File Documents.725 Cemetery Ln.0045-2019-BRES (4)
JEC0I Balancing . J JEDI Balancing, Inc. 568 Briggs Street(physical) P.O. Box 525 (mail) Erie, CO. 80516 Phone (720) 839-5333 www.jedibalancing.com Certified Test, Adjust & Balance Report Project 725 & 727 Cemetery Lane Address 725 & 727 Cemetery Lane Aspen, CO 81611 Architect Unavailable Mechanical Engineer Rader Inc Contractor Koru, LTD Date 6/7/2022 Job Number 2022-9703 Donald W. Pittser TABB Certified Supervisor TABB Firm Certification#BB009003C Stamp Expires 9/30/2022 Warranty Information: The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB International Standards for Environmental Systems Balance. The measurements shown, and the information given, in this report are certified to be accurate and complete, at the time and date information was gathered. Any variances from design quantities, which exceed TABB tolerances, are noted in the TAB report project summary. This project has a one-year guarantee on all Testing,Adjusting &Balancing from the date listed on this cover page. Instrumentation: Instrument I Manufacturer Model _ Serial Number Calibration Due Tachometer _ Shimpo MT-200 B199B5005P 12-07-2022 Air Temperature Probe Evergreen Telemetry PR-T-1 1700353 07-28-2022 Immersion Temperature Probe Evergreen Telemetry PR-T-4-6 _ 1700204 07-28-2022 Humidity _ Evergreen Telemetry S-H-3-5 2100306B 08-04-2022 Volt-Amp Meter Fluke 378 FC 54710023 07-16-2022 Air Pressure 1 Evergreen Telemetry S-PVF-1 8601242 07-19-2022 Air Velocity/Airfoil Evergreen Telemetry S-PVF-1 8601242 07-19-2022 Flowhood Evergreen Telemetry 3 Pound _ 8601242 07-19-2022 Hydronic Pressure TSI HM-675 71646134 07-16-2022 Hydronic Differential Pressure TSI HM-675 71646134 07-16-2022 Abbreviation Index TAB: Testing,Adjusting&Balancing Cx: Commissioning OD: Outside Diameter AHU:Air Handling Unit Motor FLA:Full Load Amperage Tl: Terminal 1 RTU: Roof Top Unit S.F.: Service Factor T2: Terminal 2 PACU: Packaged Air Conditioning Unit RPM: Revolutions per Minute T3: Terminal 3 MAU:Make Up Air Unit P.F.:Power Factor CS: Circuit Setter FCU: Fan Coil Unit Nom.Elf.:Nominal Efficiency BV: Balance Valve VAV:Variable Air Volume TDH: Total Dynamic Head K Factor: Correction Factor FPB: Fan Powered Box AK: Area Correction PSI: Pounds per Square Inch CUH: Cabinet Unit Heater Valve D.P.:Discharge Pressure UH:Unit Heater Valve S.P.: Suction Pressure ERV: Energy Recovery Ventilator ERU: Energy Recovery Unit EF:Exhaust Fan PEF: Power Exhaust Fan KEF: Kitchen Exhaust Fan SF: Supply Fan RF: Return Fan TF: Transfer Fan Diff.: Differential SEF: Smoke Exhaust Fan DX: Direct Expansion SACU: Spilt Air Conditioner Unit SP: Static Pressure TSP: Total Static Pressure in.wc:Inches Water Column ESP:External Static Pressure HW:Heating Water VP:Velocity Pressure CHW: Cooling Water SA: Supply Air CW: Condenser Water RA:Return Air HX: Heat Exchanger OSA: Outside Air SWD: Sidewall Diffuser MA:Mixed Air EAT:Entering Air Temperature OA: Outside Air CD: Ceiling Diffuser EWT:Entering Water Temperature SD: Supply Diffuser ER: Exhaust Register LAT:Leaving Air Temperature MVD:Manual Volume Damper RG: Return Grille LWT:Leaving Water Temperature OBD: Opposed Blade Damper NAC:No Access CFM: Cubic Feet Per Minute CMH: Cubic Meters per Hour NG:Not Given FPM:Feet Per Minute SSD: Square Supply Diffuser NIC:Not in Contract SRD: Square Return Diffuser E: Existing M:Meter TG: Transfer Grille cm: Centimeter Pa: Pascal 1/s:Liters per Second mm:Millimeter kPa:Kilopascal ADM:Air Data Meter(manometer) SPF: Stairwell Pressurization Fan Design D.P.: Design Differential Pressure Actual D.P.: Recorded Differential Pressure Ind.Imp.Dia.Indicated Impeller Diameter CRAC: Computer Room Air Conditioning Unit ., ,,, JEDI Balancing Table Of Contents PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser Table Of Contents 1 2022 9703 725 and 727 Cemetery Lane Report Summary.pdf 1 2 Field Note Report Summary 2 3 Air Handling Unit 3 3.1 725 ERV-A-01 3 3.2 725 ERV-A-01 /Exhaust 4 3.3 725 ERV-A-01 /Supply 4 3.4 725 F-Al 6 3.5 725 F-Al/SPP-01 7 3.6 725 F-Al/OSA 8 3.7 725 F-Al/F-A-01 A 9 3.8 725 F-Al/F-A-01 B 9 3.9 725 F-A1/F-A-01 C 10 3.10 727 ERV-B-01 11 3.11 727 ERV-B-01/Exhaust 12 3.12 727 ERV-B-01/Supply 12 3.13 727 F-B1 14 3.14 727 F-B1/SPP-01 15 3.15 727 F-B1/OSA 16 3.16 727 F-B1/F-B-01A 17 3.17 727 F-B1/F-B-01 B 17 3.18 727 F-B1/F-B-01 C 18 4 Fan Unit 19 4.1 725 EF-01-01 19 4.2 725 EF-01-02 20 4.3 725 EF-01-03 21 4.4 725 EF-01-04 22 4.5 725 EF-02 23 4.6 727 EF-01-01 24 4.7 727 EF-01-02 25 4.8 727 EF-01-03 26 4.9 727 EF-01-04 27 4.10 727 EF-02 28 5 Hydronic Pump 29 5.1 725 P-01 BOILER 29 5.2 725 P-02 WH 30 5.3 725 P-03 RADIANT 31 5.4 725 P-04 SNOWMELT 32 5.5 725 RP-01 DOM HW 33 5.6 727 P-01 BOILER 34 5.7 727 P-02 WH 35 5.8 727 P-03 RADIANT 36 JEDI Balancing, Inc. JEDI Balancing Table Of Contents PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser 5.9 727 P-04 SNOWMELT 37 5.10 727 RP-01 DOM HW 38 6 725 727 CEMETERY LANE TAB DRAWINGS.pdf 39 6.1 M0.0-MECHANICAL-COVER-SHEET-Rev.0 39 6.2 M0.1-MECHANICAL-ZONING-FLAN-Rev.0 39 6.3 M1.0-MECHANICAL-SCHEDULES-Rev.0 39 6.4 M1.1-MECHANICAL-SCHEDULES-Rev.0 39 6.5 M2.0-LOUEF-LEVEL-MECHANICAL-FLAN-Rev.0 39 6.6 M2.1-MAIN-LEVEL-MECHANICAL-PLAN-Rev.0 39 6.7 M2.2-UPPER-LEVEL-MECHANICAL-PLAN-Rev.0 39 6.8 M3.0-MECHANICAL-SCHEMATICS-Rev.0 39 6.9 M4.0-MECHANICAL-SPECIFICATIONS-Rev.0 39 6.10 M4.1-SEQUENCE-OF-OPERATION-Rev.0 39 JEDI Balancing, Inc. JEDI Balancing, Inc. 568 Briggs Street(physical) P.O.Box 525(mail) JEOI Erie,CO. 80516 Balancing Phone(720)839-5333 www.jedibalancing.com Report Summary and Remarks Project: 725&727 Cemetery Lane Project: 2022 9703 Scope:The Test and Balance(TAB)scope of work consisted of Air Handling Unit(ERV)-2,(F)-2,(VVT)-6,Exhaust Fan (EF)-10,Pump-10,Balance Valves-9 Procedures: ERV-Constant Volume Each unit has constant volume fans that were set for design airflow and the associated exhaust inlets were set for total air volume.The Outside Air CFM was measured as individually listed under each unit.The Exhaust Air CFM was measured as individually listed under each unit.All final TAB settings and performance measurements were completed,and data was recorded on to the appropriate test report forms. F—Constant Volume with Zone Dampers Each unit has a constant volume fan that was set for design airflow and the associated supply outlets were balanced in full cooling demand.The total Supply Air CFM was measured as individually listed under each unit.The Outside Air CFM was measured as individually listed under each unit.The Return Air CFM was measured as individually listed under each unit.All final TAB settings and performance measurements were completed,and data was recorded on to the appropriate test report forms.The associated VAV's Zone Dampers were indexed to full cooling and outlets proportioned for design airflow. Exhaust Fans with Grilles and Hoods The fans were energized,measured and set for total airflow.The associated inlets were balanced as noted in this report. The Exhaust Air CFM was measured as individually listed under each unit. Final settings and performance measurements were completed,and data recorded on to the appropriate test report forms. Hydronic Systems The Circulation Pumps were indexed to full flow conditions.Initial pump performance and final pump performance was set and noted in this report.The final system settings were completed,and final performance data was recorded.The water coils were index to full flow conditions. Each coil was then balanced using the circuit setters for the most accurate measurement;in lieu of coil pressure drops.The test results and issues are reported on the individual test pages. Motor Tag Data Not Accessible(Embedded) Embedded Motor—Limited motor nameplate information provided.Motor nameplate information is obscured by the motor mounting bracket and not visible without disassembly of the motor from the unit.The motor is accessible for service and maintenance. No Access Between Coils Some unit arrangement prevents access to obtain a complete static pressure profile for all the components. Static pressure test ports could not be safely drilled between the heating and cooling coils without risking damage to the coils and are recorded as"Not Accessible"in the Report. Schematic Line Diagrams Report includes reduced mechanical drawings used for the test and balance work.These"Keyed Drawing"were used in place of single line schematic diagrams and include the unique designations for the tested items in the final TAB report. Submittals: Submittals were not provided for the project. to+/-10%of design flow rates Any values outside the specified tolerances are noted on the Equipment Comment Log and the individual test report pages. Previously Forwarded/Accepted As-Is Equipment Comment Log Project Summary The following page(s)lists all project comments and issues.All items described and listed on the following Equipment Comment Log have been previously forwarded for resolution and have been accepted as reported. Page 1 of 48 JEDI Balancing Field Note Report Summary PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser Test System/ Unit Name Date Contact Notes/ Logs Hydronic Pump 725 P-01 BOILER 6-Jun-22 Bryan Hund No ports or circuit setter. Operational check on med speed. Hydronic Pump 725 P-02 WH 6-Jun-22 Bryan Hund No ports or circuit setter. Operational check only on max. Pump placed into auto adapt control after testing. Hydronic Pump 725 P-03 RADIANT 6-Jun-22 Bryan Hund Pump was tested on med speed. Hydronic Pump 725 P-04 SNOWMELT 6-Jun-22 Bryan Hund Pump was tested on high speed. Hydronic Pump 725 RP-01 DOM HW 6-Jun-22 Bryan Hund No ports or circuit setter. Operational check on med speed. `Hydronic Pump 727 P-01 BOILER 6-Jun-22 Bryan Hund No ports or circuit setter. Operational check on med speed. Hydronic Pump 727 P-02 WH 6-Jun-22 Bryan Hund No ports or circuit setter. Operational check only on max. Pump placed into auto adapt control after testing. Hydronic Pump 727 P-03 RADIANT 6-Jun-22 Bryan Hund Pump was tested on med speed. Hydronic Pump 727 P-04 SNOWMELT 6-Jun-22 Bryan Hund Pump was tested on high speed. Hydronic Pump 727 RP-01 DOM HW 6-Jun-22 Bryan Hund No ports or circuit setter. Operational check on med speed. Balance Valve 725 P-03 RADIANT/RZ-A- 6-Jun-22 Bryan Hund 4 loops connected. 01 Balance Valve 725 P-03 RADIANT/RZ-A- 6-Jun-22 Bryan Hund 2 loops connected. 02 Balance Valve 725 P-03 RADIANT/RZ-A- 6-Jun-22 Bryan Hund 2 loops connected. 03 Balance Valve 727 P-03 RADIANT/RZ-B-01 6-Jun-22 Bryan Hund 4 loops connected. Balance Valve 727 P-03 RADIANT/RZ-B-02 6-Jun-22 Bryan Hund 2 loops connected. Balance Valve 727 P-03 RADIANT/RZ-B-03 6-Jun-22 Bryan Hund 2 loops connected. Balance Valve 727 P-04 SNOWMELT/SZ-B- 6-Jun-22 Bryan Hund 2 loops connected. 01 JEDI Balancing, Inc. Page 2 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 ERV-A-01 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Unit Manufacturer Renewaire 725 ERV-A-01 /Supply/Exhaust Fan Unit Model Number EV300 Motor Manufacturer EMBEDDED Unit Serial Number 2022 Motor HP 0.2 Motor RPM Not Given Starter Data Motor Frame Not Given 725 ERV-A-01 /Supply/Exhaust Fan Motor Phase 1 Starter Manufacturer Thermally Protected Motor Rated Volts 120 Motor FL Amps 3.30 Design Data Motor Service Factor 1.0 Total Flow Design 300 Supply Fan Design ESP 0.5 in.wc Sheave Data Supply Fan Design TSP Not Given in.wc 725 ERV-A-01 /Supply/Exhaust Fan Supply Fan Design RPM Not Given Drive Type Direct Drive Supply Fan Motor Design HP 317 W Supply Fan Motor Design RPM Not Given Final Data Supply Fan Motor Design Volts 115 Fan Flow Test Method Flowhood Summation Supply Fan Motor Design Phase 1 Design Filter MERV Rating Not Given Measured Data Return Fan Flow Design 300 725 ERV-A-01 /Supply/Exhaust Fan Connected Return Fan Flow 300 Fan RPM Actual Direct Drive Design Fan Speed/Setpoint Not Applicable Return Fan Design SP 0.5 in.wc Operating Hertz 60 Test Data Design Actual Supply Airflow 300 280 Outside Airflow 300 280 Return Airflow 295 Electrical Test Data 725 ERV-A-01 /Supply/Exhaust Fan Motor Volts 1 122 Motor Amps 1 2.60 Corrected Nameplate Amps 3.25 Actual BHP 0.16 Volts/Amps Measured By RMS Clamp Meter JEDI Balancing, Inc. Page 3 of 48 JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 ERV-A-01 /Exhaust Tested By: Bryan Hund Date: 6/7/2022 Test Data Test Pressures Actual TSP 0.57 in.w.c. EF HEX SP In -0.22 in.w.c. External SP 0.36 in.w.c. EF HEX SP Out -0.43 in.w.c. Exhaust Fan SP In -0.43 in.w.c. Exhaust Fan SP Out 0.14 in.w.c. Static Pressure Profile 111111111111111 0.21 0. 5 /7;7 11 �E F —0.22 —0.43 0.14 SYSTEM/UNIT: 725 ERV-A-01 /Supply Tested By: Bryan Hund Date: 6/7/2022 Test Data Test Pressures Actual TSP 0.65 in.w.c. Supply Fan SP In -0.41 in.w.c. External SP 0.35 in.w.c. Supply Fan SP Out 0.24 in.w.c. Heating Coil SP In 0.24 in.w.c. Heating Coil SP Out 0.13 in.w.c. SF HEX SP In -0.11 in.w.c. SF HEX SP Out -0.41 in.w.c. Static Pressure Profile 0.30 0.65 I I CJ —0.11 —0.91 0.24 JEDI Balancing, Inc. Page 4 of 48 ., ., .., JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser 725 ERV-A-01 Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 MEDIA RM SD 18/6 300 280 280 93 Flow Hood Totals: - - - 300 280 280 93 - - - - 725 ERV-A-01 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 TLT ER 6/6 75 65 70 93 Flow Hood Inlet-02 BATH ER 6/6 75 60 70 93 Flow Hood Inlet-03 RR ER 6/6 75 75 75 100 Flow Hood Inlet-04 RR ER 6/6 75 85 80 107 Flow Hood Totals: - - - 300 285 295 98 - - - - JEDI Balancing, Inc. Page 5 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 F-Al Tested By: Bryan Hund Date: 6/6/2022 Unit Data Motor Data Unit Manufacturer York 725 F-Al/Supply Fan Unit Model Number TM9Y120D2OMP11A Motor Manufacturer Embedded Unit Serial Number W2A0543035 Motor HP 3/4 Motor RPM 1050 Starter Data Motor Frame Not Given 725 F-Al/Supply Fan Motor Phase 1 Starter Manufacturer Thermally Protected Motor Rated Volts 120 Motor FL Amps 8.40 Design Data Motor Service Factor 1.0 Total Flow Design 2250 Supply Fan Design ESP 0.5 in.wc Sheave Data Supply Fan Design TSP Not Given in.wc 725 F-Al/Supply Fan Supply Fan Design RPM Not Given Drive Type Direct Drive Supply Fan Motor Design HP Not Given Supply Fan Motor Design RPM Not Given Final Data Supply Fan Motor Design Volts 115 Fan Flow Test Method Flowhood Summation Supply Fan Motor Design Phase 1 OA Damper Pos 100% Design Filter MERV Rating 8 OA Flow Test Method Airfoil Traverse RA Damper Position Not Applicable Test Data Duct Static Setpoint 0.70 in.wc Design Actual Supply Airflow 2250 2215 Measured Data Outside Airflow 1000 960(MAU 725 F-Al/Supply Fan Mode) Fan RPM Actual Direct Drive Return Airflow 1255 Fan Speed/Setpoint Cool wired high Operating Hertz 60 Electrical Test Data 725 F-Al/Supply Fan Filter Data Motor Volts 1 121 725 F-Al/SF Filter Bank Motor Amps 1 7.40 Filter Type RETURN/OSA AIR Corrected Nameplate Amps 8.33 MERV Rating MERV 8 Actual BHP 0.67 Filter Quantity(set 1) 1 Volts/Amps Measured By RMS Clamp Meter Filter Size(set 1) 14X24X1 JEDI Balancing, Inc. Page 6 of 48 JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 F-A1/SPP-01 Tested By: Bryan Hund Date: 6/6/2022 Test Data Test Pressures Actual TSP 1.26 in.w.c. Filter SP In -0.24 in.w.c. External SP 0.91 in.w.c. Filter SP Out -0.39 in.w.c. DX Coil SP In 0.84 in.w.c. DX Coil SP Out 0.67 in.w.c. Gas Heat Exchanger In 0.87 in.w.c. Gas Heat Exchanger Out 0.84 in.w.c. Supply Fan SP In -0.39 in.w.c. Supply Fan SP Out 0.87 in.w.c. Static Pressure Profile 0.15 1.26 0.03 0.17 S I ISI / i /,, ! ilii/ i ,, i —0.24 —0.39 0.87 0.84 0.67 JEDI Balancing, Inc. Page 7 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 F-Al/OSA Tested By: Bryan Hund Date: 6/6/2022 Unit Data Final Data Traverse Location OSA Duct Design Total Flow 1000 CFM Type of Traverse Rectangular Actual Total Flow 962 CFM Outer Height 12 in. Average Reading 822 FPM Outer Width 14 in. Sum of Readings 7394 FPM Air Flow Area(Ak) 1.17 sq.ft. Static Pressure -0.26 in.w.c. Readings Height 3 Air Temperature 58.0°F Readings Width 3 Altitude 8000 Ft Total Readings 9 Instrument Used Alnor Probe Airfoil Traverse Data Points N O O O C) C.) C.) A Row 1 815 817 818 Row 2 829 828 828 N Row 3 830 819 818 V 14 JEDI Balancing, Inc. Page 8 of 48 JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 F-Al/F-A-01A Tested By: Bryan Hund Date: 6/6/2022 Measured Data Max Design Flow 419 CFM Max Actual Flow 425 CFM 725 F-Al/F-A-01A Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 M CLOSET SD 12/6 30 45 30 100 Flow Hood Outlet-02 M BATH SD 12/6 115 140 120 104 Flow Hood Outlet-03 M BED SD 12/6 137 200 135 99 Flow Hood Outlet-04 M BED SD 12/6 137 100 140 102 Flow Hood Totals: - - - 419 485 425 101 - - - - SYSTEM/UNIT: 725 F-Al/F-A-01B Tested By: Bryan Hund Date: 6/6/2022 Measured Data Max Design Flow 617 CFM Max Actual Flow 650 CFM 725 F-A1/F-A-01B Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 ENTRY SD 12/6 150 240 160 107 Flow Hood Outlet-02 ENTRY SD 12/6 130 240 135 104 Flow Hood Outlet-03 MUD RM SD 12/6 25 55 25 100 Flow Hood Outlet-04 CORRIDOR SD 12/6 115 140 120 104 Flow Hood Outlet-05 BED SD 12/6 60 80 65 108 Flow Hood Outlet-06 BED SD 12/6 137 200 145 106 Flow Hood Totals: - - - 617 955 650 105 - - - - JEDI Balancing, Inc. Page 9 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 F-A1/F-A-01C Tested By: Bryan Hund Date: 6/6/2022 Measured Data Max Design Flow 1214 CFM Max Actual Flow 1140 CFM 725 F-A1/F-A-01C Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final I % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 STAIRS SD 12/6 200 70 185 93 Flow Hood • Outlet-02 POWDER SD 12/6 30 70 30 100 Flow Hood Outlet-03 LIVING SD 12/6 142 130 140 99 Flow Hood Outlet-04 LIVING SD 12/6 150 120 140 93 Flow Hood Outlet-05 LIVING SD 12/6 150 110 145 97 Flow Hood • Outlet-06 LIVING SD 12/6 142 115 135 95 Flow Hood Outlet-07 DINING SD 12/6 200 145 185 93 Flow Hood • Outlet-08 DINING SD 12/6 200 140 180 90 Flow Hood • Totals: - - - 1214 900 1140 94 - - - - JEDI Balancing, Inc. Page 10 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 ERV-B-01 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Unit Manufacturer Renewaire 727 ERV-B-01/Supply/Exhaust Fan Unit Model Number EV300 Motor Manufacturer EMBEDDED Unit Serial Number 2022 Motor HP 0.2 Motor RPM Not Given Starter Data Motor Frame Not Given 727 ERV-B-01/Supply/Exhaust Fan Motor Phase 1 Starter Manufacturer Thermally Protected Motor Rated Volts 120 Motor FL Amps 3.30 Design Data Motor Service Factor 1.0 Total Flow Design 300 Supply Fan Design ESP 0.5 in.wc Sheave Data Supply Fan Design TSP Not Given in.wc 727 ERV-B-01/Supply/Exhaust Fan Supply Fan Design RPM Not Given Drive Type Direct Drive Supply Fan Motor Design HP 317 W Supply Fan Motor Design RPM Not Given Final Data Supply Fan Motor Design Volts 115 Fan Flow Test Method Flowhood Summation Supply Fan Motor Design Phase 1 Design Filter MERV Rating Not Given Measured Data Return Fan Flow Design 300 727 ERV-B-01/Supply/Exhaust Fan Connected Return Fan Flow 300 Fan RPM Actual Direct Drive Design Fan Speed/Setpoint Not Applicable Return Fan Design SP 0.5 in.wc Operating Hertz 60 Test Data Design Actual Supply Airflow 300 285 Outside Airflow 300 285 Return Airflow 290 Electrical Test Data 727 ERV-B-01/Supply/Exhaust Fan Motor Volts 1 122 Motor Amps 1 2.65 Corrected Nameplate Amps 3.25 Actual BHP 0.16 Volts/Amps Measured By RMS Clamp Meter JEDI Balancing, Inc. Page 11 of 48 JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 ERV-B-01/Exhaust Tested By: Bryan Hund Date: 6/7/2022 Test Data Test Pressures Actual TSP 0.58 in.w.c. EF HEX SP In -0.24 in.w.c. External SP 0.37 in.w.c. EF HEX SP Out -0.46 in.w.c. Exhaust Fan SP In -0.46 in.w.c. Exhaust Fan SP Out 0.13 in.w.c. Static Pressure Profile 0.22 0 . 11 �E F —0.29 —0.46 0.13 SYSTEM/UNIT: 727 ERV-B-01/Supply Tested By: Bryan Hund Date: 6/7/2022 Test Data Test Pressures Actual TSP 0.70 in.w.c. Supply Fan SP In -0.44 in.w.c. External SP 0.40 in.w.c. Supply Fan SP Out 0.26 in.w.c. Heating Coil SP In 0.26 in.w.c. Heating Coil SP Out 0.23 in.w.c. SF HEX SP In -0.14 in.w.c. SF HEX SP Out -0.44 in.w.c. Static Pressure Profile 0.30 0.70 I I I I) —0.14 —0.44 0.26 JEDI Balancing, Inc. Page 12 of 48 ., ., .., JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser 727 ERV-B-01 Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 CORRIDOR SD 18/6 300 285 285 95 Flow Hood Totals: - - - 300 285 285 95 - - - - 727 ERV-B-01 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 TLT ER 6/6 75 45 70 93 Flow Hood Inlet-02 BATH ER 6/6 75 50 70 93 Flow Hood Inlet-03 RR ER 6/6 75 50 75 100 Flow Hood Inlet-04 RR ER 6/6 75 100 75 100 Flow Hood Totals: - - - 300 245 290 97 - - - - JEDI Balancing, Inc. Page 13 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 F-B1 Tested By: Bryan Hund Date: 6/6/2022 Unit Data Motor Data Unit Manufacturer York 727 F-B1/Supply Fan Unit Model Number TM9Y120D2OMP11A Motor Manufacturer Embedded Unit Serial Number W1M9455425 Motor HP 3/4 Motor RPM 1050 Starter Data Motor Frame Not Given 727 F-B1/Supply Fan Motor Phase 1 Starter Manufacturer Thermally Protected Motor Rated Volts 120 Motor FL Amps 8.40 Design Data Motor Service Factor 1.0 Total Flow Design 2250 Supply Fan Design ESP 0.5 in.wc Sheave Data Supply Fan Design TSP Not Given in.wc 727 F-B1/Supply Fan Supply Fan Design RPM Not Given Drive Type Direct Drive Supply Fan Motor Design HP Not Given Supply Fan Motor Design RPM Not Given Final Data Supply Fan Motor Design Volts 115 Fan Flow Test Method Flowhood Summation Supply Fan Motor Design Phase 1 OA Damper Pos 100% Design Filter MERV Rating 8 OA Flow Test Method Airfoil Traverse RA Damper Position Not Applicable Test Data Duct Static Setpoint 0.70 in.wc Design Actual Supply Airflow 2248 2120 Measured Data Outside Airflow 1000 940(MAU 727 F-B1/Supply Fan Mode) Fan RPM Actual Direct Drive Return Airflow 1180 Fan Speed/Setpoint Cool wired high Operating Hertz 60 Electrical Test Data 727 F-B1/Supply Fan Filter Data Motor Volts 1 123 727 F-B1/SF Filter Bank Motor Amps 1 7.50 Filter Type RETURN/OSA AIR Corrected Nameplate Amps 8.20 MERV Rating MERV 8 Actual BHP 0.69 Filter Quantity(set 1) 1 Volts/Amps Measured By RMS Clamp Meter Filter Size(set 1) 14X24X1 JEDI Balancing, Inc. Page 14 of 48 JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 F-B1/SPP-01 Tested By: Bryan Hund Date: 6/6/2022 Test Data Test Pressures Actual TSP 1.16 in.w.c. Filter SP In -0.20 in.w.c. External SP 0.84 in.w.c. Filter SP Out -0.36 in.w.c. DX Coil SP In 0.76 in.w.c. DX Coil SP Out 0.64 in.w.c. Gas Heat Exchanger In 0.80 in.w.c. Gas Heat Exchanger Out 0.76 in.w.c. Supply Fan SP In -0.36 in.w.c. Supply Fan SP Out 0.80 in.w.c. Static Pressure Profile i i 0. 16 1.16 0.04 0.12 _ T 7 , , .. ,„) T , ,.•,:. L, 17-1 ! 1 ! / L ,, i , —0.20 —0.36 0.80 0.76 0.64 JEDI Balancing, Inc. Page 15 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 F-B1/OSA Tested By: Bryan Hund Date: 6/6/2022 Unit Data Final Data Traverse Location OSA Duct Design Total Flow 1000 CFM Type of Traverse Rectangular Actual Total Flow 942 CFM Outer Height 12 in. Average Reading 805 FPM Outer Width 14 in. Sum of Readings 7244 FPM Air Flow Area(Ak) 1.17 sq.ft. Static Pressure -0.26 in.w.c. Readings Height 3 Air Temperature 58.0°F Readings Width 3 Altitude 8000 Ft Total Readings 9 Instrument Used Alnor Probe Airfoil Traverse Data Points N O O O C.) C.) C.) A Row 1 807 893 BCC Row 2 811 81C 892 Row 3 799 794 818 V 14 JEDI Balancing, Inc. Page 16 of 48 JEDI Balancing Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 F-B1/F-B-01A Tested By: Bryan Hund Date: 6/6/2022 Measured Data Max Design Flow 440 CFM Max Actual Flow 415 CFM 727 F-B1/F-B-01A Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 M BATH SD 12/6 125 100 120 96 Flow Hood Outlet-02 M CLOSET SD 12/6 25 110 25 100 Flow Hood Outlet-03 M BED SD 12/6 145 110 135 93 Flow Hood Outlet-04 M BED SD 12/6 145 100 135 93 Flow Hood Totals: - - - 440 420 415 94 - - - SYSTEM/UNIT: 727 F-B1/F-B-01B Tested By: Bryan Hund Date: 6/6/2022 Measured Data Max Design Flow 560 CFM Max Actual Flow 545 CFM 727 F-B1/F-B-01B Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 CORRIDOR SD 12/6 40 55 40 100 Flow Hood Outlet-02 MUD RM SD 12/6 75 60 75 100 Flow Hood Outlet-03 ENTRY SD 12/6 75 80 75 100 Flow Hood Outlet-04 STAIRS SD 12/6 170 100 160 94 Flow Hood Outlet-05 BED SD 12/6 125 95 120 96 Flow Hood Outlet-06 BED SD 12/6 50 65 50 100 Flow Hood Outlet-07 CLOSET SD 12/6 25 45 25 100 Flow Hood Totals: - - - 560 500 545 97 - - JEDI Balancing, Inc. Page 17 of 48 JEDI Balancing • Air Handling Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 F-B1/F-B-01C Tested By: Bryan Hund Date: 6/6/2022 Measured Data Max Design Flow 1248 CFM Max Actual Flow 1160 CFM 727 F-B1/F-B-01C Supply Outlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final I % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Outlet-01 STAIRS SD 12/6 200 170 180 90 Flow Hood • Outlet-02 POSWER SD 12/6 30 80 30 100 Flow Hood Outlet-03 LIVING SD 12/6 175 130 165 94 Flow Hood Outlet-04 LIVING SD 12/6 175 120 170 97 Flow Hood Outlet-05 DINING SD 12/6 167 110 160 96 Flow Hood • Outlet-06 DINING SD 12/6 167 100 155 93 Flow Hood Outlet-07 DINING SD 12/6 167 130 150 90 Flow Hood • Outlet-08 DINING SD 12/6 167 125 150 90 Flow Hood • Totals: - - - 1248 965 1160 93 - - - - JEDI Balancing, Inc. Page 18 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 EF-01-01 Tested By: Bryan Hund Date: 6/6/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 70 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 123 Motor Amps 1 Actual 0.14 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 725 EF-01-01 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 110 70 113 Flow Hood Totals: - - - 62 110 70 113 - - - - JEDI Balancing, Inc. Page 19 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 EF-01-02 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 75 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 122 Motor Amps 1 Actual 0.13 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 725 EF-01-02 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 75 75 121 Flow Hood Totals: - - - 62 75 75 121 - - - - JEDI Balancing, Inc. Page 20 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 EF-01-03 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 75 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 121 Motor Amps 1 Actual 0.12 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 725 EF-01-03 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 75 75 121 Flow Hood Totals: - - - 62 75 75 121 - - - - JEDI Balancing, Inc. Page 21 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 EF-01-04 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 70 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 121 Motor Amps 1 Actual 0.14 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 725 EF-01-04 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 105 70 113 Flow Hood Totals: - - - 62 105 70 113 - - - - JEDI Balancing, Inc. Page 22 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 EF-02 Tested By: Bryan Hund Date: 6/6/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-30VQ3 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.61 Motor Service Factor 1.0 Design Data Total Flow Design 257 Sheave Data Total Connected Design Flow 257 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 280 Fan Motor Design HP 62 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint Not Applicable Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 123 Motor Amps 1 Actual 0.54 Test Pressures Corrected Nameplate Amps 0.60 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 725 EF-02 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 GARAGE ER 8" 257 280 280 109 Flow Hood Totals: - - - 257 280 280 109 - - - - JEDI Balancing, Inc. Page 23 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 EF-01-01 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 75 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 121 Motor Amps 1 Actual 0.14 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 727 EF-01-01 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 75 75 121 Flow Hood Totals: - - - 62 75 75 121 - - - - JEDI Balancing, Inc. Page 24 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 EF-01-02 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 70 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 122 Motor Amps 1 Actual 0.13 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 727 EF-01-02 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 70 70 113 Flow Hood Totals: - - - 62 70 70 113 - - - - JEDI Balancing, Inc. Page 25 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 EF-01-03 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 70 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 121 Motor Amps 1 Actual 0.12 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 727 EF-01-03 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 110 70 113 Flow Hood Totals: - - - 62 110 70 113 - - - - JEDI Balancing, Inc. Page 26 of 48 JEDI Balancing Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 EF-01-04 Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-0511VQ1 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.17 Motor Service Factor 1.0 Design Data Total Flow Design 62 Sheave Data Total Connected Design Flow 62 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 70 Fan Motor Design HP 15 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint 80 CFM Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 122 Motor Amps 1 Actual 0.13 Test Pressures Corrected Nameplate Amps 0.17 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 727 EF-01-04 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 RR ER 4" 62 110 70 113 Flow Hood Totals: - - - 62 110 70 113 - - - - JEDI Balancing, Inc. Page 27 of 48 JEDI Balancing • Fan Unit PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 EF-02 Tested By: Bryan Hund Date: 6/6/2022 Unit Data Motor Data Fan Manufacturer Panasonic Motor Manufacturer EMBEDDED Fan Model Number FV-30VQ3 Motor HP Not Given Fan Serial Number 2022 Motor RPM Not Given Type of Service EXHAUST Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor FL Amps 0.61 Motor Service Factor 1.0 Design Data Total Flow Design 257 Sheave Data Total Connected Design Flow 257 Drive Type Direct Drive Design ESP 0.25 in.wc Design TSP Not Given in.wc Final Data Fan Design RPM Not Given Total Fan Flow Actual 275 Fan Motor Design HP 62 W Fan Flow Test Method Flowhood Summation Fan Motor Design RPM Not Given Fan Motor Design Voltage 115 Measured Data Fan Motor Design Phase 1 Fan RPM Actual Direct Drive Fan Speed/Setpoint Not Applicable Electrical Test Data Operating Hertz 60 Motor Volts 1 Actual 123 Motor Amps 1 Actual 0.52 Test Pressures Corrected Nameplate Amps 0.60 Fan SP In Actual Atmosphere in.wc Volts/Amps Measured By RMS Clamp Meter Fan SP Out Actual No Access in.wc 727 EF-02 Exhaust Inlet Summary System/Unit Area Served Outlet Size inch Design Prelim Final % Instrument Open Area Ak(sq ft) Final Type Airflow Airflow Airflow Final (sq ft) Velocity CFM CFM CFM FPM Inlet-01 GARAGE ER 8" 257 275 275 107 Flow Hood Totals: - - - 257 275 275 107 - - - - JEDI Balancing, Inc. Page 28 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 P-01 BOILER Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS15-58FC Motor HP 60/80/87 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service BOILER Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 0.55/0.66/0.75 Motor S.F. 1.0 Design Data Pump Design Flow 8 GPM Design TDH 7 Ft Total Connected Flow 8 GPM Pump Design RPM Not Given Motor Design HP 1/25 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual See Note GPM Final D.P. See Note PSI Electrical Test Data Motor Volts 1 123 Volts Motor Amps 1 0.60 Amps Corrected Nameplate Amps 0.64 Pump BHP 0.10 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 725 P-01 BOILER 6/6/2022 Bryan Hund No ports or circuit setter.Operational check on med speed. JEDI Balancing, Inc. Page 29 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 P-02 WH Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number Comfort 10-16 A PM Motor HP Not Given Pump Serial Number 2022 Motor RPM Not Given Type of Service WH Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 120 Starter Manufacturer Thermally Protected Motor F.L.Amps 0.07 Motor S.F. 1.0 Design Data Pump Design Flow 14 GPM Design TDH 14 Ft Total Connected Flow 14 GPM Pump Design RPM Not Given Motor Design HP 1/6 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual See Note GPM Final D.P. See Note PSI Electrical Test Data Motor Volts 1 123 Volts Motor Amps 1 0.06 Amps Corrected Nameplate Amps 0.07 Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 725 P-02 WH 6/6/2022 Bryan Hund No ports or circuit setter.Operational check only on max.Pump placed into auto adapt control after testing. JEDI Balancing, Inc. Page 30 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 P-03 RADIANT Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS15-58FC Motor HP 60/80/87 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service RADIANT Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 0.55/0.66/0.75 Motor S.F. 1.0 Design Data Pump Design Flow 2 GPM Design TDH 15 Ft Total Connected Flow 2 GPM Pump Design RPM Not Given Motor Design HP 1/25 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual 2.6(Sight Glass)GPM Electrical Test Data Motor Volts 1 123 Volts Motor Amps 1 0.60 Amps Corrected Nameplate Amps 0.64 Pump BHP 0.10 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 725 P-03 RADIANT 6/6/2022 Bryan Hund Pump was tested on med speed. 725 P-03 RADIANT Balance Valve Summary System/Unit Manufacturer Model Size Design Actual %Final Valve D.P. Valve D.P. Valve Position Number Flow Flow Deviation Design Actual _ RZ-A-01* 1.00 1.10(Sight 1 Glass) RZ-A-02* 0.40 0.5(Sight 1 Glass) RZ-A-03* 0.60 1.0(Sight 1 Glass) Totals: - - - 2.00 0.00 0 - - - Log: 725 P-03 RADIANT/RZ-A-01 6/6/2022 Bryan Hund 4 loops connected. 725 P-03 RADIANT/RZ-A-02 6/6/2022 Bryan Hund 2 loops connected. 725 P-03 RADIANT/RZ-A-03 6/6/2022 Bryan Hund 2 loops connected. JEDI Balancing, Inc. Page 31 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 P-04 SNOWMELT Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS26-99FC Motor HP 150/179/197 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service SNOWMELT Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 1.3/1.5/1.8 Motor S.F. 1.0 Design Data Pump Design Flow 2 GPM Design TDH 28 Ft Total Connected Flow 2.1 GPM Pump Design RPM Not Given Motor Design HP 1/6 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual 2.3(Sight Glass)GPM Electrical Test Data Motor Volts 1 123 Volts Motor Amps 1 0.90 Amps Corrected Nameplate Amps 1.76 Pump BHP 0.14 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 725 P-04 SNOWMELT 6/6/2022 Bryan Hund Pump was tested on high speed. 725 P-04 SNOWMELT Balance Valve Summary System/Unit Manufacturer Model Size Design Actual %Final Valve D.P. Valve D.P. Valve Position Number Flow Flow Deviation Design Actual SZ-A-01A 0.80 0.9(Sight 1 Glass) _ SZ-A-01 B 1.30 1.4(Sight 1 Glasse Totals: - - - 2.10 0.00 0 - - JEDI Balancing, Inc. Page 32 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 725 RP-01 DOM HW Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS26-99FC Motor HP 150/179/197 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service DOM HW Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 1.3/1.5/1.8 Motor S.F. 1.0 Design Data Pump Design Flow 2 GPM Design TDH 1.5 Ft Total Connected Flow 2 GPM Pump Design RPM Not Given Motor Design HP 9 W Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual See Note GPM Final D.P. See Note PSI Electrical Test Data Motor Volts 1 121 Volts Motor Amps 1 1.39 Amps Corrected Nameplate Amps 1.49 Pump BHP 0.22 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 725 RP-01 DOM HW 6/6/2022 Bryan Hund No ports or circuit setter.Operational check on med speed. JEDI Balancing, Inc. Page 33 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 P-01 BOILER Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS15-58FC Motor HP 60/80/87 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service BOILER Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 0.55/0.66/0.75 Motor S.F. 1.0 Design Data Pump Design Flow 8 GPM Design TDH 7 Ft Total Connected Flow 8 GPM Pump Design RPM Not Given Motor Design HP 1/25 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual See Note GPM Final D.P. See Note PSI Electrical Test Data Motor Volts 1 123 Volts Motor Amps 1 0.59 Amps Corrected Nameplate Amps 0.64 Pump BHP 0.10 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 727 P-01 BOILER 6/6/2022 Bryan Hund No ports or circuit setter.Operational check on med speed. JEDI Balancing, Inc. Page 34 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 P-02 WH Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number Comfort 10-16 A PM Motor HP Not Given Pump Serial Number 2022 Motor RPM Not Given Type of Service WH Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 120 Starter Manufacturer Thermally Protected Motor F.L.Amps 0.07 Motor S.F. 1.0 Design Data Pump Design Flow 14 GPM Design TDH 14 Ft Total Connected Flow 14 GPM Pump Design RPM Not Given Motor Design HP 1/6 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual See Note GPM Final D.P. See Note PSI Electrical Test Data Motor Volts 1 121 Volts Motor Amps 1 0.07 Amps Corrected Nameplate Amps 0.07 Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 727 P-02 WH 6/6/2022 Bryan Hund No ports or circuit setter.Operational check only on max.Pump placed into auto adapt control after testing. JEDI Balancing, Inc. Page 35 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 P-03 RADIANT Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS15-58FC Motor HP 60/80/87 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service RADIANT Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 0.55/0.66/0.75 Motor S.F. 1.0 Design Data Pump Design Flow 2 GPM Design TDH 15 Ft Total Connected Flow 2 GPM Pump Design RPM Not Given Motor Design HP 1/25 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual 2.2(Sight Glass)GPM Electrical Test Data Motor Volts 1 121 Volts Motor Amps 1 0.59 Amps Corrected Nameplate Amps 0.65 Pump BHP 0.10 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 727 P-03 RADIANT 6/6/2022 Bryan Hund Pump was tested on med speed. 727 P-03 RADIANT Balance Valve Summary System/Unit Manufacturer Model Size Design Actual %Final Valve D.P. Valve D.P. Valve Position Number Flow Flow Deviation Design Actual _ RZ-B-01* 1.00 1.1 (Sight 1 Glass) RZ-B-02* 0.40 0.5(Sight 1 Glass) RZ-B-03* 0.60 0.6(Sight 1 Glass) Totals: - - - 2.00 0.00 0 - - - Log: 727 P-03 RADIANT/RZ-B-01 6/6/2022 Bryan Hund 4 loops connected. 727 P-03 RADIANT/RZ-B-02 6/6/2022 Bryan Hund 2 loops connected. 727 P-03 RADIANT/RZ-B-03 6/6/2022 Bryan Hund 2 loops connected. JEDI Balancing, Inc. Page 36 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 P-04 SNOWMELT Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS26-99FC Motor HP 150/179/197 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service SNOWMELT Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 1.3/1.5/1.8 Motor S.F. 1.0 Design Data Pump Design Flow 2 GPM Design TDH 28 Ft Total Connected Flow 2.2 GPM Pump Design RPM Not Given Motor Design HP 1/6 Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual 2.4(Sight Glass)GPM Electrical Test Data Motor Volts 1 123 Volts Motor Amps 1 0.92 Amps Corrected Nameplate Amps 1.76 Pump BHP 0.14 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 727 P-04 SNOWMELT 6/6/2022 Bryan Hund Pump was tested on high speed. 727 P-04 SNOWMELT Balance Valve Summary System/Unit Manufacturer Model Size Design Actual %Final Valve D.P. Valve D.P. Valve Position Number Flow Flow Deviation Design Actual SZ-B-01* 2.20 2.4(Sight 2 Glass) _ Totals: - - - 2.20 0.00 0 - - Log: 727 P-04 SNOWMELT/SZ-B-01 6/6/2022 Bryan Hund 2 loops connected. JEDI Balancing, Inc. Page 37 of 48 JEDI Balancing • Hydronic Pump PROJECT: 725&727 CEMETERY LANE DATE: 6/7/2022 LOCATION: ASPEN, CO CONTACT: Josh Cota PROJECT#: 2022-9703 AUTHOR: Donald Pittser SYSTEM/UNIT: 727 RP-01 DOM HW Tested By: Bryan Hund Date: 6/7/2022 Unit Data Motor Data Pump Manufacturer Grundfos Motor Manufacturer Not Given Pump Model Number UPS26-99FC Motor HP 150/179/197 watts Pump Serial Number 2022 Motor RPM Not Given Type of Service DOM HW Motor Frame Not Given Motor Phase 1 Starter Data Motor Rated Volts 115 Starter Manufacturer Thermally Protected Motor F.L.Amps 1.3/1.5/1.8 Motor S.F. 1.0 Design Data Pump Design Flow 2 GPM Design TDH 1.5 Ft Total Connected Flow 2 GPM Pump Design RPM Not Given Motor Design HP 9 W Design Impeller Diam. Not Given in. Final Test Data Final Flow Actual See Note GPM Final D.P. See Note PSI Electrical Test Data Motor Volts 1 123 Volts Motor Amps 1 1.40 Amps Corrected Nameplate Amps 1.46 Pump BHP 0.23 BHP Volts/Amps Measured By RMS Clamp Meter Operating HZ 60 Log: 727 RP-01 DOM HW 6/6/2022 Bryan Hund No ports or circuit setter.Operational check on med speed. JEDI Balancing, Inc. Page 38 of 48 AHU Stamp DESIGN CONDITIONS DUCTWORK LEGEND PIPING LEGEND GENERAL LEGEND FLAN AEEREVIATIONS WINTER DESIGN TEMPERATURES: INDOOR: l0°F DB SINGLE LINE DESCRIPTION DOUBLE LINE ---0� OR �4 GATE VALVE CO CARBON MONOXIDE SENSOR AAv AIR ADMITTANCE VALVE(STUDOR OR EQUAL) OUTDOOR: -15°F DB -1,-.1- OR S, CHECK VALVE C2 CARBON DIOXIDE SENSOR AFF ABOVE FINISHED FLOOR 90°ELBOW DOWN V CI OR TL BALL VALVE OH HUMIDISTAT ABv ABOVE SUMMER DESIGN TEMPERATURES: INDOOR: l2°F DB OUTDOOR: 82°F DB 90°ELBOW UP hI BUTTERFLY VALVE OD DEHUMIDISTAT BLW BELOW A OR IN PLUG VALVE ® NITROGEN DIOXIDE SENSOR CFM CUBIC FEET PER MINUTE(AIR QUANTITY) Iw� ELEVATION 1900 FEET )r') (AT 30°WHEN POSSIBLE.OFFSET TO CHANGE ELEVATION Is CIRCUIT SETTER WITH GPM * OCCUPANY SENSOR(RE:ELECTRICAL) CLG CEILING OM' N -, vl R' in ARROW SLOPES DN.) GLOBE VALVE ® ERV PUSH BUTTON CONTROLLER(LIGHTED) CO CLEANOUT r in WALL R-VALUE IAVG) 21(CAV) W Z 'M, OR STRAINER(Y-TYPE)WITH BLOW-DOWN PT ERv PERCENT TIMER CONTROLLER(LIGHTED) COCONC. CONCRETE J' 6 IGONT) ROUND RADIUS ELBOW �" 1154 )�- w D� OR -:4- TWO-WAY AUTOMATIC CONTROL VALVE OS SENSOR COTG CLEAN-OUT TO GRADE (O W ROOF R-VALUE(AVG) 25(CAV) vl LU ON DOWN ral I- 1- . --, F 24(CONT) 90'STRAIGHT TEE EMIR OR pp SOLENOID VALVE AUTOMATICE-WAY DIVERTING VALVE O STATIC PRE55URE SNOWMELT R5EN50RR 091/094) DMPR DAMPER D O 0 GLASS U-VALUE(AVG) 035 OR YV PRESSURE REGULATOR(OR REDUCING VALVE) O THERMOSTAT EA EXHAUST AIR CI"- 90°CONICAL TEE am, Z \' O GLASS SHADING COEFFICIENT IAVG) 036 �m, ❑M-1 TUWO-WAY MODULATING CONTROL VALVE S WALL ON/OFF CONTROL SWITCH EC ELECTRICAL CONTRACTOR lJEi O\ .` u C THREE-WAY MODULATING MIXING VALVE $T WALL TIMER SWITCH ER/EG EXHAUST REGISTER/EXHAUST GRILLE • > X ELECTRICAL POWER AVAILABLE 120/I,240/I / 45'BRANCH MO. �I�, V. 1 4 W (NO 3 PHASE) t L�rp THERMOSTATIC MIXING VALVE(TMv) SV VARIABLE SPEED CONTROL ETR EXISTING TO REMAIN 2 d DP DIFFERENTIAL PRESSURE VALVE EXH EXHAUST �' Z / 45'CONICAL TEE y tt EMS 5¢ OR a}' PRESSURE RELIEF VALVE /\ I R DEVICE W_ v 1 FCC/ FLOOR CLEAN-OUT W tQ �� SIZE OR SHAPE TRANSITION V MANUAL AIR VENT FD FIRE DAMPER OR FLOOR DRAIN ur Rl el r SHEET INDEX 1� T DESIGNATION KEY: x z a X 1 0 l\��/� AUTOMATIC AIR VENT FPC FIRE PROTECTION CONTRACTOR W O Lo F Y VACUUM BREAKER GPM GALLONS PER MINUTE(WATER FLOW RATE) @ CO V SHEET DESCRIPTION PAGE ROUND FLEXIBLE DUCT ii:���.:� - (q p ®--I OR €1.-+] PRESSURE GAUGE WITH GAUGE COCK SIZE(INCHES) LD SUPPLY DIFFUSER(LINEAR) is, W MOO MECHANICAL COVER SHEET I J O C Q PRESSURE SENSOR NOTE: FOR STANDARD MODULE SIZE MC MECHANICAL CONTRACTOR ((_� U! M0.1 MECHANICAL ZONING PLAN 2 90°ELBOW DOIN - REGISTERS,SIZE GIVEN IS NECK ll- 4' PRESSURE/TEMPERATURE TEST PORT SIZE. REFER TO AIR DEVICE SCHEDULE MOD MOTOR OPERATED DAMPER 'X(111 0 el SHEET FOR MODULE SIZE. �'1 MID MECHANICAL SCHEDULES 3 Q �' Z LT TEMPERATURE SENSOR OA/OSA OUTSIDE AIR F MI.1 MECHANICAL SCHEDULES 4 -1 90'ELBOW UP AIR QUANTITY(CFM) PE Stamp " 0 o THERMOMETER WELL CA-COMB.AIR OED OPEN END DUCT A Z M2.0 LOWER LEVEL MECHANICAL PLAN 5 DROP/RISE DROP/RISE OA-OUTSIDE AIR DQ L/Cp��a i m O OFFSET TO CHANGE ELEVATION(AT 30° I-d THERMOMETER 12/6 CD-I 250 RA-RETURN AIR PC PLUMBING CONTRACTOR = 0�.... `/Yr 11 N F I� WHERE POSSIBLE).ARROW N DIRECTION ! EA-EXHAUST AIR %0�' A•(;titi S�rf M2.I MAIN LEVEL MECHANICAL PLAN 6 ] ] OF AIRFLOW.INDICATE DROP OR RISE. �'©,• f �'ley 9'o. rf F BTU METER(FLOW 4 TEMPERATURE DIFFERENCE) MA-MIXED AIR PR PIPE RISER Q d, M22 UPPER LEVEL MECHANICAL PLAN 1 n ' Pit Zt r Y MUA-MAKE-UP AIR 8/30/19 0 O O ROUND RADIUS ELBOW FLOW METER TYPE OF AIR DEVICE. RA RETURN AIR % i,� S 2 j a M30 MECHANICAL SCHEMATICS 8 r MAD MECHANICAL SPECIFICATIONS 9 I 4 RE:SCHEDULE SHEET 1 q1 x�JN`1' m R' III----II���� I--�� ICI FLOW SWITCH RR RETURN REGISTER r19Q. J,: O M4.1 SEQUENCE OF OPERATION 10 RECTANGTURNING VANESELBOW WITH f Y AQUASTAT RCi RETURN AIR GRILLE r rr1s`f`UMAI.��G= Z w Ell l000a- OR ter- BRAIDED TYPE FLEXIBLE PIPE CONNECTOR SA SUPPLY AIR N Q El RISER J NCH TAKE-OFF WITH SQUARE SQUT RAARE ELBOW 4 L11JJ ELASTOMERIC PIPING ISOLATOR(WITH KEVLAR) /�-+7 N A N �( 5.DMPR SMOKE DAMPER W 0 SPLITTER DAMPER -1 I I- PIPE UNION D "'I `T ION K� SR SUPPLY REGISTER(SIDEWALL OR DUCT MOUNTED) W ILL W O ST J SPLIT BRANCH TAKE-OFF +- QUICK CONNECT(GAS) OR HOSE BIB(WATER) SV STUDOR VENT(SIZED BY CONTRACTOR) ) W WITH RADIUS ELBOW 4Z m SPLITTER DAMPER I DUCTING: PIPING: TYP TYPICAL -log r 11 OR L� RADIANT OR SNOWMELT MANIFOLD WITH ACCESS OA-OUTSIDE AIR CW-CHILLED WATER BRANCH TAKE-OFF WITH 2EllPIPE UP OR PIPE UP 4 DOWN EA-EXHAUST AIR OW-DOMESTIC WATER m O HW-HEATING WATER TRANS TRANSITION Q RADIUS HEEL AND DAMPER GENERAL: G-GAS J)4 0 C- OR 0 PIPE DOW TA TRANSFER AIR 11��11 a O US-UTILITY SHAFT R-REFRIGERANT BRANCH TAKE-OFF WITH FLOOR DRAIN SD-STORM DRAIN UNO UNLESS NOTED OTHERWISE (� O 3 Z SM-SNOWI`1ELT ,Ijl LL z AIR EXTRACTORrSEIS OD-OVERFLOW DRAIN US UTILITY SHAFT } FLOOR SINK m WV-WASTE 4 VENT LINED DUCTWORK j f -II HORIZONTAL CLEANOUT v VTR VENT THROUGH ROOF 9 Q O (UNLESS NOTED OTHERWISE) 1, - RISER NUMBER FQN��IJ' F N 0 OR ® FLOOR CLEAN-OUT W/ WITH rW' O 2 SQUARE NECK CEILING DIFFUSER OM METER WCO WALL CLEAN-OUT 11 K N ® UNLESS DINDICTI INDICATEDL THROW OTHERWISE ® Le 7 XFER TRANSFER LfTi. O Z a PIPING DESIGNATIONS AIR TERMINAL UNIT w ROUND NECK DIRECTIONAL CEILING DIFFUSER 01 DES I N J\ ION J/ \/ O UNLESS INDICATEDIA OTHERWISEF K EQUIPMENT AEERE Y IAT ION W W CWS/R CHILLED WATER SUPPLY/RETURN O U r r SIDEWALL SUPPY GRILLE T CS/R CONDENSER WATER SUPPLY/RETURN T OR REGISTER WITH I--- 1 HWS/R HEATING WATER SUPPLY/RETURN TERMINAL TYPE: AHU AIR HANDLING UNIT �j W O AIR EXTRACTOR t "" i HLLIS/R(HT) HEATING WATER SUPPLY/RETURN HIGH TEMP CV-CONSTANT VOLUME BOX(SERIES) r l rL-r Q di FP-FAN POWERED BOX(PARALLEL) AS AIR SEPARATOR v W di HWS/R(LT) HEATING WATER SUPPLY/RETURN LOW TEMP W Ul 2 2 I/2 2 OI ST STATIC WATER CSURE CLASS CHANGE ©©®© RS 4 RL REFRIGERANT GELRAN T SUPPLY/RETURN REF.LIQUID vR-vAR11ABLE VOLUME w/REHEAT B BOILER(Hoi WATER) ''a^^ - -----DCW----- DOMESTIC COLD WATER(DCW) ��COOLING AIR QUANTITY(CFM) CH CHILLER ^� vl W DHW -- DOMESTIC HOT WATER(DHW) m 1100 CC COILING COIL ` V W m SUPPLY DUCT RISER m -----DHR----- DOMESTIC HOT WATER RECIRC(DHR) m 540 MINIMUM AIR QUANTITY(CFM)FOR �7 0_ DHW-T -- DOMESTIC HOT WATER(TEMPERED) VENTILATION OR HEATING. w CH CABINET HEATER RETURN,EXHAUST OR W WASTE PRIMARY AIR VALVE SIZE CT COOLING TOWER CELL W IL AlOUTSIDE AIR DUCT RISER -----V----- VENT F W GW GREASE WASTE CV CONSTANT VOLUME BOX 5-F CEILING RETURN AIR 1.1.11 PRESSURIZED WASTE DEF DISHWASHER EXHAUST FAN O ^�-/ GRILLE OR REGISTER \�� IW INDIRECT WASTE N .1 BD BUILDING DRAIN E M O D E L LEGEND EBH ELECTRIC BASEBOARD HEATER >Q I BS BUILDING SEWER ECU EVAPORATIVE COOLING UNIT IL Q ST DOOR GRILLE SD STORM DRAIN OD OVERFLOW DRAIN(STORM) POINT OF DISCONNECTION EF EXHAUST FAN SOD SEDIMENT 4 OIL DRAIN 0 POINT OF NEW CONNECTION Issued For w d 41 MANUAL BALANCING DAMPER G NATURAL GAS ERv ENERGY RECOVERY VENTILATOR(AIR TO AIR HX) r O MPG MEDIUM PRESSURE NATURAL GAS (A) ABANDON No. Date Comment LPG PROPANE GA5 (D) DEMO ET EXPANSION TANK I 8/14/19 COORDINATION 3 J. ��""77 D DRAIN FC FAN COIL 2 8/30/19 PERMIT MOTORIZED DAMPER (El EXISTING CD CONDENSATE DRAIN FP FAN POWERED BOX O 0 F FIRE SPRINKLER (F) FUTURE 3 L CA COMPRESSED AIR (N) NEW GE GLYCOL FEEDER N O SMOKE DAMPER GEO GEOEXCHANGE SOURCE Z U (R) RELOCATE HC HEATING COIL Si 17-1° SWS/R SOLAR WATER SUPPLY/RETURN J ® -~� (E) EXISTING HP HEAT PUMP MECHANICAL. N W FIRE DAMPER (UG) UNDERGROUND HX HEAT EXCHANGER COVER SHEET =W Z PUP S�lEOLS COMBINATION FIRE AND SMOKE DAMPER H HUMIDIFIER N O F/S _F/S INLINE WET ROTOR PUMP KEF KITCHEN EXHAUST FAN K j LT, I ® CEILING RADIATION DAMPER U5fl INLINE WET ROTOR PUMP(W/INTEGRAL CHECK) My MIXING VALVE N Z JJ��"" P PUMP(SEE PIPING LEGEND FOR DETAILS) Q W ��``TT INLINE CLOSE-COUPLED PUMP X GRAVITY BACKDRAFT DAMPER RF RETURN/RELIEF AIR FAN Q u Q SF SUPPLY FAN Project No. Scale: CY Z Q . BASE MOUNTED END SUCTION PUMP 9002.00 N/A (5 N DUCT MOUNTED SMOKE DETECTOR 10 BASE TOILET EXHAUST FAN Q Z sr `--' tMv THERMOSTATIC MIXING VALVE Drawn By: Checked By: Z 0 / CEILING ACCESS PANEL / ,1SU1 JDR UH UNIT HEATER Q W ti al)Z 0 Z— v v vv VARIABLE VOLUME BOX Q w K 2 K d WALL CAP-BATH OR DRYER EXHAUST 1�y VR VARIABLE VOLUME BOX W/REHEAT O• }Q WITH INTEGRAL BACKDRAFT DAMPER WH WATER HEATER 111 1110 Q fiO Page 39 of 48 AI-IJ Stamp SLEET LE END OD DEHUMIDISTAT I I RADIANT ® HUMIDISTAT I FLOOR ZONE MUA MAKE-UP AIR UNIT OS OCCUPANCY SENSOR — PB PUSH BUTTON CONTROL WITH DELAY OFF AIR ZONE OM' 0,1 N -_--- I*1-41*,,:i2,0v,r_N„ PT PERCENT TIMER CONTROL — // ME w � � w RZ RADIANT ZONE _ Ex O SLAB TEMPERATURE SENSOR SNOWMELT ZONE"I >VI w SA SNOWMELT AREA K 1� —: -- I II I SM SNOW/ICE SENSOR(TEKMAR 091/0940 O Q I A AS LL n U r . 1 OT THERMOSTAT/WALL SENSOR O Z O I T WALL TIMER SWTIGH : � O �IC Z _,• 3 II L�1 1 IW pc.• 03 ;„-, t7 O rPOWDER 03- Z 67 X r O , ,,,.....i 1112 4 .+� NEIN O�. W o a, 3 �1 O v INA ..iiil r 'I' �1 `- Z= (Eli) -II- 01 PE Stamp m Iiiik 1 0, x. S z 4 nvv ax __OQ►.DOLlpVr�'�I, HIMEG�f�.l!.HF,9ti�y p'rrF I i 14 8/30/19spry r o L� nL % R S 2 1i % (a r ,11 /II9 ' .� JR� ,h.,otUNAL.ts--- m w 17,U d P O� L m w UFFE LEVEL I/S" _ 1_0 ® TE r 1 0 LL3 el W N JJ F (,,,, WQ . , ,_ W, gin_ 0 ° Li Lji w LT L H o1Bsz�►oB L ,WIff1t11� ----, gF-2 w 9 HF BATHROOM ={NI 1 = Q BUNK ROOMI ^� ~_N1 �N� �II Mi ®r...,_ R� �ilIOG� �0� �I m p /101 �����lir oae—A .7.4ThillWMir 8 a S— 11 R7i1 I P '--- ,21„ ENTRY MUDROOM el IdFor 1 \ / Hry LWAY ", )=HM-A-Ib RZ O 1 O No. omment Q II I, ® O 8/14/19 COORDINATION 3 3 FRONT ENT• O _ �►� j 2 8/30/19 PERMIT 1101-BI 141/ram STORAGE _ I��� I°11pi7DROO DI_AI.I _ _ Q z HALLWAYEHM-_ IME➢IAI �ECHA �HE➢RDDM ZLOSET � ��� MEOIA F 0HM-B-Ib r—I108-BI CLOSET MASTE' U 005-B Opt-g ,r �—�'P3 E CLOSET 1 , uaox11RZ_g_I _,I,,,�, 00-H _ O007-AI�� O�I ,F8 F-B-Ib I h07-AI ���� .O 004-B �� RZ 02 I BATHROOM RZ-A-I I�� Z O r1 ���� RB-2 �� Q1r B-lb �� L---- w 1M ���� STDRA' �� _F-g-la _ 0�'1 S1t= L ��'S I ��,Q �1.�1. x �I O RZ�A O 9 1 �L ", ox �� Mas ER ®� �1 �Ier� ooe �� Ra-21 BEDRDD' I MECHANICAL w A BATHR00 0 • 1 004-A ,rrT1T,�-7.- N jholl ���� :ATHROOM 1,� P BATHR00 �`oo rn,;.'.7 LAUNDRY BATHROOM �� j 7�� === L+ p}� h0s^I pp �� ,, Elul oo7-B 006-B �� L 1 1� r rr1ZONINCs PLAN w u MASTER BEDROOM MASTER _��- �.O\ 1 ^I '�O' F-A-Ia 7 I�iI1—II �� J _ Z I CLOSET TER =M IMBM \_V\ O _,�I �S1R� � � BATHROOM CLOSEI{'�" THROOM ®lS1R� �p. _, . l ® , ��� fiy- F.n:�"'7 1 1 A —_mown ., I xEa. p Z_ rq' r ,�i� 11,'9.� MASTER�:EDROOM —u—� —i � ii 1. R' 1 ��Hiir hol-tJ AminIA HM- -E B 2a 111� In EHMIa ' J Project No. Scale: a Z Q 19002.00 I/8" = I'-0" o z a,lx Drawn By: Checked By: 0 0 i JSU1 JDR w z= MAIN LEVEL LOWER LEVEL0w0 MO.1 2.d w Q Quo Yage 4U of 46 AHJ Stamp FURNACES MARK CFM OA E.S.P.(IN.W.C.) HEATING CAP.(HIGH/LOW MBH) COOLING CAPACITY(Mk) ELECTRICAL AIR MANUFACTURER REMARKS CFM s EL. .1E00' INPUT 9 EL. OUTPUT S 1,900' SENSIBLE LATENT VOLT/PHASE FLA MOCP FILTER 4 MODEL NO. F-A-I 2250 1000 0.68 0.50 20/TS 89/55 SEE CC-A-I 115/I 12.5 20 MERV a YORK 2-STAGE BURNER,CONDENSATE NEUTRALIZER, CMUA) (EDH-A-2) TMSV120D20MP12C HIGH ALTITUDE KIT (aT,S00 FEET ELEVATION) F-B-I 1000 YORK 2-STAGE BURNER,CONDENSATE NEUTRALIZER, 2250 0.68 0.50 120/T8 59/55 SEE CC-B-1 115/1 12.5 20 MERV a �H= N (MUA) (EDH-B-2) TIMSV120D20MP12C HIGH ALTITUDE KIT (al,900 FEET ELEVATION) m EQUALS:CARRIER,LENNOX,YORKr4 LL' (V I Z w W CONDENSING UNITS � '� - 0 NOMINAL CLG NUMBER OF SATURATED OUTDOOR NOM. ELECTRICAL MANUFACTURER HOT GAS O CD O I- MARK SERVES REFRIG. 4 MODEL NO. BYPASS ACCESSORIES0 00 Z Ol O CAPACITY(TONS) STAGES SUCTION TEMP('F) TEMP('F) SEER VOLT/PHASE MCA MOCP YORK LOW AMBIENT OPERATION TO 35°F,COMPRESSOR START ASSIST CAPACITOR AND RELAY, • �— O CU-A-1 F-A-1 5 2 42 9O 15 R-410a 230/1 31.4 50 NO CRANKCASE HEATER,EVAPORATOR FREEZE THERMOSTAT,HARD SHUT-OFF TXV, X YFK60B2IS SUPPORT FEET ICl7 Q Q E YORK LOW AMBIENT OPERATION TO 35°F,COMPRESSOR START ASSIST CAPACITOR AND RELAY, Z CU-B-1 F-B-I 5 2 42 9O 15 R-410a 230/1 31.4 50 NO CRANKCASE HEATER,EVAPORATOR FREEZE THERMOSTAT,HARD SHUT-OFF TXV, E 'tt w YFK60B21S SUPPORT FEET W V EQUALS:CARRIER,LENNOX,TOW.. Z = ., o �tp z oi x O ELECTRIC DUCT NEATENS COOLING COILS (DX) W O to @ F o MARK SERVES ELECTRICAL MBH AIR SIDE MANUFACTURER SYM. DESCRIPTION CAPACITY ELECTRIC MANUF.4 MODEL REMARKS O EAT LAT FLOW DUCT VEL. 4 MODEL NO. ,,e\P (°F) ('F) (GPM/ (WA-0 (FPM) \" ,X( COOLING COIL 5 TONS NOMINAL YORK 0.30"E.S.P..2250 CFM �, Al w EDH-A-I ERv-A-I 5/I 6 g 41 TO 300 8/8 6T5 MARKEL GG-A-I 4a MBH SENSIBLE ?w 2 KW 5-I-HF-2KW-SW-SH PE stamp _i w 12°F EAT,4s°LAT C 60D 0 115/1 MARKEL I CC-B-1 COOLING COIL 5 TONS NOMINAL 48 MBH SENSIBLE YORK 0.3m^E.S.P. 2250 CFM UO ll 3 U EDH-B-1 ERv-B-1 6 8 41 10 300 6/6 6T5 -I2°F EAT,as°LAT CF60D =sp gam', m o 2 KW 115-1-HF-2KW-SW-SH ;,o`•y 1;i>F-.si^a'', F n 230/1 MARKEL ' 44e``8/30/19 '� w EDH-A-2 F-A-I(MUA) 15.0 -20 14 1000 14/12 851 a z1 22 KW 230-1-HF-22KW-14W-12H lit 15103 ; t 80 EDH-B-2 F-5-1(MUA) 15.0 -20 14 1000 14/12 851 Oc rr _i O 22 0KUJ 30-I-HF-22KW-14W-12H FANS 4 ERvS ' F +...-••r �= m 0 REMARKS 'ss`ONAIENG= Z w FAN Q- ¢ Ov O I-SINGLE PHASE SCR CONTROL,DIFFERENTIAL PRESSURE FAN INTERLOCK,DOOR INTERLOCK DISCONNECT SWITCH. MANUFACTURER Q� 0 0��' Q' N SYM. DESCRIPTION CFM SP a EL W/A/HP VOLT SONES 4 MODEL NO. v'� Sr` O�O� Ir 1',I OR' EQUALS:MARKEL,BERKO,MARLEY,TPI,INDEECO,THERMOLEC. O %J 0 O0 1�1 In BATH PANASONIC 11 m EF-1 62 0.25" 15 W 115/1 0.5 A I A I AIR DEVICES EXHAUST FV-08VQ5 .42 m o EF-2 GARAGE 251 0.25" 62 W 115/1 2.0 PANASONIC A I A 1 r SYM. USE MANUF. FRAME MODULE NECK FINISH ACC. REMARKS EXHAUST FV-30VQ3 Q d MODEL TYPE SIZE SIZE T E ERv-A-1 ENERGY RECOVERY 300 0.50,, 311 W 115/I -- RENEWAIRE B 3 B 1 O 3 z EXHAUST TITUS TYPE 4 RE: RE: BY AG-35B OBD WALL/CEILING VENTILATOR EV300 EG-1 SPRING LATCH LL 3 GRILLE CT-PP-0 1/4"BORDER PLANS PLANS ARCH FOR 3 WIDTHS ERV-B-1 ENERGY RECOVERY 300 0.50" 311 W 115/I -- RENEWAIRE B 3 B 1 Q o VENTILATOR2 RETURN TITUS TYPE 4 RE: RE: BY WALL/CEILING EV300 0= RG-1 -- SPRING LATCH GRILLE CT-PP-0 1/4"BORDER PLANS PLANS ARCH DAMPER: SUPPORT: DUCT CONNECTION: CONTROL: w' A. INTEGRAL GRAVITY I. RIGID SUPPORT A. RIGID I. RE:SEQUENCE SUPPLY TITUS TYPE 4 RE: RE: BY AG-35B OBD WALL/CEILING BACKDRAFT DAMPER 2. HANG UNIT WITH NEOPRENE B. FLEX DUCT r I O w Z SG-1 SPRING LATCH B. EXTERNAL GRAVITY ISOLATORS C. FLEXIBLE CANVAS DUCT w Q GRILLE CT-PP-0 1/4"BORDER PLANS PLANS ARCH FOR 3".WIDTHS W r z a BACKDRAFT DAMPER 3. HANG UNIT WITH SPRING CONNECTORS rl SUPPLY TITUS TYPE 6 RE: RE: BY AG-35B OBD FLOOR INSTALLED AT FAN VIBRATION ISOLATORS D. FANTECH FC CLAMPS O w SG-2 REMOVABLE CORE GRILLE CT-PP-3 NO FLANGE PLANS PLANS ARCH FOR 3".WIDTHS SO"DEFLECTION CC.. ONE MOTORIZED DAMPER r!, O U S= TRANSFER TITUS TYPE 4 RE: RE: BY WALL/CEILING W 7 O TG-1 -- SPRING LATCH EQUALS:GREENHECK,LOREN COOK,SOLER 4 PALAU,TWIN CITY,FANTECH,RENEWAIRE,VENMAR,PANASONIC. Imo--1 N GRILLE CT-PP-0 I/4"BORDER PLANS PLANS ARCH EXTERIOR RUSKIN RE: RE: BAKED 2"DEEP WTI .i LV-I STANDARD 3/4 DRAINABLE BLADES ,_ LOUVER ELF211D PLANS PLANS ENAMEL BIRDSCREEN GRD EQUALS:TITUS,KRUEGER,PRICE,AIR HORIZONS. N QI Vthi w LOUVER EQUALS:RUSKIN,GREENHECK,AMERICAN WARMING,NCA. SECTION 403.3.2.1 (ORD. 40) 5ALANCED VENTILATION CALCULATION w a Efi UNIT A: ((0.01 *4200 SF)+ [7°5*(4 BR's+1)])*0.75=60 CFM (ERV-A-1 PROVIDES 300 CFM) N m 0 >z UNIT B: ((0.01 *4200 SF)+ [7°5*(4 BR's+ 1)])*0.75=60 CFM (ERV-B-1 PROVIDES 300 CFM) a aS Issued For w d O No. Date Comment O I 5/14/15 COORDINATION 9 2 8/30/19 PERMIT H Q O 0 L O NQ o w d� MECHANICAL w It1 SCHEDULES 'gild z o z K ti w ‘)1)4:, Q a w www Project No. Scale: CY 4 Q 19002.00 N/A o 4 m Drawn By: Checked By: 9,i JSW JDR in)z= 4w)- M1.0 two Quo Page 41 of 48 AHJ Stamp ACCESSORIES PUMPS PO I L E IRS I-HIGH ALTITUDE KIT 4-NOT USED �J 2-ASME RATED(H-STAMP) 5-NOT USED 3-50%PROPYLENE GLYCOL 6-NOT USED .k 0 P 0" SYM. TYPE S.L.INPUT ALT OUTPUT FUEL DELTA e ELEC. MANUFACTURER EFF. ACCESSORIES SYM. GPM TDH H VOLT/PH MANUFACTURER DESCRIPTION �k7U Q4Z� �W� 2�¢ MBH MBH T QQ 4 MODEL (FT.) 8 MODEL NO. O h c'1'P 00 - WALL MOUNT115/I LOCHINvAR 1,2,5 NAT. B-I STAINLESS STEEL 110 103 309/ 95 0 F-I 8 1 1/25 15/I GRUNDFOS B-I BOILER A 2 A I CONDENSING GAS 2.1 A WHB (ION UPS 15-58 FC EQUALS,LOCHINVAR,IBC,TRIANGLE TUBE,WEIL-M%LAIN,BUDERUS,BURNHAM. OM N GRUNDFOS WH-I WATER HEATER O W P-2 14 14 I/6 115/I A 2 A I UPS 26-99 FC GRUNDFOS RADIANT HEATING WATER HEATERS N ( (n Z P-3 2 15 1/25 15/I A 2 A > W- w UPS 15-58 FC cq Aw GRUNDFOS SZ-I SNOWMELT ZONEralSYM. DESCRIPTION STORAGE RECOVERY DOMESTIC BOILER MANUF.4 MODEL REMARKSLe' ill CO z F-4 2 28 1/6 115/I A 3 A I (GALS) (GPH) CONDITIONS CONDITIONS ~ ^ UPS 26-99 FC p L ,0 0 O GRUNDFOS DOMESTIC HOT WATER INDIRECT-FIRED 100 DEG RISE 180 DEG LOCHINVAR 2 U 0RP-I 2 1.5 9 W 115/1 RECIRCULATION A 4 B I.2 WH-1 113 308 40°F EWT 14 GPM z UP 10-16 A PM BU/LC DOM.HEATING 140°F LWT 65 FT.P.D. SIT119 O \Q Z o CHECK VALVE: SPEED: MATERIAL: CONTROL, EQUALS:BUDERUS,LOCHINVAR,TRIANGLE TUBE,WEIL-McLAIN,14TP. . 0 .. 4 A. INTEGRAL CHECK VALVE I. 3-SPEED PUMP,OPERATE ON SPEED I A. CAST IRON 1. RE:SEQUENCE OF /� (r� B. EXTERNAL CHECK VALVE 2. 3-SPEED PUMP,OPERATE ON SPEED 2 B. BRONZE OPERATION ICL7 / Q Q IU_ C. NONE 3. 3-SPEED PUMP,OPERATE ON SPEED 3 2. A=AUTOMATIC4. ON/OFF ® G, ® ® G, 2 ���tt LL d 5. VARIABLE SPEED VIA INTEGRAL CONTROL AI I� 51-1 AI�ATO��✓ W V ° \ z 6. VARIABLE SPEED VIA TEKMAR CONTROL LU _ O SYM. SERVES RECOMMENDED GPM P.D. MANUF.4 MODEL REMARKS 112: CO 61 1� EQUALS,GRUNDFOS,WILO,TACO,BELL 4 GOSSETT. MAX GPM (FT.) Z O x r AS-I HEATING SYSTEM 10 VARIES I SPIROTHERM W 0 m V L CTRIC NEAT MATS wR 10 TI (1') ia 1r co Wa EQUALS:SPIROTHE M,TACO,BELL 8 GOSSETT,CALEFFI. O -- m i SYM. DESCRIPTION CAPACITY ELECTRIC MANUF.4 MODEL REMARKS ;"x>�`(111 I EXPANSION TANKS ui W ELECTRIC HEAT MAT 12 WATTS PER SF NUHEAT/PENTAIR FLOOR SENSOR 4 WALL MOUNTED 0, E1-1M-A-1a 96 SF ESTIMATED 115/1, 1152 W ELECTRIC HEAT SIGNATURE THERMOSTAT, PE Stamp A Z (MASTER BATH A) MATS UL LISTED FOR WET LOCATIONS �" m O 12 WATTS PER SF NUHEAT/PENTAIR RELAYS AS REQUIRED SYM. SERVES MOUNTING ACCEPT. TOTAL MANUF.4 MODEL REMARKS =oQ►AO L/C4,11 N F ELECTRIC HEAT MAT VOL.(GALS) VOL.(GALS) v �"""� ' oF EHM-A-lb 33 SF ESTIMATED 115/1,396 W ELECTRIC HEAT C,.�f'.l�`KF� O'li F n (MASTER BATH A SHOWER) MATS re 8/3W19i o ELECTRIC HEAT MAT 12 WATTS PER SF NUHEAT/PENTAIR FLOOR SENSOR 4 WALL MOUNTED FLEXCON S fW 0 g 2 mit 0 0 EHM-A-2a 30 SF ESTIMATED 115/I,360 W ELECTRIC HEAT SIGNATURE THERMOSTAT, ET-1 HEATING SYSTEM FIFE 2.5 4.5 HTX 30 i �t' rJ ' 4 d (BATH A) MATS UL LISTED FOR WET LOCATIONS, ELECTRIC HEAT MAT 12 WATTS PER SF NUHEAT/PENTAIR FLEXCON /I'O'�Ff+«•r'r.0_-. m 0 EHM-A-2b 21 SF ESTIMATED 115/I,252 W ELECTRIC HEAT ET-2 DOMESTIC SYSTEM FIFE 2.5 4.8 PH 12 S/UnAt�N= N 0 BATH A SHOWER) MATS ‘,,,,,,,,, z ELECTRIC HEAT MAT 12 WATTS PER SF NUHEAT/PENTAIR FLOOR SENSOR 4 WALL MOUNTED EQUALS:FLEXCON,AMTROL,TACO,WESSELS. EHM-B-la 96 SF ESTIMATED 115/1, 1152 W ELECTRIC HEAT SIGNATURE THERMOSTAT, 'O 0 (MASTER BATH B) MATS UL LISTED FOR WET LOCATIONS d ELECTRIC HEAT MAT 12 WATTS PER SF NUHEAT/PENTAIR RELAYS AS REQUIRED m EHM-B-lb 33 SF ESTIMATED 115/1,396 W ELECTRIC HEAT CONDENSATE NEUTRAL IZAT ION TUPE MASTER BATH B SHOWER) MATS 7 ii m ELECTRIC HEAT MAT 12 WATTS PER SF NUHEAT/PENTAIR FLOOR SENSOR 4 WALL MOUNTED F-I'1 EHM-5-2a 30 SF ESTIMATED 115/1,360 W ELECTRIC HEAT SIGNATURE THERMOSTAT, SYM. SERVES MAXIMUM MAXIMUM PIPE MANUF.4 MODEL REMARKS m O (BATH B) MATS UL LISTED FOR WET LOCATIONS, MBH GPH CONN.SIZE Q Z ELECTRIC HEAT MAT 12 WATTS PER SF NUHEAT/PENTAIR -Q EHM-5-2b 21 SF ESTIMATED 115/I,252 W ELECTRIC HEAT -(BATH B SHOWER) MATS ALL HEATING SYSTEMS AXIOM FINISH WITH I L CNT-I (PROVIDE(I)CNT AT EACH 400 1.6 3/4"NPT NEUTRALIZING MEDIA CD 3 Z FURNACE AND BOILER) NC-1 �L 3 EQUALS:AXIOM,SCHIER. _ J Z L LIFT STATION (DUPLEX GRINDER) RADIANT ZONE SCHEDULE (UNIT A) FQL]( i` 1 MARK ROOM(S) EFFECTIVE BTU/H BTU/H TUBE TOTAL #OF LOOP GPM/LOOP P.D. HEADER TUBING ^ O 0/N W Z SYM. DESCRIPTION COMPONENTS AREA(SF) PER SF CENTERS LENGTH LOOPS LENGTHS (ET) SIZE SIZE fTl r 1 Z Q RZ-A-I MEDIA,BATH 007,LAUNDRY 685 8500 I2 9 913 4 228 0.2 0.9 3/4" I/2" `u' IOI d kl - RZ-A-2 BED 004,BATH 006 277 3800 14 9 369 2 185 0.2 0.6 3/4" 1/2" O Z W PUMPS: (2)1,1503 VERTICAL DISCHARGE GRINDER PUMPS WITH STAINLESS STEEL CUTTER, T \ W N 115 VOLT,SINGLE PHASE,1.0 AMPS,18 GPM g 22 FEET TDH,1/2 HP. RZ-A-3 SUNK ROOM,BATH O 352 5200 15 9 469 2 235 0.3 1.3 3/4" /2" `/ W= TOTALS 1314 17500 13 1752 8 235 1.3 Ir T1, r CONTROL PANEL: (I)(PM 10-1035)NEMA I ELECTRICAL ALTERNATOR CONTROL PANEL FOR NOTES: ^` �j N DUPLEX INSTALLATIONS WITH OPTIONAL DRY AUXILIARY CONTACT FOR ALARM SEE MECHANICAL ZONING PLANS FOR DETAILED ZONE LAYOUTS. C J IL( Q F INDOOR OUTPUT. `/ rT, W LIFT STATION U.N.O.ZONES INCLUDE ASSOCIATED BATHS,CLOSETS*HALLS. I^.L.(� J LS-I FLOAT SWITCHES: (1)THREE SWITCHES AND WEIGHTS h�l Q, (SPEC BASED N '^ ON ZOELLER) JUNCTION BOX: (V JUNCTION BOX TYPE 4x FOR DUPLEX �v/l• BASIN.COVER.ETC: (I)30.0 x 60"DEEP SOLID FIBERGLASS BASIN WITH STEEL COVER, �1 1,6 W ANTI-FLOTATION DEVICE,1-1/2"VENT,1-1/2"DISCNARGE,FURNISHED WITH NO HOLES RADIANT ZONE SCHEDULE (UNIT B) l� z$ DRILLED,BALL AND CHECK VALVES(P/N 30-0100),AND PIPE SEALS MARK ROOM(S) EFFECTIVE BTU/H BTU/H GPM TUBE TOTAL #OF LOOP GPM/LOOP P.D. HEADER TUBING W 5) AREA(SF) PER SF CENTERS LENGTH LOOPS LENGTHS (FT) SIZE SIZE W Q. EQUALS,ZOELLER,STANCOR,LIBERTY PUMPS. KZ-B-I MEDIA,BATH 006,LAUNDRY 727 8600 12 1.0 9 969 4 242 0.2 0.9 3/4. 1/2" ,^ }2 RZ-B-2 BED 00I,BATH 003 243 3800 1 6 0.4 9 324 2 I 62 0.2 0.5 3/4" 1/2" V / m O RZ-B-3 BUNK ROOM,BATH 011 352 5300 15 0.6 9 469 2 235 0.3 1.3 3/4" 1/2" ^l SNOWMELT ZONE SCHEDULE (UNIT A) TOTALS 1322 17700 13 2.0 1763 8 242 1.3 O NOTES: (1- ZONE DESCRIPTION EFFECTIVE BTU/H BTU/H GPM TUBE TOTAL #OF LOOP GPM/LOOP P.D. MANIFOLD TUBING SEE MECHANICAL ZONING PLANS FOR DETAILED ZONE LAYOUTS. IL A AREA(SF) PER SF CENTERS LENGTH LOOPS LENGTHS (FT) SIZE SIZE U.N.O.ZONES INCLUDE ASSOCIATED BATHS,CLOSETS 4 HALLS. 4 D SZ-A-I a GARAGE APRON 86 1 25 10750 0.8 9 1 1 5 1 1 25 0.8 1.7 3/4" 5/8" Issued For Z U- SZ-A-I b ENTRY WALKWAY 132 1 25 16500 _ 1.3 9 176 1 186 1.3 5.3 3/4" 5/8" 111 r O TOTALS 218 27250 2.1 291 -Q,O No. Date Comment I 5/14/15 COORDINATION B 9 2 8/30/19 PERMIT ,Q O o SNOWMELT ZONE SCHEDULE (UNIT B) 3 N 0 ZONE DESCRIPTION EFFECTIVE BTU/H ETU/1-1 GPM TUBE TOTAL #OF LOOP GPM/LOOP P.D. MANIFOLD TUBING Z Ti AREA(SE) PER SE CENTERS LENGTH LOOPS LENGTHS (ET) SIZE SIZE Q W SZ-B-I GARAGE APRON,ENTRY 236 I 25 29500 2.2 9 31 5 2 167 3.9 3/4" 5/8" MECHANICAL W I~U TOTALS 236 29500 2.2 315 4) > SCHEDULES 'gill z o z K_IW oiz Q a w to . Project No. Scale: CY Z wl Q 19002.00 N/A o d m Drawn By: Checked By: 0 z�0 JSU) JDR w z= M1.1 Qiio Page 42 of 48 AHJ Stamp T 2 T T T 6 7 8 9 0 IZE 0 Lit' llJ N I til ral vl uj oP ul I- I O p w- cnUl- L 0 , 0o \4Z' o 2 • > M —I ICE ° z J /6m \ �6/615 1 11 I 151:0z X i O I- _ w 6/6 EG-I l5 J -� m II "m 9 X m w 1 ovine r- BATHROA OM CLOSET o ROUGH-IN FOR BUNK ROOM Pe stamp , 1r , FUTURE s 11 O HUMIDIFIER O10-A Ilghi N F 012 B1 011 B1 ME- CIA i-ct-t,irli:e...:4: r>Fy'�'c' 7'CLOSET BATHROOM ECTON of oCTERTICAL11 1 /19 4BUNK ROOM ,u` \ 2m{ oI I r�i' Ls-I I0 0 010-B 3"m BOILER AND 4"m FURNACE FLUE AND I "A"... r... ' :OCA PIPES.SLOPE MINIMUM 1/4"PER LF 1,I1111,en1! .c t1_ _ r---- - SACK TO BOILER AND FURNACE. I f I �� p_�I` .'f,s UMAI ENG\' m w }^� U A 3"m BOILER AND 4"m FURNACE FLUE TERMINATE ABOVE ROOF.INSTALL PER _ - t`vk..., I AND GA PIPES.SLOPE MINIMUM I/4" MANUFACTURER'S REQUIREMENTS. �y� 1 °e;�� \ CONNECT 14/12(UNLINED, cD O PER LF BACK TO BOILER AND L46ND --- 'IS'GI_ \ ;'i•V AM NLENUM S ALLEPERRMANUFACTINATE BURER'S OOF. 8"m OA P'WRAP) 1 01 0 78-A n e O DER A)TORETURN RNA EPWRAP W I 8"m(TYP OF 3) WITH I"OF DUCT WRAP. REQUIREMENTS. O ' LL RE:SPECS. }tili ft uv ‘44, I 7 12/10 TG-I xFER 5°m Z LS-I (TYP OF 2).HIGH IN LAUNDRY, , p LOW IN MEDIA ROOM. �� INSTALL EDH-A-2 IN CI 1115 I VERTICAL SECTION OF �I ,r INSTALL UL 705 LISTED DRYER ,11��M�__..-. �� DUCT. Q Il�: fo..� =L BOOSTER FAN AND SECONDARY LINT - 3 INSTALL MOD IN TRAP IF REQUIRED FOR DRYER 24/1 RA VERTICAL EXHAUST, RL��l• ••y` �� �� O2 Q Q SECTION OF DUCT. - — i _ JHF-A-I 1 GC-A-I. ],1 eta Q - - ,pQ .4 0PROVIDE _� ] �� P 4-' `twO FROUGH-IN FOR frir I _:A - ^ 6/6 EG-I l5 O LL7wFUTURE - ' .- v B l'i, r� O <liHUMIDIFIER. _ a Ali ► i� - v_ w Qr �� W Rv-B- ��;-' i I' I- i i . STORAGE W zINSVERTICALTALL H B 2 ED[AY CE� ■� ,LI_ J _!IiIA .JIr _ 001 O OWsecnoN of Ducr MIL:1 ;1 a m BEDROOM CLOSET U 8"m EA w=./„., railiMAI o MEDIA r+a� e w E.-Alia' illf:7- 005 B -=__ .n+ a,m IIII FM � a Fara • I i I C4 V,_ NI thi.ci Ail "NEWIN 1!! I. °,co- B II'1 MT=�' ERV-A-I A STAIR z o p ro , ���10 RA ;� ;� �: L�I ar.!! . 9 B �!�]l! I_ - � r�► .I� S��m OA I l �m � 1i -III Aw wfi ZaIm =_r F-B-Ic 1 007-B l�l�l9 -. _ L 'p�p,�'�� � '!y ,/� , 2 II e • ■ - - ® ® �) `.; `ll `'■rn'il�l�il���'_Uliir l■/ 10/I0 F-A-Id_ MEDIA _I N }ii-___I=Epouminnwrici m— Imom m - rai - - - 0 0� O W E `��`= 006—A r® �� r'sa i f O--- '• IS/6 SG-1 300 H III II _' - II 1 Issued For Z in a m �1 �I__1 ,, ww. 6/6 EG-I l5 ` ' ___ -rim _ wl L No. Date Comment l"m ��I j ��� 8/14/15 COORDINATION 3 Q mow A_ I ��I I 2 8/30/IS PERMIT 10/10 FC-B-Io diaMMar _ 1 1 '/��146"e ` - - - - °o INSTALL UL 105 LISTED �v/� l _ '� 3 L DRYER BOOSTER FAN fu='l -.L Z 8 AND SECONDARY LINT TRAP IF REQUIRED FORiT_F DRYER EXHAUST. , - - - - - - - - LOWER LEVEL wI MECHANICAL PLAN iu 4"m DRYER EA 8"m OA(I"WRAP) =4 Z ) (TYP OF 2) O z � 47tw MEDIA 24/8(UNLINED,OA).WRAP WITH 12/10 TG-I XFER Z N t? I"OF DUCT WRAP.RE:SPECS. (TYP OF 2),HIGH IN I O LAUNDRY,LOWIN m(Y MEDIA ROOM,. NORTH >w w Project No. Scale: CY Z I 24/10(UNLINED,OA)UP.WRAP R'- WITH I.OF DUCT WRAP.RE: 19002 00 1/4" = v-0" O U' m IY SPECS. Drawn By: Checked By: '2'Z(0 Jell.) JDR w z= Q w K M2.0 .Wo Qiio Page 43 of 48 AHJ Stamp T 2 3 4 T 6 7 8 9 0 141- ( ,, W lL I Z kn I I I I rai - op Lu 1- I ' re O p w- cnUr LT gl 2 „0 \4 � o} q > X ro w 4 4 w 20/6(UNLINED,RA)UP. Kit' Z (IMP OF 2) EF_2 cc W V - \ . f EF02 z = _ = Ir— iI II II II II - - - '- - i -,-1 • - _ 1:11:z X r O O ill F EF_2 0m `t EF02 `DO _ W 20/6(UNLINED,RA)UP. • (TYP OF 2) W r � / I GARAGE X 6' ZW 111 A El PE stamp _i 16/14 RA DOWN S Z '- _-`stDO 11U i1 f0 U -e /301199dy'. r U --- _--1 I A%>F1 Q�rr U GARAGE _ 12/6 SCs-2 15 12/5(UNLINED) ' (17;14;48 =� U7 / 1110-B - WALL STACK. w I5,{�,0r2 -�i a L (IMP) + + 'i�'$,.j !•P0-; -IX 3'0 BOILER AND 4"d FURNACE FLUE AND Q �, `D,�E<:,.,"III"�ENG---\�V-_ m Q L CA PIPES.SLOPE MINIMUM I/4"PER LF } 24/8(UNLINED,OA)DOWN. yt`UBAL`_ Z w „ 3"0 BOILER AND 4°m FURNACE FLUE AND BACK TO BOILER AND FURNACE. WRAP WITH I"OF DUCT o rr CA PIPES.SLOPE MINIMUM 1/4"PER LF TERMINATE ABOVE ROOF.INSTALL PER WRAP.RE:SPECS. d p BACK TO BOILER AND FURNACE. MANUFACTURER'S REQUIREMENTS. - A W 0 • TERMINATE ABOVE ROOF.INSTALL PER _ IL MANUFACTURER'S REQUIREMENTS. 28/6 RG-I RA , I _L v 12/6 SG-2 115 �•L� 0 IS/12 LV-I EA(HIGH)"MAINTAIN 3' / /_ g��� 1 24/24 Lv-I OA(LOW) m 1 II��-��11 MINIMUM VERTICAL SEPARATION. * f I�(1,000 GFM) L BETWEEN EXHAUST AND INTAKE IB/12 Lv-I OA(LOW) ` 12/6 SC-I-I 25 a m 7 AND 18/12 Lv-I-I EA _ UP�ll Q OZ LOUVERS. (HIGH).MAINTAIN 3' �1 ❑ MINIMUM VERTICAL R C f� •OOM / W E _ SEPARATION. ^ I5Y - - [WA - 12/6 5G-2 25 y I1i : 1-A Z UP �_� • _ Milr 109-s J o 2 a o _ Z 4 HALLWAY UP } 0 2 o N — IF F-\ / \ / fG 4.4 DRYER EA O NT ~ 1��ill 2� FRONT ENT" �/ �/ �c 4"mDRYEREA �� EN � WQ cuB1 I� �ZtT�Zrs .r� —�� 11 B 0 • 01 A - W [� ?a ALLWAY —. 28/6 R i-1 RA . O O W �.—.—.—.—. I FFFTtiti�I I,12/6 5Cs-2 40 108-B P ri nc�T - MASTER EF 01 03 LLL O 1 - W ul LT 0000 2/6 RG-I RAC CLOSET( — SET ® UP DN z N o 1_ EF 01 01 - ML—� 12/6 SG-1 30f - pEF O 102 — 1 o3-A - U W Q 14ir 711, Z I II . 'I = Olo - [DR0 WDR00M W'12/6 SG-2 1452/6 SG-2 110 • ZwuP DN 02-B, EFO103 Q MASTERU�" EF0101 02 A odzO 111 11 EF 1 " BATHs70M THR00 SAIRw Y EF- c F-I R w 8- iLI_ 3ATHROOM l- ; � 10 A: �Ilux At4"•BATHEA wMASTER BEDOOM I� Qi' iN W)4 Bpi !!" I A }o -� m LO��T L 'STER �4 m n ' 13 a� N >o lini 06 '] t s — :4THROOM IRi. 0 6} _ 3 ° } 8U } 5 6 } - a i _ — B W W ��' � II MASTER BEDROOM o u .. a wm .r �w I_i I T �1��I Q S ' y _� • 106� Issued For Z d 1 1 11 Q Q °\" m m No. Date Comment I 1 -ME_ � O ` �= m } 1 (( ' li ,U' c 8/14/19 COORDINATION Q v v -L m I 12/6 SG-2 60 I 2 5/30/IS PERMIT ,1 o ''''')::- 12/6N 3� SC-2 145 ++ + + } 12/6 SG-2 150. (IN MASTER FLOOR) Q 3^^ 12/6 SG-2 50 3 CENTER ON WINDOW.GRILLE SHOWN OFFSET FOR CLARITY. Z O 12/5(UNLINED) u 4' (TYP OF 2) _ (TY(TYPE)STACK. s e 4 MAIN LEVEL NI 0 `^ =w U ARCHITECT TO COORDINATE INSTALLATION OF MECHANICAL PLAN 12/6 SG-2 25 ' CONDENSING UNITS TO ENSURE NOISE LEVEL AT N z PROPERTY LINE MEETS CITY OF ASPEN'S REQUIREMENTS.ACOUSTICAL MATERIAL MAY O Z 4"•DRYER EA NEED TO BE INSTALLED TO REDUCE K I-w (TYP OF 2) CONDENSING UNIT NOISE LEVELS. 24/10(UNLINED,OA) I I Z N z DOWN.WRAP WITH I" TERMINATE EXHAUSTS MINIMUM 3' t? OF DUCT WRAP.RE: ABOVE INTAKE LOUVER AND 3' MAINTAIN 3'MINIMUM SEPARATION FROM Q a w SPECS. FROM OPERABLE OPENINGS INTO EXHAUST TERMINATIONS TO OPERABLE NORTH >L.v THE BUILDING. OPENINGS INTO THE BUILDING.(TYP) 0 U w Project No. Scale: Z,9 19 02.00 I/4" = 1'-0" o a m Drawn By: Checked By: 0 i JSUJ JDR w z= M2.1 Q.0 Page 44 of 48 AHJ Stamp T 2 T T T 6 7 8 9 0 r4 E 0 in W N , in til I I WVI �▪ w W in F I- I O p w- CD 0 I— L 0 . .0o \4ZO o > X ICz -I4 LPL i W W = S Q rz? X6' iT W 0 r WillIWI—mmilliglilliblIft....._ 20/6(UNLINED,RA)DOWN. N4 CO � T(TYP OF 2) l!-1 Elk t W I II II n DN 20/12 RG-1 RA y" 7 % —20/I2 f2G-1 RA :X( in zw PE Stamp _i N 5 4 oA►.uo uc ,,, m o v =,�12/ 150 12/6 5G-2 150f, �Vif 3..f>F�.'rf�',I' F a .411rU �44T�8/30/199d'Y{ ' O O 5 p �. r 0 4"'IJ�,Q(VpQ��I L — - �I——T + (D FURNACEIEFLUENDANDmCA d Q PIPES.SLOPE MINIMUM `�0 OLIVING I/4"PER LF BACK TO - IL(Cr_ _ _ _ BOILER AND FURNACE. w O in cv— 204-A r -.- TERMINATE ABOVE ROOF.- • 2 = INSTALL PER 11 m I t 20/6(UNLINED,RA)DOWN. 3 MANUFACTURER'S Z 3 + (TYP OF 2) 6 REQUIREMENTS. 1115 ,�12/6 SG-2 I15 �7 ,�12/6 SG-2 142 12/6 SG-2 142 f, Q Z 5Q - _ 12/6 5G-2 30 1 12/6 5G-2 30 1 T L ri _ _ _ _ _ _—J O .,Z 204 B r1 3"m BOILER AND 4"4 FURNACE FLUE AND �� 'PHWllERd 1 , 4 A9 Q Q `J CA PIPES. OILER AND FU NA PER LF I ry 201-A p�9�_ 2 Q; F IN 1 BACK TO BOILER AND FURNACE. IUI(-�4"m + ,] �2J O I 111 TERMINATE ABOVE ROOF.INSTALL PER t 1�1 �� MANUFACTURER'S REQUIREMENTS. DININ I 7 az N — 1 EF O 1 04 O w �I 12/6 SG-2 200 W Zli — ,�1z/6sG-2115 IWDER z/6SG2z00f1 O ii— EFO104 •••• Ir, ' - I DN U Z Q o cv = . W/� W 11 '�12/6 SG-2 16l 1 Ir Ir n ' °� - ^� vl V)- 12/6 SG-2 200f } 8 KITCHEN IS�TnApAIR I Q►J)� W a ' S L - ,�12/6 SG-2 200 L 0 I- = — W N - I- -- n1 - ,,^^ }2 , 1 I T. I 0 i _ - N Qz v }a I � STAIR -- `q KITCHEN_ EMI II u ` cT i;`.-f II p II a D 71 I s I20-B _ _ _ _ _ _ _ _ I Issued For w d 12/6 SG-2 p16l N - - Q,O , � No. Date Comment t 203-B t 8 1' I II II= I 5/14/1S COORDINATION B Q MI 2 8/30/19 PERMIT J I ICI I I I I .I II I I - - - - r - - - - - O O M E L —_ QO 4 w II UPPER LEVEL w MECHANICAL PLAN w fy u ION,KITCHEN EA. r▪w z TERMINATE ABOVE ROOF 0 WITH WEATHERPROOF EO Z CAP, K}� w ION,KITCHEN EA.TERMINATE ABOVE ROOF WITH WEATHERPROOF CAP. t ,Nj, Q a w NORTH >m te w w Project No. Scale: CY CY Z I Q 19002.00 I/4' = 1'-0" p,z 1, m Drawn By: Checked By: 0 i JSU1 JDR w z= M2.2 Page 45 of 48 AHJ Stamp FOR THICKNESS LATION REFER j/ OENGFORBAuNTRACTOR s SHALL ,,q,, TO SPECS MAXIMUM FRICTION TO RADIANT ZONES -HANGER ROD RATE OF 4'PRESSURE '!a"MANIFOLD DROP PER 100'OF P/T TEST PORT PIPING,(TYP) _ _ _ ISOLATION VALVE CIRCUIT SETTER BALANCE TO FLOW SHOWN IN RADIANT ZONE CHECK VALVE LOCATE ON SCHEDULE. �DGW� ,FROM WATER DISCHARGE SIDE O PUMP IF DOMESTIC ENTRY —� WATER PIPING �DHW _ — — — N w N PUMP IS NOT EQUIPPED WITH TO UNIT �DHR I®1 J ~� al104 m INTEGRAL CHECK VALVE) RP I 3,,,, w N i w MASTIC N o.: in in S LO w JOINTS TO CUT INSULATION - <, m _ 1 LA (q Tr w VAPOR ROVIDEIGHT TO PROPER LOCATE CONTROL VALVES ON 0 1 ral N LENGTH TO RETURN PIPE IN MECH ROOM, N N N 0 ® 0 . 0 0 O SEAL. INCLUDE ISOLATION VALVES.SIZE w_ (n 0 1— LT_ INCLUDE 10 EQUIVALENT PIPE CONTROL VALVE FOR MAXIMUM 3' 0/ COMPRESSION PRESSURE DROP.(TYP) O O O DIAMETERS OF STRAIGHT PIPE AT PUMP B-I 0 Z '' O INLET 4 OUTLET.CHECK VALVE TO BE0 OF INSULATION. INSTALLED MINIMUM 6 PIPE DIAMETERS L O FROM PUMP OUTLET,IF APPLICABLE. • (TYP OF ALL PUMPS). .Q X i DUCT WRAPPING fi�� CAL NLINE �Efi OfiOw , >p, Cz W SCHEMATIC FL1"F pEfiAIL OZ W NOT TO SCALE © NO SCALE © O©,2 nl 14' Z = o 0�® r®� ,,n�� pc.z 10 X o 6) P-2 I'" ‘,c) 0 a) F INSTALL PEX TUBING. sp 3j^ ® '� PER MANUFACTURER'S a ElieRECOMMENDATIONS. LOOPS SHALL i.: Am BE EQUIVALENT LENGTHS. O (t 5%OF EACH OTHER) �® o IL AS-I SHUT-OFF VALVE,TYP. 411- T TS-I 61 WH-I �- z w Sin" HWS I 9 I" PE Stamp 0 m MANUFACTURER'S MANIFOLD. WM III ...."�,� 3 Z COORDINATE LOCATION WITH HU1R N.O. I" TT 2 __`O�.wOwL/.y�1'��1' 10 O GENERAL CONTRACTOR,TYP. ' sq�� ,�Of y�,yF9�`i"°'� F AIR VENT U HIGH POINT ; O rQF8/30/19 d'ti1 ', O O fa x� i f Q. SHUT-OFF VALVES. HOSE BIB— — (W S P2 �" i a E — HWS—e SEE BOILER PIPING SCHEMATIC °- (TYP) „— TEES.CLOSELY SPACED _ ___- 1�,�•0;,F j'�' ,4.4-r m 0 y FOR CONTINUATION.EACH ZONE STAINLESS STEEL --- •'�s4sIWO---- N w HWR—Z TO HAVE DEDICATED RETURN ® WELL(TYP). GNT- --- h,,",,„= O PIPE THAT IS HOME-RUN BACK TO MECH RPM,SUPPLY CAN BE TIED TO — -- --� N p BALANCING VALVES INTEGRAL COMMON SUPPLY PIPE OR HOME-RUN. , 0 TO MANIFOLD WITH INTEGRAL FLOW rT, 0_ METERFOR EACH LOOP.BALANCE TO GPM/LOOP PIPE DOWN TO FLOOR 0 fr SHOWNH IN//RADIIAANT ZONE SAND ISNOWMELT ZONE SCHEDULES,SHEET MI.I SCHEMATIC ROUTE BOILER CONDENSATE DRAIN a TERMINATE WITH }w RAD I HN / SI VOUJ MELT AN I OL J J //�� V /� THROUGH CONDENSATE 0 10 O RING Ls ''c fi I Ls NEUTRALIZATION TUBE PRIOR AIR GAP PER CODE(TYP). F NO SCALE �(/��� TO DISCHARGE INTO FLOOR 01 O \J NO SCALE DRAIN WITH AIR GAP. ® ���111 5a SEALANT ALL SIDES PLACE FASTENERS CONCRETE SLAB.MIN 3/4" O 2 Z PLENUM DUCT SHALL EXTEND EXTERIOR WALL �j EAR THE PIPEDOES NOT FROM CONCRETE OFEPI)PEE O /►/ Q THROUGH THE WALL AND,FORw THE BOTTOM AND SIDES,SHALL FLOAT IN THE SLAB. a - BE FLUSH WITH THE OUTER MORE MAY BE REQUIRED SURFACE OF SLAB. 2 LOUVER WITH SPRING VIBRATION- N SURFACE OF THE WALLrAl ISOLATOR(TYP.) IF PIPE RISES.ENSURE O= DRAWABLE BLADES ' F_A //\\RA BENDS ARE SECURED. r 11 N EXTENDED SILL ��� �' r1 BIRD SCREEN OA TO SPACE —7 \ Liu EA FROM SPACE w O w Q ""*,....P. 1 �I � EA TO OUTSIDE �®®®•� EI —, \ / 'E� OA FROM OUTSIDE I '\��� ° O W'WDUCTS IRE:PLANE) ������' EA BOA ' ���IIIIIIIO U w ri1 TAP HIGH ON PLENUM. ���� '''° W N ORIGID ROUND DUCT CTYP.) 4, j11 1 d ____— _1ACOUSTICAL ROUND FLEX40, ENLARGEMENT CNI wN PLANS,12"MINIMUM DUCTING CTYP.) WIRE MESH ` VDEPTH.PLENUM WITH INSULATION PER SPECS Z w DRILL WEEP HOLES IN THE - �'1 BOTTOM FRAME OF THE SHALL BE UNLINED (4"MIINIMUM- COMPACT SUBBASE d AND WRAPPED PER BACKDRAFT DAMPER ON VAPOR BARRIER w OQ, EXHAUST DISCHARGE LOUVER FOR DRAINAGE SPECS. BAGKDRAFT DAMPER ON OA (243 =0- SEAL LOUVER PLENUM INTAKE. 5/S"PEX TUBING.KEEP 'w WATERTIGHT WITH SOLDER SLOPE 2"PER ENERGY TRANSFER CORE TUBING 6"AWAY FROM / )-F OR 100 YEAR MASTIC LINEAR FOOT FOR HEAT AND HUMIDITY FLEXIBLE CANVAS DUCT S�+ WALLS. V / 01 O RECOVERY CONNECTORS OR EQUAL �� JLA� ON GRADE ^l Q LOUVER INSTALLATION DETAIL SEE ENLARGEMENT ERV INSTALLATION DETAIL SNOJJMELT TUEING INSTALLATION SCHEMATIC OH NO SCALE © NO SCALE O NO SCALE © v.- aw Issued For W d UNLINED PLENUM BOX WORM-DRIVE NOTE: PIN SPACING MUST DUCT No. Date Comment ,00 PAINTED FLAT BLACK INSIDE STAINLESS STEEL CONFORM TO LINER MTR'S ? 5/14/IS COORDINATION Li a 1 CLAMP CRITERIA FOR DUCT LINER 2 8/30/IS PERMIT ,n a ACOUSTICAL Imo\\� i�/� TYPE AND VELOCITY p� _ 0 o FLEXIBLE DUCTWORK i FULLY EXTENDED 1 \ SPECIFIED. INCLUDE MFTR'S ,i�iiz Xxxxxxii i4 7 ii. i"� I ® INSTALLATION CRITERIA IN ,�/ N O (SEE SPECS FOR MAX \ ( i Q l� 3" 4 MIN LENGTHS) \ SUBMITTAL DATA. MAX12" % j U OOO i r—— w WORM-DRIVE ,�/ STAINLESS STEEL 3� MECHANICAL w-u CLAMP — — SPIN-IN DUCT ACOUSTICAL CLIPS CTYP) SCHEMATICS =w z FITTING WITH FLEXIBLE DUCTWORK o uN�J,- SPIN-IN DUCT BALANCE DAMPER FULLY EXTENDED / OIL'z FITTING WITH WHEN ACCESSIBLE (SEE SPECS FOR MAX ` / K} BALANCE DAMPER 8 MN LENGTHS) ,.j Z N Z PINS (TYP) ` MAX 12" �// SPOT WELDED TO TYP O uy1 ? I' ACOUSTICALLY LINED 3 .. 4 NOT MORE THAN a Z 1 N 1 DUCTWORK / Q w PLENUM Box �/ 3" FROM EDGE x //// OF LINER o u o I z' ® ��/ Project No. Scale: Q,Z Q �� LINING REFER SPECS 19002.00 N/A O L i ALL ENDS OF LINER Drawn B: checked By: e TO BE TREATED W/ y 9 a w n ADHESIVE. JSW JDR w z= FLOOR DIFFUSER CONNECTION SCHEMATIC DIFFUSER CONNECTION SCHEMATIC TYPICAL- DUCT LINER SCHEMATIC W)1 ^ Q NO SCALE © NO SCALE O NO SCALE O /�3•O u w 0 ��/� u arc0 Page 46 of 48 Mechanical Specifications A"J Stamp General 35.Waste lines above ground-Standard weight,C.I.soil pipe,and fittings,or hubless,C.I.soil pipe and fittings.Up through 2-1/2"maybe standard 75.All thermostats shall have a temperature range suitable for the application and have adjustable set points.The thermostats shall be able to display weight,galvanized steel pipe with black,C.I.drainage fittings. temperature setpoint and room temperature.All thermostats shall be approved by the Owner. 1. Immediately notify the Engineer of any discrepancies. 36.Waste lines below grade and in crawl space and all Vent lines for residential may be Schedule 40 ABS-DWV plastic pipe and fittings(ASTM 76.Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 CFM,in the return duct or plenum upstream of any 2. It shall be assumed that all subcontractors are experienced and thoroughly knowledgeable in their respective areas of the construction industry and D2661)or Schedule 40 PVC-DWV plastic pipe and fittings(ASTM D2665).All pipe and fittings shall bear NFS-DW V mark and shall be joined filters,exhaust air connections or outdoor air connections.Installation shall comply with NFPA 72 and Section 606 of the 2015 IMC.Upon shall perform in a responsible manner in an appropriate construction sequence. with solvent weld joints as recommended by the manufacturer. detection of smoke,fan shall automatically shut down. 3. Do not scale drawings.Verify dimensions in field prior to commencement of work. 37.Heating Water piping-Piping may be type'K'copper for all buried lines using wrought copper fittings and I100F solder.For non-buried piping, 77.See Sequence of Operation for additional control information. type'L'copper,wrought copper fittings,and no lead solder.All buried pipe shall be surrounded with 4"of clean sand.Provide alternate price for A M_ CA 4. It is the intent of these drawings and specifications to establish a standard of quality.The Engineer reserves the right to take exceptions to approve PEX tubing(with oxygen diffusion barrier).Unless otherwise noted,piping on plans has been sized for copper,and if PEX piping is used,increase Balancing �•/ CAM V methods and materials not reflected herein. size of piping one nominal size from size shown on plans.ie.Plans call for V piping&PEX is to be substituted,a I"PEX line shall be installed. 104 E 0w 78.Air and water flows must be balanced,and fan belts,pumps,and drive systems adjusted as required.Balance Contractor shall furnish subsequent air w r z 5. Failure to order,or release order,for materials and/or equipment will not be accepted as a reason to substitute alternate materials,equipment,or 38.PEX piping shall be supported by continuous cradles supplied by the manufacturer. balances after acceptance of the building. N � 1A z installation methods. > in '� w 39.Drain Pan piping-Not Buried:Type'M'copper,wrought copper fittings,and no lead solder.-Buried:Type'L'copper,wrought copper fittings, 79.Submit a written balance report.Balancing procedures shall be in accordance with NEBB or AABC guidelines for proportional balance.Submit ✓t u 00 w 6. Work shall be performed in a workmanlike manner to the satisfaction of the Architect&the Engineer. and no lead solder.All buried pipe shall be surrounded with 4"of clean sand.Drain pan piping may also be PEX or Schedule 40 ABS-DW V plastic report on standard NEBB forms. I- I- • ", pipe and fittings(ASTM D2661)or Schedule 40 PVC-DWV plastic pipe and fittings(ASTM D2665). ral O - Q 7. Labor,materials,and equipment shall conform to the latest applicable editions of local,State of Colorado,and National Codes and ordinances.If 80.Airside measurements shall include all motor amperage,voltage readings,motor RPM,fan RPM,fan CFM,fan inlet static pressure,fan outlet static Iy U I- V conflict between those publications exists,the most stringent requirement shall apply. 40.Condensing Boiler Condensate shall be neutralized via a neutralization basin before discharge into building drainage system.Condensate piping pressure,and inlet and outlet grille CFM. M 261 Z shall be PVC or other approved material suitable for pH levels of 3. 0 ,Q Z "' O 8. Provide record drawings to architect.Drawings shall include all addendum items,change orders,alterations,re-routings,etc. 81.Hydronic measurements shall include circuit setters,all motor amperage,voltage readings,motor RPM,pump RPM,pump GPM as calculated from V O , 41.Refrigeration Piping-Type'L',ACR Grade copper,cleaned,dehydrated,capped and charged with clean nitrogen at the factory.Use wrought the pump curve,inlet and outlet pressures at pumps,and temperature and pressure drop at all coils. • )- 9. The drawings show the intent of the mechanical systems but do not show all details required.It is the responsibility of the Contractors to install copper fittings and hard solder having a minimum melting point of 1100F for buried lines,no lead solder for non-buried lines.Valves and 10:ID <[ N. X k complete&operable systems,which conform to the manufacturers'installations instructions&industry standards. specialties shall be standard brass or bronze valves for refrigeration service.Buried pipe shall be surrounded by 4"clean sand. 82.Adjust flows to within 10%of required quantity.If actual quantity is less than 90%of design,investigate cause,attempt to rectify and notify 2 l�L d Engineer.Submittal of balance report with less than required flows without explanation is cause for rejection of report. j Z 10.Systems shall be tested for proper operation.If tests show work is defective,Contractor shall make corrections necessary at no cost to Owner. 42.Gas Piping-Schedule 40 black steel pipe,150 lb.malleable iron screwed fittings on above ground pipe,welded fittings with all piping coated and CC W � 0 \ w wrapped on buried pipe.CSST pipe is permitted for final connections only. 83.Submit three copies of all submittals in addition to any required by the Contractor.These copies shall be retained by the Owner,Contractor and - C) I1.It is the Contractors'and manufacturers'responsibility to assure themselves that the code authorities will approve any product to be installed on the Engineer. ZW 112:_ project. 43.Gas Valves-Lubricated plug valve 175 lb.W.O.G.iron screwed or flanged. V. t- Radiant Floor Heating Z 0x I O 12.Provide necessary trenching,backfill,excavation,supports,piping,insulation,saw cutting and patching,concrete/paving,etc.,as required.Backfill 44.Copper pipe Valves and Specialties: LU ‘, 0r!� tll F trenches in 6"layers and to 90%compaction and patch to match existing grade. 84.Radiant tubing shall be 1/2"nominal diameter.Tubing shall be PEX-a crosslinked polyethylene with an oxygen diffusion barrier,manufactured by @ lU B Gate Valves: Bronze,Class 125,200 lb.W.O.G. the Engle method. is. CO (] 13.Systems shall be professionally labeled.Piping shall be labeled with color coded commercial grade labels indicating piping service and flow Ball Valves: Bronze,Class 125,200 lb.W.O.G. O -' direction.Equipment,fans,pumps,valves,switches and controls shall be labeled with engraved plastic or metal tags and an equipment/valve Check Valves: Bronze,Class 125,200 lb.W.O.G. 85.Piping shall be installed in continuous loops,no splices allowed.Tube centers and the maximum loop lengths are specified in the Radiant Zone schedule shall be provided and mounted on the mechanical room walk Equipment labels shall follow the same nomenclature as the mechanical Balancing Valves: 125 psig w.p.for 250F service tight shut-off,Illinois dual-purpose,balancing/shut-off valve,Hoffman,Sarco,or equivalent. Schedule on the plans. ) ( Q- 1- Lu drawings. II 45.Support pipe with rod and clevis or clamps.No pipe tape allowed. 86.Tubing loops off each manifold shall be installed in equivalent lengths(+/-5%). ' z' = 14.See architectural reflected ceiling plan for all ceiling penetrations. PE Stara Cl~ 46.Provide expansion joints or loops on all heating water piping runs in excess of 50'. 87.The Contractor shall install manifolds as provided by the tubing manufacturer.The manifolds shall consist of a return header(including:balancing p S a) 15.Coordinate architectural,structural,electrical,landscaping,fire protection,and interior design drawings with mechanical drawings prior to valve for each loop,compression fitting to receive tubes and air vent)and supply header(including:manual shut-off valve for each loop and _- `U0 0JCp.'k m O installation. 47.Dielectric Unions-Furnish and install a dielectric union at all connections where non-ferrous material is in contact with ferrous material and fluid is compression fitting to receive tubes). ,v eQ...* .,F'I'rc„I II N U not protected with corrosion inhibitors. %G�r�y I`/yF9�r�e�II 16.Offset piping,ductwork,etc.as necessary to accommodate structure,beams,columns,and existing equipment. Snowmelt �44f'8/30/19'r{ I, O 0 48.Grade and valve all heating water piping with%"hose end valves to permit drainage of the system.Vent all high points in equipment rooms as uw 5 2 A p - Verify exact locations of existing and new underground utilities,piping,and raceway systems prior to trenching.Contractor shall obtain and verify necessary with automatic air vents piped to convenient drain.All high points in system outside of equipment rooms with manual air vents as 88.Snowmelt tubing shall be 5/8"nominal diameter.Tubing shall be PEX-a crosslinked polyethylene with an oxygen diffusion barrier,manufactured by iI trfA f r 0- exact utility company drawings and requirements. required to relieve air in the system. the Engle method in accordance with ASTM F 876. I cs16, �wt i 5 m O Electrical 49.Provideplasticgrommets on all heatingwater piping passingthroughwood and studs. 89.Piping shall be installed in continuous loops,no splices allowed.Tube centers and the maximum looplengths are specified in the Snowmelt Zone I t 55 lOMAI.ENG" N w p p B joistsP gP Gt P v��� O Schedule on the plans. 18.Contractor must carefully verify electrical service voltage and phase available before ordering any equipment. 50.Install plumbing clean-outs as required by applicable codes. N p 90.Tubing loops off each manifold shall be installed in equivalent lengths(+/-5%). ft d 19.The following are to be furnished by MC and wired by EC:equipment motors,magnetic starters,line voltage thermostats,factory disconnect Boiler Flue&Combustion Air PipingV w switches(if specified as part of factory wired equipment)resistance heaters,fire and smoke detectors. 91.The Contractor shall install manifolds as provided by the tubing manufacturer.The manifolds shall consist of a return header(including:balancing 0 V 51.Boiler flue piping shall be CPVC,complying with ASTM F441,or a polypropylene venting system,listed in accordance with ULC-5636,and rated valve for each loop,compression fitting to receive tubes and air vent)and supply header(including:manual shut-off valve for each loop and 'Z 11 m 20.The following are to be furnished and wired by EC:disconnect switches,thermal overload switches,manual operating switches and contactors. for flue gas venting systems. compression fitting to receive tubes). =,F 21.The following are to be furnished and wired by MC:low voltage thermostats,control transformers,control relays,control panels,motorized valves, 52.Boiler combustion air piping shall be PVC,complying with ASTM D 1785. 92.Snowmelt distribution piping shall be pre-insulated pex. m z Q motorized dampers,pilot lights,multi-speed switches and interlocks. 11 1u5yt"I Antifreeze Solutions 93.Secure piping in snowmelt areas by attaching tubing to wire mesh using plastic tie straps,every 3'on straight runs and at apex of turn for any change IY E Shop Drawings of direction.No metal wiring shall be used. 53.DILUTION WATER QUALITY:Contractor shall be responsible for testing the water and submitting a report to the Owner&Engineer,prior to >"l CD B 22.Submit entire HVAC shop drawing submittal data at one time. Submittal to be indexed in a neat and orderly manner.Partial submittals will not be system fill."Hard"water shall not be used.The water used to dilute the concentrated inhibited glycol-based heat transfer fluid must be either 94.Snowmelt system shall be pressure tested in accordance with tubing manufacturer's instructions as required for warranty protection.In the absence Z I accepted.Submittals shall include,but not be limited to:equipment,fixtures,insulation,diffusers,pumps,fans,piping,valves,boilers,and furnaces. distilled,deionized,or contain less than 25 ppm of chloride,25 ppm of sulfate,50 ppm of calcium,and 50 ppm of magnesium,with a total hardness of manufacturer's instruction,pressurize the entire snowmelt system with compressed air.Charge system to a pressure of not less than 80 psig or Q Cl not to exceed 100 ppm.If good quality water is unavailable,the manufacturer of the glycol product will provide the heat transfer fluid and water to more than 100 psig.Pressure test shall last for 24 hours with not less than a 2 psig drop.With system air charged,soap test all joint on and within E N Insulation meet the specifications of the system. the manifolds.After hydrostatic test pressure has been applied,examine piping,joints and connections for leakage.Eliminate any leaks as w �/ (1 necessary&re-test.Any portion of tubing layout that rises as a result of being pressurized shall be re-secured to be at the proper level within the 23.Piping Insulation Schedule: 54.Fill heating water system with 50%propylene glycol/50%water solution,by volume,for freeze protection to-28°F and burst protection to-60°F. slab structure when poured. �� 0 m Z Include corrosion inhibitors. rrI� 1 w Q Service Thickness(in.) 95.Entire snowmelt system shall be left pressurized with monitoring pressure gauge throughout installation of concrete or sand/pavers.Continually l 1�1 Z d HWS/R(less than 1.5"pipe) 1.5 Ductwork monitor pressure on system to make certain tubing system remains intact with no leaks or punctures. ` O Z w HWS/R(1.5"pipe and greater) 2.0 O I' \ w w Domestic Hot Water 1.0 55.Duct sizes shown on drawings are outside(sheet metal)duct dimensions. 96.Manifolds shall be tagged to identify area served.Each connection on supply&return manifolds shall be permanently labeled with loop number. �/ F- Domestic Cold Water 0.5 w 1 Ill O Domestic Hot Water Recirculation 1.0 56.All ductwork shall be sealed airtight with duct mastic.Where duct tape is used,it shall be listed and labeled in accordance with UL 181. 97.Prior to final system fill and commissioning,the PEX tubing system and manifolds shall be chemically cleaned as prescribed by the tubing r \ !�1 z m N Refrigeration Suction 0.5 manufacturer.Supply all tools,connections,labor,and accessories necessary to properly remove all foreign material,chemical,and residue within v rTl in= Refrigerant Liquid 0.5 57.All returns shall be ducted.Panning of stud cavities,joist bays,etc.is not allowed. the tubing system before permanently charging system and placing into operation. WA 1.1 I I 0 Piping insulation shall be U.L.approved,white,all service,glass fiber,snap-on,pipe insulation.Insulate fittings with glass fiber blanket insulation 58.Provide 1/4"galvanized mesh screen on all open end ducts(OED). 98.After entire system has been properly cleaned and flushed,fill system with clean water to proper cold fill pressure.Add propylene glycol to theCN1 IL and premolded PVC covers. snowmelt system to the concentration specified using a positive displacement pump.Antifreeze fluid shall include corrosion inhibitors.Purge each Z w 59.Seal all ductwork joints and vapor barrier penetrations at all exterior walls. individual loop to eliminate air pockets in the system.After purging remove fill connection to any potable water lines to prevent any possibility of d 24.Insulate all new refrigerant suction piping&condensate piping with flexible,closed-cell elastomeric insulation.Insulation shall have a flame spread contamination. w UQ, index of not more than 25 and a smoke-developed index of not more than 50 when test in accordance with ASTM E 84,latest revision. 60.Ducts and piping penetrating through roof shall have roof flashing with caulk type counter flashing sleeve or by method acceptable by roofing w 0- manufacturer.Installation shall be watertight. Z Cy 25.Insulate all new heating water,domestic hot water,domestic hot water recirculation,radiant floor(mains and runouts to areas being heated)and w snowmelt piping(mains and runouts to areas beingheated)with U.L.approved,white,all service,glass fiber,snap-on,pipe insulation.Minimum 61.Provide backdraft dampers at anyand all ductworkpenetrations through exterior wall(except outside air and combustion air ductwork). } PP g PP P dd P g ( P ) m 15 R-Value of 3.0 for all piping.Insulate fittings with glass fiber blanket insulation and premolded PVC covers.Provide deduct alternate price to � Q D insulate with Armafex. 62.Provide turning vanes in all mitered rectangular elbows. >Z Q 26.Insulation shall be installed under all radiant heated floors on slab.Insulation shall have a minimum R-value of 10 at a mean testing temperature of 63.Provide volume dampers at all accessible round duct take-offs. a i 75 F. Q)7 64.Make all final connections to supply GRD's with acoustic flexible duct.Minimum length shall be 4 feet.Maximum length shall be 8 feet. 27.Insulation shall be installed under all exterior snowmelt areas.Insulation shall be Dow Styrofoam Highload extruded polystyrene foam board Issued For tit O insulation that has an R-5 per inch insulation value and 2"thick.Insulation installed under traffic areas must be traffic rated. 65.All ductwork or surfaces which are visible behind a grille,register,diffuser or louver shall be painted flat black. No. Date Comment O I 8/14/19 COORDINATION t 9 28.Insulation for all types of piping shall be carried full size through pipe hangers or pipes shall be supported with vibration clamps. 66.All dryer vents and bathroom exhaust ducts from fan/light fixtures shall be 4"galvanized round(unless noted otherwise). 2 8/30/19 PERMIT i Q 29.Internally line all new RECTANGULAR Exhaust Air(EA),Return Air(RA),&Supply Air(SA)ductwork with 1/2"thick,2.0 PCF,U.L.rated, 67.Sheet metal and fittings to be pursuant to SMACNA and ASHRAE standards. 2 0 non-corrosive,non-combustible,glass fiber insulation complying with ASTM C 1071.Refer to plans for duct labels.Liner fasteners shall be B L galvanized steel,welded with integral head. 68.All ducts shall be 26 gauge minimum.Duct gauge and construction shall conform to SMACNA HVAC Duct Construction Standards. N O U i 30.All new Outside Air(OA)ductwork shall be unlined.Refer to plans for duct labels. 69.Contractor to coordinate exact location of grilles and registers before installation. (T_I F MECHANICAL w 31.Externally wrap all unlined Outside Air(OA)ductwork and louver plenums with 1"thick,1.0 PCF,U.L.rated,flexible,non-combustible,blanket 70.Seal off all ducts during construction. m SPECIFICATIONS w w 0insulation complying with ASTM C 553.Vapor barrier jacket shall be FSK(foil-scrim-kraft).Minimum R-Value of 6.0. r w Z Vibration Isolation lb' 32.Insulate the final 5'of all exhaust ductwork at exterior terminations with 2"thick insulation with a continuous vapor barrier.Minimum R-Value of p 1C 0 6.0. 71.Where specified,duct-to-fan connections shall be made with flexible canvas duct connector material.Provide duct alignment within 1/2"at the fan K j w collar and duct collar. 33.Insulate transfer ducts with 1/2"thick,2 PCF,U.L.rated,glass fiber duct insulation with a continuous vapor barrier. N Z 72.Where specified,spring vibration isolators for support of equipment shall be properly aligned so that support rod does not contact spring housing. 0_a z Pi ping Q X w� Controls >w w ,w 34.Domestic Hot,Cold&Recirculation piping inside building-Buried lines type'K'copper water tube,wrought copper fittings and 1100F solder. Project No. 5ca le: O z o Non-buried lines,type'L'copper water tube,wrought copper fittings and no lead solder.Provide alternate pricing for PEX tubing(no oxygen 73.Mount all thermostats and humidistats 5'-0"above finished floor. 0-'-wl 19002.00 N/A o diffusion barrier necessary).Unless otherwise noted,piping on plans has been sized for copper,and if ASTM PEX piping is used,increase size of z Ospiping one nominal size from size shown on plans,ie.Plans call for a%"line&PEX is to be substituted,a I"PEX line shall be installed. 74.Thermostats&remote temperature sensors shall not be installed above heat emitting equipment,including wall mounted touch screen controls.Do Drawn By: Checked By: Q w 0 not mount on exterior walls or above/below forced air supply registers. Jell.) J D R W Z i Q w K M4.0 .7 it Wo U Qiio Page 47 of 48 Sequence of Operation A"J stamp 1. B-1 Boiler&WH-1 Water Heater(Central) a. Boiler shall be controlled and modulated by integral boiler controls.Configure for"domestic hot water prioritization". b. Upon a call for domestic hot water production from TS-2 temperature sensor,P-2 pump shall start and B-1 boiler shall be enabled.P-1 pump shall be off.Boiler setpoint shall be 180°F(adj). c. Upon a call for space heating,P-1 pump shall start and B-1 boiler shall be enabled.P-2 pump shall be off.Boiler shall be modulated by integral controls to maintain the HWS setpoint at TS-1 temperature sensor.HWS setpoint shall be automatically reset inverse linearly by integral boiler controls based on outside air temperature(125°F @ -20°F to 90°F @ 70°F,adj). OM= N d. HWS setpoint shall be ramped up to 125°F(adj)on a call for snowmelting. E 0 w 14 LU N I 2. Radiant Floor Heating N in w a. Upon a call for heating from associated thermostat,on/off zone valve on heating water return pipe shall open. > �l Radiant heating pump P-3 shall run. IU op r b. Hydronic radiant floor shall provide heating for the lower level only. Di. ,_. . O 3. F-1 Furnace(Multi-Zone)&CU-1 Condensing Unit(Two-Stage)&EDH-1 Electric Duct Heater O U r tY a. BLOWER:Blower shall run for any calls for heating,cooling,or kitchen make-up air. O Z '— b. MODE: Furnace mode of operation(heating or cooling)shall be determined by the zone board. L., o N c. COOLING:Upon a call for cooling,fan shall start and CU-1 condensing unit shall be enabled.Condensing unit •0 2 )— > ,i)shall be staged by the zoning control board to meet the cooling load.Condensing unit shall be furnished with soft ID Q 1 Q i start and anti-cycling controls. 2 —' II- IL d. HEATING:Upon a call for heating,fan shall start and gas-furnace shall start.2-stage gas burner shall be staged by W ° z ui integral controls to meet the space heating demand. w l� e. KITCHEN MAKE-UP AIR:Blower shall be electrically interlocked with kitchen exhaust fan.When exhaust fan is Z = Q running,normally closed OA damper shall open(1000 CFM)and normally open RA damper shall partially close rg = 00 (P (1250 CFM).EDH-1 electric duct heater shall be controlled by a single phase SCR control.After air flow is proven by air proving switch,SCR control shall modulate coil to maintain 72°F(adj)discharge air temperature. W (P o to F f ZONING:Provide a zoning system.Zoning system shall include 3 zone dampers and controls as required.Zone ,, COV dampers shall open/close based on cooling/heating demand.Furnace fan speed shall modulate as directed by (0 o integral controls to maintain constant supply duct static pressure.Exact static pressure setpoint shall be determined la -.. by contractor during TAB.Initial setpoint is estimated to be approximately 0.5"w.c. / 01 4. Snowmelting �, 0 w a. Provide(1)snow/ice sensor and socket(Tekmar 091/094)per unit.Refer to M0.1 for location. Z F b. Provide(1)Tekmar 654 snowmelt control per unit. PE Stamp 0 N c. Upon a call for snowmelting from snow/ice sensor,P-4 snowmelt pump and boiler shall be enabled.Tekmar _ `. m O DO Ilg control shall turn off P-4 snowmelt pump when the call for snowmelting has been satisfied. _=N0�,,. ti '4 N F d. Provide a 12-hour timer switch in the mechanical room for manual override. %6�fF'y 1`NFq-. 4 t4 8/30/19 d'ti1 '� o e. Tekmar system shall be setup for W W SD(warm weather shut down)at approximately 45°F(adj).System shall not : j W4 5 2 m{ i O 0 operate if outdoor temperature is above this setting. d i f. Tekmar system shall be setup for CWCO(cold weather cut out)at approximately 10°F(adj).System shall not '++-$� 1f�¢ j 0 operate if outdoor temperature is below this setting. + O,� r % 0 P P g '�,FS iortA t•v_A� ra w ''`A,,,------ z U 5. Fans a. EF-1 bath exhaust fans shall each be controlled by an on/off wall switch. N O b. EF-2 garage exhaust fan shall be energized via a motion sensor in the garage ceiling.Once energized,fan shall run V is for 30 minutes(adj)as set by adjustable timer.Any trigger of the motion sensor during the timed run period shall T W reset the timer. 11 0ft w m 6. ERV-1 Energy Recovery Ventilator&EDH-1 Electric Duct Heater =i- a. ERV-1 shall be controlled by a percent timer control(Renewaire PT Percent Timer Control)which shall control m O percent of unit operation per hour(adjustable from 0 to 100%).Control shall be located in the mechanical room. j Q b. ERV-1 shall also be controlled by multiple push button controls(Renewaire PB-L Push Button Point-of-use I, tay L Control Lighted).Refere to sheet MO.1 for locations.Press button once for 20 minutes of timed ventilation 50 operation,twice for 40 minutes,and three times for 60 minutes.Press and hold button for about five seconds to LL cancel ventilation cycle. O >r c. Wire percent timer and push button controls in parallel. Q 0 d. EDH-1 shall be located at ERV-1 fresh air supply duct. 2i e. EDH-1 shall be controlled by a single phase SCR control.SCR control shall modulate coil to maintain 70°F(adj) §` discharge air temperature. 11 N O K Ill z 7. Pumps w ray' z 0_a. P-1 B-1 boiler pump:on whenever boiler is called to fire for radiant heating or snowmelting.P-2 pump shall be ` O z w off. O r , w N b. P-2 WH-1 water heater pump:on whenever boiler is called to fire for DHW heating from TS-2 temperature sensor. \./ F F P-1 pump shall be off. 1 l O c. P-3 radiant floor pump:on whenever there is a call for radiant floor heating. r !�1 z N N d. P-4 snowmelt pump:on whenever there is a call for snowmelting from SZ-1. \./ W w i e. RP-1 domestic hot water recirculation pump:controlled automatically by integral controls. r---^1aI 8. LS-1 Lift Station ` V �y z w a. Lift station shall be controlled by duplex control panel. 0 b. When the"stop"and"lead"floats are closed pump 1 will start and the pump 1 run light will illuminate.Pump 1 w CE will remain operational until the"stop"float opens. Clit =a c. The next time the"stop"and"lead"floats are closed the alternating circuit will energize pump 2 and the pump 2 }w run light will illuminate. Pump 2 will remain operational until the"stop"float opens. This cycle will repeat each m 15 time the fluid level rises and falls. ^ d. If the fluid level continues to rise after the first pump has been energized the"lag"float will close. When the"lag" ` V et float has closed the second pump will energize.Both pumps will remain operational until the"stop"float opens 0 N and the following will occur: _ - The audible high water horn will sound. 4 - The auxiliary dry contacts will close. Issued For w d - A signal shall be sent to the owner. No. Date Comment IK� I 8/14/l3 COORDINATION 3 2 8/30/10 PERMIT Q O z E L 3Z L O Q Uw dLY SEQUENCE OF w 91 OPERATION i N z o z K ti w oiZ Q t-In 0 1 w Project No. Scale: aZ Ct Q 19002.00 N/A o d m Drawn By: Checked By: i z�0 JSUJ JDR w z'i M4.1 Q'10 Page 48 of 48