HomeMy WebLinkAboutFile Documents.230 E Hopkins Ave.0089.2018 (75).ACBKZoning Comments 2 - 230 E Hopkins - 0089.2018.ACBK Page Label: M-113 ROOF HVAC PLAN Page Index: 5 Author: sophiev Date: 9/5/2019 8:14:26 AM Unit: Count File Name: 230 E. Hopkins_Drawings_Mechanical_2019-07-26.pdf We had an internal discussion regarding Section 26.575.020.F.4.a – Allowed Exceptions to Height Limitations – Chimneys, flues, and similar venting apparatus. This section applies regardless of if the apparatus is under the height limit. There are three items that need to be adjusted, bubbled in red. The blue line and purple lines are the approximate locations of the 20’ setback from the street facing facades. Chimneys, flues, vents, and similar venting apparatus must be within the envelope created by those setback lines. 230 E. Hopkins_Drawings_Mechanical_2019-07-26.pdf (1) Page Label: A0.4z SURFACE AREA CALCULATIONS / DEMOLITION Page Index: 4 Author: sophiev Date: 9/5/2019 8:11:23 AM Unit: Count File Name: 230 E. Hopkins_Drawings_Zoning_2019-08-07.pdf Please remove this area on all places where it appears on the demolition elevations; it should not be counted. 230 E. Hopkins_Drawings_Zoning_2019-08-07.pdf (1) 4 1 A E E 4 C C D D F F G G 2 2 66 5 B B 3 3 5 PROPERTY LINE PROP E R T Y L I N E PROPERTY LINE PRO P E R T Y L I N E PROPERTY LINE SETBACK LINE SETB A C K L I N E SETBACK LINE SETB A C K L I N E MONARCH STREET HO P K I N S A V E N U E ALL E Y 77 EXISTING ADDITION EXISTING ADDITION A EXI S T I N G ADD I T I O N EXI S T I N G ADD I T I O N 1 DNWHy WHy UP UP UP GENERAL NOTES: 1.ALL DUCTWORK DIMENSIONS ARE SHOWN INSIDE TO INSIDE. 2.ALL INTERIOR SUPPLY AND RETURN DUCTWORK SHALL INCLUDE 1" LINERUNLESS OTHERWISE NOTED. ALL OUTSIDE AIR INTAKE AND ROUNDDUCTWORK SHALL BE WRAPPED WITH 1.5" THICK INSULATION UNLESSOTHERWISE NOTED. EXTERIOR DUCTWORK SHALL BE WRAPPED WITH 2"OF INSULATION (QDUCT OR EQUIV.) 3.ALL SQUARE 90 DEGREE ELBOWS SHALL HAVE TURNING VANES. 4.ALL DUCTWORK PASSING THROUGH FIRE-RATED ASSEMBLIES SHALLINCLUDE FIRE DAMPERS RATED TO MATCH THAT OF THE ASSEMBLY. SHEET DETAIL NOTES: ROUTE OUTSIDE AIR DUCT TO MAINTAIN 10' CLEARANCE FROMEXHAUST DUCT TERMINATION & PLUMBING VENTS.TERMINATE FURNACE AND BOILER FLUES AND COMBUSTION AIR PERMANUFACTURER INSTRUCTIONS. MAINTAIN AT LEAST 12" CLEARANCEBETWEEN THE FLUE TERMINATION OF ONE APPLIANCE TO THECOMBUSTION AIR TERMINATION OF ANY OTHER APPLIANCE. TERMINATE 16x16 (19x19) OUTSIDE AIR DUCT AT LEAST 3' ABOVE ROOFDECK. PROVIDE RAIN CAP OR GOOSENECK. FACE AWAY FROM AC-1DISTANCE TO AVOID PULLING IN HOT DISCHARGE AIR. MOUNT CONDENSING UNIT ON VIBRATION ISOLATION. ROUTEREFRIGERATION PIPING FROM CONDENSING UNIT TO ASSOCIATEDCOOLING COIL, FAN COIL, OR AC UNIT (SEE SCHEDULE ON SHEETM-601). SIZE REFRIGERANT PIPING ACCORDING TO MANUFACTURERGUIDELINES. WHERE EQUIPMENT IS LOCATED WITHIN 10' OF THE ROOFEDGE, ENSURE A MINIMUM 42" TALL GUARD IS PROVIDED PER 2015 IBC1015.6. TERMINATE 14x12 (18x16) OUTSIDE AIR DUCT AT LEAST 3' ABOVE ROOFDECK. PROVIDE RAIN CAP OR GOOSENECK. INSTALL SMOKE RELIEF UP HIGH, INTERLOCK MOTORIZED DAMPERWITH FIRE ALARM SYSTEM. DAMPER SHALL HAVE ACTUATOR WITHSPRING OPERATED RETURN, NORMALLY OPEN. THE DAMPER SHALL BECLOSED AND UPON A LOSS OF POWER THE ACTUATOR SPRING SHALLOPEN THE DAMPER.AEC IS NOT ABLE TO PROVIDE ACOUSTICAL MODELING OF EXTERIOREQUIPMENT, NOR PROVIDE DOCUMENTATION SUPPORTINGCOMPLIANCE WITH THE CITY OF ASPEN NOISE ORDINANCE. ANACOUSTICAL CONSULTANT IS RECOMMENDED TO VERIFYCOMPLIANCE. NOISE MITIGATION MEASURES (BY OTHERS) MAY BEREQUIRED. 1 2 EH6 CU10 CU9 CU4(F-4) (FC-1) (FC-2) CU5 (F-5) CU7(F-7) CU8(F-8) CU6(F-6) CU2 (F-2) CU1(F-1) CU3(F-3)2" FLUE & 2" COMBUSTIONAIR TERMINATION PERMANUFACTURER (6) 2" FURNACE FLUE(1) 212" FURNACE FLUE(3) 4" BOILER FLUE AC1 1 14/12 ( 1 8 / 1 6 ) 14/12 (17/15) DN LV1HOISTWAY VENTING30x30 M 6 MD3 2 3 3 4 4 4 4 4 4 4 4 4 4 4 5 5 6 5 (6) 2" FURNACE COMBUSTION AIR(1) 212" FURNACE COMBUSTION AIR(3) 4" BOILER COMBUSTION AIR T 7 EH-6 7 7 7 7 7 7 FIREPLACE FLUE UP THROUGH ROOF(COORDINATE SIZE & TERMINATIONWITH MANUFACTURER, SHOWN HEREFOR REFERENCE) FIREPLACE FLUE UP THROUGH ROOF(COORDINATE SIZE & TERMINATIONWITH MANUFACTURER, SHOWNHERE FOR REFERENCE) a ce Drawn By: DATE: AEC PRO MO U N T A I N F O R G E 07-30-18P 01-23-19C 01-30-19C 03-08-19A 04-18-19C 05-31-19A DGD SCA M 5 NORTH ROOF HVAC PLAN SCALE: 1/4" = 1'0" We had an internal discussion regarding Section26.575.020.F.4.a – Allowed Exceptions to HeightLimitations – Chimneys, flues, and similar ventingapparatus. This section applies regardless of if the apparatus is underthe height limit. There are three items that need to beadjusted, bubbled in red. The blue line and purple lines arethe approximate locations of the 20’ setback from the streetfacing facades. Chimneys, flues, vents, and similar ventingapparatus must be within the envelope created by thosesetback lines. F E D MO AREA 164 SF DEMO AREA 34 SF 28 SF 28 SF 58 SF DEMO 240 SF W.S.A. 07 01 TOTAL WALL AREA = 240 SF FENESTRATION AREA = 56 SF NET WALL AREA = 184 SF DEMO AREA = 58 SF 01 02 02 11 SF 6 SF 11 SF 11 SF 6 SF 18 SF 23 SF 6 SF 17 SF 6 SF 17 11 SF 4 SF 4 SF 4 SF 2 S 20 SF 20 SF 20 SF 10 SF 4 SF 4 SF 4 SF 2 SF 19 SF 19 SF 19 SF 9 SF 38 SF 22 SF 979 W.S 111 SF 05 B B Please remove this area on all places where it appears on the demolition elevations; it should not be counted. All flues have been relocated within the required setbacks. Roof chimney deleted See updated A2.3 roof plan and flue location dimensioning See A6.11 / A6.13 / A6.14 See mechanical drawings. See updated demolition elevations on sheet A0.4z. 09/06/2019