HomeMy WebLinkAboutFile Documents.630 W Hopkins Ave.0052-2020-BRES (48) Kübed Fire Suppression 630 W. Hopkins—Water Supply Utilities Permit Coordinator City of Aspen Water Department 500 Doolittle Drive Aspen, CO 81611 04/13/2020 To Whom it May Concern: It will be necessary to have a minimum 2 inch diameter underground water supply line for the combination domestic water supply and fire suppression riser for the —5,800 SF NFPA 13D sprinkled residence at 630 W. Hopkins. This is due to the overall size of the home as well as the additional hydraulic design parameters established by the local 'Authority Having Jurisdiction'. The Aspen Fire district, in their 2016 NFPA adopted code Resolutions and Amendments— Section 2.q states: (q) The following shall be added to the end of Section 903.3.5: Automatic sprinkler systems that are supplied by a public water works system shall he equipped with no less than a two inch service connection for all one- and two-family dwellings designed to NFPA 13D or no less than a four inch service connection for all structures designed to NFPA 13 and NFPA 13R. A reduction in the size of the service connection may be approved by the fire code official. Thank you Jeff Kubica Principal Kubed Fire Suppression 970-366-1048 Jeff Kubica 19 Lindvig Court Suite 202 970-366-1048 Aspen 81611 K I ' Jeff@KubedFire.com www.KubedFireSuppression.com 06/30/2020 ASPEN BUILDING DEPARTMENT