Aspen CO 81611
Inspection Type: Hood and Duct Inspection
FIR, Inspection Date: 7/12/2022 By: Legersky, Jan (AF7090)
Form: Hood Time In: 14:00 Time Out: 14:30
Authorized Date: 07/12/2022 By: Legersky, Jan (AF7090)
Inspection Description:
Kitchen Exhaust Hood Fire Suppression System
Inspection Topics:
Nozzles
Are nozzles properly positioned over appliances to adequately protect them?
Nozzles shall be positioned to adequately protect the hazard and or appliances placed beneath the hoodNozzles shall be positioned to adequately protect the
hazard and or appliances placed beneath the hood
Status: PASS
Notes:
Fire Suppression System Discharge
Does the fire suppression system discharge upon activation of pull station?
The fire suppression system shall discharge upon activation of pull station.
Status: PASS
Notes:
Does the fire suppression system discharge upon release of fusible link?
The fire suppression system shall discharge upon release of fusible link.
Status: PASS
Notes:
Utilities Shut Off
Does the gas service shut off upon activation of the fire suppression system?
Gas service shall disconnect upon activation of the fire suppression system.
Status: PASS
Notes:
Does the electrical service shut off upon activation of the fire suppression system?
The electrical service shall shut off upon activation of the fire suppression system
Status: PASS
Notes:
Exhaust Fan
Does the kitchen hood exhaust fan turn on upon activation of fire suppression system?
The kitchen hood exhaust fan shall turn on upon activation of the fire suppression system.
Status: PASS
Notes:
Printed on 07/12/22 at 15:47:22 Page 1 of 3
Make Up Air
Does the make up air shut off upon activation of the fire suppression system?
The make up air shall shut off upon activation of the fire suppression system.
Status: PASS
Notes:
Fire Alarm System
If a building fire alarm system is installed, does the activation of the fire suppression system send a signal to the fire alarm
control panel and notify the proper personnel or occupant notification?
Upon activation of the kitchen hood fire suppression system,a signal shall be transmitted to the fire alarm control panel the notify the proper personnel or
occupants.
Status: PASS
Notes:
UL 300 Listing
Is the fire suppression system listed to UL 300 Standard?
Kitchen hood fire suppression systems shall be listed to UL 300 Standard unless otherwise approved.
Status: PASS
Notes:
Portable Fire Extinguishers
Is a portable fire extinguisher of the proper size and hazard classification readily available for the class of fire anticipated?
A portable ABC type fire extinguisher shall be properly mounted and readily available in an approved location.
Status: PASS
Notes:
Is a type "K" portable fire extinguisher of the proper size readily available?
A type"K"portable fire extinguisher of the proper size shall be mounted and readily available in an approved location.
Status: PASS
Notes:
Is the type "K" portable fire extinguisher bi-lingual placard mounted in an approved location?
A bi-lingual explanation placard shall be mounted in an approved location.
Status: PASS
Notes:
Additional Time Spent on Inspection:
Category Start Date /Time End Date /Time
Notes: No Additional time recorded
Total Additional Time: 0 minutes
Inspection Time: 30 minutes
Total Time: 30 minutes
Summary:
Overall Result: Passed
Conducted test& inspection of system as outlined in inspection report. The system
Inspector Notes: functioned as designed and no issues were found at this time.