"
3/4" PLYWOOD
Revise stone veneer details to provide weeps per 2015 IRC
R703.8.5.
2"SEE PLAN 3 1/2"5/8"
FOUNDATION WATERPROOFINGCONTINUE TO BOTTOM OFFOOTING (SHOWN DASHED)
4" DIAMETER A.B.S PERFORATEDFOUNDATION DRAIN
FIBERGLASS FILTER CLOTH
BACKFILL W/ SCREENED GRAVEL
R-11 RIGID INSULATION
WALL FRAMING W/BLOCKING AS REQUIRED
CONC. WALL RE: STRUCT.
5/8" GYPSUM WALL BOARD OROTHER INTERIOR FINISH -SEE SCHEDULE
SEE PLAN FOR FLOORING TYPE
SHEATHINGWATERPROOFING
METAL DRIP
MTL. WALL TIES @ (1) PER 2SQ. FT. MAX. - NON-CORRUGATED
GROUT & JOINTS PERAPPROVED MOCK-UP
3" (NOMINAL) STONEVENEER
HSS UNDER STONE; SEE STRUCTURAL FOR SIZE
STEEL BEAM, PACK OUT AS REQD; SEESTRUCTURAL
3/4" PLYWOOD
STEEL BEAM, PACK OUT AS REQD; SEESTRUCTURAL
3/4" PLYWOOD
CONC SLAB; SEE STRUCTURAL
14" WOOD JOIST; SEESTRUCTURAL
5/8" GYPSUM WALL BOARD;SEE SCHEDULE
FOUNDATION WATERPROOFINGCONTINUE TO BOTTOM OFFOOTING
BACKFILL W/ SCREENED GRAVEL
R-11 RIGID INSULATION
WALL FRAMING W/BLOCKING AS REQUIRED
CONC. WALL RE: STRUCT.
5/8" GYPSUM WALL BOARD,SEE SCHEDULE
METAL DRIP
DECKING
WATERPROOFING
HSS UNDER STONE; SEESTRUCTURAL FOR SIZE
WRAP WATERPROOFING AT STEELHSS
WATERPROOFING
SHEATHING
MTL. WALL TIES @ (1) PER 2 SQ.FT. MAX. - NON-CORRUGATED
3" (NOMINAL) STONE VENEER
METAL DRIP
SIMPSON MTL HANGE
STEEL BEAM, PACK O STRUCTURAL
6" SOUND-
FINISH GRADE SLOPE AWAY
CONCRETE TOPPING
CONCRETE DECKING CONCRETE
STONE AT P
3/4" PLYWO
WATERPRO
.4
1 1/2" WALL DETAIL & ASSEMBLY TE
7 TYPICAL FOOTER CONDITION1 ½" = 1'-0"
GL
T. O. PLYWOOD100'-0"T. O. SLAB99'-7"
T. O. STRUCTURE99'-2"
DECK TRANSITION DETAIL41 ½" = 1'-0"
GARAGE ENTRY
DECK MASTER
PATIO TRANSITION DETAIL11 ½" = 1'-0"
GL
T. O. PLYWOOD111'-0"
T. O. PLYWOOD110'-10"
EXTERIOR LIVING ROOM
T. O. 99'-4
14" WOOD JOIST; SEESTRUCTURAL
14" WOOD JOIST; SEE
The roof plan
suggests the roof deck
is sloped to a centraldrain. How is the slopeprovided? Revise4/A7.4 to provide
greater detail on
waterproofing and
drainage.
DESIGN CORPSALIUS
DESIGN CORPSALIUS
ASP
E
N
, CO
21
9
MO
N
A
R
C
H
STR
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
WINDOW DETAILS
7.5
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
1 1/4"
1 1/4"3 49/64
"
3 3/4"
3 3/4"
WINDOW TRIM
WOOD TRIM PER INTERIORSPECIFICATIONS
WINDOW TRIM
JAMB EXTENSION
WOOD CASING PERINTERIOR SPECIFICATIONS
WOOD CASING PERINTERIOR SPECIFICATIONS
WOOD TRIM PER INTERIORSPECIFICATIONS
JAMB EXTENSION
WOOD CASING PERINTERIOR SPECIFICATIONS
WOOD CASING PERINTERIOR SPECIFICATIONS
WINDOW HEAD FLASHING- INSTALL PER STUCCOMANUFACTURER'SSPECIFICATIONS
EXPANDED FLANGECASING BEADBACKER ROD & SEALANT
LAHABRA BRAND STUCCOINSTALLED PER SPECS-SANTA BARBARA FINISHCOAT -COLOR TBD
SILL PAN
LAHABRA BRAND STUCCOINSTALLED PER SPECS-SANTA BARBARA FINISHCOAT -COLOR TBD
EXPANDED FLANGECASING BEAD
BACKER ROD & SEALANT
STONE SILL
WOOD TRIM PER INTERIORSPECIFICATIONS
JAMB EXTENSION
WOOD CASING PERINTERIOR SPECIFICATIONS
WOOD CASING PERINTERIOR SPECIFICATIONS
STEEL C-CHANNEL HEADER
BACKER ROD & SEALANT
HEAD FLASHING
BACKER ROD & SEALANT
BACKER ROD & SEALANT
BACKER ROD & SEALANT
WINDOW HEAD FLASHINGSEALANT
SEALANT
SEALANT
7.5
1 3" = 1'-0"
3" = 1'-0"2
3" = 1'-0"3
WINDOW HEAD @ HORIZONTAL WOOD SIDING
WINDOW JAMB @ HORIZONTAL WOOD SIDING
WINDOW SILL @ HORIZONTAL WOOD SIDING
GL
GL
GL
3" WINDOW TEMPLATE
4 3" = 1'-0"
3" = 1'-0"5
3" = 1'-0"6
WINDOW HEAD @ STUCCO
WINDOW JAMB @ STUCCO
WINDOW SILL @ STUCCO
GL
GL
GL
7 3" = 1'-0"
3" = 1'-0"8
3" = 1'-0"9
WINDOW HEAD @ STONE
WINDOW JAMB @ STONE
WINDOW SILL @ STONE
GL
GL
GL
Window details on 7.5reference stucco thatis not shownanywhere else. If thereis to be stucco on thisproject, reviseelevations, wallsections, and details.Label if it is EIFS orcementitious. If usingEIFS, provide adrainage plane or itwill require specialinspection (2015 IBC1704). If no stucco,update your windowdetails.
DESIGN CORPSALIUS
DESIGN CORPSALIUS
ASP
E
N
, CO
219
MON
A
R
C
H
STR
E
E
T
MTE1703
ISSUE
PROJECT No:DRAWN BY:
DRAWING SET
COPYRIGHT 2017 ALIUS DESIGNCORPS LLC. ALL RIGHTS RESERVED
DOOR & WINDOWSCHEDULES
10.1
04/17/2017SCHEMATIC I SET 05/09/2017SCHEMATIC II SET 05/15/2017RDS06/28/2017PERMIT SET
WIDTH HEIGHTSILL HEIGHT001CASEMENT3'-0"4'-0"36"12 EGRESS002CASEMENT3'-0"4'-0"36"12 EGRESS003CASEMENT3'-0"4'-0"36"12 EGRESS004CASEMENT3'-0"4'-0"36"12 EGRESS005CASEMENT3'-0"4'-0"36"12 EGRESS101CASEMENT3'-0"6'-0"102CASEMENT 3'-0"6'-0"103CASEMENT 3'-0"6'-0"104CASEMENT 3'-0"4'-0"105FIXED 3'-0"6'-0"TEMPERED GLASS106FIXED3'-0"6'-0"TEMPERED GLASS107FIXED3'-0"6'-0"TEMPERED GLASS108FIXED3'-0"6'-0"TEMPERED GLASS109FIXED3'-0"6'-0"TEMPERED GLASS110CASEMENT3'-0"6'-0"111CASEMENT 3'-0"6'-0"112CASEMENT 3'-0"6'-0"113CASEMENT 3'-0"6'-0"114CASEMENT 3'-0"6'-0"115CASEMENT 3'-0"2'-6"5'-5 1/4"116FIXED 2'-0"8'-2 1/4"4"117AWNING 3'-0"2'-0"118AWNING 3'-0"2'-0"119CASEMENT 3'-0"6'-0"120CASEMENT 3'-0"6'-0"121FIXED 3'-0"2'-0"122FIXED 3'-0"2'-0"123AWNING 3'-0"2'-0"124AWNING 3'-0"6'-0"125CASEMENT 3'-0"6'-0"126CASEMENT 3'-0"2'-0"127FIXED 3'-0"2'-0"128FIXED 3'-0"2'-0"129CASEMENT 3'-0"6'-0"130AWNING 3'-0"2'-0"131AWNING 3'-0"2'-0"132CASEMENT 3'-0"6'-0"133CASEMENT 3'-0"6'-0"134FIXED 3'-0"2'-0"135FIXED 3'-0"2'-0"136AWNING 3'-0"2'-0"137AWNING 3'-0"2'-0"138CASEMENT 3'-0"6'-0"139CASEMENT 3'-0"6'-0"140FIXED 3'-0"2'-0"141FIXED 3'-0"2'-0"142FIXED 3'-0"6'-0"143FIXED 3'-0"6'-0"144FIXED 3'-0"6'-0"145FIXED 3'-0"6'-0"146FIXED 3'-0"6'-0"147FIXED 3'-0"6'-0"148CASEMENT 3'-0"6'-0"149FIXED 3'-0"6'-0"150FIXED 3'-0"4'-0"151FIXED 3'-0"4'-0"152FIXED 3'-0"4'-0"153FIXED 3'-0"2'-8"154FIXED 3'-0"2'-8"155FIXED 3'-0"4'-0"156FIXED 3'-0"4'-0"157FIXED 3'-0"4'-0"158FIXED 3'-0"4'-0"
WINDOW SCHEDULE
ID AREASIZE COMMENTSSTYLE
201FIXED 3'-0"6'-0"202FIXED 3'-0"6'-0"203FIXED 3'-0"6'-0"204FIXED 3'-0"6'-0"205FIXED 3'-0"6'-0"206FIXED 3'-0"6'-0"207FIXED 3'-0"6'-0"208FIXED 3'-0"6'-0"209FIXED 3'-0"6'-0"210FIXED 3'-0"6'-0"211CASEMENT 3'-0"6'-0"212CASEMENT 3'-0"6'-0"213CASEMENT 3'-0"6'-0"214CASEMENT 3'-0"2'-0"215FIXED 3'-0"2'-0"216FIXED 3'-0"2'-0"217FIXED 3'-0"2'-0"218CASEMENT 3'-0"6'-0"219CASEMENT 3'-0"6'-0"220CASEMENT 3'-0"6'-0"221FIXED 3'-0"6'-0"222FIXED 3'-0"6'-0"223CASEMENT 3'-0"6'-0"224CASEMENT 3'-0"6'-0"225CASEMENT 3'-0"6'-0"226FIXED 3'-0"2'-0"227FIXED 3'-0"2'-0"228FIXED 3'-0"2'-0"229FIXED 3'-0"2'-0"230CASEMENT 3'-0"6'-0"231CASEMENT 3'-0"6'-0"
WIDTH HEIGHTLOWER LEVEL0012'-8"8'-0"WOODLOWER LEVEL0023'-0"8'-0"WOODLOWER LEVEL002a2'-10"8'-0"GLASS SAPHIRE GLASS SHOWER DOORLOWER LEVEL0035'-0"8'-0"WOOD DOUBLE POCKET DOORLOWER LEVEL0042'-8"8'-0"LOWER LEVEL0052'-8"8'-0"LOWER LEVEL005a2'-10"8'-0"GLASS SAPHIRE GLASS SHOWER DOORLOWER LEVEL0072'-8"8'-0"LOWER LEVEL007a5'-8"8'-0"DOUBLE SWING DOORLOWER LEVEL0082'-8"8'-0"LOWER LEVEL008a2'-10"8'-0"GLASS SAPHIRE GLASS SHOWER DOORLOWER LEVEL0092'-8"8'-0"MAIN LEVEL 1012'-6"6'-8"MAIN LEVEL 101a8'-0"8'-0"MAIN LEVEL 101b8'-0"8'-0"MAIN LEVEL 1025'-0"8'-0"DOUBLE SWING DOORMAIN LEVEL 1065'-9 1/2"7'-8 3/4"MAIN LEVEL 106a5'-9 1/2"7'-8 3/4"MAIN LEVEL 1073'-0"8'-0"MAIN LEVEL 107a2'-10"8'-0"DOUBLE SWING DOORMAIN LEVEL 107b5'-0"8'-0"DOUBLE SWING DOORMAIN LEVEL 1082'-6"8'-0"WOOD POCKETMAIN LEVEL 108a4'-10"8'-0"WOOD POCKETMAIN LEVEL 108b3'-0"8'-0"GLASS SAPHIRE GLASS SHOWER DOORMAIN LEVEL 1093'-0"8'-0"METAL/GLASS EXTERIOR DOORUPPER LEVEL 2013'-0"8'-0"METAL/GLASS EXTERIOR DOORUPPER LEVEL 201a2'-8"8'-0"UPPER LEVEL 2022'-10"8'-0"UPPER LEVEL 202a2'-10"8'-0"GLASS SAPHIRE GLASS SHOWER DOORUPPER LEVEL 2033'-0"8'-0"UPPER LEVEL 2043'-0"8'-0"UPPER LEVEL 2053'-0"8'-0"UPPER LEVEL 205a5'-0"8'-0"UPPER LEVEL 2062'-10"8'-0"UPPER LEVEL 206a2'-8"8'-0"UPPER LEVEL 206b2'-6"8'-0"GLASS SAPHIRE GLASS SHOWER DOOR
ID MATERIALSIZE COMMENTS
DOOR SCHEDULE
FLOOR
The following windowsmust be safety glazedper 2015 IRC R308.4.Revise the windowschedule on 10.1.104, 105-109, 116,148, 149, 201-210,224, 225.
COORDINATED
DOCUMENTED IN DETAILS
ELABORATED IN DETAILS
11/27/17