Fire Suppression
630 W. Hopkins—Water Supply
Utilities Permit Coordinator
City of Aspen Water Department
500 Doolittle Drive
Aspen, CO 81611
04/13/2020
To Whom it May Concern:
It will be necessary to have a minimum 2 inch diameter underground water supply line for the
combination domestic water supply and fire suppression riser for the —5,800 SF NFPA 13D
sprinkled residence at 630 W. Hopkins. This is due to the overall size of the home as well as the
additional hydraulic design parameters established by the local 'Authority Having Jurisdiction'.
The Aspen Fire district, in their 2016 NFPA adopted code Resolutions and Amendments—
Section 2.q states:
(q) The following shall be added to the end of Section 903.3.5:
Automatic sprinkler systems that are supplied by a public water works system shall he
equipped with no less than a two inch service connection for all one- and two-family
dwellings designed to NFPA 13D or no less than a four inch service connection for all
structures designed to NFPA 13 and NFPA 13R. A reduction in the size of the service
connection may be approved by the fire code official.
Thank you
Jeff Kubica
Principal
Kubed Fire Suppression
970-366-1048