HomeMy WebLinkAboutFile Documents.427 Rio Grande Pl.0016.2019 (69).ACBKCM
I
GF
I
Mechanical, Electrical & Energy Consultants
Denver
7600 East Orchard Rd Suite 250-S
Greenwood Village, CO 80111-2539
303.796.6000
Billings
175 North 27th Street, Suite 1312
Billings, MT 59101-2048
406.545.6420
Cheyenne
500 West 18th Street, Suite 200
Cheyenne, WY 82001-4368
307.459.6100
Salt Lake City
4760 S. Highland Drive, Suite 106
Salt Lake City, UT 84115
801.360.7024
Helena
P.O. Box 9643
Helena, MT 59604
406.438.1467
Bogota, Colombia
Calle 40B # 8-68 Edificio Torre San Marcos, 501
Bogota D.C. 110231 Colombia
+57.1.485.0689
7600 East Orchard Road, Suite
250-S Greenwood Village, CO
80111-2518 303.796.6000
www.mkkeng.com
CONSULTING ENGINEERS, INC.
I
X
X
G
3
V
A
M
J
D
J
J
L
MM
P
P/T
L
F
T
F
F
F
F
D
H
F F
F
FAAP
F
FAGP
FACP
TV
W
P
J
X
J
G
SPD
T
N
F
M
MCP - MOTOR CIRCUIT PROTECTION
XFMR
VFD
TTB
RVNR
NTS
NIC
MLO
WP
ZS
XP
UG
WG
SR
SC
PT
OL
OC
NO
NL
NC
- WEATHERPROOF
- LIMIT OR POSITION SWITCH
- EXPLOSION PROOF
- TRANSFORMER
- VARIABLE FREQUENCY DRIVE
- UNDERGROUND
- TELEPHONE TERMINAL BOARD
- SAFE OR STOP/RUN
- WIREGUARD
- REDUCED VOLTAGE, NON-REVERSING
- SHORT CIRCUIT
- POTENTIAL TRANSFORMER
- OVER CURRENT
- NOT TO SCALE
- OVERLOAD
- NORMALLY OPEN
- NOT IN CONTRACT
- NORMALLY CLOSED
- MAIN LUGS ONLY
- NIGHT LIGHT
- COPPERCU
MCC
MCA
EWC
ETM
MCB
LOR
MCCB
GRC
FWE
FLA
FVNR
FVR
HOA
ELR
LS
LT
IG
LC
HP
GFI
ES
EM
- LEVEL SWITCH
- MOTOR CONTROL CENTER
- MOLDED CASE CIRCUIT BREAKER
- MINIMUM CIRCUIT AMPS
- MAIN CIRCUIT BREAKER
- LET THROUGH
- LOCAL-OFF-REMOTE
- LIGHTING CONTACTOR
- ISOLATED GROUND
- HAND-OFF-AUTOMATIC
- HORSEPOWER
- FULL VOLTAGE, NON-REVERSING
- FULL VOLTAGE, REVERSING
- FULL LOAD AMPS
- GALVANIZED RIGID CONDUIT
- GROUND FAULT INTERRUPTER
- FURNISHED WITH EQUIPMENT
- ELAPSED TIME METER
- EMERGENCY STOP
- ELECTRIC WATER COOLER
- END OF LINE RESISTOR
- EMERGENCY
NOTE: ALL ABBREVIATIONS SHOWN
AFG
AFF
CPT
AIC
BFG
AFC
AL
CR
CT
CB
AC
- ALUMINUM
- CIRCUIT BREAKER
- CORROSION RESISTANT
- BELOW FINISHED GRADE
- CURRENT TRANSFORMER
- CONTROL POWER TRANSFORMER
- ABOVE COUNTER
- AMPS INTERRUPTING CURRENT
- ABOVE FINISHED CEILING
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
ARE NOT NECESSARILY USED.
1. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS FOR EXACT
DIMENSIONS.
2. REFER TO THE ARCHITECTURAL PLANS, ELEVATIONS, AND DIAGRAMS FOR LOCATIONS OF THE
FLOOR AND WALL DEVICES. IF DEVICES ARE NOT NOTED OTHERWISE THEY SHALL BE MOUNTED
LONG AXIS VERTICAL AT THE FOLLOWING HEIGHTS AFF TO CENTER OF DEVICE: SWITCHES +42",
RECEPTACLES +18", VOICE/DATA JACKS +18".
3. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ANY NEW ELECTRICAL SERVICE
INSTALLATION OR MODIFICATIONS TO THE EXISTING ELECTRICAL SERVICE WITH THE LOCAL
UTILITY COMPANY PRIOR TO STARTING ANY WORK.
4. COORDINATE ALL EQUIPMENT LOCATIONS WITH THE OWNER PRIOR TO ROUGH-IN.
CONTRACTOR TO INCLUDE A BOX WALK REVIEW WITH OWNER AND ARCHITECT PRIOR TO
ROUGH-IN. COORDINATE THE WIRING DEVICE LOCATIONS WITH THE ARCHITECTURAL
ELEVATIONS, CASEWORK SHOP DRAWINGS, AND EQUIPMENT INSTALLATION DRAWINGS.
COORDINATE THE LOCATION OF THE MECHANICAL EQUIPMENT WITH THE MECHANICAL PLANS
AND THE MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN. COORDINATE THE LOCATION OF THE
LUMINAIRES WITH THE ARCHITECTURAL REFLECTED CEILING PLANS.
5. ANY ITEMS DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR, AT NO
ADDITIONAL COST TO THE OWNER.
6. ALL 120V BRANCH CIRCUITS SHALL BE 3-WIRE (PHASE,NEUTRAL,GROUND). PHASE, NEUTRAL,
AND GROUND CONDUCTORS SHALL BE SIZE 12 AWG UNLESS OTHERWISE NOTED. BRANCH
CIRCUITS SHOWN AS A SINGLE HOMERUN SHALL NOT BE COMBINED WITH OTHER CIRCUITS. ALL
BRANCH CIRCUITS AND FEEDERS SHALL HAVE EQUIPMENT GROUNDING CONDUCTORS
INSTALLED IN THE RACEWAY.
7. PROVIDE (1) 1"C WITH BUSHING AND PULL WIRE FROM EACH TELEPHONE, DATA,
COMMUNICATION, AND THERMOSTAT OUTLET TO ABOVE THE ACCESSIBLE CEILING, UNLESS
NOTED OTHERWISE.
8. THE CONTRACTOR SHALL MAINTAIN FIRE-RATINGS FOR ALL CONDUIT PENETRATIONS THROUGH
FIRE-RATED CONSTRUCTION. REFER TO ARCHITECTURAL CODE PLAN.
9. COORDINATE THE LOCATIONS AND CONTROLS OF ALL APPLICABLE FIRE/SMOKE DAMPERS WITH
THE MECHANICAL CONTRACTOR, PRIOR TO CONSTRUCTION.
10. ALL MOUNTING OF ELECTRICAL DEVICES (LUMINAIRES, TRANSFORMERS, PANELS, OUTLETS,
CONDUIT RUNS, ETC.) SHALL COMPLY WITH STATE AND LOCAL SEISMIC REQUIREMENTS. ALL
LUMINAIRES SHALL BE SUPPORTED INDEPENDENTLY OF THE CEILING SUPPORT HANGERS IN
COMPLIANCE WITH IBC AND NEC REQUIREMENTS.
11. ADA COMPLIANCE: ELECTRICAL DEVICES PROJECTING FROM THE WALLS WITH THEIR LEADING
EDGES BETWEEN 27" AND 80" AFF SHALL PROTRUDE NO MORE THAN 4" INTO WALKWAYS OR
CORRIDORS.
12. BACK TO BACK MOUNTING OF RECEPTACLES OR COMMUNICATION OUTLETS IS NOT PERMITTED.
THE MINIMUM SEPARATION BETWEEN DEVICES SHALL BE 6" O.C. IN COMMON WALLS AND 24"
O.C. IN SOUND-RATED WALLS.
13. GFCI DEVICES SHALL BE PROVIDED AS NOTED AND SHALL COMPLY WITH NEC AND LOCAL
REQUIREMENTS. NO FEED-THRU GFCI PROTECTION SHALL BE PERMITTED FOR DOWNSTREAM
DEVICES. GFCI DUPLEX RECEPTACLES SHALL BE UL 943 2006 "LOCK-OUT" ACTION OR
"NOTIFICATION" COMPLIANT.
14. ALL RECEPTACLES IN BREAK ROOMS SHALL BE GFCI PROTECTED. PROVIDE REMOTE BLANK
FACE GFCI DEVICE IN AN ACCESSIBLE LOCATION AS REQUIRED FOR INACCESSIBLE
RECEPTACLES. VERIFY EXACT REMOTE BLANK FACE GFCI DEVICE LOCATION WITH ARCHITECT
PRIOR TO ROUGH-IN.
15. SWITCHES CONTROLLING LIGHTING LOADS: WHERE SWITCHES CONTROL LIGHTING LOADS
SUPPLIED BY A GROUNDED GENERAL PURPOSE BRANCH CIRCUIT, THE GROUNDED CIRCUIT
CONDUCTOR (NEUTRAL WIRE) FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
AT THE SWITCH LOCATION.
16. WHERE DIMMING CONTROL IS SPECIFIED AS A PORTION OF A CIRCUIT THAT ALSO HAS
SWITCHED LIGHTING IN ADJACENT SPACES, PROVIDE A SEPARATE, DEDICATED NEUTRAL WIRE
FROM THE DIMMING DEVICE BACK TO THE ORIGINATING PANEL.
17. ALL LOW VOLTAGE AND SYSTEMS CABLING LOCATED ABOVE THE ACCESSIBLE CEILING SHALL
BE PROPERLY RATED FOR THE APPLICATION. WITHOUT EXCEPTION, ALL CABLING SHALL BE
HUNG FROM BRIDLE-TYPE RINGS OR PLACED IN CABLE TRAYS BY THE ELECTRICAL
CONTRACTOR. IN EXPOSED CEILING AREAS, ALL CABLING SHALL BE RUN IN CONDUIT TO THE
NEAREST ACCESSIBLE CEILING LOCATION.
18. ELECTRICAL DEVICE IDENTIFICATION LABELS: PROVIDE ADHESIVE FILM LABEL, MACHINE
PRINTED, IN BLACK, BY THERMAL TRANSFER OR EQUIVALENT PROCESS WITH MINIMUM LETTER
HEIGHT OF 3/8" ON ALL ELECTRICAL DEVICES. LABEL SHALL IDENTIFY ORIGINATING PANEL AND
CIRCUIT NUMBER IN THE FOLLOWING FORMAT: PANEL-CKT. REFERENCE SPECIFICATIONS FOR
ADDITIONAL LABELING REQUIREMENTS. WHERE THE PROJECT SPECIFICATIONS INDICATE MORE
STRINGENT LABELING REQUIREMENTS, THOSE REQUIREMENTS SHALL TAKE PRECEDENCE.
19. PROVIDE TYPED PANEL DIRECTORIES FOR PANELS.
T165°= COMBINATION, 165°F
SUBSCRIPTS:
TELEVISION OUTLET
WALL MOUNTED TELEPHONE OUTLET, +48" AFF
= COMBINATION, 190°F
TELEPHONE TERMINAL BOARD - TTB
WALL MOUNTED TELEPHONE OUTLET
FLOOR MOUNTED TELEPHONE AND/OR DATA
WALL MOUNTED DATA OUTLET
WALL MOUNTED COMBINATION TELEPHONE/DATA
REMOTE PILOT LIGHT WITH TEST SWITCH
FIREFIGHTERS TELEPHONE JACK
SPRINKLER SYSTEM TAMPER SWITCH
SPRINKLER SYSTEM FLOW SWITCH
SMOKE DETECTOR IN VENTILATING DUCT
LIFE SAFETY SPEAKER WITH STROBE
= COMPENSATION, 165°F
FAN SHUT-DOWN CONNECTION
OUTLET BOX, AS NOTED
COMMUNICATION SYSTEM
SURGE PROTECTIVE DEVICE
CONDUIT STUB-OUT - CAP & MARK
NO. OF ARROWS INDICATE NO. OF CIRCUITS
CIRCUIT HOMERUN TO PANEL OR CABINET,
SEALOFF
CIRCUIT TURNED UP
CIRCUIT TURNED DOWN
CONDUIT RUN
ENGINE GENERATOR
CIRCUITING
TRANSFORMER
PANELBOARD
PAY PHONE
OUTLET BOX
= SHUNT TRIP
= MULTISPEED
= VARIABLE FREQUENCY
= SOLID-STATE, REDUCED VOLTAGE
ENCLOSED CIRCUIT BREAKER, MOLDED-CASE,
COMBINATION DISCONNECT AND STARTER
FUSED DISCONNECT SWITCH
SAFETY DISCONNECT SWITCH
SUBSCRIPTS:
ST
THERMAL-MAGNETIC FIXED
SSRV
VF
MS
CONTROL MODULE
MONITOR MODULE
DAMPER CONNECTION
LIFE SAFETY SPEAKER
REMOTE PILOT LIGHT
MAG. DOOR HOLDER
T190°
TF165°
THERMAL-MAGNETIC FIXED
ENCLOSED CIRCUIT BREAKER, MOLDED-CASE,
ENCLOSED FUSED DISCONNECT SWITCH
= SHUNT TRIP
= KEY INTERLOCK
= GROUND FAULT CIRCUIT INTERRUPTER
= ZONE-SELECTIVE INTERLOCKING
= COMPENSATION, 135°F
= COMBINATION, 135°F
= IONIZATION
FIRE ALARM GRAPHIC PANEL
GROUND FAULT PROTECTION
CURRENT TRANSFORMER
MOTOR, NUMBER INDICATES HORSEPOWER
GENERAL ALARM COMBINATION HORN/STROBE
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
CEILING OR WALL MOUNTED DETECTOR
= PHOTOELECTRIC
GENERATOR
OUTLET WITH SPECIAL DEVICE, AS NOTED
WALL MOUNTED OUTLET WITH SPECIAL DEVICE,
ABOVE CEILING POWER DISTRIBUTION BOX
POKE THROUGH, AS NOTED
SURFACE RACEWAY, AS NOTED
MAGNETIC MOTOR STARTER
FLOOR MOUNTED COMBINATION OUTLET BOX,
FLOOR MOUNTED POWER BOX, AS NOTED
WALL MOUNTED OUTLET BOX
JUNCTION BOX, AS NOTED
OUTLET BOX
CONNECTION TO MOTOR
TELE-POWER POLE
AS NOTED
AS NOTED
FIRE ALARM STROBE
T
TF
FIRE ALARM HORN
SUBSCRIPTS:
MANUAL PULL STATION
FIRE ALARM
= GROUND FAULT INTERRUPTER
= 6" ABOVE COUNTER
STRAIGHT BLADE SINGLE RECEPTACLE
STRAIGHT BLADE DUPLEX RECEPTACLE
STRAIGHT BLADE DOUBLE DUPLEX RECEPT. (FOURPLEX)
AC
GFI
SUBSCRIPTS:
POWER
VOLT METER
TRANSFER SWITCH
AMMETER
POWER TRANSFORMER
KI
ZSI
ST
GFCI
= MULTISPEED
= SOLID-STATE, REDUCED VOLTAGE
= VARIABLE FREQUENCY
ARE NOT NECESSARILY USED.
NOTE: ALL SYMBOLS SHOWN ON LEGEND
CIRCUIT BREAKER, MOLDED-CASE, THERMAL-MAGNETIC FIXED
MAGNETIC MOTOR STARTER
GROUND CONNECTION AS NOTED
FUSES
SUBSCRIPTS:
VF
MS
SSRV
SUBSCRIPTS:
SCHEMATIC WIRING GRAPHICS
DISCONNECT SWITCH
METER
P
= COMBINATION PHOTOELECTRIC AND THERMAL
= COMPENSATION, 190°F
PT
TF190°
- TRANSIENT VOLTAGE SURGE SUPPRESSORTVSS
SPD - SURGE PROTECTIVE DEVICE
CEILING OR WALL MOUNTED EXIT SIGN
BOLLARD
RECESS MOUNTED LUMINAIRE
SURFACE MOUNTED RECTALINEAR LUMINAIRE
STRIP LUMINAIRE
TRACK LIGHT
DIRECTIONAL ACCENT OR WALL-WASH LUMINAIRE
RECESSED DOWNLIGHT
LIGHTING
WALL MOUNTED LUMINAIRE
SURFACE MOUNTED NON-LINEAR LUMINAIRE
WALL MOUNTED LINEAR LUMINAIRE
SHADING INDICATES EMERGENCY LUMINAIRE
RECESS MOUNTED DIRECTIONAL LUMINAIRE
STEP LIGHT OR RECESSED WALL LUMINAIRE
SURFACE MOUNTED LUMINAIRE HIDDEN
UNDER COVE, CABINET, ETC.
PENDANT MOUNTED LINEAR LUMINAIRE
NON-LINEAR PENDANT LUMINAIRE
LANDSCAPE LUMINAIRE
TAPE LIGHT
1. VERIFY ALL FIRE ALARM SYSTEM REQUIREMENTS. PROVIDE BATTERY AND CIRCUIT LOAD
CALCULATIONS AS REQUIRED. COMPLETE THE FIRE ALARM PROGRAMMING, UPDATE RELATED
GRAPHIC DISPLAYS, AND THEN TEST CIRCUITS AT THE END OF THE PROJECT.
2. ALL STROBES AND HORN/STROBES SHALL BE SYNCHRONIZED PER NFPA AND LOCAL
REQUIREMENTS.
3. THE CONTRACTOR SHALL OBTAIN A STATE REGISTERED ENGINEER TO REVIEW, SEAL, AND
SIGN SHOP DRAWINGS FOR PLAN REVIEW SUBMISSION. THE ENGINEER OF RECORD FOR
THESE DRAWINGS SHALL NOT SEAL THE FIRE ALARM SHOP DRAWINGS.
NOTATIONS
UPPER CASE LETTER AT LUMINAIRES
(F1, , ETC.) INDICATES
LUMINAIRE TYPE. = TYPE F1
LUMINAIRES IN AREA INDICATED.
SHADING WITHIN LUMINAIRE DENOTES
PLUS (+) SIGN WITH DIMENSION AT
OUTLET INDICATES HEIGHT ABOVE
FINISHED FLOOR OR GRADE TO
CENTERLINE OF OUTLET.
2 -
3 -
1 -
1
F1
UNIT ON EMERGENCY POWER.
WALL-MOUNTED LINE VOLTAGE SWITCH
SWITCH SUBSCRIPTS:
LIGHTING CONTROLS:
CORNER OR CEILING MOUNTED OCCUPANCY
= KEY-OPERATED
= DIMMERD
K
= 3-WAY
= 4-WAY
3
4
WALL-MOUNTED LOW-VOLTAGE CONTROL,
LOW VOLTAGE CONTROL SUBSCRIPTS:
= WITH PHOTOCELL
= DUAL-TECH OCCUPANCY SENSOR
P
= PIR OCCUPANCY SENSOR1
2
PUSH-BUTTON OR KEYPAD
SENSOR OR DAYLIGHT SENSOR AS
LOWER CASE LETTER INDICATES CONNECTION
BETWEEN LUMINAIRE AND CONTROL DEVICE
a
= 0 - 10 V DIMMERD
= ELV DIMMERED
- SET TO VACANCY MODE, UNO
- SET TO VACANCY MODE, UNO
P
DESIGNATED BELOW, UNO:
= DUAL-TECH OCCUPANCY SENSOR
= PIR OCCUPANCY SENSOR1
D
- SET TO VACANCY MODE, UNO
- SET TO VACANCY MODE, UNO
LV - LOW VOLTAGE
ABBREVIATIONS
GENERAL NOTES (FOR ALL ELECTRICAL SHEETS)ELECTRICAL LEGEND
GENERAL NOTES-FIRE ALARM SYSTEMS
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
3
8
A
M
E0.0
2016.01.0223
ELECTRICAL
LEGEND SHEET
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
F D
SB
600
SB
L3- 2
L3- 2
L3- 2
L3- 2
L3- 2
L3- 2
L3- 2
L3- 2
L3- 2
L1- 2
L1- 2
L1- 2
L1- 2
L1- 2
L1- 2
L1- 2
L1- 2
L1- 2
L1- 2
SC
L3- 4EM-26
602
SB
SC
SC
SC
SC
603
603
603
202
TYP
TYP
TYP
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
4
2
A
M
E1.0
2016.01.0223
ELECTRICAL
SITE PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
1" = 20'-0"1 ELECTRICAL SITE PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
FLAG NOTES (THIS SHEET)
202 PROVIDE FOUR-(4) 4" SERVICE ENTRANCE CONDUITS WITH PULL WIRES FOR TELEPHONE, DATA,
AND CATV AS NEEDED FROM THE TELECOM/DATA ROOM TO THE NEAREST UTILITY PEDESTAL OR
MANHOLE AS DIRECTED BY VENDOR. COORDINATE AND VERIFY EXACT ROUTING OF CONDUIT AND
LOCATION OF PEDESTAL OR MANHOLE PRIOR TO INSTALLATION.
600 SEE SHEET E3.1 FOR ELECTRIC SERVICE DETAILS.
602 PHOTOVOLTAIC SYSTEM TO BE DESIGNED BY OTHERS.
603 REFER TO LANDSCAPE DRAWINGS FOR BOLLARD MOUNTING DETAILS.
03/16/2019
D
D
DD
D
2
D
D
3
3
2
A
11
ELECTRICAL
003
C D E F
D
LB
12
13
G H I
X
1
2
P8
P7
C
104
X
STAIR
S001
EXISTING PARKING GARAGE
P1
ELEVATOR
000
X
X
C
C
C
C C
C C
DATA CENTER
004
STORAGE
002
VESTIBULE
001
STORAGE
006
MECHANICAL
005
LB- 1 EM- 1 LB- 1
LB- 1 LB- 1 LB- 1 LB- 1 LB- 1
EM- 1 LB- 1 EM- 1 LB- 1 EM- 1
LB- 1
EM- 1
LB- 1 LB- 1 LB- 1
EM- 1
EM- 1 EM- 1
EM- 1 EM- 1
EM- 1 EM- 1
EM- 1
LB- 2
EM- 1
EM- 1
EM- 1 EM- 1
EM- 1 EM- 1
EM- 1
LB- 2 LB- 2 LB- 2
EM- 1
LB- 2 LB- 2
LB- 2
EM- 1
LB- 2
EM- 1 LB- 1 EM- 1 LB- 1 EM- 1 LB- 1 LB- 1
LB- 1LB- 1LB- 1LB- 1LB- 1LB- 1LB- 1
EM- 1 LB- 1 EM- 1 LB- 1
X
EM
SB
MB
105
X
X
107 108
X
X
XX
LB- 1
109
X X
LB- 1
X
110
EM- 28
EM- 28 EM- 28
EM- 28
107
PUMP ROOM
008
X
GENERATOR
007
C
105111
ATS-EM
ATS-SB
EM- 25
EM- 25EM- 25
EM- 25
112
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
4
4
A
M
E2.0
2016.01.0223
GALENA
BASEMENT
LEVEL
LIGHTING PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
GENERAL NOTES (LIGHTING)
A CIRCUIT EXIT SIGNS AND SENSING LEADS AHEAD OF LOCAL CONTROLS.
B ALL FIXTURES SHOWN SHADED SHALL BE POWERED FROM THE LIFE SAFETY BRANCH OF THE
GENERATOR AND BE CONNECTED TO THE LOCAL SWITCHLEG OR SENSOR THROUGH A UL924-RATED
DEVICE.
C LIGHTING SYSTEM WILL HAVE LIGHTING CONTROLS TO MEET ALL ENERGY CODE REQUIREMENTS.
CODE-REQUIRED LIGHT REDUCTION WILL BE DONE WITH STANDARD 0-10V LED DIMMING. IN
ADDITION TO CODE LEVEL CONTROLS, ALL PRIVATE OFFICES WILL HAVE OCCUPANCY SENSORS.
SET TO VACANCY MODE. SEE LIGHTING CONTROL MATRIX SHEET E6.0 FOR MORE INFORMATION.
D ALL DRAWINGS ARE DIAGRAMMATICAL ONLY. SYMBOLS ARE NOT NECESSARILY TO SCALE. USE
ARCHITECTURAL PLANS FOR DIMENSIONS. IF THESE DRAWINGS DIFFER SUBSTANTIALLY FROM
ARCHITECTURAL DRAWINGS, NOTIFY ARCHITECT IMMEDIATELY FOR A RESOLUTION.
E OCCUPANCY SENSOR PLACEMENT IS DIAGRAMMATICAL ONLY. FOLLOW MANUFACTURER'S
PLACEMENT RECOMMENDATIONS FOR PLACEMENT AND AIMING FOR FULL COVERAGE OF
OCCUPANCY.
F ALL EXIT SIGNS ARE TO BE CONNECTED TO LOCAL EM CIRCUIT AHEAD OF LOCAL SWITCHING.
FLAG NOTES (THIS SHEET)
104 REFER TO SHEET E5.0 FOR LIGHTING IN ELEVATOR PIT AND HOISTWAY.
105 ALL FIXTURES IN THIS ROOM TO RECEIVE BATTERY PACKS.
107 COORDINATE FIXTURE LOCATIONS WITH MECHANICAL DUCT WORK.
108 COORDINATE EXIT SIGN VISIBILITY WITH MECHANICAL DUCT WORK.
109 COORDINATE EXIT SIGN VISIBILITY WITH STORAGE SHELVING.
110 MOUNT STRIP FIXTURES AS HIGH AS UNIFORMLY POSSIBLE.
111 COORDINATE STRIP FIXTURES WITH GENERATOR, INTAKE AND EXHAUST IN THIS ROOM.
112 CIRCUIT STAIRWELL FIXTURES WITH ABOVE.
1/8" = 1'-0"1
GALENA BASEMENT LEVEL LIGHTING
PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
1
2
3
4
5
6
7
8
9
10 11
12 1314
15
16 17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32 33 34
35
36
37
3839
4041
42434445
464748
49
50
51 52
5354 55
56 57 58 59
60 61
62
63
64 65
6667
1
2
3
4
Doors to electric
room must be
equipped with panic
hardware per NEC
110.26(C)(3).
Provide egress door on each end of
elec. room or demonstrate
compliance with exceptions
D
D
D
D
D
D
D
D
D
D D
D
D
D
P
D
A
11
C D
D.5 D.5
E
33
F
B11B11
C
F
D
SA SA
SA
SA
SA
SA
12
13
G H I
SA
X
X
X
1
2
P8
P7
C
J
C
B23
MENS
102
WOMENS
103
STAIR
S001
VEST
107
TRASH
108
ELEC
106
100
C
LCP M1
L1
103
AA
A
LOBBY
101
LOBBY
101
B6 B6
106 106
L1- 1 L1- 1
C
C
L1- 1 L1- 1 L1- 1
L1- 1 L1- 1
L1- 1
EM- 9
L1- 1
L1- 1 L1- 1
L1- 1
L1- 1
EM- 9
L1- 1L1- 1
L1- 1
L1- 1
EM- 25
EM- 25
EM- 7 EM- 7 EM- 7 EM- 7
EM- 7EM- 7EM- 7
EM- 7EM- 7EM- 7EM- 7
EM- 7 EM- 7
EM- 7EM- 7
EM- 9
EM- 9
EM- 9 EM- 9
EM- 9
EM- 9
EM- 9
EM- 9
EM- 9
EM- 9
L1- 1
L1- 1
104
C
104
SD
EM- 9
L1- 4
L1- 4
L1- 4
EM- 9
L1- 4
L1- 4
L1- 4
EM- 9
L1- 4
L1- 4
L1- 4
EM- 9
L1- 4
L1- 4
L1- 4
EM- 9
L1- 4
EM- 25 EM- 25
X
TYP OF 10
100
J
TYP OF 13
EM- 27
EM- 27
112
112
113
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
4
7
A
M
E2.1
2016.01.0223
GALENA MAIN
LEVEL
LIGHTING PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
GENERAL NOTES (LIGHTING)
A CIRCUIT EXIT SIGNS AND SENSING LEADS AHEAD OF LOCAL CONTROLS.
B ALL FIXTURES SHOWN SHADED SHALL BE POWERED FROM THE LIFE SAFETY BRANCH OF THE
GENERATOR AND BE CONNECTED TO THE LOCAL SWITCHLEG OR SENSOR THROUGH A UL924-RATED
DEVICE.
C LIGHTING SYSTEM WILL HAVE LIGHTING CONTROLS TO MEET ALL ENERGY CODE REQUIREMENTS.
CODE-REQUIRED LIGHT REDUCTION WILL BE DONE WITH STANDARD 0-10V LED DIMMING. IN
ADDITION TO CODE LEVEL CONTROLS, ALL PRIVATE OFFICES WILL HAVE OCCUPANCY SENSORS.
SET TO VACANCY MODE. SEE LIGHTING CONTROL MATRIX SHEET E6.0 FOR MORE INFORMATION.
D ALL DRAWINGS ARE DIAGRAMMATICAL ONLY. SYMBOLS ARE NOT NECESSARILY TO SCALE. USE
ARCHITECTURAL PLANS FOR DIMENSIONS. IF THESE DRAWINGS DIFFER SUBSTANTIALLY FROM
ARCHITECTURAL DRAWINGS, NOTIFY ARCHITECT IMMEDIATELY FOR A RESOLUTION.
E OCCUPANCY SENSOR PLACEMENT IS DIAGRAMMATICAL ONLY. FOLLOW MANUFACTURER'S
PLACEMENT RECOMMENDATIONS FOR PLACEMENT AND AIMING FOR FULL COVERAGE OF
OCCUPANCY.
F ALL EXIT SIGNS ARE TO BE CONNECTED TO LOCAL EM CIRCUIT AHEAD OF LOCAL SWITCHING.
FLAG NOTES (THIS SHEET)
100 PROVIDE TAPE LED LIGHT TYPE J ALONG THE WIDTH OF EACH STEP. ALL THREE LEVELS. REMOTE
DRIVERS TO BE FIELD LOCATED. RUN SWITCH LEG BACK TO ELECTRICAL ROOM FOR FUTURE
CONTROLS.
103 MULTI-BUTTON. CONNECT TO ALL STUMBLE LIGHTING (TYPE C).
104 REFER TO SHEET E5.0 FOR LIGHTING IN ELEVATOR PIT AND HOISTWAY.
106 REFER TO A6.4 FOR MOUNTING DETAILS. (2) B6 FIXTURES MOUNTED BEHIND MIRROR.
112 CIRCUIT STAIRWELL FIXTURES WITH ABOVE.
113 LIGHTING CONTROL PANEL WITH ASTRONOMICAL TIME CLOCK AND UL924 DEVICES AS REQUIRED.
1/8" = 1'-0"1 GALENA MAIN LEVEL LIGHTING PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
68 69
70 71
72
73
74 75
76
77
78 79
80 81
82 83
84
85
86
87
10
11
12
13
1
2
3
4 5
6
7
8
1
2
23
'
-
0
"
5'
-
1
0
"
11
'
-
0
"
11
'
-
1
"
5'
-
8
"
3
4
5
6
122
DD
D
D
D
D
D
D
D
D
D
D
11
C
D
SA
J
12
13
G H I
1
2
P8
P7
C
B23
STAIR
S001
CORRIDOR
207
ELEVATOR
000
WOMENS
203
MENS
202
TD
204
JANITOR
205
ELEC
206
ELEVATOR
000
B11B11
C
C
AA
M2
L2
A
103
104
112
SAX
B6 B6
106 106
L2- 1 L2- 1
OFFICE
209
L2- 1 L2- 1 L2- 1 L2- 1
L2- 1
L2- 1
EM- 13EM- 13
L2- 1
L2- 1
EM- 25
EM- 25
EM- 13
EM- 13
EM- 13
EM- 13 EM- 13 EM- 13
EM- 13 EM- 13 EM- 13
EM- 13
L2- 1
L2- 1
L2- 1L2- 1
EM- 13 EM- 13
EM- 13EM- 13EM- 13EM- 13
C
EM- 13
EM- 13
EM- 13
X
X
X
X
X
104
EM- 25 EM- 25
EM- 25
J
100
TYP OF 10
100
J
TYP OF 13
EM- 27
EM- 27
112
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
4
9
A
M
E2.2
2016.01.0223
GALENA
MIDDLE LEVEL
LIGHTING PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
GENERAL NOTES (LIGHTING)
A CIRCUIT EXIT SIGNS AND SENSING LEADS AHEAD OF LOCAL CONTROLS.
B ALL FIXTURES SHOWN SHADED SHALL BE POWERED FROM THE LIFE SAFETY BRANCH OF THE
GENERATOR AND BE CONNECTED TO THE LOCAL SWITCHLEG OR SENSOR THROUGH A UL924-RATED
DEVICE.
C LIGHTING SYSTEM WILL HAVE LIGHTING CONTROLS TO MEET ALL ENERGY CODE REQUIREMENTS.
CODE-REQUIRED LIGHT REDUCTION WILL BE DONE WITH STANDARD 0-10V LED DIMMING. IN
ADDITION TO CODE LEVEL CONTROLS, ALL PRIVATE OFFICES WILL HAVE OCCUPANCY SENSORS.
SET TO VACANCY MODE. SEE LIGHTING CONTROL MATRIX SHEET E6.0 FOR MORE INFORMATION.
D ALL DRAWINGS ARE DIAGRAMMATICAL ONLY. SYMBOLS ARE NOT NECESSARILY TO SCALE. USE
ARCHITECTURAL PLANS FOR DIMENSIONS. IF THESE DRAWINGS DIFFER SUBSTANTIALLY FROM
ARCHITECTURAL DRAWINGS, NOTIFY ARCHITECT IMMEDIATELY FOR A RESOLUTION.
E OCCUPANCY SENSOR PLACEMENT IS DIAGRAMMATICAL ONLY. FOLLOW MANUFACTURER'S
PLACEMENT RECOMMENDATIONS FOR PLACEMENT AND AIMING FOR FULL COVERAGE OF
OCCUPANCY.
F ALL EXIT SIGNS ARE TO BE CONNECTED TO LOCAL EM CIRCUIT AHEAD OF LOCAL SWITCHING.
FLAG NOTES (THIS SHEET)
100 PROVIDE TAPE LED LIGHT TYPE J ALONG THE WIDTH OF EACH STEP. ALL THREE LEVELS. REMOTE
DRIVERS TO BE FIELD LOCATED. RUN SWITCH LEG BACK TO ELECTRICAL ROOM FOR FUTURE
CONTROLS.
103 MULTI-BUTTON. CONNECT TO ALL STUMBLE LIGHTING (TYPE C).
104 REFER TO SHEET E5.0 FOR LIGHTING IN ELEVATOR PIT AND HOISTWAY.
106 REFER TO A6.4 FOR MOUNTING DETAILS. (2) B6 FIXTURES MOUNTED BEHIND MIRROR.
112 CIRCUIT STAIRWELL FIXTURES WITH ABOVE.
1/8" = 1'-0"1 GALENA MIDDLE LEVEL LIGHTING PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
88
89
90
91
92 93 94 95
9697
5
6
78
9
98
99
100
101102
103
3
4
104
105
9
1011
12
13
1415
16 17
106
22
'
-
1
1
"
6'
-
0
"
6'
-
0
"
11
'
-
1
"
11
'
-
0
"
D
DD
D
D
D
D
D
D
D
A
11
C D E F
SA
SA
SA
SA
F
SA
SA
SA
SA
12
13
X
X
X
X
X
X
1
2
P8
P7
Q
C
B23
L3
M3
101
MEETING ROOM
309
VEST
307
MEETING ROOM
310
ELEC
306
WOMENS
303
MENS
302
JANITOR
305
TD
304
ELEVATOR
000
B11B11
C
C
AA
A
103
104
CC
C
X
X
B6 B6
106 106
L3- 1 L3- 1
C
EM- 21
L3- 2
L3- 2
EM- 21
EM- 19
EM- 19
EM- 19 EM- 19
EM- 19
EM- 19
EM- 19
L3- 1
EM- 21
EM- 19
L3- 1
L3- 1
L3- 1
L3- 1
EM- 19
L3- 1L3- 1
EM- 19
L3- 1
L3- 1
L3- 1 L3- 1
L3- 1
EM- 21
L3- 2
EM- 19
EM- 19
EM- 19
EM- 19
EM- 19
L3- 2
EM- 19
A
900
X
X
A A
L3- 1
L3- 1 L3- 1 L3- 1
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
5
2
A
M
E2.3
2016.01.0223
GALENA UPPER
LEVEL
LIGHTING PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
GENERAL NOTES (LIGHTING)
A CIRCUIT EXIT SIGNS AND SENSING LEADS AHEAD OF LOCAL CONTROLS.
B ALL FIXTURES SHOWN SHADED SHALL BE POWERED FROM THE LIFE SAFETY BRANCH OF THE
GENERATOR AND BE CONNECTED TO THE LOCAL SWITCHLEG OR SENSOR THROUGH A UL924-RATED
DEVICE.
C LIGHTING SYSTEM WILL HAVE LIGHTING CONTROLS TO MEET ALL ENERGY CODE REQUIREMENTS.
CODE-REQUIRED LIGHT REDUCTION WILL BE DONE WITH STANDARD 0-10V LED DIMMING. IN
ADDITION TO CODE LEVEL CONTROLS, ALL PRIVATE OFFICES WILL HAVE OCCUPANCY SENSORS.
SET TO VACANCY MODE. SEE LIGHTING CONTROL MATRIX SHEET E6.0 FOR MORE INFORMATION.
D ALL DRAWINGS ARE DIAGRAMMATICAL ONLY. SYMBOLS ARE NOT NECESSARILY TO SCALE. USE
ARCHITECTURAL PLANS FOR DIMENSIONS. IF THESE DRAWINGS DIFFER SUBSTANTIALLY FROM
ARCHITECTURAL DRAWINGS, NOTIFY ARCHITECT IMMEDIATELY FOR A RESOLUTION.
E OCCUPANCY SENSOR PLACEMENT IS DIAGRAMMATICAL ONLY. FOLLOW MANUFACTURER'S
PLACEMENT RECOMMENDATIONS FOR PLACEMENT AND AIMING FOR FULL COVERAGE OF
OCCUPANCY.
F ALL EXIT SIGNS ARE TO BE CONNECTED TO LOCAL EM CIRCUIT AHEAD OF LOCAL SWITCHING.
FLAG NOTES (THIS SHEET)
101 NINE-HEAD, 35' TALL LUMINAIRE. COORDINATE STRUCTURAL REQUIREMENTS WITH STRUCTURAL
DESIGN. SWITCH TO BE LOCATED IN ELECTRICAL ROOM ON MAIN LEVEL THROUGH TIME CLOCK
CONTROL. SEE LIGHTING CONTROL MATRIX SHEET E6.0 FOR MORE DETAILS.
103 MULTI-BUTTON. CONNECT TO ALL STUMBLE LIGHTING (TYPE C).
104 REFER TO SHEET E5.0 FOR LIGHTING IN ELEVATOR PIT AND HOISTWAY.
106 REFER TO A6.4 FOR MOUNTING DETAILS. (2) B6 FIXTURES MOUNTED BEHIND MIRROR.
900 ELECTRICAL INSTALLATION IN THIS AREA MUST CONFORM TO NEC ARTICLE 518.
1/8" = 1'-0"1 GALENA UPPER LEVEL LIGHTING PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
18
19 20 21
2223
24
25
26
27
28
1
2
29
22
'
-
7
"
5'
-
1
0
"
10
'
-
1
0
"
5'
-
8
"
11
'
-
2
"
F
F
F P
F P
F P
FACP
F
F
F
F
F
J F
J
SPD
F
F
N
MT
F
M
M
T
F D
F D F DFD
J
F
MJ
M
T
M
T
F F F
M M M
M
T
M
T
N
N
N
F
F
F
J
M
J
M
J
M
M M
F
F
J
F F
F
F
M
M
MM
M
M
T
T
M
M
F
F
J
F F F F
T T T
F D F D
J
F F
M
A C D E
MSB
LB
GFI
GFI
GFI
GFI 209
G H I
1
2
P8
P7
E-1
E-280 KW
NATURAL
GAS GENSET
203
200
201201
601
EM
SB
202
EXISTING GARAGE NOT IN SCOPE OF WORK
MB
MECHANICAL
005
ELECTRICAL
003
STORAGE
006STORAGE
002
VESTIBULE
001
DATA CENTER
004
GFI
GFI
GFI
GFI
GFI
GFI
E-1
E-2
ELEVATOR
000
E-3
LB-9
LB-9
LB-9
LB-9
SB-1
LB-9
LB-9
LB-10
SB-1
SB-1
LB-8
LB-8
LB-7 LB-8
LB-9
LB-10
LB-11
LB-12
LB-12SB-2
MSB-32,34,36
SB-3
MSB-31,33,35
WH-1
MB-37,39,41
MB-1
RCP-1
MB-2,4,6
SP-3
SP-1
MB-3
SB-4
TCP PANEL
MSB-56,58,60
AHU-1
MB-7
CP-1
MB-11
CP-3
MB-9
UH-1
WWHP-1WWHP-2 WWHP-3
MSB-50,52,54 MSB-49,51,53 MSB-55,57,59
MB-9
GF-2
EM-2
EM-2
EM-2 EM-2
B-1 BP-1
B-2 BP-2
B-3 BP-3
MSB-37,39,41 MB-8,10,12
MSB-38,40,42 MB-13,15,17
MSB-43,45,47 MB-14,16,18
MB-19,21,23 MB-20,22,24
HWP-3 HWP-4
MB-5
UH-3
EF-2
GWP-1 GWP-2
CWP-2
CWP-1
MB-32,34,36
MB-31,33,35
MB-26,28,30MB-25,27,29
MB-43
MB-43
LB-13
LB-13
PUMP ROOM
008
214
208
LB-12
GENERATOR
007
ATS-SB
ATS-EM
BATTERY
CHARGER
LB-15,17
JACKET
HEATER
RETURN SUPPLY
215
303
EM-30
216
216
HEAT TRACE
LB-19
MB-38,40,42
MB-44,46,48
HWP-1
HWP-2 WATER ENTRY
217
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
5
3
A
M
E3.0
2016.01.0223
GALENA
BASEMENT
LEVEL
ELECTRICAL
PLAN PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
FLAG NOTES (THIS SHEET)
200 COA TRANSFORMER WITH PRECAST VAULT.
201 ROUTE (9)3-1/2"C (ONE SPARE) SERVICE CONDUITS UNDERGROUND AND STUB INTO BASEMENT
LEVEL MAIN ELECTRICAL ROOM 005. STUB-DOWN INTO SWITCHBOARD AS REQUIRED. CONDUITS
SHALL BE ROUTED A MINIMUM OF 36" ABOVE OR BELOW SANITARY AND STORM SEWER LINES.
COORDINATE CONDUIT ROUTING.
202 PROVIDE FOUR-(4) 4" SERVICE ENTRANCE CONDUITS WITH PULL WIRES FOR TELEPHONE, DATA,
AND CATV AS NEEDED FROM THE TELECOM/DATA ROOM TO THE NEAREST UTILITY PEDESTAL OR
MANHOLE AS DIRECTED BY VENDOR. COORDINATE AND VERIFY EXACT ROUTING OF CONDUIT AND
LOCATION OF PEDESTAL OR MANHOLE PRIOR TO INSTALLATION.
203 NEMA 3R SERVICE ENTRY AND HOT SEQUENCE CT'S PROVIDED BY ELECTRICAL CONTRACTOR.
METER SHALL BE FURNISHED BY COA AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
208 REFER TO ELEVATOR DETAILS ON SHEET E5.0 FOR ADDITIONAL INFORMATION.
209 DATA CENTER POWER, GROUNDING, AND COOLING REQUIREMENTS ARE UNKNOWN AT THIS TIME.
TO BE DETERMINED DURING DATA CENTER BUILD OUT.
214 FIRE ALARM CONTROL PANEL. CIRCUIT TO EM-25. PROVIDE (2) PHONE LINES TO CONTROL PANEL.
215 COORDINATE LOCATION OF MAIN SWITCHBOARD WITH MECHANICAL MAIN DUCT WORK.
COORDINATE WITH MECHANICAL TO MAINTAIN 6' CLEARANCE ABOVE ELECTRICAL EQUIPMENT.
216 EPO SWITCH TO TRIP BOILER SHUNT TRIP BREAKERS.
217 HEAT TRACE PROVIDED BY MECHANICAL CONTRACTOR. PROVIDE FINAL CONNECTION AND
THERMAL OVERLOAD SWITCH. CONTROLLER BY MECHANICAL.
303 DATA CENTER TO BE PROTECTED BY CHEMICAL AGENT. PROVIDE INTERFACE BETWEEN CHEMICAL
AGENT AND FIRE ALARM. COORDINATE EXACT POWER REQUIREMENTS WITH FIRE PROTECTION
CONTRACTOR PRIOR TO ROUGH-IN.
601 COA TRANSFORMER AND SERVICE ENTRY LOCATED ABOVE ON GRADE.
GENERAL NOTES (POWER)
A REFER TO ELECTRICAL SCHEDULES ON SHEET E6.0 FOR EQUIPMENT CONNECTION SCHEDULE AND
MECHANICAL EQUIPMENT SCHEDULE.
B REFER TO SECURITY PLAN FOR DEVICE LOCATIONS. COORDINATE WITH SECURITY CONTRACTOR
FOR ROUGH-IN REQUIREMENTS.
C PROVIDE 4" CONCRETE PADS FOR ALL FLOOR AND GROUND MOUNTED ELECTRICAL EQUIPMENT.
D PROVIDE THREE, 3" CONDUITS FROM THE MAIN DATA ROOM LOCATED ON THE GROUND LEVEL TO
THE SECOND AND THIRD FLOOR DATA ROOM.
E REFER TO MECHANICAL DRAWINGS FOR EQUIPMENT LOCATION AND SPECIFICATIONS.
1/8" = 1'-0"1
GALENA BASEMENT LEVEL ELECTRICAL
PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
J
J F
F
F
F P
FAAP
F
F
F
F
F
F F
F
F
M
T
F D
F DFD
F D
F D
F D
M
M
T
T
M
T
M
T
M
T
M
T
M
T
M
T
M
T
J
A
11
C D
D.5
E
3
F
WP GFI WP GFI WP GFI
WP GFI
WP GFI
WP GFI
WP GFI
WP GFI
TRASH
108
203
200
201
12
13
G H I
GFI GFI
E-3
E-3
1
2
P8
P7
208
LOBBY
101
STAIR
S001
VEST
107
ELEVATOR
000
WOMENS
103
ELEC
106
JANITOR
105
TD
104
ELEVATOR
000
L1
LCP M1
EWC
GFI
AC, GFIAC, GFIWP GFI WP GFI
L1-16
L1-16
L1-15 L1-15 L1-15
L1-9 L1-14
L1-18
L1-18
L1-17
L1-17
L1-8
L1-12
L1-8
L1-7 L1-7 L1-9
L1-9
L1-10
L1-11
L1-10
L1-10L1-10
L1-13
SP-2
M1-1
UH-2
EF-4
M1-2
M1-2
FPVAV-1
M1-3
CUH-2
M1-4
CUH-3
M1-4
CUH-7
M1-4
FPVAV-3
M1-5
FPVAV-2
M1-6
CUH-4
M1-7
EM-8
EM-8 EM-8
EM-8EM-8
EM-8
MENS
102
213
L1-12
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
5
5
A
M
E3.1
2016.01.0223
GALENA MAIN
LEVEL
ELECTRICAL
PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
FLAG NOTES (THIS SHEET)
200 COA TRANSFORMER WITH PRECAST VAULT.
201 ROUTE (9)3-1/2"C (ONE SPARE) SERVICE CONDUITS UNDERGROUND AND STUB INTO BASEMENT
LEVEL MAIN ELECTRICAL ROOM 005. STUB-DOWN INTO SWITCHBOARD AS REQUIRED. CONDUITS
SHALL BE ROUTED A MINIMUM OF 36" ABOVE OR BELOW SANITARY AND STORM SEWER LINES.
COORDINATE CONDUIT ROUTING.
203 NEMA 3R SERVICE ENTRY AND HOT SEQUENCE CT'S PROVIDED BY ELECTRICAL CONTRACTOR.
METER SHALL BE FURNISHED BY COA AND INSTALLED BY THE ELECTRICAL CONTRACTOR.
208 REFER TO ELEVATOR DETAILS ON SHEET E5.0 FOR ADDITIONAL INFORMATION.
213 PROVIDE JUNCTION BOX AND CONDUIT TO THIS LOCATION FROM PANEL 'SB'. POWER
REQUIREMENTS TO BE DETERMINED DURING TI DESIGN.
GENERAL NOTES (POWER)
A REFER TO ELECTRICAL SCHEDULES ON SHEET E6.0 FOR EQUIPMENT CONNECTION SCHEDULE AND
MECHANICAL EQUIPMENT SCHEDULE.
B REFER TO SECURITY PLAN FOR DEVICE LOCATIONS. COORDINATE WITH SECURITY CONTRACTOR
FOR ROUGH-IN REQUIREMENTS.
C PROVIDE 4" CONCRETE PADS FOR ALL FLOOR AND GROUND MOUNTED ELECTRICAL EQUIPMENT.
D PROVIDE THREE, 3" CONDUITS FROM THE MAIN DATA ROOM LOCATED ON THE GROUND LEVEL TO
THE SECOND AND THIRD FLOOR DATA ROOM.
E REFER TO MECHANICAL DRAWINGS FOR EQUIPMENT LOCATION AND SPECIFICATIONS.
1/8" = 1'-0"1 GALENA MAIN LEVEL ELECTRICAL PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
Provide in-use covers to
exterior receptacles.
DN
F
F
F P
F
F F F
F
F F F
J
J
J
J
F D
F D
F D F D
F D
F DM M
TT
M
T
M
T
M
T
F
F
J
A
11
C
12
13
G H I
1
2
P8
P7
STAIR
S001
CORRIDOR
207
ELEVATOR
000
WOMENS
203
MENS
202
TD
204
JANITOR
205
ELEC
206
ELEVATOR
000
EWC
AC, GFI AC, GFI
GFI
L2
M2
EWC
OFFICE
209
L2-8
L2-7
L2-7
L2-7
L2-7
L2-9
L2-10
L2-10
L2-14
E-3L2-11
L2-13
E-3
E-3
L2-12
L2-12 E-3
L2-12
FPVAV-6
CUH-8 CUH-9
FPVAV-5
FPVAV-4
M2-3
M2-4 M2-4
M2-2
M2-1
EM-14
EM-14 EM-14
EM-14
EM-14
EM-14
213
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
3
:
5
8
A
M
E3.2
2016.01.0223
GALENA
MIDDLE LEVEL
ELECTRICAL
PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
FLAG NOTES (THIS SHEET)
213 PROVIDE JUNCTION BOX AND CONDUIT TO THIS LOCATION FROM PANEL 'SB'. POWER
REQUIREMENTS TO BE DETERMINED DURING TI DESIGN.
GENERAL NOTES (POWER)
A REFER TO ELECTRICAL SCHEDULES ON SHEET E6.0 FOR EQUIPMENT CONNECTION SCHEDULE AND
MECHANICAL EQUIPMENT SCHEDULE.
B REFER TO SECURITY PLAN FOR DEVICE LOCATIONS. COORDINATE WITH SECURITY CONTRACTOR
FOR ROUGH-IN REQUIREMENTS.
C PROVIDE 4" CONCRETE PADS FOR ALL FLOOR AND GROUND MOUNTED ELECTRICAL EQUIPMENT.
D PROVIDE THREE, 3" CONDUITS FROM THE MAIN DATA ROOM LOCATED ON THE GROUND LEVEL TO
THE SECOND AND THIRD FLOOR DATA ROOM.
E REFER TO MECHANICAL DRAWINGS FOR EQUIPMENT LOCATION AND SPECIFICATIONS.
1/8" = 1'-0"1
GALENA MIDDLE LEVEL ELECTRICAL
PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
F P
F
F
F
F F
F
F
F
F
F
F
J
J
J
J
T
M
F D
F D
F D
M M
M
M
M
T
T T
T
T
J
F
F
A
11
ELEVATOR
000
D E F
AC, GFIAC, GFI
WP GFI
WP GFI
WP GFI
MEETING ROOM
309
12
13
TD
304
MENS
302
JANITOR
305
VEST
307
1
2
P8
P7
WOMENS
303
ELEC
306
OFFICE
308
MEETING ROOM
310
LOBBY
301
EWC
GFIL3
M3
WP
PV
WP GFI
WP GFI
L3-8
E-3
L3-16
L3-7
L3-8
L3-16
L3-11
L3-11
E-3
L3-13
L3-12
E-3
E-3
L3-10
L3-9L3-9
L3-9L3-9
L3-15
L3-14
L3-12
L3-12
M3-1
EF-3
M3-4
M3-2 M3-2
M3-3
M3-2
FPVAV-7
CUH-10 CUH-11
FPVAV-8
CUH-12
EM-20
EM-20
EM-20
900
213
WP
WP
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
0
A
M
E3.3
2016.01.0223
GALENA UPPER
LEVEL
ELECTRICAL
PLAN
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
FLAG NOTES (THIS SHEET)
213 PROVIDE JUNCTION BOX AND CONDUIT TO THIS LOCATION FROM PANEL 'SB'. POWER
REQUIREMENTS TO BE DETERMINED DURING TI DESIGN.
900 ELECTRICAL INSTALLATION IN THIS AREA MUST CONFORM TO NEC ARTICLE 518.
GENERAL NOTES (POWER)
A REFER TO ELECTRICAL SCHEDULES ON SHEET E6.0 FOR EQUIPMENT CONNECTION SCHEDULE AND
MECHANICAL EQUIPMENT SCHEDULE.
B REFER TO SECURITY PLAN FOR DEVICE LOCATIONS. COORDINATE WITH SECURITY CONTRACTOR
FOR ROUGH-IN REQUIREMENTS.
C PROVIDE 4" CONCRETE PADS FOR ALL FLOOR AND GROUND MOUNTED ELECTRICAL EQUIPMENT.
D PROVIDE THREE, 3" CONDUITS FROM THE MAIN DATA ROOM LOCATED ON THE GROUND LEVEL TO
THE SECOND AND THIRD FLOOR DATA ROOM.
E REFER TO MECHANICAL DRAWINGS FOR EQUIPMENT LOCATION AND SPECIFICATIONS.
1/8" = 1'-0"1
GALENA UPPER LEVEL ELECTRICAL
PLAN
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
FAULT CURRENT CALCULATIONS
Maximum Available Fault Current (IAIC)
I SCA = (I AIC x M)
Where M = 1 / (1+f), and f = (1.732 x L x I AIC) / (C x n x E)
Po
i
n
t
Fault Location
Le
n
g
t
h
,
f
e
e
t
Co
n
d
u
c
t
o
r
s
si
z
e
#
c
o
n
d
u
c
t
o
r
s
pe
r
p
h
a
s
e
Cu
(1)
Al
(2)Co
n
d
u
i
t
Ma
g
n
e
t
i
c
(
1
)
No
n
m
a
g
n
.
(
2
)
Vo
l
t
a
g
e
Ph
a
s
e
"C" Value
Pr
e
v
i
o
u
s
fa
u
l
t
v
a
l
u
e
Fault value
U Service Transformer Secondary Winding per CCA 59,100
1 OUTDOOR SERVICE ENTRY 10 500 11 1 2 208 3 26706 59100
58,126
2 MSB 20 500 11 1 2 208 3 26706 58126
56,272
3 PNL LB 20 "3/0" 1 1 1 208 3 12843 56272
32,532
4 PNL MB 40 350 2 1 1 208 3 19703 56272
38,134
5 PNL M1 20 "3/0" 2 1 1 208 3 12843 56272
41,229
6 PNL L1 20 "3/0" 2 1 1 208 3 12843 56272
41,229
7 PNL M2 40 "3/0" 2 1 1 208 3 12843 56272
32,532
8 PNL L2 40 "3/0" 2 1 1 208 3 12843 56272
32,532
9 PNL M3 60 "3/0" 1 1 1 208 3 12843 56272
17,645
10 PNL L3 60 "3/0" 1 1 1 208 3 12843 56272
17,645
11 ELEV 1 - GALENA 60 "2/0"1 1 1 208 3 10755 56272
15,570
12 ELEV 2 - RIO GRANDE 250 "2/0" 1 1 1 208 3 10755 56272
4,732
13 B-1 70 300 3 1 1 208 3 18176 56272
35,136
14 B-2 70 300 3 1 1 208 3 18176 56272
35,136
15 B-3 70 300 3 1 1 208 3 18176 56272
35,136
16 WWHP-3 60 300 1 1 1 208 3 18176 56272
22,095
17 WWHP-2 60 300 1 1 1 208 3 18176 56272 22,095
18 WWHP-1 60 300 1 1 1 208 3 18176 56272 22,095
19 AHU-1 70 250 2 1 1 208 3 16483 56272
28,207
20 ATS-SB 20 4 1 1 1 208 3 3806 56272
16,253
21 PNL SB 50 4 1 1 1 208 3 3806 16253
5,851
22 ATS EM 20 1 1 1 1 208 3 7292 56272
24,624
23 PNL EM 20 1 1 1 1 208 3 7292 24624
15,761
G
J
J
J
FEEDER SCHEDULEFEEDER SCHEDULE
600D
800D
1000D
1200D
ELEV
45D (3#6+#10G)1"C
400D
450D
500D
350D
300D
175D
225D
250D
200D
110D
90D
125D
150D
100D
80D
60D
70D
50D
(3-350KCMIL+#4G)2-1/2"C
(3-500KCMIL+#3G)3"C
(3-250KCMIL+#4G)2-1/2"C
(3#2/0+#6G)2"C
(3#4/0+#4G)2"C
(3#3/0+#6G)2"C
(3#1+#6G)1-1/2"C
(3#2+#8G)1-1/4"C
(3#1/0+#6G)1-1/2"C
(3#1+#6G)1-1/2"C
(3#1+#8G)1-1/2"C
(3#3+#8G)1-1/4"C
(3#4+#10G)1-1/4"C
(3#4+#8G)1-1/4"C
(3#6+#10G)1"C
WIRE AND CONDUIT SIZE - 3∅, 3W
35D
40D
30D
(3#8+#10G)3/4"C
(3#8+#10G)3/4"C
(3#10+#10G)3/4"C
(3#1/0+#1/0G)1-1/2"C
4[(3-350KCMIL+#3/0G)3"C]
3[(3-400KCMIL+#2/0G)2-1/2"C]
3[(3-300KCMIL+#1/0G)2-1/2"C]
2[(3-250KCMIL+#2G)2-1/2"C]
2[(3-350KCMIL+#1G)2-1/2"C]
2[(3#4/0+#2G)2"C]
2[(3#3/0+#3G)2"C]
2500Y
3000Y
4000Y
800Y
1000Y
1200Y
1600Y
2000Y
11[(4-500KCMIL+500KCMIL G)4"C]
8[(4-500KCMIL+400KCMIL G)3-1/2"C]
7[(4-500KCMIL+350KCMIL G)3-1/2"C]
6[(4-400KCMIL+250KCMIL G)3"C]
5[(4-400KCMIL+#4/0G)3"C]
4[(4-350KCMIL+#3/0G)3"C]
3[(4-400KCMIL+#2/0G)3"C]
3[(4-300KCMIL+#1/0G)2-1/2"C]
175Y
350Y
400Y
450Y
500Y
600Y
300Y
225Y
250Y
200Y
110Y
125Y
150Y
100Y
90Y
80Y
60Y
70Y
50Y
(4#2/0+#6G)2"C
2[(4-250KCMIL+#2G)2-1/2"C]
(4-350KCMIL+#4G)3"C
(4-500KCMIL+#3G)3"C
2[(4-350KCMIL+#1G)3"C]
(4-250KCMIL+#4G)2-1/2"C
(4#4/0+#4G)2-1/2"C
2[(4#4/0+#2G)2"C]
2[(4#3/0+#3G)2-1/2"C]
(4#3/0+#6G)2"C
(4#2+#8G)1-1/4"C
(4#1+#6G)1-1/2"C
(4#1/0+#6G)2"C
(4#1+#6G)1-1/2"C
(4#1+#8G)1-1/2"C
(4#3+#8G)1-1/4"C
(4#4+#10G)1-1/4"C
(4#4+#8G)1-1/4"C
(4#6+#10G)1"C
WIRE AND CONDUIT SIZE - 3∅, 4W
45Y
35Y
40Y
30Y
(4#6+#10G)1"C
(4#8+#10G)1"C
(4#8+#10G)1"C
(4#10+#10G)3/4"C
4000U 11[(4-500KCMIL)4"C]
MECH REFER TO MECHANICAL SCHEDULE
U
1
3
2
10
4 5
6 7
8 9
13
23
24
11
21
22
3
14 17 18 19 2015
M M
SP
D
M
EM
LIGHTING
CIRCUIT
EM
LIGHTING
CIRCUIT
EM
LIGHTING
CIRCUIT
MIDDLE LEVEL
MAIN LEVEL
ROOF
BASEMENT LEVEL
UPPER LEVEL
CITY OF ASPEN
ELECTRICAL
UTILITY PADMOUNT
TRANSFORMER WITH
PRECAST
TRANSFORMER VAULT
BY EC. PER COA
REQUIREMENTS
1. PROVIDE A 3" CONDUIT FROM MSB TO THE PROPOSED
INVERTER LOCATION FOR FUTURE PV. PROVIDE WITH
PULL STRING AND CAP BOTH ENDS FOR CONNECTION TO
THE FUTURE PV. PROVIDE 400A SPACE FOR BREAKER TO
BE SIZED BASED ON INSTALLED PV REQUIREMENTS.
2. PROVIDE DEMAND METERS, COMPATIBLE WITH METERING
SYSTEM, TO MONITOR PANEL AND EQUIPMENT AS NOTED.
PROVIDE SIZE AS REQUIRED FOR METERED PANEL.
COORDINATE AND VERIFY EXACT TYPE WITH OWNER
PRIOR TO ORDERING.
3. REFER TO MECHANICAL SCHEDULE ON E6.0 FOR
DISCONNECT REQUIREMENTS.
4. PROVIDE ARC FLASH ENERGY REDUCTION PER NEC 240.87.
5. PROVIDE 80KW NATURAL GAS GENERATOR. DERATE FOR
ALTITUDE.
A. LOCAL ELECTRICAL UTILITY IS COA (CITY OF ASPEN
UTILITY). ELECTRICAL CONTRACTOR TO MEET COA
REQUIREMENTS FOR INSTALLATION.
B. GENERATOR MUST MEET OR EXCEED THE CALIFORNIA
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT
REQUIREMENTS TO ACHIEVE WELL BUILDING POINT.
C. PROVIDE BACKFED TYPE BREAKERS WHERE REQUIRED
FOR PV SYSTEM.
D. ALL PANELS TO INCLUDE INDIVIDUAL CIRCUIT METERING
PER TO ACHIEVE LEED DEMAND RESPONSE, 1 POINT AND
LEED ADVANCED ENERGY METERING, 1 POINT. eGUAGE OR
SIMILAR.
1
ONE-LINE DIAGRAM FLAG NOTES:
ONE-LINE DIAGRAM GENERAL NOTES:
2 2 52
3
3
3
3
3
3
3
3
3
3
3
3
3
3
4
M
PANEL
LB
PANEL
M1
PANEL
L1
PANEL
M2
PANEL
L2
PANEL
M3
PANEL
L3
PANEL
EM
PANEL
SB
PANEL
MB
UTILITY
PRIMARY
4000U
NEMA 3R OUTDOOR
SERVICE ENTRY - MSD
4000A, 208Y/120V, 3PH, 4W
4000A
3P
4000Y
BASEMENT POWER
AND LIGHTING
ELEV
200A
3P
ELEV
MAIN SWITCHBOARD MSB-4000A, 208Y/120V, 3PH, 4W
ELEV
CONTROLLER
N
G
#4 UFER
#3/0 BLDG
STEEL AND
WATER ENTRY
MAIN
MECHANICAL
400A
3P
200Y
MAIN POWER
AND LIGHTING
400A
3P
400Y 400Y
MIDDLE
MECHANICAL
400A
3P
MIDDLE
POWER AND
LIGHTING
400A
3P
400Y 400Y
UPPER
MECHANICAL
200A
3P
UPPER
POWER AND
LIGHTING
200A
3P
200Y 200Y
350A
3P
400A
SPACE
100A3P
ATS
100A3P
100A
3P
100Y
100Y
100Y
60A
3P
60Y
350A
350AF
ELEV
ELEV
ELEV
CONTROLLER
350A
3P
350A
350AF
60A
3P
ATS
60A3P
60Y
60Y
60A3P
600A
3P
600Y
BASEMENT
MECHANICAL
SPACES:
(3) 200A3P
(3) 100A3P
B-2 WWHP-3 WWHP-2 WWHP-1 AHU-1B-3B-1
60Y
MECH MECH MECH MECH MECH MECH MECH
ELEV ELEV
#6 GROUND ROD
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
0
A
M
E4.0
2016.01.0223
ELECTRICAL
ONE LINE
DIAGRAM
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
1
A
M
E4.1
2016.01.0223
PANEL
SCHEDULES
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
[1] SPACE DEDICATED FOR FUTURE PV SYSTEM. DESIGNED AND PROVIDED BY OTHERS.
[2] ALL THREE BOILERS WILL NOT BE IN OPERATION AT THE SAME TIME.
[3] PROVIDE SHUNT TRIP BREAKER FOR EPO.
Notes:
C TO A:1
B TO C:1
Electric Range Large 0 0.00% 0 A TO B:0.99
Electric Range Small 0 0.00% 0 Phase Balance
Electric Clothes Dryer 0 0.00% 0
Existing Load 0 0.00% 0 Spare:796.7
Kitchen Equipment 0 0.00% 0 Design:4000
Elevator 0 0.00% 0 Load:3203.3
Heating 476000 100.00% 476000 Amperes
Cooling 0 0.00% 0
Equipment 4100 100.00% 4100 Spare:286
Appliance 0 0.00% 0 Demand:1154
Motor 606290 107.18% 649850 Design:1440
Receptacle 12360 90.45% 11180 Connected 1109.1
Lighting 10334 125.00% 12917 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 364570
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 370447
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 374063
-- Space -- -- -- 83 0 0 84 -- -- --Space --
-- Space -- -- -- 81 0 0 82 -- -- --Space --
-- Space -- -- -- 79 0 0 80 -- -- --Space --
-- Space -- -- -- 77 0 0 78 -- -- --Space --
-- Space -- -- -- 75 0 0 76 -- -- --Space --
-- Space -- -- -- 73 0 0 74 -- -- --Space --
-- Space -- -- -- 71 0 0 72 -- -- --Space --
-- Space -- -- -- 69 0 0 70 -- -- --Space --
-- Space -- -- -- 67 0 0 68 -- -- --Space --
65 0 ... 66
63 ... ... 64ATS-SB 500 540 500 20
61 ... ... 62
20 3500 3085 ATS-EM
59 ... ... 60
57 ... ... 58WWHP-3 M 89640 400
55 ... ... 56
500 174240 M AHU-1
53 ... ... 54
51 ... ... 52WWHP-1 M 89640 400
49 ... ... 50
400 89640 M WWHP-2
47 0 0 48 -- -- --Space --
45 0 0 46 -- -- --Space --[2],[3] B-3 H 0 800
43 0 0 44 -- -- --Space --
41 ... ... 42
39 ... ... 40[3] B-1 H 224000 800
37 ... ... 38
800 224000 H B-2 [3]
35 ... ... 36
33 ... ... 34[3] ELEVATOR 000 - GALENA EL 41570 350
31 ... ... 32
350 41570 EL ELEVATOR 000 - RIO GRANDE [3]
29 0 0 30
27 ... 0 28M32630 200
25 ... 0 26
0 0 SPACE FOR FUTURE PV [1]
23 0 ... 24
21 ... ... 22M21500 400
19 ... ... 20
200 2000 900 685 L3
17 ... ... 18
15 ... ... 16M14780 400
13 ... ... 14
400 2000 900 408 L2
11 ... ... 12
9 ... ... 10MB89180 600
7 ... ... 8
400 1000 1080 631 L1
5 0 ... 6
3 0 ... 4SPD0 60
1 0 ... 2
200 5000 900 1152 LB
Notes Description L R
M | A | E | H |
C | EL | EX |
KE
A B C
M | A | E | H |
C | EL | EX |
KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
4000 A : Ampacity : Fed From : Neutral Bus FLOOR : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service MLO : Mains Type (MLO or MCB)
MSB
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
Notes:
C TO A:0.3
B TO C:0.9
A TO B:0.27
Phase Balance
Spare:174.7
Design:200
Load:25.3
Amperes
Equipment 1500 100.00% 1500 Spare:62.9
Appliance 0 0.00% 0 Demand:9.1
Motor 2000 101.25% 2025 Design:72
Receptacle 0 0.00% 0 Connected 8
Lighting 4463 125.00% 5578 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 1500
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 1378
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 5085
Spare -- -- 20 41 0 42
Spare -- -- 20 39 0 40
Spare -- -- 20 37 0 38
Spare -- -- 20 35 0 36
Spare -- -- 20 33 0 34
Spare -- -- 20 31 0 32
E-FACP E 500 20 29 ... ... 30 20 1000 EQUIPMENT
L-GRAND STAIR 32 0 20 27 ... ... 28 20 0 128 L-PUMP ROOM
L-S001 STAIR 520 0 20 25 ... ... 26 20 100 M M-ROOF DAMPER
Spare (UPPER LEVEL LIGHTING) -- -- 20 23 0 0 24 20 -- --Spare
L-UPPER LEVEL EXTERIOR 108 0 20 21 ... 0 22 20 -- --Spare
L-UPPER LEVEL EM 527 0 20 19 ... ... 20 20 300 M M-UPPER LEVEL DAMPERS
Spare (MID LEVEL LIGHTING) -- -- 20 17 0 0 18 20 -- --Spare
Spare (MID LEVEL LIGHTING) -- -- 20 15 0 0 16 20 -- --Spare
L-MID LEVEL EM 694 0 20 13 ... ... 14 20 600 M M-MID LEVEL DAMPERS
Spare (MAIN LEVEL LIGHTING) -- -- 20 11 0 0 12 20 -- --Spare
L-MAIN LEVEL EXT EM 1111 0 20 9 ... 0 10 20 -- --Spare
L-MAIN LEVEL EM 480 0 20 7 ... ... 8 20 600 M M-MAIN LEVEL DAMERS
Spare (BASEMENT LIGHTING) -- -- 20 5 0 0 6 20 -- --Spare
Spare (BASEMENT LIGHTING) -- -- 20 3 0 0 4 20 -- --Spare
L-BASEMENT EM 864 0 20 1 ... ... 2 20 400 M M-BASEMENT DAMPERS
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
100 A : Ampacity ATS-EM : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service MLO : Mains Type (MLO or MCB)
EM
Notes:
C TO A:0
B TO C:0
A TO B:0.96
Phase Balance
Spare:193.6
Design:200
Load:6.4
Amperes
Equipment 500 100.00% 500 Spare:69.7
Appliance 0 0.00% 0 Demand:2.3
Motor 0 0.00% 0 Design:72
Receptacle 540 100.00% 540 Connected 2
Lighting 1000 125.00% 1250 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 0
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 1000
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 1040
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
ELEVATOR - RIO - CAB LIGHTS 500 0 20 3 ... ... 4 20 500 E-TCP PANEL
R-004 DATA CENTER 540 0 20 1 ... ... 2 20 0 500 ELEVATOR GALENA - CAB LIGHTS
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
60 A : Ampacity ATS-SB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service MLO : Mains Type (MLO or MCB)
SB
03/16/2019
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
2
A
M
E4.2
2016.01.0223
PANEL
SCHEDULES
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
Notes:
C TO A:0.7
B TO C:0.8
A TO B:0.88
Phase Balance
Spare:173.3
Design:200
Load:26.7
Amperes
Equipment 500 100.00% 500 Spare:62.4
Appliance 0 0.00% 0 Demand:9.6
Motor 500 125.00% 625 Design:72
Receptacle 3060 100.00% 3060 Connected 9.2
Lighting 1152 125.00% 1440 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 2540
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 3120
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 3552
Spare -- -- 20 41 0 0 42 20 -- --Spare
Spare -- -- 20 39 0 0 40 20 -- --Spare
Spare -- -- 20 37 0 0 38 20 -- --Spare
Spare -- -- 20 35 0 0 36 20 -- --Spare
Spare -- -- 20 33 0 0 34 20 -- --Spare
Spare -- -- 20 31 0 0 32 20 -- --Spare
Spare -- -- 20 29 0 0 30 20 -- --Spare
Spare -- -- 20 27 0 0 28 20 -- --Spare
Spare -- -- 20 25 0 0 26 20 -- --Spare
Spare -- -- 20 23 0 0 24 20 -- --Spare
Spare -- -- 20 21 0 0 22 20 -- --Spare
HEATING 1000 20 19 ... 0 20 20 -- --Spare
17 ... 0 18 20 -- --SpareH-003 JACKET HEATER 3000 20
15 ... 0 16 20 -- --Spare
R-008 PUMP ROOM 360 0 20 13 ... 0 14 20 -- --Spare
E-006 DOOR POWER E 500 20 11 ... ... 12 20 0 540 R-001,002
R-005 MECH 1260 0 20 9 ... ... 10 20 0 360 R-006
E-003 BATTERY CHARGER E 500 20 7 ... ... 8 20 0 540 R-003, 007 ELEC GENERATOR
Spare -- -- 20 5 0 0 6 20 -- --Spare
Spare -- -- 20 3 0 0 4 20 -- --Spare
L-BASEMENT GENERAL 896 0 20 1 ... ... 2 20 0 256 L-BASEMENT CORE
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
200 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service MLO : Mains Type (MLO or MCB)
LB
Notes:
C TO A:0.9
B TO C:0.5
A TO B:0.43
Phase Balance
Spare:377
Design:400
Load:23
Amperes
Equipment 0 0.00% 0 Spare:135.7
Appliance 0 0.00% 0 Demand:8.3
Motor 1000 112.50% 1125 Design:144
Receptacle 4140 100.00% 4140 Connected 7.5
Lighting 2409 125.00% 3011 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 1900
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 3940
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 1709
Spare -- -- 20 83 0 0 84 -- -- --Space --
Spare -- -- 20 81 0 0 82 -- -- --Space --
Spare -- -- 20 79 0 0 80 -- -- --Space --
Spare -- -- 20 77 0 0 78 -- -- --Space --
Spare -- -- 20 75 0 0 76 -- -- --Space --
Spare -- -- 20 73 0 0 74 -- -- --Space --
Spare -- -- 20 71 0 0 72 -- -- --Space --
Spare -- -- 20 69 0 0 70 -- -- --Space --
Spare -- -- 20 67 0 0 68 -- -- --Space --
Spare -- -- 20 65 0 0 66 20 -- --Spare
Spare -- -- 20 63 0 0 64 20 -- --Spare
Spare -- -- 20 61 0 0 62 20 -- --Spare
Spare -- -- 20 59 0 0 60 20 -- --Spare
Spare -- -- 20 57 0 0 58 20 -- --Spare
Spare -- -- 20 55 0 0 56 20 -- --Spare
Spare -- -- 20 53 0 0 54 20 -- --Spare
Spare -- -- 20 51 0 0 52 20 -- --Spare
Spare -- -- 20 49 0 0 50 20 -- --Spare
Spare -- -- 20 47 0 0 48 20 -- --Spare
Spare -- -- 20 45 0 0 46 20 -- --Spare
Spare -- -- 20 43 0 0 44 20 -- --Spare
Spare -- -- 20 41 0 0 42 20 -- --Spare
Spare -- -- 20 39 0 0 40 20 -- --Spare
Spare -- -- 20 37 0 0 38 20 -- --Spare
Spare -- -- 20 35 0 0 36 20 -- --Spare
Spare -- -- 20 33 0 0 34 20 -- --Spare
Spare -- -- 20 31 0 0 32 20 -- --Spare
Spare -- -- 20 29 0 0 30 20 -- --Spare
Spare -- -- 20 27 0 0 28 20 -- --Spare
Spare -- -- 20 25 0 0 26 20 -- --Spare
Spare -- -- 20 23 0 0 24 20 -- --Spare
Spare -- -- 20 21 0 0 22 20 -- --Spare
Spare -- -- 20 19 0 0 20 20 -- --Spare
R-101,107 360 0 20 17 ... ... 18 20 1000 E-107 DOOR POWER
R-SOUTH EXTERIOR 540 0 20 15 ... ... 16 20 0 360 R-EAST EXTERIOR
R-104 180 0 20 13 ... ... 14 20 0 180 R-101
E-MAIN EWC 180 0 20 11 ... ... 12 20 0 360 R-101
R-ELECTRICAL YARD 540 0 20 9 ... ... 10 20 0 720 R-MAIN RESTROOM GROUP
R-BIKE RACK 360 0 20 7 ... ... 8 20 0 360 R-108
Spare -- -- 20 5 0 0 6 20 -- --Spare
Spare -- -- 20 3 0 ... 4 20 0 1780 LIGHTING
L-MAIN LEVEL CORE 533 0 20 1 ... ... 2 20 0 98 L-MAIN LEVEL EXTERIOR
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
400 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service 400A MCB : Mains Type (MLO or MCB)
L1
03/16/2019
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
3
A
M
E4.3
2016.01.0223
PANEL
SCHEDULES
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
Notes:
C TO A:0.6
B TO C:0.4
A TO B:0.23
Phase Balance
Spare:387.7
Design:400
Load:12.3
Amperes
Equipment 0 0.00% 0 Spare:139.6
Appliance 0 0.00% 0 Demand:4.4
Motor 2000 106.25% 2125 Design:144
Receptacle 1800 100.00% 1800 Connected 4.2
Lighting 408 125.00% 511 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 1360
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 540
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 2307
Spare -- -- 20 83 0 0 84 -- -- --Space --
Spare -- -- 20 81 0 0 82 -- -- --Space --
Spare -- -- 20 79 0 0 80 -- -- --Space --
Spare -- -- 20 77 0 0 78 -- -- --Space --
Spare -- -- 20 75 0 0 76 -- -- --Space --
Spare -- -- 20 73 0 0 74 -- -- --Space --
Spare -- -- 20 71 0 0 72 -- -- --Space --
Spare -- -- 20 69 0 0 70 -- -- --Space --
Spare -- -- 20 67 0 0 68 -- -- --Space --
Spare -- -- 20 65 0 0 66 20 -- --Spare
Spare -- -- 20 63 0 0 64 20 -- --Spare
Spare -- -- 20 61 0 0 62 20 -- --Spare
Spare -- -- 20 59 0 0 60 20 -- --Spare
Spare -- -- 20 57 0 0 58 20 -- --Spare
Spare -- -- 20 55 0 0 56 20 -- --Spare
Spare -- -- 20 53 0 0 54 20 -- --Spare
Spare -- -- 20 51 0 0 52 20 -- --Spare
Spare -- -- 20 49 0 0 50 20 -- --Spare
Spare -- -- 20 47 0 0 48 20 -- --Spare
Spare -- -- 20 45 0 0 46 20 -- --Spare
Spare -- -- 20 43 0 0 44 20 -- --Spare
Spare -- -- 20 41 0 0 42 20 -- --Spare
Spare -- -- 20 39 0 0 40 20 -- --Spare
Spare -- -- 20 37 0 0 38 20 -- --Spare
Spare -- -- 20 35 0 0 36 20 -- --Spare
Spare -- -- 20 33 0 0 34 20 -- --Spare
Spare -- -- 20 31 0 0 32 20 -- --Spare
Spare -- -- 20 29 0 0 30 20 -- --Spare
Spare -- -- 20 27 0 0 28 20 -- --Spare
Spare -- -- 20 25 0 0 26 20 -- --Spare
Spare -- -- 20 23 0 0 24 20 -- --Spare
Spare -- -- 20 21 0 0 22 20 -- --Spare
Spare -- -- 20 19 0 0 20 20 -- --Spare
Spare -- -- 20 17 0 0 18 20 -- --Spare
Spare -- -- 20 15 0 0 16 20 -- --Spare
E-209 DOOR POWER 500 20 13 ... ... 14 20 500 E-209 DOOR POWER
E-MID EWC 180 0 20 11 ... ... 12 20 1000 180 E-207 DOOR POWER
E-MID EWC 180 0 20 9 ... ... 10 20 0 360 R-204
R-MID RESTROOM GROUP 720 0 20 7 ... ... 8 20 0 180 R-206
Spare -- -- 20 5 0 0 6 20 -- --Spare
Spare -- -- 20 3 0 0 4 20 -- --Spare
L-MID LEVEL CORE 408 0 20 1 ... 0 2 20 -- --Spare
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
400 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service 400A MLO : Mains Type (MLO or MCB)
L2
Notes:
C TO A:1
B TO C:0.6
A TO B:0.61
Phase Balance
Spare:183.1
Design:200
Load:16.9
Amperes
Equipment 0 0.00% 0 Spare:65.9
Appliance 0 0.00% 0 Demand:6.1
Motor 2000 106.25% 2125 Design:72
Receptacle 2820 100.00% 2820 Connected 5.7
Lighting 908 125.00% 1135 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 1540
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 2600
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 1583
Spare -- -- 20 83 0 0 84 -- -- --Space --
Spare -- -- 20 81 0 0 82 -- -- --Space --
Spare -- -- 20 79 0 0 80 -- -- --Space --
Spare -- -- 20 77 0 0 78 -- -- --Space --
Spare -- -- 20 75 0 0 76 -- -- --Space --
Spare -- -- 20 73 0 0 74 -- -- --Space --
Spare -- -- 20 71 0 0 72 -- -- --Space --
Spare -- -- 20 69 0 0 70 -- -- --Space --
Spare -- -- 20 67 0 0 68 -- -- --Space --
Spare -- -- 20 65 0 0 66 20 -- --Spare
Spare -- -- 20 63 0 0 64 20 -- --Spare
Spare -- -- 20 61 0 0 62 20 -- --Spare
Spare -- -- 20 59 0 0 60 20 -- --Spare
Spare -- -- 20 57 0 0 58 20 -- --Spare
Spare -- -- 20 55 0 0 56 20 -- --Spare
Spare -- -- 20 53 0 0 54 20 -- --Spare
Spare -- -- 20 51 0 0 52 20 -- --Spare
Spare -- -- 20 49 0 0 50 20 -- --Spare
Spare -- -- 20 47 0 0 48 20 -- --Spare
Spare -- -- 20 45 0 0 46 20 -- --Spare
Spare -- -- 20 43 0 0 44 20 -- --Spare
Spare -- -- 20 41 0 0 42 20 -- --Spare
Spare -- -- 20 39 0 0 40 20 -- --Spare
Spare -- -- 20 37 0 0 38 20 -- --Spare
Spare -- -- 20 35 0 0 36 20 -- --Spare
Spare -- -- 20 33 0 0 34 20 -- --Spare
Spare -- -- 20 31 0 0 32 20 -- --Spare
Spare -- -- 20 29 0 0 30 20 -- --Spare
Spare -- -- 20 27 0 0 28 20 -- --Spare
Spare -- -- 20 25 0 0 26 20 -- --Spare
Spare -- -- 20 23 0 0 24 20 -- --Spare
Spare -- -- 20 21 0 0 22 20 -- --Spare
Spare -- -- 20 19 0 0 20 20 -- --Spare
Spare -- -- 20 17 0 0 18 20 -- --Spare
R-304 180 0 20 15 ... ... 16 20 1000 E-DOOR POWER
R-301 180 0 20 13 ... ... 14 20 0 180 R-308
E-307 DOOR POWER 1000 20 11 ... ... 12 20 0 540 R-PLAZA
RECEPTACLE 720 0 20 9 ... ... 10 20 0 480 E-3RD EWC
R-306 180 0 20 7 ... ... 8 20 0 360 R-309 TERRACE
Spare -- -- 20 5 0 0 6 20 -- --Spare
Spare -- -- 20 3 0 ... 4 20 0 224 L-PLAZA STAIR
L-3RD FLOOR CORE 479 0 20 1 ... ... 2 20 0 207 L-3RD FLOOR EXTERIOR
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
200 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service 200A MCB : Mains Type (MLO or MCB)
L3
03/16/2019
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
4
A
M
E4.4
2016.01.0223
PANEL
SCHEDULES
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
Notes:
C TO A:1
B TO C:1
A TO B:0.98
Phase Balance
Spare:340.9
Design:600
Load:259.1
Amperes
Equipment 1600 100.00% 1600 Spare:122.6
Appliance 0 0.00% 0 Demand:93.4
Motor 63580 106.58% 67763 Design:216
Receptacle 0 0.00% 0 Connected 89.2
Lighting 0 0.00% 0 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 29943
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 29983
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 29253
-- Space -- -- -- 59 0 0 60 -- -- --Space --
-- Space -- -- -- 57 0 0 58 -- -- --Space --
-- Space -- -- -- 55 0 0 56 -- -- --Space --
-- Space -- -- -- 53 0 0 54 -- -- --Space --
-- Space -- -- -- 51 0 0 52 -- -- --Space --
-- Space -- -- -- 49 0 0 50 -- -- --Space --
Spare -- -- 20 47 0 ... 48
Spare -- -- 20 45 0 ... 46
M-UH-3 & EF-2 M 710 20 43 ... ... 44
60 8760 M-HWP-2
41 ... ... 42
39 ... ... 40H-WH-1 H 24000 100
37 ... ... 38
60 8760 M-HWP-1
35 ... 0 36
33 ... 0 34M-CWP-1 M 11150 80
31 ... 0 32
80 0 M M-CWP-2 [1]
29 ... 0 30
27 ... 0 28M-GWP-1 M 16730 110
25 ... 0 26
110 0 M M-GWP-2 [1]
23 ... 0 24
21 ... 0 22M-HWP-3 M 6060 20
19 ... 0 20
20 0 M M-HWP-4 [1]
17 ... ... 18
15 ... ... 16M-BP-2 M 2390 20
13 ... ... 14
20 2390 M M-BP-3
M-CP-3 M 510 20 11 ... ... 12
M-UH-1,GF-2 M 1020 20 9 ... ... 10
M-CP-1,2 M 510 20 7 ... ... 8
20 2390 M M-BP-1
E-AHU-120V E 1600 20 5 ... ... 6
M-SP-1 M 1130 20 3 ... ... 4
M-RCP-1 M 200 20 1 ... ... 2
20 870 M M-SP-3
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
600 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service MLO : Mains Type (MLO or MCB)
MB
Notes:
C TO A:0.5
B TO C:0.6
A TO B:0.76
Phase Balance
Spare:385.9
Design:400
Load:14.1
Amperes
Equipment 0 0.00% 0 Spare:138.9
Appliance 0 0.00% 0 Demand:5.1
Motor 4780 105.91% 5063 Design:144
Receptacle 0 0.00% 0 Connected 4.8
Lighting 0 0.00% 0 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 1020
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 1620
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 2140
-- Space -- -- -- 41 0 0 42 -- -- --Space --
-- Space -- -- -- 39 0 0 40 -- -- --Space --
-- Space -- -- -- 37 0 0 38 -- -- --Space --
-- Space -- -- -- 35 0 0 36 -- -- --Space --
-- Space -- -- -- 33 0 0 34 -- -- --Space --
-- Space -- -- -- 31 0 0 32 -- -- --Space --
-- Space -- -- -- 29 0 0 30 -- -- --Space --
-- Space -- -- -- 27 0 0 28 -- -- --Space --
-- Space -- -- -- 25 0 0 26 -- -- --Space --
-- Space -- -- -- 23 0 0 24 -- -- --Space --
-- Space -- -- -- 21 0 0 22 -- -- --Space --
-- Space -- -- -- 19 0 0 20 -- -- --Space --
-- Space -- -- -- 17 0 0 18 -- -- --Space --
-- Space -- -- -- 15 0 0 16 -- -- --Space --
-- Space -- -- -- 13 0 0 14 -- -- --Space --
-- Space -- -- -- 11 0 0 12 -- -- --Space --
-- Space -- -- -- 9 0 0 10 -- -- --Space --
M-CUH-4 M 300 20 7 ... 0 8 -- -- --Space --
M-FPVAV-3 M 510 40 5 ... ... 6 40 510 M M-FPVAV-2
M-FPVAV-1 M 510 40 3 ... ... 4 20 1110 M M-CUH-2,3,7
M-SP-2 M 1130 20 1 ... ... 2 20 710 M M-UH-2,EF-4
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
400 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service 400A MCB : Mains Type (MLO or MCB)
M1
Notes:
C TO A:0
B TO C:0
A TO B:0.67
Phase Balance
Spare:395.6
Design:400
Load:4.4
Amperes
Equipment 0 0.00% 0 Spare:142.4
Appliance 0 0.00% 0 Demand:1.6
Motor 1500 105.00% 1575 Design:144
Receptacle 0 0.00% 0 Connected 1.5
Lighting 0 0.00% 0 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 0
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 900
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 600
-- Space -- -- -- 41 0 0 42 -- -- --Space --
-- Space -- -- -- 39 0 0 40 -- -- --Space --
-- Space -- -- -- 37 0 0 38 -- -- --Space --
-- Space -- -- -- 35 0 0 36 -- -- --Space --
-- Space -- -- -- 33 0 0 34 -- -- --Space --
-- Space -- -- -- 31 0 0 32 -- -- --Space --
-- Space -- -- -- 29 0 0 30 -- -- --Space --
-- Space -- -- -- 27 0 0 28 -- -- --Space --
-- Space -- -- -- 25 0 0 26 -- -- --Space --
-- Space -- -- -- 23 0 0 24 -- -- --Space --
-- Space -- -- -- 21 0 0 22 -- -- --Space --
-- Space -- -- -- 19 0 0 20 -- -- --Space --
-- Space -- -- -- 17 0 0 18 -- -- --Space --
-- Space -- -- -- 15 0 0 16 -- -- --Space --
-- Space -- -- -- 13 0 0 14 -- -- --Space --
-- Space -- -- -- 11 0 0 12 -- -- --Space --
-- Space -- -- -- 9 0 0 10 -- -- --Space --
-- Space -- -- -- 7 0 0 8 -- -- --Space --
-- Space -- -- -- 5 0 0 6 -- -- --Space --
M-FPVAV-6 300 40 3 ... ... 4 20 600 M-CUH-8,9
M-FPVAV-4 300 40 1 ... ... 2 40 300 M-FPVAV-5
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
400 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service 400A MCB : Mains Type (MLO or MCB)
M2
Notes:
C TO A:0
B TO C:0
A TO B:0.3
Phase Balance
Spare:191.9
Design:200
Load:8.1
Amperes
Equipment 0 0.00% 0 Spare:69.1
Appliance 0 0.00% 0 Demand:2.9
Motor 2630 110.74% 2913 Design:72
Receptacle 0 0.00% 0 Connected 2.6
Lighting 0 0.00% 0 KVA
Load Classification Connected Load Demand Factor Demand Load Panel Totals
L = Lighting; M = Motor; R = Receptacle; RA = Electric Range Phase C: 0
EX = Existing; H = Heating; KE = Kitchen Equipment; Phase B: 600
Load Type Abbreviations:A = Appliance; C = Cooling; D = Dryer; E = Equipment; EL = Elevator; Phase A: 2030
-- Space -- -- -- 41 0 0 42 -- -- --Space --
-- Space -- -- -- 39 0 0 40 -- -- --Space --
-- Space -- -- -- 37 0 0 38 -- -- --Space --
-- Space -- -- -- 35 0 0 36 -- -- --Space --
-- Space -- -- -- 33 0 0 34 -- -- --Space --
-- Space -- -- -- 31 0 0 32 -- -- --Space --
-- Space -- -- -- 29 0 0 30 -- -- --Space --
-- Space -- -- -- 27 0 0 28 -- -- --Space --
-- Space -- -- -- 25 0 0 26 -- -- --Space --
-- Space -- -- -- 23 0 0 24 -- -- --Space --
-- Space -- -- -- 21 0 0 22 -- -- --Space --
-- Space -- -- -- 19 0 0 20 -- -- --Space --
-- Space -- -- -- 17 0 0 18 -- -- --Space --
-- Space -- -- -- 15 0 0 16 -- -- --Space --
-- Space -- -- -- 13 0 0 14 -- -- --Space --
-- Space -- -- -- 11 0 0 12 -- -- --Space --
-- Space -- -- -- 9 0 0 10 -- -- --Space --
-- Space -- -- -- 7 0 0 8 -- -- --Space --
-- Space -- -- -- 5 0 0 6 -- -- --Space --
M-FPVAV-8 300 40 3 ... ... 4 40 300 M-FPVAV-7
M-EF-3 1130 20 1 ... ... 2 20 900 M-CUH-10, 11, 12
Notes Description L R
M | A | E | H
| C | EL | EX
| KE
A B C
M | A | E | H
| C | EL | EX
| KE
R L Description Notes
: Avail. Fault Current No : IG Bus No : Feed thru Lugs : Modifications
200 A : Ampacity MSB : Fed From : Neutral Bus Surface : Mounting
120/208 Wye : Voltage 3 : Phase 4 : Wire Service 200A MCB : Mains Type (MLO or MCB)
M3
03/16/2019
NO SCALE
CM
CM
F C M
CM CM
CM
CM
CM
NO SCALE
CM
CM
LO
O
P
PO
W
E
R
F T190°
F
P
FP
F
T
X
ST
ST
F F
TYPICAL MACHINEROOMLESS ELEVATOR DETAIL
TYPICAL ELEVATOR SHUNT TRIP SCHEMATIC
TYPICAL ELEVATOR PIT DETAIL
P/T
J
TYPICAL FIRE ALARM RISER DIAGRAM
C
FACP
M
F
M
R R
M
T T
M
MM 190°
MM
F
MM
T
F
FAAP
P
F F
T
F T
F
F
D
R
120V EM CIRCUIT
R
SIAMESE WP
CONNECTION
HORN/LIGHT
EXTERIOR
TO ELEVATOR
CONTROLLER
MAIN FLOW
SWITCH
ALT. MAIN
1/2" CONDUIT WITH PULL WIRE
TO "TTB" FOR CONNECTION TO
REMOTE MONITORING STATION.
MAXIMUM OF (12)
FIRE/SMOKE DAMPERS
PER 20A1P CIRCUIT
DAMPER ON THIS CIRCUIT
TO NEXT FIRE/SMOKE
FIRE ALARM SYSTEM NOTES:
TAMPER SWITCHES IN
MAIN WATER ENTRY ROOM
TYPICAL INITIATING CIRCUIT
TO NEXT DEVICE
TYPICAL ANNUNCIATION CIRCUIT
TO MECHANICAL UNIT
BY DIVISION 23.
BUILDING FIRE
ALARM RISER
MECHANICAL UNIT
TYPICAL FOR EACH
DA
T
A
24
V
O
L
T
GRAPHIC
120V EM CIRCUIT
1. REFER TO FLOOR PLANS FOR ESTIMATED QUANTITIES AND
LOCATIONS OF DEVICES. FINAL COUNT BY FIRE ALARM VENDOR.
2. PROVIDE WIRING AS DIRECTED BY FIRE ALARM SYSTEM
MANUFACTURER.
3. CONDUIT IS NOT REQUIRED FOR WIRING LOCATED ABOVE
ACCESSIBLE CEILING AREAS. PROVIDE PLENUM RATED CABLE AS
REQUIRED BY CODES. CONDUIT IS REQUIRED FOR ALL OTHER
SPACES AND WALL CAVITIES, MINIMUM SIZE 3/4" OR AS REQUIRED
TO MEET CODES.
4. PROVIDE REMOTE LAMPS WITH TEST SWITCH FOR DUCT
DETECTORS LOCATED IN INACCESSIBLE AREAS. LABEL PER
SPECIFICATIONS.
5. PROVIDE A PHOTOELECTRIC SMOKE DETECTOR PER NFPA AT
EACH FACP AND EACH POWER SUPPLY LOCATION.
6. COORDINATE WITH FIRE SPRINKLER CONTRACTOR ON EXACT
QUANTITIES AND LOCATIONS OF FLOW AND TAMPER SWITCHES.
7. CONTROL MODULES MUST BE LOCATED WITHIN 3'-0" OF
DEVICE OR EQUIPMENT THEY ARE CONTROLLING.
8. PROVIDE (1) PHOTOELECTRIC SMOKE DETECTOR AND (1) 190°
THERMAL DETECTOR AT EACH SPRINKLER HEAD LOCATED IN
ELEVATOR SHAFT. COORDINATE QUANTITIES AND LOCATIONS
WITH SPRINKLER CONTRACTOR.
9. REFER TO "TYPICAL ELEVATOR SHUNT TRIP SCHEMATIC" ON THIS
SHEET FOR ADDITIONAL ELEVATOR RECALL AND SHUT DOWN
REQUIREMENTS.
(2)(4)
120V CIRCUIT (XXX-X)
H N
MSB-(37,39,41)
MSB-(38,40,42)
MSB-(43,45,47)
BLDG A - XXX-X VIA SWITCH IN
FACP BLDG B - XXX-X VIA SWITCH
IN FACP
ELEV,ELEV. 1
NOTES
LADDER
SEPARATE BRANCH CIRCUIT
REQUIRED FOR PIT LIGHTING AND
RECEPTACLE. DON'T CONNECT
LIGHT TO LOAD SIDE OF GFI
RECEPTACLE. NEC 620.24.
+50"
1. ONLY DETECTORS AT LANDINGS, AND HOISTWAY SHALL INITIATE
ELEVATOR RECALL. DO NOT RECALL UPON GENERAL FIRE ALARM.
2. ELEVATOR RECALL AND SHUNT-TRIP SHOULD BE INITIATED VIA
THE FACP AND CONTROL MODULES WHICH ALLOWS WIRING TO BE
SUPERVISED. BUT, SOME AUTHORITIES HAVING JURISDICTION
REQUIRE RECALL WIRING TO BE SEPARATE FROM FIRE ALARM
WIRING, IN WHICH CASE USE DETECTORS WITH AUXILLIARY
RELAYS.
3. IF MACHINE ROOM OR HOISTWAY ARE SPRINKLERED THEN MEANS
TO AUTOMATICALLY DISCONECT POWER (SHUNT TRIP) PRIOR TO
WATER FLOW IS REQUIRED ASME 17.1-102.2(C)(3).
FIRE ALARM NOTES
GFI
PROVIDE 4'-0" LED STRIP LIGHT, WET LOCATION
LISTED, VERTICALLY MOUNTED IN EACH
CORNER OF ELEVATOR SHAFT ON EACH LEVEL
THAT THE SHAFT IS INTENDED TO BE
ACCESSED. LITHONIA LIGHTING: #XWMLED.
PIT RECEPTACLES MUST BE GFI NEC 620.85
PROVIDE SWITCH FOR PIT LIGHT(S)
SWITCH FOR PIT LIGHT SHALL BE
ACCESSIBLE FROM THE PIT ACCESS
DOOR DOOR. ASME A17.1 2.2.5.3
1. SMOKE DETECTORS LOCATED IN THE ELEVATOR LANDINGS
(LOBBIES) AND TOP OF HOIST WAY SHALL RECALL THE ELEVATOR
TO THE EGRESS FLOOR.
2. DO NOT INSTALL SMOKE OR HEAT DETECTORS IN ELEVATOR PIT.
VERIFY THIS WITH SPRINKLER REQUIREMENTS AND WITH THE
LOCAL INSPECTOR.
3. THE ELEVATOR DISCONNECTING MEANS SHALL NOT DIS-
CONNECT THE CAR, PIT OR MACHINE ROOM LIGHTING
RECEPTACLES OR AIR CONDITIONING.
4. THE FRAMES OF ALL MOTORS, MACHINES, CONTROLLERS, ETC.
SHALL BE GROUNDED IN ACCORDANCE WITH NEC ART. 250. THE
METALLIC RACEWAYS SHALL BE GROUNDED.
5. NEMA 4 RATINGS FOR ALL ELECTRICAL DEVICES INSTALLED IN
ROOMS THAT ARE SPRINKLERED IS REQUIRED PER ASME 17.
6. PROVIDE 120V POWER CONNECTION ELEVATOR LIGHTING AND AC
EQUIPMENT.
NOTE: ELEVATOR #2, 012c,
REQUIRES MAINTENANCE
FROM THE TOP OF THE
ELEVATOR CAR. PROVIDE
LIGHTS AND A RECEPTACLE
AT THE FLOOR IN WHICH
MAINTENANCE WILL BE
PERFORMED (USUALLY THE
TOP OF THE SHAFT).
DUPLICATE FIXTURES IN
ELEVATOR PIT.
c.
b.
PER NFPA/ANSI REQUIREMENTS. ELEVATOR RECALL SYSTEM/SHUNT TRIP, SEQUENCE
EACH ELEVATOR SHALL BE PROVIDED WITH A COMPLETE ELEVATOR RECALL SYSTEM
OF EVENTS, SHALL BE AS FOLLOWS:
NOTES:
1.
a.
H
N
COMPLETION OF ELEVATOR RECALL.
120V NORMALLY OPEN CONTACT.
PROVIDED WITH "RECALL COMPLETE"
CONTACT SHALL CLOSE UPON
ELEVATOR CAB CONTROLLER.
LTG AND FAN
ELEV CAB
ELEVATOR
WHEN ASSOCIATED ELEVATOR LOBBY, ELEVATOR MACHINE ROOM, OR ELEVATOR SHAFT
SMOKE DETECTOR GOES INTO ALARM, AND UPON A VERIFICATION CYCLE IF USED, THE
BUILDING WILL GO INTO GENERAL ALARM AND WILL INITIATE ELEVATOR RECALL.
WHEN A THERMAL DETECTOR RATED 190 DEGREES, LOCATED IN THE ELEVATOR MACHINE
ROOM OR ELEVATOR SHAFT IS ACTIVATED, THE SHUNT TRIP ON ELEVATOR MACHINERY WILL
TRIP ONLY AFTER THE AUTOMATIC RECALL IS COMPLETE, THUS DISCONNECTING THE POWER
TO THE ELEVATOR, MACHINE ROOM LIGHT AND RECEPTACLE, AND ELEVATOR CAB LIGHT AND
FAN. THIS CIRCUIT IS INDEPENDENT OF THE FIRE ALARM SYSTEM AND SHALL BE ROUTED VIA
THE ELEVATOR CONTROLLER CONTACTS WHICH VERIFY THAT RECALL IS COMPLETE. THE
INTENT IS TO DISCONNECT POWER ONLY AFTER THE ELEVATORS HAVE RECALLED TO THEIR
ASSIGNED FLOOR, BUT BEFORE WATER FLOWS.
THE SPRINKLER HEAD FUSIBLE LINK RATED AT 286 DEGREES F. MELTS, DISPERSING WATER TO
EXTINGUISH FLAMES.
TO FACP FOR SHUNT
2.UPON LOSS OF POWER TO SHUNT TRIP AN ALARM SHALL BE INDICATED AT THE FACP AND
REMOTE MONITORING COMPANY.
TRIP MONITORING
SEPARATE CIRCUIT REQUIRED FOR
ELEVATOR CAB LIGHTS AND
VENTILATION FOR NEC 620.22.
TO ELEV. CONTROLLER FOR CAB
LIGHTS (NEC 620.22 & 620.53)
SMOKE DETECTOR LOCATED AT
ELEVATOR LOBBY OF EACH FLOOR,
NFPA 72-5.6.5. IT SHALL INITIATE
ELEVATOR RECALL.
SWITCH FOR ELEVATOR CAB
LIGHTING SHALL BE BE LOCKABLE
IN THE OPEN POSITION. (NEC
620.22, 620.53) SUGGEST HUBBLE
"CIRCUIT LOCK" FDS30 FUSED DISC.
COORDINATE REQUIREMENTS
WITH LOCAL JURISDICTION, SOME
REQUIRE SHUNT TRIP OF ELEV.
CAB LIGHTING. IF ROOM IS
SPRINKLERED MUST BE PROVIDED
WITH NEMA 4X RATING PER ASME
17.
REFER TO POWER PLAN FOR
LOCATION AND QUANTITY.
SMOKE DETECTOR LOCATED AT TOP OF
SHAFT IF REQUIRED FOR CONTROL OF
ELEVATOR SHAFT DAMPER
(COORDINATE WITH DIV. 15) OR IF
HOISTWAY IS SPRINKLED. IT SHALL
INITIATE ELEVATOR RECALL. (ASME
17.1- 211.3b REQUIRES SMOKE
DETECTORS IN SPRINKLED HOISTWAYS.)
COMBINATION 190° F RATE OF
RISE/FIXED TEMP. HEAT DETECTOR
LOCATED AT TOP OF SHAFT (ONLY IF
SHAFT IS SPRINKLED) SHALL INITIATE
ELEVATOR SHUT DOWN ASME A17.1
102.2(c)(3). NFPA 72-3-8.14.3 PROHIBITS
PUTTING DETECTORS IN THE HOISTWAY
(SHAFT OR PIT) UNLESS IT IS SPRINKLED.
ELEVATOR RECALL. TYPICAL
FOR EACH ELEVATOR.
HEAVY DUTY AUXILIARY RELAY
20A, 120V. LOCATE NEXT TO
CONTROL MODULE
LOCATED IN
ACCESSIBLE LOCATION
NOTES:
DENOTE BRANCH CIRCUITS BACK TO PANEL ON
THIS DIAGRAM OR ON THE DRAWING.
INDICATE TO WHAT (I.E. APC, PATCH PANEL,
SPARE, ETC.
EMERGENCY POWER OFF WIRING DIAGRAM
NO SCALE
4 POLE CONTACTOR WITH 120V COIL,
MECHANICALLY HELD, IN LOCKABLE NEMA 1
ENCLOSURE
RED "MUSHROOM" HEAD EPO
SWITCH WITH MAINTAINED
CONTACTS
ACCESSORY CONTROL
MODULE
1
2
TYPICAL ELECTRIC DOOR
LOCK CIRCUIT
HEAVY DUTY AUXILIARY
RELAY 20A, 120V. LOCATE
NEXT TO CONTROL
MODULE.
TELEPHONE ENTRY PANEL
TO NEXT DEVICE
ELECTRIC DOOR
LOCK
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
4
A
M
E5.0
2016.01.0223
ELECTRICAL
DETAILS
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019
KEY DESCRIPTION
LOAD
(kVA)VOLTAGE PHASE FEEDER
O.C. PROTECTION
REMARKS
C.B. FUSE
AHU-1 AIR HANDLER UNIT 174.240 208 3 2[(3-250KCMIL+#2G)2-1/2"C] 500A3P 500A [3]
AHU-1 AIR HANDLER UNIT - 120V, LIGHTS, RECEP 1.600 120 1 (2#12+#12G)1/2"C 20A1P
GWP-1 & 2 GROUND WATER PUMP, 15HP 16.730 208 3 (3#4+#6G)1-1/4"C 110A3P
80A [3],[5]
CWP -1 & 2 CONDENSER WATER PUMP, 10HP 11.150 208 3 (3#6+#8G)1"C 80A3P
50A [3],[5]
HWP-1 & 2 HEATING WATER PUMP, 7-1/2HP 8.760 208 3 (3#8+#10G)3/4"C 60A3P
40A [3],[5]
HWP-3 & 4 HEATING WATER PUMP, 5HP 6.060 208 3 (3#10+#10G)3/4"C 40A3P
30A [3],[5]
BP-1,2, & 3 BOILER PRIMARY, 2HP 2.700 208 3 (3#12+#12G)1/2"C 15A3P
12A [3]
CP-1 COIL PUMP, 5HP 6.060 208 3 (3#10+#10G)3/4"C 40A3P
30A [3]
WWHP-1 & 2 WATER TO WATER HEAT PUMP 89.640 208 3 (3-300KCMIL+#4G)2-1/2"C 400A3P 400A
[3]
WWHP-3 WATER TO WATER HEAT PUMP 89.640 208 3 (3-300KCMIL+#4G)2-1/2"C 400A3P 400A
[3]
B-1 ELECTRIC BOILER 224.820 208 3 3[3-300KCMIL+#1/0G)2-1/2"C] 800A3P
[4],[6],[7]
B-2 ELECTRIC BOILER 224.820 208 3 3[3-300KCMIL+#1/0G)2-1/2"C] 800A3P
[4],[6],[7]
B-3 ELECTRIC BOILER 224.820 208 3 3[3-300KCMIL+#1/0G)2-1/2"C] 800A3P
[4],[6],[7]
DC-1 DATA COOLING 4.160 208 1 (2#10+#10G)1/2"C 40A1P 30A
[8]
DC-2 DATA COOLING 4.160 208 1 (2#10+#10G)1/2"C 40A1P 30A
[8]
DC-3 DATA COOLING 4.160 208 1 (2#10+#10G)1/2"C 40A1P 30A
[8]
DC-4 DATA COOLING 4.160 208 1 (2#10+#10G)1/2"C 40A1P 30A
[8]
DC-5 DATA COOLING 4.160 208 1 (2#10+#10G)1/2"C 40A1P 30A
[8]
DC-6 DATA COOLING 4.160 208 1 (2#10+#10G)1/2"C 40A1P 30A
[8]
DC-7 DATA COOLING 4.160 208 1 (2#10+#10G)1/2"C 40A1P 30A
[8]
AC/CU-1 AIR CONDITIONING AND CONDENSING UNIT 3.850 208 1 (2#12+#12G)1/2"C 30A2P
[2]
FC-1 FAN COIL, (2)1/2HP 2.240 208 1 (2#12+#12G)1/2"C 15A2P
GF-1 & 2 GLYCOL FEEDER 0.480 120 1 (2#12+#12G)1/2"C 20A1P
CUH-1 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-2 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-3 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-4 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-5 CABINET UNIT HEATER, 1/15HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-6 CABINET UNIT HEATER, 1/15HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-7 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-8 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-9 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-10 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-11 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
CUH-12 CABINET UNIT HEATER, 1/10HP 0.300 120 1 (2#12+#12G)1/2"C 20A1P
UH-1 UNIT HEATER, 1/20HP 0.200 120 1 (2#12+#12G)1/2"C 20A1P
UH-2 UNIT HEATER, 1/20HP 0.200 120 1 (2#12+#12G)1/2"C 20A1P
UH-3 UNIT HEATER, 1/20HP 0.200 120 1 (2#12+#12G)1/2"C 20A1P
EF-1 EXHAUST FAN, 1/2HP 1.130 120 1 (2#12+#12G)1/2"C 20A1P
15A
EF-2 EXHAUST FAN, 1/6HP 0.510 120 1 (2#12+#12G)1/2"C 20A1P
9A
EF-3 EXHAUST FAN, 1/2HP 1.130 120 1 (2#12+#12G)1/2"C 20A1P 15A
EF-4 EXHAUST FAN, 1/6HP 0.510 120 1 (2#12+#12G)1/2"C 20A1P 9A
RP-1 RE-CIRCULATION PUMP, 1/25HP 0.200 120 1 (2#12+#12G)1/2"C 20A1P 2.5A
WH-1 WATER HEATER 24.000 208 3 (3#1+#8G)1-1/2"C 100A3P -
SP-1 SUMP PUMP, 1/2HP 1.130 120 1 (2#12+#12G)1/2"C 20A1P 15A
SP-2 SUMP PUMP, 1/2HP 1.130 120 1 (2#12+#12G)1/2"C 20A1P 15A
SP-3 SUMP PUMP, 1/2HP 1.130 120 1 (2#12+#12G)1/2"C 20A1P 15A
FPVAV-1 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
FPVAV-2 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
FPVAV-3 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
FPVAV-4 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
FPVAV-5 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
FPVAV-6 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
FPVAV-7 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
FPVAV-8 FAN POWERED VAV BOX, 1HP 1.840 120 1 (2#12+#12G)1/2"C 40A1P 25A
NOTES: 1. AIR CONDITIONING UNIT POWERED BY CONDENSING UNIT. PROVIDE (2#12+#12G)1/2"C FROM AIR CONDITIONING UNIT TO CONDENSING UNIT ON ROOF.
2. UNIT PROVIDED WITH FUSE DISCONNECT SWITCH.
3. PROVIDE FUSING AS REQUIRED PER ACTUAL EQUIPMENT BEING INSTALLED NAMEPLATE DATA.
4. BOILERS REQUIRE A SEPARATE 120V-1PH, 600VA CONNECTION FOR CONTROLS. PROVIDE DISCONNECT SWITCH WITH LOCK-OFF CAPABILITY.
5. BOTH PUMPS WILL NOT RUN SIMULTANEOUSLY. TO BE INTERLOCKED BY THE BAS SYSTEM.
6. ALL THREE BOILERS WILL NOT RUN SIMULTANEOUSLY. TO BE INTERLOCKED BY THE BAS SYSTEM.
7. PROVIDE SHUNT TRIP BREAKERS CONNECTED TO EPO SWITCH IN MECHANICAL ROOM.
8. IN-ROW COOLERS ARE TO BE LOCATED IN DATA CENTER. LAYOUT TO BE FINALIZED IN TI SCOPE.
MECHANICAL EQUIPMENT SCHEDULE
RESTROOMS LV OCCUPANCY 20 MIN - -
RESTROOM LIGHTING TO BE ON DURING BUSINESS HOURS. OUTSIDE
OF BUSINESS HOURS TO BE ON OCCUPANCY SENSOR.
CONTROLS TO BE MODIFIED IN TI DESIGN.
3
TENANT SPACES 0-10V LV VACANCY 60 MIN - -
STUMBLE LIGHTING TO BE CONTROLLED FROM ELECTRICAL ROOM.
OUTSIDE OF BUSINESS HOURS TO BE ON OCCUPANCY SENSOR.
CONTROLS TO BE MODIFIED IN TI DESIGN.
PROVIDE UL294 RELAY FOR EM EGRESS LIGHTING.
3
MECHANICAL,
ELECTRICAL, DATA
CENTER
120V - -- -
PROVIDE MANUAL ON/OFF FOR SAFETY.
3
ELEVATOR LOBBIES LV - -
ELEVATOR LOBBY LIGHTING TO BE ON DURING BUSINESS HOURS.
OUTSIDE OF BUSINESS HOURS TO BE ON OCCUPANCY SENSOR.
CONTROLS TO BE MODIFIED IN TI DESIGN.
3
VESTIBULES LV OCCUPANCY 20 MIN 15, +30" 30 MIN
VESTIBULE LIGHTING TO BE ON DURING BUSINESS HOURS. OUTSIDE
OF BUSINESS HOURS TO BE ON OCCUPANCY SENSOR.
CONTROLS TO BE MODIFIED IN TI DESIGN.
3
STORAGE ROOMS LV VACANCY 20 MIN - -
MANUAL ON, AUTOMATIC OFF.3
TRASH LV VACANCY 20 MIN MANUAL ON, AUTOMATIC OFF.3
GRAND STAIR --- -
GRAND STAIR LIGHTING TO BE ON DURING BUSINESS HOURS.
OUTSIDE OF BUSINESS HOURS TO BE ON OCCUPANCY SENSOR OR
MANUAL CONTROL.
CONTROLS TO BE MODIFIED IN TI DESIGN.
3
EGRESS STAIRS LV OCCUPANCY 20 MIN - -
EGRESS STAIR ON VIA FIXTURE MOUNTED OCCUPANCY SENSOR.3
EXTERIOR LIGHTING ASTRONOMICAL TIME CLOCK AND PHOTOCELL ON/OFF.3
SD FIXTURES 0-10V LV - -- -
ASTRONOMICAL TIME CLOCK AND PHOTOCELL ON/OFF. PROVIDE
ABILITY TO DIM SD FIXTURES TO MEET LEED LIGHT TRESPASS
REQUIREMENTS.
3
KEY NOTES:
1. REFER TO PLANS FOR CONTROL ZONES.
2. MANUAL ON TO TURN LIGHT ON TO LAST DIMMED LEVEL.
3. PROVIDE UL924 SWITCHING DEVICE AS REQUIRED FOR EM CIRCUITS.
LIGHTING CONTROL MATRIX
AREA - SWITCH LEGS
LED
DIMMING
TYPE
SWITCH
TYPE
OCCUPANCY
SENSOR TYPE
OCCUPANCY
SENSOR TIME
OUT
OCCUPANCY
SENSOR
SETTING
PHOTOSENSOR FC
TARGET AND TARGET
HEIGHT
PHOTOSENSOR
TIME DELAY CONTROL SEQUENCE KEY NOTES
GENERAL NOTES:
1. ON/OFF DIMMER CAPABILITY CAN BE SUBSTITUTED FOR ON/DIM-TO-OFF (WITH A JUMP FROM
LOWEST DIMMING POINT TO OFF) BASED ON PRICING.
2. LV, REMOTE WITH INDICATOR LED.
3. LV, AS SHOWN ON PLANS.
CHARLES
CUNNIFFE
ARCHITECTS
COPYRIGHT CHARLES CUNNIFFE ARCHITECTSC
SHEET NO.
JOB NO.
2/
7
/
2
0
1
8
7
:
2
4
:
0
8
A
M
E6.0
2016.01.0223
ELECTRICAL
SCHEDULES
AS
P
E
N
C
I
T
Y
O
F
F
I
C
E
S
42
5
R
I
O
G
R
A
N
D
E
P
L
A
C
E
AS
P
E
N
,
C
O
LUMINAIRE SCHEDULE
TYPE LOCATION
SOURCE
DESCRIPTION
INPUT
LOAD (VA)
INPUT
VOLTAGE (V)
DIM
TYPE MOUNTING MANUFACTURER AND CATALOG NUMBER
KEY
NOTESTYPE LUMENS CCT CRI
3000 K EXIT 5 277 V
A RR'S, UPPER
VESTIBULE
LED LED - 1500
LUMENS
4000 K 80+ 6" DIAMETER LED DOWNLIGHT. 19 120 V 0-10V RECESSED LITHONIA LDN6
#LDN6 40/15 LO6AR MVOLT EZ1
B6 RESTROOMS LED LED - 470 LM/FT 4000 K 80+ 6' OVERALL LENGTH LED PERIMETER
FIXTURE.
24 120 V 0-10V PENDANT ECOSENSE SLIM COVE DIM
#SCD M 40K MULT
B11 RESTROOMS, ELEV
LOBBY
LED LED - 470 LM/FT 4000 K 80+ 11' OVERALL LENGTH LED PERIMETER
FIXTURE.
44 120 V 0-10V PENDANT ECOSENSE SLIM COVE DIM
#SCD M 40K MULT
B23 RESTROOMS, ELEV
LOBBY
LED LED - 470 LM/FT 4000 K 80+ 23' OVERALL LENGTH LED PERIMETER
FIXTURE.
92 120 V 0-10V PENDANT ECOSENSE SLIM COVE DIM
#SCD M 40K MULT
C BACK OF HOUSE LED LED - 5000
LUMENS
4000 K 80+ 4' LENGTH LED STRIP FIXTURE. 32 120 V 0-10V PENDANT OR
WALL
LITHONIA LIGHTING CLX
#CLX L48 5000LM HEF FDL MVOLT GZ10 40K 80CRI
#ZL1D-L48-5000LM-FST-MVOLT-40K-80CRI-PLR-WH
D ENCLOSED STAIR LED LED - 4200
LUMENS
4000 K 80+ 4' LENGTH LED STAIRWELL FIXTURE. 40 120 V 0-10V WALL PRUDENTIAL WAL14 SERIES
#WAL14 LED4 HO 4' WFA TMW SC UNV WM DM10 OCO
F VESTIBULE LED LED - 1010
LUMENS
4000 K 80+ NARROW DEPTH RECESSED CEILING
DOWNLIGHT WITH SYMMETRICAL LIGHT
DISTRIBUTION. WIDE BEAM
15 120 V 0-10V RECESSED BEGA
#55 924
J STEPS LED LED - 147 LM/FT 4000 K 80+ EACH STAIR STEP TO HAVE ONE
FULL-LENGTH LED ROPE LIGHT. REMOTE
DRIVERS TO BE LOCATED IN ACCESSIBLE
LOCATION TBD
8 120 V 0-10V RECESSED
WALL
VOLT SIDE EMITTING
# SE41K-24V - PROVIDE REMOTE DRIVER AND ALL PARTS
REQUIRED FOR A COMPLETE SYSTEM
Q PENDANT IN CENTER
STAIR
LED LED 4000 K 80+ DECORATIVE CENTERPIECE PENDANT,
ALLOW $10,000
116 120 V 0-10V PENDANT SPI
#SIP11879-L19-120-277V-4000K-CAA-OAH-AC2
SA EXTERIOR WALL LED LED - 4215
LUMENS
4000 K 80+ LED WALL SCONCE WITH TYPE IV MEDIUM
DISTRIBUTION.
27 120 V 0-10V WALL +11' WE-EF OLV344 LED SERIES
#622-7723
SB EXTERIOR BOLLARD LED LED - 800
LUMENS
4000 K 80+ LED BOLLARD.11 120 V 0-10V BOLLARD SLV LIGHTING
RUSTY 70 ROUND
SC EXTERIOR STEPS LED LED 4000 K 80+ LED STEP LIGHT.8 120 V 0-10V RECESSED
WALL +18"
MP LIGHTING L49
#L49 6 D W41S W 0 A
SD EXTERIOR LED LED - 375 LM/FT 4000 K 80+ 4" LINEAR WET LOCATION LISTED 15 120 V 0-10V RECESSED FOCAL POINT SEEM 4
#FSM4LWL FL 375LF 30K 1C UNV L11
X EXIT SIGN LED LED 5 120 V SURFACE LITHONIA LIGHTING EDG SERIES
OWNER EQUIPMENT SCHEDULE
KEY DESCRIPTION LOAD (VA) VOLT
Number of
Poles FEEDER
O.C. PROTECTION
REMARKSC.B. FUSE
E-1 ELEVATOR 41570 208 V 3 REFER TO ELEVATOR DETAILS FOR ADDITIONAL INFORMATION.
E-2 ELEVATOR CAB LIGHTS 500 120 V 1 REFER TO ELEVATOR DETAILS FOR ADDITIONAL INFORMATION.
E-3 DOOR HARDWARE POWER 500 120 V 1 POWER FOR DOOR HARDWARE. REFER TO ARCHITECTURAL DOOR SCHEDULE FOR TYPE
OF DEVICE. COORDINATE WITH DOOR HARDWARE PROVIDER.
GENERAL NOTES
1. LOWER CASE "x" IN PRODUCT NUMBER INDICATES EITHER: A. COLOR OR FINISH TO BE SPECIFIED BY ARCHITECT, B.
FIXTURE LENGTH TO BE AS INDICATED ON DRAWINGS, OR C. TO BE SPECIFIED BY OTHERS OR TO BE DETERMINED.
2. CATALOG NUMBERS MAY BE INCOMPLETE. CONTRACTOR TO PROVIDE ALL ACCESSORIES, ETC. FOR A FULLY FUNCTIONAL
LUMINAIRE AND CONTROLS SYSTEM THAT MEETS THE INTENT OF THE DRAWINGS.
ISSUE: DATE:
50% DD 10/30/17
100% DD 12/12/17
PERMIT 02/07/18
03/16/2019