HomeMy WebLinkAboutFile Documents.234 W Francis St.0118-2020-BRES (23) -� -. No CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE: February 14, 2025 PROJECT: 234 W FRANCIS ADDRESS: ASPEN, COLORADO DESIGN ENGINEER: REG HVAC CONTRACTOR: T&E MARSHALL NEBB TAB FIRM: CERTIFIED BALANCE INC. OF COLORADO ADDRESS: 924 26 ROAD GRAND JUNCTION, COLORADO (970) 245-7757 TABB CERTIFICATION NO: 2823 CERTIFICATION ILkiL: PROJECT: 234 W FRANC I S ADDRESS: ASPEN, COLORADO THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENT AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENT SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE REPORT PROJECT SUMMARY. THIS REPORT IS BASED ON BUILDING, SPACE AND EQUIPMENT CONDITION ON DATES TESTED. SUBMITTED AND CERTIFIED BY: NEBB CERTIFIED TAB FIRM NAME CERTIFIED BALANCE INC. OF COLORADO CERTIFICATION NO. 2823 CERTIFICATION EXPIRATION DATE 12/31/2025 REPORT DATE: February 14, 2025 slsnCe• rh 9 0 u RONALD P.GORMAN o CERTIFICATION 2823 Exp. 12/31.25 eja . Sep •sonic NEBB QUALIFIED TAB SUPERVISOR NAME Ronald P. Gorman NEBB QUALIFIED TAB SUPERVISOR SIGNATURE Table of Contents 234 W FRANCIS Section Page Engineering Notes 1 Air Handlers FCU Summary 2 FCU-1/8 Air Outlets 4 FCU-9/16 Air Outlets 5 HRVs 6 Exhaust Fans 9 KH-1 Baffle Readings 10 Pumps 11 Calibration 16 Abbreviations 17 Plans Summary and Engineering Notes THE FOLLOWING WAS NOTED WHILE COMPLETING THE TEST AND BALANCE ON THIS PROJECT. ALSO, SEE THE INDIVIDUAL REPORTS FOR ADDITIONAL COMMENTS. SUMMARY REPORT: This project has been balanced per plans and specifications using the National Environmental Balancing Bureau (NEBB) standards and procedures . The air handlers and fans have been checked for operating amperage, voltage, rotation, RPM, belt tension, alignment, and operating static pressure . All outlets have been proportioned to +-100 of the total airflow of the system unless otherwise noted. The heating water systems were balanced to +-100 of total flow of each system unless other wise noted. The heating, cooling and exhaust systems are working within the design criteria. _ EF-1/KH-1 : According to the submittals the fan and hood are suppose to have 1, 600 CFM design. Due to the interlock of a wall mounted speed control the hood is drawing 2, 108 CFM. After reading through the information for the fan controller I found the wall mounted dial will override the controller from 0-100% . I can set a high speed limit in the digital controller but the dial bypasses it . Page 1 of 17 PROJECT: 234 W FRANCIS SYS DESIGN REGISTER ACTUAL LOCATION NO. MANUFACTURE MODEL CFM CFM CFM SPEED DESIGN FCU KITCHEN 1 PRICE FCHG70 1,600 1,610 1,570 100% THEATER 2 PRICE FCHG30 450 520 503 100% AV/IT 3 PRICE FCHG40 760 760 778 65% LIVING ROOM 4 PRICE FCHG30 450 450 473 80% GARAGE BEDROOM 5 PRICE FCHG20 250 250 259 45% MECHANICAL RM 6 PRICE FCHG20 350 350 362 70% BEDROOM 7 PRICE FCHG20 250 300 314 40% BEDROOM 8 PRICE FCHG20 200 200 211 50% LAUNDRY 9 PRICE FCHG40 700 700 692 60% BEDROOM 10 PRICE FCHG20 200 200 214 40% CABIN 11 PRICE FCHG20 350 420 426 70% MASSAGE 12 PRICE FCHG20 200 200 213 40% SPA LOUNGE 13 PRICE FCHG20 150 150 162 30% GYM 14 PRICE FCHG20 350 400 403 75% STUDY 15 PRICE FCHG20 250 250 259 45% MASTER BEDROOM 16 PRICE FCHG20 200 250 246 45% REMARKS: TEST DATE: 1/15/25 1/16/25 FILE NAME: 1585 25 Page 2 of 17 PROJECT: 234 W FRAN FAN COIL SUMMARY ki TEST REPORT __ -- COOLING COIL -- ---- H EATING COIL SYS DESIGN ACTUAL ACTUAL TEMP. TEMP. DESIGN ACTUAL ACTUAL TEMP. ACTUAL DESIGN ACTUAL TEMP. LOCATION NO. EAT EAT LAT DIFF. EWT LWT DIFF. EAT EAT LAT DIFF. MBH EWT LWT LWT DIFF. DESIGN FCU 0 - KITCHEN 1 80 73 59 14 45 56 11 50 52 91 39 51.4 122 100 101 21 THEATER 2 80 75 57 18 46 54 8 65 67 85 18 7.6 122 100 99 23 AV/IT 3 80 73 60 13 46 54 8 - - - - - - - - - LIVING ROOM 4 80 73 58 15 46 54 8 65 69 84 15 6.0 122 100 104 18 GARAGE BEDROOM 5 80 74 59 15 45 55 10 65 69 91 22 4.8 122 100 103 19 MECHANICAL RM 6 80 74 59 15 46 56 10 65 69 91 22 6.7 122 100 100 22 BEDROOM 7 80 74 59 15 46 56 10 65 68 93 25 6.6 122 100 103 19 BEDROOM 8 80 75 60 15 45 54 9 65 67 90 23 4.1 122 100 99 23 LAUNDRY 9 80 73 60 13 45 56 11 65 65 93 28 16.3 122 100 103 19 BEDROOM 10 80 75 57 18 46 56 10 65 67 92 25 4.5 123 100 101 22 CABIN 11 80 74 57 17 46 54 8 65 69 92 23 8.2 123 100 100 23 MASSAGE 12 80 73 58 15 45 56 11 65 66 90 24 4.3 122 100 103 19 SPA LOUNGE 13 80 73 58 15 45 55 10 65 65 90 25 3.4 122 100 99 23 GYM 14 80 73 59 14 45 55 10 65 65 92 27 9.1 122 100 99 23 STUDY 15 80 75 60 15 45 56 11 65 68 83 15 3.3 122 100 103 19 MASTER BEDROOM 16 80 73 59 14 46 55 9 65 67 92 25 5.2 123 100 104 19 REMARKS: TEST DATE: 1/15/25 1/ FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 3 of 17 'J- AIR OUTLET TEST REPORT I •'JL PROJECT 234 W FRANCIS SYSTEM FCU REGISTERS Outlet Design Prel. Final Area Served # Type Size CFM CFM CFM % FCU-1 KITCHEN 20 1 SA1 128 . 5 X 4 . E 940 921 921 ss% KITCHEN 20 2 SA1 36 X 4 270 262 262 97% DINING 20 3 SA1 94 X 5 400 387 387 97% TOTAL 1, 610 1, 570 1, 570 98% FCU-2 THEATER 5 1 SA1 70 X 5 520 498 503 97% FCU-3 AV/IT 9 1 SA1 30 X 8 380 518 367 97% AV/IT 9 2 SA1 30 X 8 380 686 411 108% TOTAL 760 1, 204 778 102% FCU-4 LIVING RM 23 1 SA3 44 X 5 225 532 276 123% LIVING RM 23 2 SA3 44 X 5 225 89 197 88% TOTAL 450 621 473 105% FCU-5 GARAGE BEDROOM 29 1 SA1 36 X 5 250 343 259 104% FCU-6 MECH ROOM 1 1 SA2 12 X 6 175 234 179 102% MECH ROOM 1 2 SA2 12 X 6 175 219 183 105% TOTAL 350 453 362 103% FCU-7 BEDROOM 10 1 SA1 36 X 5 300 579 314 105% FCU-8 BEDROOM 3 1 SA 30 X 5 200 318 211 106% REMARKS: FCU-4 #2 CABLE DAMPER BROKE, NON FUNCTIONAL. WITH THE AID OF MECH CONTRACTOR WE WERE ABLE TO PRY OPEN THE DAMPER USING A BAR, NOT ACCESS TO DAMPER. TEST DATE: 1/15/25 1/16/25 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 4 of 17 AIR OUTLET TEST REPORT I •'JL PROJECT 234 W FRANCIS SYSTEM FCU REGISTERS Outlet Design Prel. Final Area Served # Type Size CFM CFM CFM % FCU-9 LAUNDRY 8 1 SA1 30 X 5 200 298 189 95% LAUNDRY 8 2 SA1 30 X 5 200 345 204 102% ICE 8 3 SA1 20 X 10 300 373 299 100% TOTAL 700 1, 016 692 99% FCU-10 BEDROOM 2 1 1 1 SA1 30 X 5 200 359 214 107% FCU-11 CABIN 25 1 SA3 24 X 5 140 171 149 106% CABIN 25 2 SA3 24 X 5 140 164 141 101% CABIN 25 3 SA3 24 X 5 140 157 136 97% TOTAL 420 492 426 101% FCU-12 MASSAGE 17 1 1 1 SA1 30 X 5 200 402 213 107% FCU-13 SPA LOUNGE 13 1 SA1 24 X 5 150 419 162 108% FCU-14 GYM 12 1 SA1 48 X 5 400 488 403 101% FCU-15 DRESSING ROOM 27 1 SA1 36 X 5 250 329 259 104% FCU-16 MASTER BEDROOM 28 1 SA1 36 X 5 250 311 246 98% REMARKS: TEST DATE: 1/15/25 1/16/25 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 5 of 17 J[ Lj[: ENERGY RECOVERY - UNIT TEST REPORT PROJECT: 234 W FRANCIS LOCATION: BOILER ROOM SYSTEM/UNIT: v-1 UNIT DATA MOTOR DATA Make GREENHECK Make/Frame ENCLOSED Model MINICORE-5—VG—FM H.P. . 25 Serial Number 22866019 RPM Arr./Class CROSS OVER ERV Volts 2 0 8/2 3 0 Discharge HORIZONTAL Phase/Hertz 1/6 0 SA Amps 1 . 5/1 . 7/1 . 7 EA Amps 1 . 5/1 . 7/1 . 7 Drive Type DIRECT DRIVE TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL OUTDOOR AIR FAN EXHAUST AIR FAN Total CFM 300 314 Total CFM 300 321 Filter Exhaust Air Blower Outdoor )...: I1.1: Return Air Air Exhaust 4 re 1 :..00._ Supply Air Air Heat Exchanger Matrix Supply Air Blower (Transfers Energy from Exhaust to Outdoor Air) I REMARKS: SPEED DIALS SET AT #5 TEST DATE: 1/16/25 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 6 of 17 1 ENERGY RECOVERY UNIT TEST REPORT PROJECT: 234 W FRANCIS LOCATION: BOILER ROOM SYSTEM/UNIT: v-2 UNIT DATA MOTOR DATA Make GREENHECK Make/Frame ENCLOSED Model MINICORE-5—VG—FM H.P. . 25 Serial Number 22866021 RPM Arr./Class CROSS OVER ERV Volts 2 0 8/2 3 0 Discharge HORIZONTAL Phase/Hertz 1/6 0 SA Amps 1 . 5/1 . 7/1 . 7 EA Amps 1 . 5/1 . 7/1 . 7 Drive Type DIRECT DRIVE TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL OUTDOOR AIR FAN EXHAUST AIR FAN Total CFM 200 217 Total CFM 200 211 Filter Exhaust Air Blower Outdoor air Return Air Air Exhaust < :H° Supply Air Air Heat Exchanger Matrix Supply Air Blower (Transfers Energy from Exhaust to Outdoor Air) REMARKS: SPEED DIALS SET ON #4 TEST DATE: 1/16/25 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 7 of 17 1 ENERGY RECOVERY UNIT TEST REPORT PROJECT: 234 W FRANCIS LOCATION: MECH SPACE 3 SYSTEM/UNIT: v-3 UNIT DATA MOTOR DATA Make GREENHECK Make/Frame ENCLOSED Model MINICORE-5—VG—FM H.P. . 25 Serial Number 22866020 RPM Arr./Class CROSS OVER ERV Volts 2 0 8/2 3 0 Discharge HORIZONTAL Phase/Hertz 1/6 0 SA Amps 1 . 5/1 . 7/1 . 7 EA Amps 1 . 5/1 . 7/1 . 7 Drive Type DIRECT DRIVE TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL OUTDOOR AIR FAN EXHAUST AIR FAN Total CFM 300 318 Total CFM 300 322 Filter Exhaust Air Blower Outdoor air Return Air Air Exhaust < :H° Supply Air Air Heat Exchanger Matrix Supply Air Blower (Transfers Energy from Exhaust to Outdoor Air) REMARKS: SPEED DIALS SET AT #5 TEST DATE: 1/16/25 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 8 of 17 - - FAN TEST REPORT JLJ AL: PROJECT 234 W FRANCIS EF-1 : GREENHECK, SQ-160-V-G, VARIGREEN MOTOR, 120V, 1/60 EF-2 : GREENHECK, CSP-A390-V-G, 120V, 1/60 EF-3 : PANASONIC, FV-10NLF1E, 120V, 1/60 Area Design Final Served # EF CFM CFM KITCHEN HOOD ISEE BAFFLE READING EF-1 1, 600 2, 108 SEE ENGINEERING NOTES PAGE MECH ROOM EXHAUST I EF-2 300 316 GARAGE EF-3 120 129 REMARKS: TEST DATE: 1/16/25 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 9 of 17 Exhaust Baffle Filter CFM Worksheet for Shortrid_ge VelGrid Job Name: 234 W FRANCIS rev.5 Job Number: 1585 25 Hood Number 1 Information Filter Information Model: Length= Notes: Reference Filter Size Free Area K Factor" Filter#1 Filter#2 Filter#3 Filter#4 Filter#5 Filter#6 Filter#7 Filter#8 Filter#9 Filter#10 Filter#11 Total CFM 1 No Filter 0 0 Filter Size 16"x 20"v 16"x 20"v 16"x 20"v 16"x 20"v 16"x 20"v 16"x 20"v No Filter v No Filter v No Filter v No Filter v No Filter v 2 10"x 16" 0.78 1.2 Velocity 154 159 183 185 174 149 3 10"x 20" 0.99 1.2 CFM 323 334 384 389 365 313 2108 4 12"x 12" 0.69 1.2 5 12"x 16" 0.97 1.2 6 12"x 20" 1.25 1.2 7 12"x 24" 1.52 1.2 8 16"x 16" 1.35 1.2 No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V No Filter V—No Filter V— 9 16"X 20" 1.75 1.2 10 16"x 25" 2.22 1.2 11 20"x 20" 2.23 1.2 12 20"x 25" 2.85 1.2 13 24"x 24" 3.36 1.2 *NOTE: K-Factor Is the same for all Baffle style filters. •No Filter V—No Filter V—No Filter V No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V— 'No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V—No Filter V— Total Exhaust CFM's= 2108 CFM Page 10 of 17 - - PUMP TEST REPORT PROJECT 234 W FRANCIS PUMP DATA PUMP NO. PUMP NO. PUMP NO. Pump Number P-1 P-2 P-3 Location BOILER ROOM BOILER ROOM BOILER ROOM Service BOILER 1 BOILER 2 BUFFER TANK HW Manufacturer GRUNDFOS GRUNDFOS GRUNDFOS Model Number UPMXL 25-124 UPMXL 25-124 MAGNA 3 40-80F Serial Number N/A N/A 10010225 GPM/Head 38/7 ' 38/7 ' 40/5 ' Req. NPSH Pump RPM Impeller Dia. Motor Mfr./Frame GRUNDFOS GRUNDFOS GRUNDFOS Motor HP/RPM 3-120 WATTS 3-120 WATTS 16-285 WATTS Volts 115 115 115 Phase/Hertz 1/60 1/60 1/60 Amps/S.F. 0 . 05-1 . 7 0 . 05-1 . 7 0 . 30-2 . 57 Seal Type MECH MECH MECH TEST DATA ACTUAL ACTUAL ACTUAL Pump. Off-Press. _ NO TEST PORTS NO TEST PORTS PUMP SET WITH Valve Shut Diff. OR GAUGES INSTALLED OR GAUGES INSTALLED INTERNAL CONTROLLER Act. Impeller Diann. Valve Open Diff. Valve Open GPM Final Dischg. Press. Final Suction Press. CONSTANT PRESSURE Final Diff. Press. 2 . 2 PSI 5 ' Finial GPM 41 GPM Voltage Amps RPM REMARKS: *Measurements are in inches unless otherwise stated. TEST DATE: 1/16/2 5 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 11 of 17 - - PUMP TEST REPORT PROJECT 234 W FRANCIS PUMP DATA PUMP NO. PUMP NO. PUMP NO. Pump Number P-6 P-7 P-8 Location BOILER ROOM BOILER ROOM BOILER ROOM Service FCU HW LOOP RADIANT ZONE RADIANT ZONE Manufacturer GRUNDFOS GRUNDFOS GRUNDFOS Model Number MAGNA 3 40-80F ALPHA2 26-99 ALPHA2 26-99 Serial Number 10010826 N/A N/A GPM/Head 18 . 2/20 . 7 ' 4 . 6/11 . 2 ' 6 . 7/10 . 2 ' Req. NPSH Pump RPM Impeller Dia. Motor Mfr./Frame GRUNDFOS GRUNDFOS GRUNDFOS Motor HP/RPM 16-285 WATTS 15-120 WATTS 15-120 WATTS Volts 115 115 115 Phase/Hertz 1/60 1/60 1/60 Amps/S.F. 0 . 30-2 . 57 0 . 2-1 . 7 0 . 2-1 . 7 Seal Type MECH MECH MECH TEST DATA ACTUAL ACTUAL ACTUAL Pump. Off-Press. _ PUMP SET WITH NO TEST PORTS OR NO TEST PORTS OR Valve Shut Diff. INTERNAL CONTROLLER GAUGES INSTALLED GAUGES INSTALLED Act. Impeller Diann. Valve Open Diff. Valve Open GPM _ Final Dischg. Press. Final Suction Press. CONSTANT PRESSURE Final Diff. Press. 9 PSI 2 0 . 8 ' Finial GPM 20 . 1 Voltage Amps RPM SPD 3 SPD 3 REMARKS: *Measurements are in inches unless otherwise stated. TEST DATE: 1/16/2 5 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 12 of 17 - - PUMP TEST REPORT PROJECT 234 W FRANCIS PUMP DATA PUMP NO. PUMP NO. PUMP NO. Pump Number P-9 P-10 P-11 Location BOILER ROOM BOILER ROOM BOILER ROOM Service SNOWMELT HX SOURCE SNOWMELT HX LOAD HWC-1 Manufacturer GRUNDFOS GRUNDFOS GRUNDFOS Model Number UPS 15-58FC UPS 26-99FC ALPHA 26-99 Serial Number N/A N/A N/A GPM/Head 12 . 6/10 . 1 ' 9 . 9/13 . 6 ' 20 . 8/8 . 8 ' Req. NPSH Pump RPM Impeller Dia. Motor Mfr./Frame GRUNDFOS GRUNDFOS GRUNDFOS Motor HP/RPM 60/80/87 WATTS 150/179/197 WATTS 15-120 WATTS Volts 115 115 115 Phase/Hertz 1/60 1/60 1/60 Amps/S.F. 0 . 55/0 . 66/0 . 75 1 . 3/1 . 5/1 . 8 0 . 2-1 . 7 Seal Type MECH MECH MECH TEST DATA ACTUAL ACTUAL ACTUAL Pump. Off-Press. _ NO TEST PORTS OR NO TEST PORTS OR NO TEST PORTS OR Valve Shut Diff. GAUGES INSTALLED GAUGES INSTALLED GAUGES INSTALLED Act. Impeller Diann. Valve Open Diff. Valve Open GPM Final Dischg. Press. Final Suction Press. Final Diff. Press. SET WITH COIL CS Finial GPM 21 GPM Voltage Amps RPM SPD 2 SPD 2 SPD 2 REMARKS: *Measurements are in inches unless otherwise stated. TEST DATE: 1/16/2 5 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 13 of 17 - - PUMP TEST REPORT PROJECT 234 W FRANCIS PUMP DATA PUMP NO. PUMP NO. PUMP NO. Pump Number P-12 P-14 P-15 Location BOILER ROOM BOILER ROOM BOILER ROOM Service FC CHW PUMP HP-1 HP-2 Manufacturer GRUNDFOS GRUNDFOS GRUNDFOS Model Number MAGNA3 40-80F ALPHA2 26-99F ALPHA2 26-99F Serial Number 10010819 N/A N/A GPM/Head 42 . 7/14 . 7 ' 10 . 4/18 . 7 ' 10 . 4/18 . 7 ' Req. NPSH Pump RPM Impeller Dia. Motor Mfr./Frame GRUNDFOS GRUNDFOS GRUNDFOS Motor HP/RPM 16-285 WATTS 15-120 WATTS 15-120 WATTS Volts 115 115 115 Phase/Hertz 1/60 1/60 1/60 Amps/S.F. 0 . 3-2 . 57 0 . 2-1 . 7 0 . 2-1 . 7 Seal Type MECH MECH MECH TEST DATA ACTUAL ACTUAL ACTUAL Pump. Off-Press. _ PUMP SET WITH NO TEST PORTS OR NO TEST PORTS OR Valve Shut Diff. INTERNAL CONTROLLER GAUGES INSTALLED GAUGES INSTALLED Act. Impeller Diann. Valve Open Diff. Valve Open GPM _ Final Dischg. Press. Final Suction Press. CONSTANT PRESSURE Final Diff. Press. 6 . 4 PSI 14 . 8 ' Finial GPM 43 . 4 GPM Voltage Amps RPM SPD 2 SPD 2 REMARKS: *Measurements are in inches unless otherwise stated. TEST DATE: 1/16/2 5 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 14 of 17 - - PUMP TEST REPORT PROJECT 234 W FRANCIS PUMP DATA PUMP NO. PUMP NO. PUMP NO. Pump Number P-16 P-17 P-17 Location BOILER ROOM BOILER ROOM BOILER ROOM Service HP-3 HP-4 SPA SOURCE Manufacturer GRUNDFOS GRUNDFOS GRUNDFOS Model Number ALPHA2 26-99F ALPHA2 26-99F ALPHA2 26-99F Serial Number N/A N/A N/A GPM/Head 10 . 4/18 . 7 ' 10 . 4/18 . 7 ' 10 . 4/18 . 7 ' Req. NPSH Pump RPM Impeller Dia. Motor Mfr./Frame GRUNDFOS GRUNDFOS GRUNDFOS Motor HP/RPM 15-120 WATTS 15-120 WATTS 15-120 WATTS Volts 115 115 115 Phase/Hertz 1/60 1/60 1/60 Amps/S.F. 0 . 2-1 . 7 0 . 2-1 . 7 0 . 2-1 . 7 Seal Type MECH MECH MECH TEST DATA ACTUAL ACTUAL ACTUAL Pump. Off-Press. _ NO TEST PORTS OR NO TEST PORTS OR NO TEST PORTS OR Valve Shut Diff. GAUGES INSTALLED GAUGES INSTALLED GAUGES INSTALLED Act. Impeller Diann. Valve Open Diff. Valve Open GPM Final Dischg. Press. Final Suction Press. Final Diff. Press. Finial GPM Voltage Amps RPM SPD 2 SPD 2 SPD 2 REMARKS: *Measurements are in inches unless otherwise stated. TEST DATE: 1/16/2 5 FILE NAME: 1585 25 READINGS BY: R. GORMAN Page 15 of 17 IImo'- INSTRUMENT JL I 10 CALIBRATION REPORT PROJECT: 234 W FRANCIS DATES OF CALIBRATION INSTRUMENT/SERIAL# APPLICATION USE DATES EXTECH TACHOMETER 461995 #Q247730 RPM READINGS 10/24/2024 FLUKE 336 CBI/CO 594890164 VOLT/ AMP READINGS 1/15-16/25 10/24/2024 EVERGREEN TELEMETRY S—PVF-1 #1600176 PRESS/AIR FLOW 1/15-16/25 10/24/2024 EVERGREEN TEL. CH-15D/ HOOD #1600110 AIR FLOW READINGS 1/15-16/25 10/24/2024 EVERGREEN TELEMETRY RM—T-1 #1500302 TEMP.READINGS MODULE 1/15-16/25 10/24/2024 EVERGREEN TELEMETRY PR—T-1 #1900111 TEMP.READINGS PROBE 1/15-16/25 10/24/2024 EVERGREEN TELEMETRY PR—T-2 #2300123 TEMP.READINGS PROBE 10/24/2024 EVERGREEN TELEMETRY PR—T-4-6 #2300121 TEMP.READINGS PROBE 1/15-16/25 10/24/2024 EVERGREEN TELEMETRY PR—T-4-6 #2300128 TEMP.READINGS PROBE 10/24/2024 EVERGREEN TELEMETRY PR—T-5 #2300174 TEMP.READINGS PROBE 1/15-16/25 10/24/2024 EVERGREEN TELEMETRY PR—T-5 #2300176 TEMP.READINGS PROBE 10/24/2024 EVERGREEN TELEMETRY S—H-3-5 #1500377 AIR/HUMIDITY READINGS 10/24/2024 TSI 5725 #T57251550001 ROTATING VANE AIR 1/15-16/25 10/24/2024 PITOT TUBE 18" PRES. READINGS N/A PITOT TUBE 24" PRES. READINGS N/A PITOT TUBE 36" PRES. READINGS N/A EVERGREEN TELEMETRY S—DP-250 #2000105B WATER PRES. READINGS 1/15-16/25 10/24/2024 TEST GAGE, 0-30 LBS/CBI/CO 212 WATER PRES. READINGS 10/22/2019* TEST GAGE, 0-60 LBS/CBI/CO214 WATER PRES. READINGS 10/22/2019* TEST GAGE, 0-200 LBS/CBI/CO 215 WATER PRES. READINGS 10/22/2019* FUJI ULTRASONIC WATER METER #S0421134 WATER FLOW 1/15-16/25 10/25/2024 **checked to calibrated meter PROJECT ALTITUDE: 7, 908 CFM TRANS. FACTOR: 0 .8 0 REMARKS: AIR FLOW READINGS WITH EVERGREEN INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. DATE: 02/14/25 Page 16 of 17 Certified Balance Inc. of Colorado Abbreviations ADJ Adjusting MAX Maximum AHU Air Handler Unit MED Medium ALT Altitude MIN Minimum AMP Amperage MOD Moderate C/F Calibration Factor N/A Not Applicable CFM Cubic Feet per Minute - NEBB National Environmental Balancing Bureau CUH Cabinet Unit Heater NG Natural Gas CV Constant Volume - OD/ID Outside Diameter/Inside Diameter CW Chilled Water OSA Outside Air DB Dry Bulb Temperature OSAT Outside Air Temperature DD Direct Drive PRESS Pressure DIA Diameter _ OP Pressure Differential EAT Entering Air Temperature _ PSI Pounds per Square Inch EF Exhaust Fan RA Return air ERV Energy Recovery Ventilator RECIRC Recirculate ESP External Static Pressure I RPM Revolutions per Minute EWT Entering Water Temperature RTU Rooftop Unit EX Existing SA Supply Air EXH Exhaust SD Slot Diffuser FCU Fan Coil Unit SPD Speed FPM Feet per Minute SSC Solid State Speed Control GPM Gallons per Minute SP Static Pressure HD Head STD Standard HI High TAB Testing, Adjusting, and Balancing HP Horse Power TEMP Temperature HW Hot Water UH Unit Heater LAT Leaving Air Temperature VAV Variable Air Volume LWT Leaving Water Temperature VP Variable Pitch MAU Makeup Air Unit WB Wet Bulb Temperature Page 17 of 17 I 7 I B I 5 I 4 I 3 I 2 I- 1 I O ® Chillers mounted on rack attached ,„"a�oawam"wa ...a�"o°'E�Poar,.=„.rm. '" 1 2 to floor,provide vibration isolation T T 5 M2o2 requirements per report from 2020-09-04 Permit Set Acoustical Engineer Fan coils in main mechanical room are primarily horizontal units hung from above in order to provi•= Coordinate duct routing to avoid ducts above Ly«M=xnER floor space and ease of access from below �I electrical panel locations,typ.Reference IPRIDAY DESIGN 11/��� PROJECT NOTES PO BOX 7a2s electr cal drawin s for additional Information 9 ASPEN,C061612 _ _ ---___---_--.1 �� 380 CFM i< Dashed line represents outline of in-floor radiant heating zone.See Hydronic Schedule for rcslwxo \ Provide rack mount above it ` _°'• ` Al 0 X - - - - - - - - - - - - - additional information.Omit radiant tubing under refrigerators,coolers,freezers or other CONTACT: E floor for glycol feeders '�V. _____ !%CH-1 CH 3 _ _ 3 8 similar appliances.Omit radiant tubing from mechanical,wine storage or AN spaces,typ E aLUEGaEEry DLO 1 : 7 J r--m�-r "6 3005 SPRING ST.SUITE 202 Distribute SA for - 'I CH-2 —CH-4 16'x10" I V II 2 Install boiler per manufacturers recommendations,including:access clearances,vent ASPEN Co 81611 BT-Z - C O TEL'.e40.945.8675 Mechanical Room cooling S� I I, I M301._..._._.__I .` . r RAI 38 p xgM boiler.Provide condensate neat alitation kit and mute to nearest floor)drain/sink hack[o 6L44.8.46.4.R I� © Electrical/AV CONTACT:sREsanzoNE A2 AFA 3 1175 CFM—._!! FCU-3 • Refer to view references at . ( 1 • Imo' IyL�1,.I1r�lI Mechanical Room. aervooN Aonrrs A,F J 1Z X6 III.1■II■I 300 S.SPRING ST.SUITE 202 each fan coil for detailed duct —-- --- ASPEN C0.gg routing of each fan coil system - ■� .� A I 1 L — — O. forin Clearly label equipment in ena ID tags shown in these plans and provide appropriate access TEL:e7o.azs.zsss �'hiAF-1 m I 380 CFM T Conned OA to Mechanical Room FCU,provide for installation and maintenance,typ. CONTACT: �„MS TAIL.. v-GS- 380 CFM ( FCU-4 - ram-- IOA damper at connection to main OA trunk 1 1', (' i a'�• 30"x8" r_ 1130"x8" .0. Symbol represents a typical flush-mounted radiant zone manifold with access panel. MIL4-� HIGH COUNTRY ENGINEERING Mechanical Room fan coil _ 1 Connect to I 'EF-2 — �'1 Arrows denote recommended access direction.Coordinate locations and access panel 1517 BLAKE AVENUE,,SUITE 101 (with economizer cooling for l OA duct I� IIII IIII IpI III Ii li lih �-16, '- Coordinate duct routing in feld with steel column in this area detailing with Architect,typ. GLENWOOD SPRINGS,co 81601 space and wine unit heat �� J 3 o — HWC-1 CONTACT ROGER NEAL Jo sAirl Direct bury OA duct,BlueDuct or similaY 850 CFM TEL 9709252655 rejection) ® lhani Ai 1 o 1 x-.owing _ _ �� / 1 ry `�� OA in window well 05 Hatched area represents outline of in-slab radiant snowmelt zone.See SnowmeU Zone ,,R,00.............., L ..i o•ram, Schedule for additional information, • ,=`I III _ �'_ - �' 3O"x4H" —RESOURCE ENGINEERING CO 81 2 GROUP P l�11•`I ME hw c ��II N' ` © s �II 20 20x ■,I 30x48 Electric heat face in O snowmelt moisture and temperature sensor location,place control wire in conduit to allow c BELL VIEWiEA coo n4 m1 ('7 I _ r 1—II window wells,reference �`� for replacement of sensor. TeL coo ass 1z1s CONTACT:AUGUST_ B - 0 _ = 1 ■i� ■ 34'■G��I� � �,�' I ■ ' - L elect cal plans for, - - - - - - _ (-1-: L�„�y...,., DODSON 39E sir'■r� /���� addd mat information 7 Coordinate grille,diffuser and sensor locations and elevations with Architect and Interior Dryer booster fans, -14W DHW-1 E11 8 e1 {I�I!� • -•�� ���I O LoasERVATO REINTERNATIONALorHARPER q 9 .�bHW 2 ' _._�� !�.. �oz'r_�raA •ram;.��q o r.. - iai®i®aia7 �'•, Designer,typ. �/ 120 WALKER STREET.7E provide IIII! 111 N 'III ��'r I� r-: ' 4OO CFM/�•1 yy _ i NEW YORK NEW YORK 10013 installed etuivalent lent th Ifl % .11 r1N ,1■ 20 x20"'iRl /• RA ',��IIII 12"x6" Connect OA to RA of Laundry FCU,provide- - - • o�'• - - - g Install temperature sensors on interior walls,away from sources of heat.Coordinate final TEL.zlzz 5aa6a _ 1 m - - O CONTACT CARLNAGERACI _•.ij- Engineer.I� `_''-IE� — 1■-�-r_. IIII�I�IfiE�!ifrl`I/� I OA trunk r I I I Route belowncloe to re,terminate g ••rscr SA2 pppli:I' ta1lIitR�lI .14"x10"I IJ■ _1••1 �_ 75 CFM ,' mechanical enclosure,terminate within O p oNEaurroN ,�— ,•®, •, Provide cable actuated balancingdamper at each take-off from trunk duct or a maximum 12"x6" I1I !!.u1! ■ y = Laundry RA in millwork above I I EA1 _ _ _ enclosure above snow line or 36" GE WEST sr asz7 0 XT-4•,�„, I IIr1I - /■I._ t. 111 .` l I 1 ®cabinets I 1 30"x1 - above grade,whichever is greater of 10'from grille.Mount damper actuator(end of cable)behind face of grille.typ. BROOKLYN8NEw PORK n22z 88"._' I Terminate with a ooseneck turn- 9 coerncr r.1�TTEmmI Steam humidifier - �1 1i1�1_rl. 10 Duds routed in/through h structure above. CONSUL-DM r �1 Alp! �! "- 'x;=,` I ' MII■!� ® or I down,maintain 10'clearance from 1 O g D E,.,..°OENCLosuRE CONSULTING uc D H-3 I� 1 hil�lll��■12. I. ,y intakes to the building. Duds routed in p ceiling above. GLLC SU.P306 �,2!....e 12x6„II . _ ` �,�/,�.= r , zi �7.6=;.n r. 1 �� ��o` iota11 drop c'lin cavity 1Ansiwssr KEN CARYL AVENUE. Pipes and pumps — FCU-9Y— 12"% LTTLETON COLORED°80122 =.' 4"e. y y n.l' MK- I'r ® 300 CFM ; I I ,. _ Terminate make-up air dud above ra.within mounted on wall here ■,� r U-8 M3o3 1I p g 12 Provide 1/2"min.duct liner in rectangular ducts,or per acoustical report TEL:aoa 76a 1a6a IM3o2 'r'1 1 • - Bedroom Bath lanscaping with a gooseneck and insect screen, recommendations,whichever is more restrictive.Duds to be 26 a min.,continuous for CONTACT:EVERETr vEascHAVE it11�II= \ gg Yi I I M ® 36"x5" .- 19 Ill 9 .=wsn= wL.w,. I ■U211 '� 2 1 111 O maintain 10'from EA entire system.Dud dimensions shown are inside clear,typ.Air-side equipment must have / rl .� I O -- rectangular duct for 10'downstream/upstream of unit supply/return Irelurn connections before ERENws ACOUSTICS Lower Level ERV J WC 2, ILR�d 111�1■� ■ I Route vault exhaust and y NEW YORrc,NY lom4TE znz ��1��I��� '. �� ��� �® Lill, V T' transitioning to round dud is permitted. C� �_ I "-- make-upair ducts with PVC Redundant wine .V-- 1t A �E10 I �� I J11) RYAN II .�M3O1 1_ , 1 - ,1 J CONTACT:0.3 GRAYE(GLOTZBECKER) cellar units on rack W C-1 !:�H-1 •"�I I�I D AA- 200 CFM I I , O. Insulate OA duct with a minimum of 2"dud wrap(R-6)to avoid condensation. .P. :=LT... ..r- IIII I SA diffuser high on wall G.« O In, `_�1 I; MI•• 1.mil► 1_ _ — — a;; DDLDRADDPDDLDEBIGNB ,■J,�,9�-` r�_.1� � 30x5" - - 71 0,-; 1I L _, 14 Install air-side equipment per manufacturer's and acoustical report recommendation. COoonc OPOOL3RD DR ESIGNSSUITE 1oC Y — a1 1 3 � .;: ®. Provide 1"min.deflection springs rated for unit weight as vibration isolation,electrical GOLDEN,,COLORADO 80403 �' I �.�e Laundry SA diffusers in ceiling 250 CFM • Route exhaust to within 12"of finished vault floor Wine units are redundant, _ ",�� - _ - - B e - - - disconnect,condensate drain,flexible duct connections at unit,adequate coil,fifer and CONTACT ANOT tACELLf _!��� all•ned with face of upper cabinets o [12"x - motor access,and condensate drain(where required).Where needed,coordinate ceiling provide backdratt dampers / i— Route ductwork around steel column _ •6"z5 '�"""„ at duct connections to each— 1 •'Fri`=11I II II IIIIII ;= Q access panel in field and with Architect,typ. - unit to allow for alternating II 12 Coordinate manifold location in vault with spa equipment, operation ■altar I '- III --- core foundation wall for pipe routing and provide a pre- 15 Provide 4'of flex duct or acoustical liningt duct connections to grilles. e a 9 300 CFM i �l n ■ I T 8> insulated,jacketed air of S/R pipes below grade 1 O y y p ry \� - I -� - -. 1 between house and vault.Provide isolation valves just 16 Fireh aces stem b others.Provide exhaust,combustion,and make-up air as necessary ( (` - - .4 I 200 CFM I t ....■ ,r o - _ fort 'Ie nt to meet code and manufacture men 48"x4" . �•�a 1 10 • inside each foundation wall for service and maintenance. a spectf d equipme r requirements,typ. �' 300 CFM z, Insulate partition walls 30'x5� � � A - V•z, -- p I �R] ; - V�-, , SA1 I S -m r O. Space reserved for hydronic equipment(pumps,radiant manifolds,valves,expansion \ \\ at Wine Cellar,typ. I �ur rF �t x8" .=IIE'� __ 20"x10" ,1 Line of spa equipment vault,spa tanks and appurtenances.) ��� I r ■ I •esi.na de•ui• en b ••tIms \ rRA1 300 CFM It_ll■I IM1111�1 11 6 x6 _ �Rll M� , •6"x6" ■ 420 Terminate vents a minimum of 36"above adjacent grade.Maintain minimum separation of N I\ I �= Route SA du• * 00 CFM. I 1 10 linear feet between EA vent terminations and OA intakes. 48"x4" 1� . _ I I • RA grille in ceiling,centered above door below beam: 1\1T/I Bar grille and diffuser along I.i 11■,[� 30"x8" I 1 19 Spa design and detailing by others. ceiling in Wine Cellar , II `VI, " - -� J 1 - O centered on door i■ Q' 1 w I 1 • ' °`"`°'°""'"'� c 7 1 - _ _ _ Theater I - c r Provide temp sensor for ice SA in wall at floor,rotated to fit wall width O I machine closet in RA duct Jog duct down below steel beam • I -I- r 5 1 m' _=Q,p00UCF`•tl O -I Hall o RA m ceiling l 5 P Gym ventilator 8 0 1 18 8'0 - O ;'Vo��JpUBT•.1'LPF�irr 1�_ in drop above Powder Room,locate SA 11 II r -tared high on face of wall along ceiling IZIP ,I i I�p tl,,'•;• rir ' I _ 7 I mow x1s„ 1, ° 38880 D.5 �• II 1 II - - - - - VVfr Rough in a<ditional control wire mill 1pi O �' / .Pow er Ytemperature - I 11 t _ Ailk D.5 !� tY % .•ENGx_'' 1— r„ Hx6 '' V_1 Roo 2-1 •r os[at location Q Keep ducts oft wall to maintain11 •I __ ' ® /-J 1 clearance above elecUical 11 ilk';FCU-12 ins ��© _- 1 ��,���� anels,reference eledricalSA7I 1 04 26-2023 1 1 drawings for additional weJ� � S „ 'I,I1 50 CFM O� r 1 information \ ___ 9�■g- EL I] 14 ' -T 1 , 450 CFM_ • � 1 za x1 , p C� Fcu 13 T7. 234 W Francis i ntableflushmounttem erature I _� © ■.RI�� �r '•1✓' I min�XM hXI F I 1 •I athrooms for heating con0ol,typ Steam shower exhaust T �i®li 1 I D. r1 Bedroom �• ��• 'I 1 L lit (49 l 12 I III �ii y,0o - _ ® - —��:, a'�Iri'`u' �d Me<han 1 4 1 �Ii, Surface mount manifold on wall per E I , --�- li l . : -100 CFM 1— acoustical report recommendations O � no 5 ,, :I, _� © I®®i�i,I®O�i� ,I� — — Powder Room_ MD-3- �:.y 1 �'�• Ti 19�� �s ' Lt 5 — 11 r - I19• - - 18"x6" 50 CFM I _ R E G r r i�1lljA IL milr24x1" 11a� 3 8'0 — — . i—J sI Provide i"acoustical liner on I I r 14-1 �{-^• �3 ct r o is re 1 ©0 I I ��YJy I I _ _r - ,�\[o I\ 40 CCen[er SA diffuser I Q h, • t. 1 1004 .=150 din of return air to FCU-12 Hoop e N 6 l r16" GI -3✓1 -.1..„ - 1 ■ 'I © ® I I ( � high on wall abov. I . . - 1 0 —�� I' - O - — III 200 CFM reginacom• Engine 9.1216 I I. Oath door,below lightin. 40 24 CFM Ali150 CFM - — J 1 I ■�I E Consulting Engineers ® I! ® L V- I 48'k5" I 6"x6" ■1�1 m 11 �� 200 CFM II cove B I I R -� - -- -® 30"x5' Q I 24"x5' p LoungeY vlTr ` 11111r 36"x4" B Mechanical•Structural•Energy • S a 7 I — ,. I I ,I 3�+r , 5�, I Provide access panel far hydronic � I'� /i Mr 111, efficiency susta naminy simplicity O �� 1 50 cfm of exhaust air to V-3 L - - - A���� _ L manifold n rear of Gym millwork, A .as =a ------- '�� - i�••„1_�••1e-1 CFM coordinate detailing with Architect L III — — — 12'x8" r , - - - - 1 ® 30"x1"1 1 - ,,' 1�x8` w Mase Q Combine RA and EA into a 2020-09-04 Permit set 1 0 I 1 r �i'}•� single grille concealed in 2ozo42-04 aD%CD Check Se mp 0 I Electric heat trace in window wells,typ. b-'. 1 1 1 - J I _ 1 1 O Ia 200 CFM vertical face of cove lighting 2020-12-17 80%CD set 75 CFM 1 -"Bathroom ► 1 1 /��/ Sauna I I�11r111 =,�'T.ktp detail 2021-02-21 CD Check Set EA1 O I �` I ,1 Gym 1 _ 30„5, a _ 5 2021-03-10 CD set `o '• A'•-' - y 0� \I 2021-04-02 COA Building Permit 30"x1" 11 6"x6" Re■I r/ '•edroom 111 - JIi _I I Shower/Steamillig gd1�L 1 ��� ������ IC MN 2022-01-04 For BuildictiPermdon Surface mount manifold on 20 1 i�ip00t10 , �I �r 1ailk 022-04-0e For Construction _ wall per acoustical report I� �`il Oyiiii� ��1recommendations .,x V 1 II_'•�� 01 I ■�iii: - 1 Center FA grille above door, I�N I - .25 CF - _ ® 023 oz 21 For Construction ' 'a ^`- -- = 30426 Bulletin 04 -,.\ © • locate in vertical face of I _ x4", `\ �- aL IF- `-- e:', s 1 recessed cove lighting detail _L �� ► s zo2W am I I II Q , i I '© 01 ®P l ' es�_ a RA grille concealed in vertical face of cove lighting detail0 Ld wL ® ®150 CFM1 i 1V{I ®"• I.; - \ ! Warmboard radiant walls in shower,reference schedules fo ditional information • - - , • J•i �, 200 CFM w I .ills lJ l� l EA grille concealed in vertical face of cove lighting detail © 3 Mechanical 2 - - 30"x5" 1 i ,1 / t�•A1_. _ I; _ . F, 30"x5" i (I+3 14 FCU-10 , _ _ - - _ - • �.1 r 'Nl ;n ` li,� ���Mao'H 7 Locate space temperature sensor below bl nch for radiant control Provide 1"acoustical liner on •- 1 ! _rg Rlr'_.7771�NN. -.li Q Route ducts below steel beam in drop ceiling RA duct per acoustical report ' ';I►�MWM �� -®® aO/////( 'OO CFM - WiriMMAL r ���_ ' Reserves ace for water treatment a ui m 12 ' G ��� .-. ...... .. .; 8x4IFM11741P1 b \m3o3 £ - '® _�wN� ' _ _ _snower alon coat(�alltof rs) equipment ant Basement Mechanical Plan Maoa Mz01 - Locate steam generator for steam A G � ' mechanical9 ni b Ohe A L ------ 12„X4„ \ FCU-14 located below FCU-11,bottom of fan coil at-T-6"AFF Tap duct into RA plenum above Hold ducts tight to structure above to maintain clearance for cove lighting detail at ceiling "2 02� Locate RA grille in vertical face of recessed cove lighting detail ® O Basement Mechanical Plan 1/4" = 1'-0" - -91/4"=t'-0"" o""w„... 2988„o. I 7 I 6 I I 4 I 3 I 2 I I I 1 , I 6 I 5 I 4 I 6 I 2 I 1 I ,•.....!f>!�0400400400400400400400• •00400• .0.........•i..♦•i...•♦.. Provide separate snowmelt loopwith isolation valves ''' :�i•♦•i♦•••`•i•♦•iii♦•iii♦•i•♦•i♦•i♦•i♦•♦•♦•i♦•i•♦•i♦•i•♦•i♦•iii♦•i•♦•i♦•i•♦....�L•i♦•i•♦•i♦•♦•ii♦•i•••O♦•O•i♦•i P ,„E,„,o„w„mE„w,„o„a.."„oaruooar,w�„rm. ��♦ .{ ♦ ♦.. ...�:_. • ♦. 1 A1. �1.�.9A. _ located in mechanical room below for portion of 5 �iiiiiiiiii•'iiiiiiiiiiiiiiiiiiii•'i•4�®'iiiiiiiiiiiiiiiiii••�'i� T :•i��•e �. • sowmelt zone that is outside of property line ��•i•�I is�pii♦.•ii♦.•ii♦.•ii♦.•ii♦.•ii♦.•ii♦..•i1I••i1I••Oi••.••I••Oi•••ii..•i��® ® ® ® � •i: Property line,reference Civil for additional information Fo2020-09-04EPermit Set �EE .®I.�i�I:isipO:isipO:isipO:isip;•ii:i;•ii:i;•ii:iii:���� I•J��®I•J��®I®•O®•J���'�I�®���♦�1�♦�♦®��♦�♦�/ Lo«,wox,�R � 0:;:.J•����������;:���� V•:.•{�.`•:{�♦ �• ♦® ♦ ��� �•�®®' � ®® provide additiona125 cfm exhaust fan for trash enclosure 0ERIOAY DESIGN ,O•♦♦♦ • • ♦♦♦:♦♦.♦♦.♦♦.♦♦♦i.i��®�®®��®�®®�®��® �® d'®® Ir• � � PROJECT NOTES PO Box Tana ��•1�••••1,�•�•1�••••1�♦••��•••1�••••1�••�•0• ♦ ♦ ♦ ♦ ♦ ♦ ASPEN.CO.0612 {{ ��{•{ {•{{{•�• •{��•���•���� w ® ® w� {® . Electrical equipment,reference electdcal plans for additional information 1 Dashed line re resents outline of in-floor radiant heatin zone.See H dronic Schedule for :j1: m.•./g ......•. . .... W W W .- ' i Q- P 9 Y TEL of rcslwxo O - - s/� *- - - - - - - - - additional information.Omit radiant tubing under refrigerators,coolers,freezers or other) �,oa�E PPCHIECT E - _ _ similar appliances.Omit radiant tubing from mechanical,wine storage or AN spaces,typ. E awscREEry aLo A ♦®� �®oA�o t 300E REENG S5 SUITE.202 liter :.a-®'� Dryer vent- �pn Acoustic detailing of fence by Others O2 Install boiler per manufacturer's recommendations,including:access clearances,vent I /!Ill�fl" �•'♦ {{{{pjp� P asizes/materials,s stem fill water quality, ASPEN, soaeee�s Fan located in framing,provide access for service I I,eO®�/®0►®♦ ♦♦♦ ♦♦� I'y pipe y q ty,electrical disconnect.Slope vents back[o CONTACT:SNERI SAN8ONE Ii ��It•! O♦••�®�� :I, boiler.Mechanical Provide condensate neutralitation kit and route to nearest ilex drain/sink in BrvooN Ao0.AMs ® �.®®�®�®�i®a®�®i�-'I Mechanical Room. L. •, ® ® �••, 300E SPRING ST.SUITE 202 /•� 'j--•:4 -" �• l; O. Clearly label equipment with ID tags shown in these plans and provide appropriate access ASPEN,C061611 Ducts routed thrue framing,maintain ��,� manufacturers required spacing for penetrations 0 0����® ®Oe� Dryer ducts routed tight to bottom for installation and maintenance,typ. CONincr SARA ADAMS I � �' � r- �0� ! �•� ®®i®�oi�®i� j of stair framing up into joist bay I I MIL•'HG„••R II •_n���{0 ��♦•��♦� �i•�i��I�� .,„ O Arrows Symbol danoterepresents recomme typical nded accessflush-mounted d'vection�Coo dina[eant zone alooaton with s andaccess accesspanel. anal HIGH COUNTRY ENGINEERING fl II i hp ��,���� ,,�{��!� �i(h, detailing with Architect,typ. TES:9Tosis.2865 coa16D1 I •I 150 CFM 4�j�j� ♦1 {>�.��{ . {♦ S{t CONTACT:ROGER NEAL ,J' •J♦•♦♦J•i♦J.•iJ•.O.4, I— -I— - 5 Hatched area represents outline of in-slab radiant snowmelt zone.See Snowmelt Zone EXIMEEP � 1 ���a'®ads yrB•��♦{�•♦♦.•,♦•♦♦♦••�♦ra JL O Schedule for additional information,typ. EE„NGINE �ed.:-!� r�t 64 -I�ry) Y I— II I —RESOURCE ENGINEERING GROUP �9 1 III Garage PPr?,� �`! i•i u� I O Snowmelt moisture and temperature sensor location,place control wire in conduit to allow c�au 01 5eu co sine ss I >�'♦ `.O®A��••iS ♦♦ { for re lacement of sensor TEL:Woa4e•1216 _ B - - II - _ - - ® - - o�0i:��ii..�iiO,.r♦��♦�so>S ♦�� - - - - _ n .�,„"oE•�•„ COON ® 7 Coordinate grille,diffuser and sensor locations and elevations with Architect and Interior �� i / O LoesERVATO RE or rsunosoc HARPER / / Designer,typ. 120 WALKER STREEr TE 1 9r L. Exhaust grille aligned with framing, 1 TE�21�255 C4Ew PORK t0o13 ® O8 Install temperature sensors on Interior walls,away from sources of heat.Coordinate final CONTACT:5.446 rvA GERACI - I �' ® I centered above dog wash adjacent to M201 I i .moos with Architect and Engineer. ..ao„„/UAW ® I framing for stair boxI go O 225 CIIIIIF 1 / © A .r•:le cable actuated balancing damper at each take-off from trunk duct or a maximum 67 wEST s>"a527 � I I �' /''r e•-r o-as-e u re. •ro to.ucc to-.o a 44"x5" 1/ .f 1 from rille.Mount dam er actuator end of cable behind face of rille. BROOKLYN.New YORK 11222 TEL! I © e q I JpJ♦4'pJ♦4'J4A♦♦♦♦♦♦4A4'J 9 P ( ) 9 tYPM201 �/ 8.0025 '.^�� s � JiJdCONTACTaM4Tr EMM® I I Snowmelt i:i t' auarouted intthrough structure above. _6"x1O 2D ,OV 6"z12", t_„w� 1 tubinginstalled � � D APPOED ENCLOSURE CONSULTING LTC v / �p��']1 2 in spa coping au. routed in drop ceiling cavity above. 11757 WEST KEN CARYL AVENUE,SURE F308 I tt �{ LITILETON.SCOLORPD0601TJ �� - - - ®- m___ _ ►/I -_ x Living Room �V ::� "ro ide 1l2"min.duct liner in rectangular ducts,or per acoustical report corvTncreEVEaErr vEasclwvE %iii�� r — _� I I ��fl ��••. ec. mendations,whichever is more restrictive.Ducts[o be 26 ga min.,continuous for �agna ,wrr�,r ��®J■1/ �r Center on windows and.p� !:♦:♦' -nti-system.Duct dimensions shown are inside clear,typ.Air-side equipment must have �.�.�� .P u41 ® __ I 23 I 1:� Oi 0.� EREMos ACOUSTICS J.O,JO����'® �.'1 "x6" O coordinate framing layout ,♦♦ ea:ngalar duct for 10'downstreamlupstream of unit supplylreturn connections before P.� •i" ® ,m• " ® I O I to allow space for SA �:p • � ramitioning to round dud is permitted. NEW ORK,NY 10014 TE oz iii•♦•••i�� �� - o�• ` r Plenum box in floor ,•::� '••� I TEL:646650223E N:•.♦� 4. el: : ' ���r �� CONTACT:RYAN GRAVE(GLOTZBECKER) ♦••.♦®� \ I v I framing close to windows.♦♦ its =te OA duct with a minimum of 2"dud wrap(R-6)to avoid condensation. ®,,: J Provide concentric vent v /fjt I �� 1 I ;::% $P" Su�T+T iiiii•♦.� � I connection for boiler Sue I I /'7 - r:p� its=II air-side equipment per manufacturer's and acoustical report recommendations. coLORaoo Pool DESIGNS u. . Q Jog EA dud in roof framing . 11301 W.43RD DR.,SUITE moc ♦.•♦♦i.•i®�®® I e Kim L_ :•'O�{{♦♦{{♦�{�♦♦{-{♦ ♦:.44 -rov de 1"min.deflection springs rated for unit weight as vibration isolation,electrical GOLDEN,COLORADO 60403 ......•3®•®•, L — J ■ 1 .•....•....•. :-..p.•4•..••• TEL:720.693.8146 ,:♦;•:�♦:♦•�•®®®® T RA below open stair treads, {.N� .�..♦ .e♦.�.♦.e�.�:�..:�� •is•nned,condensate drain,flexible duct connections at unit,adequate coil,filter and p♦••{{A�� P 225 CFM �I vOJaJO�J��Ji�• mo•r access,and condensate drain where required).Where needed,coordinate ceilingCONTACT:Arvor ucEL20 ♦{{{♦0��®� I coordinate detail with Architect �� ppp♦ppp♦ppp♦p• ( ,ii....• ®• •/ Boiler vents in corner Ji..........• a r s panel in field and with Architect,typ. ` iiiip•.®®®® 4 44" I JJ�:!{.•Ji•J•Jii.� 0{•..{♦{• ® I I w�®400 CFM © {.•��e.-%,.{• — ,•.•♦♦•.• ®®®® it ����•�♦�� �• Provide 4'of flex dud or acoustical liningat duct connections to grilles. iiiii••� ®®�� - 40-o8" � • JOiiii!^{.913/16'� ® \�\ 0♦O♦..♦i•�i�i r L - L y0ii:p�{p" O. Fireplace system b others.Provide exhaust,combustion,and make-up air as necessary \ ♦♦•• ®®0®® I ♦♦ 00♦• P Y Y P rY _ _ , � •�.� - -Ent Hall_ ®'/ �/ /�// 7////�// >:p�:�p==♦���pp�: -for the specified equipment to meet code and manufacturer requirements,t C •iiiiiii' ♦: 1s r! %9 i.. \ �i0♦:ODO♦'®♦®,:� yOJiJOJi00JJ• 17 S ace reserved for h dronic equipment um \ ,:i:0♦:i• ®�i♦, 1 2'I I 1 ♦�y�pi������ O P Y (pumps,radiant manifolds,valves,expansion \ \ '. 1.® �i: I ®♦®♦®♦�♦®♦�4-G- m as a a� ®iaT maim ® aT�i�♦�♦�°� iii'iiiiii♦i♦ tanks and appurtenances.) ...•.. I ®�®�®®.�®® ®®®®® 0•...•.....,. �� �fll I I '•®®®®®®®®®®®®® �e ®•®• ♦1 _ _ _ _ _ •O•ii♦iiiiiii O I ®®®® ® ® ® � ®� ®_ .♦♦ ♦♦♦ ♦♦♦ 18 Terminate vents a minimum of ter above adjacent grade.Maintain minimum separation of N ♦pp♦♦ a - - { { { { {� ' p♦•♦y♦•♦pp♦•♦ 1011near feet between EA vent terminations and OA intakes. � I III1.1 I ®®i®®i®®i®�i®�' - -- - - _ i®®i®®i®��®®i®®i®®..3 1/`�®�!°aass i�s''a%::''aa ... .. 0��®®®� I I ♦�♦�♦•�� - W`♦ ♦ ♦ ♦•I��I♦�� iJi•Oi�ii� �i �iii 19 Spa design and detailing by others. iB i hii'd. _ II•� ®®I®®I®�I•J•::•�J� I®®I®®I����I♦.:��. � OI:J.O:J.O� : o n c O4J. ®�v ® ® ® �s•�•�T�aysLs_esLs_esLs_esL's_e'sL's_e'sL's_e'sL's_e'sL's_e'sL's_esL_•�S�®ST?® ® ® �• O♦.oi`�:ii00iid00000000♦O••i Route EA duct tight c �•iii•.��♦•�•i�0 f I ®®®®®®�a�A�® _�a•-iiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiiii � ®�'®��iiiiiiiiiiiii<: iiiiiii o roof framing 00 CFM i::'�i:♦3®♦®�� I . ®®®®®®��®®®®®,®®®®®®®®®®®®®®�®®�®®�®®�®®�®®�®®�®®�®®�®� O 7► ?se 18"x12" p"Ci"IIQFtt 1 CD/ ...iiiiii:♦�t;�®®�-- I ���♦��BOB�B®�sq�♦��8�B�B®����♦��8�♦�B®�♦®��B®�B�♦�B®�♦���: - - - - �75 CF 14x10 �',.pT TF�I1rr•O I1 ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ♦ ' ►/I' 14"x10 80' ' - - - Ail --t - ,A. �: 04'J.i '' sit IC8 ••CD _ ................ � gyp _��,�.®,��.®v®.® ®Jo°r _�$ 69� ^ - FM 1,9I ® D.5 /`�F1t to above,coordinate foal II m / -quired"clearchase / E~�� t;EN O 18"x12"�• �8"x12' required for ducts Property line,reference Civil •kitchen hood sizing and duct I '� I �O to/from below 04-26-2023 for additional information g I I Make-up air in face of upper soffit 6' routing with Architect and Q3 '� � Bath 6.4 ® Of I + 0 I�,( 24 ._ Provide paintable flush I P 940CFM / 7 %� mount temperature 234 W Francis 1Inee r t \ / I 1•0"x16" 1 ®1282"x4 Iir . a , 1 '� I •30'k41/2 KH 1 2 I I ® t� heating control,typ. 0 1 l an 19"x4 I 6 ®i®®terIr � r/ / / /i//i ®di[chen / ', ' 'fir/ X ,xi':l I m 4 � yr - - ((( o o� - - - - ��� REG Transition to-Wide duct ettop of 1o"x4 I:: p , I p R N0 / I.„s .•• ® ssoU Rcs SA ducts from below to distribute I I (♦1 I,• I +I�©®•®®•� Q I I "" r r 3 aiflow into plenum above hood 1 I I . © 30"x41/2} - L �•��• • I 140 FM 41O I reginacom•970.349.1216 / \ 1 : _ .. • • I Consulting Engineers I� ® I ® 24"XS" 1$'X4" II I B Mechanical•Structural•Energy B IJ 8"x16 `1 )l 'S1 1 Coordinate diffuser detailing_ �•�•i�����•���.r�p�yy 0•�p{ypy p��yyp�ypp�py�yj ypppy do ° RA grille located on top of millwork, 1 2 i i � j�•Qipi•O"i•�ipp•♦•i ; ppiip� ii '—. I I LL g with Architect at comer with Architect,1 ♦ ♦• �• ♦• ♦• ♦• ♦h ♦• ♦• ♦• ♦•♦♦ coordinate detailing DP I I 270 CFM ♦�®♦�®�•" : ®iJi''0'�•.•�ii�®iiiiiiiiii: iii'i•♦iii•♦E,O•i•♦iii�ii••••ii E+ Cabin IFIH' efficiency lsustainability lsimplicity I 0 ®�®�I;00�'-a,{♦�j��p'..� _♦�e.........!♦Oe':i :� :wi:0•!iii•O:!J' 350 CFM1LQ�•— J R 36"x41/2" ♦®Ht®♦♦ ♦♦Oi °Q—.—, �♦�6: �♦ ... �•e_❖.•. I 25 I _. I „ ,as iiiiiiiiiiiiiii V7 — ^.�� -. _l —I_ .. ��®�♦�O��0i••••O••iiiii0ii i��ii��'iii••ii��iii�il��ii••ii�iiiiyiii' O ,® 84"x4" i��� / -� �•® •®•tii4• •iri'••♦ii♦®IO�i®IOi••iii0♦♦.••i•Oi� / RA ducts to below I -- ERV ducts to/from above, I %•,. 4�•�,:t.�p:{:�{:F:{:gip:{:i4;•:{:�***•42 �. enter on windows and t to••iii j connected to 8"dee. 2020-09-04 Permit set /I, r- jog around beam above ♦ �1 O-..-♦�♦�-. -fie♦�♦♦�♦♦LO♦♦.♦O♦ ♦'' -' , I 2020-12-04 80%CD CheckSet I ®®®®�' oordinate framing layout to !� plenum below rille 1 u I1 allow space for SA plenum 1$'X4' zozo-tz-n eo%cD set 2"x10"wall framing required •�♦ _- box in floor framing dose to dn� 2021-02-21 ce Check Set I Q5 for SA ducts to kitchen -�.• ��.•�• windows.- zozl-03-m co set 40 CFM 140 CFM 2021-04-02 COA Building Permit ®400 CFM SA diffuser centered high on wall above bar,coordl at _ I 2o2zo1-o4 COA Building Permit 1 final length with Architect and Interior Designer (♦ 2022-02-04 For oonstmction � I ® . 24"x5" j® 24"z5" I `,, 94"x5" I ) A022-04-08 For Construction r' O 023-02-21 For Constmction 1 1 Provide 8"clear drop for , - - - - J p P p�p����� 1st 7+ P Entry Y I, o • ��� �\ 5 023-042s Bulletin 04 / town I..._15a� 16,k6" "JI I Chi hatSA dextends uct across ast column shall be inactive } en grille In floor ri clear a walls at ndeach_ I� _-- _ __. _-_ - _.h IY [. __ and Powder Room j J i6'z6' Route dud u to column,an SA diffuser i end,coordinate grille stiffeners and ® — , fastening detail with Architect Q 202 _ I P I )) Route to V-2 on level below 1 ® > I 61 I Entry I I Powder Room 18 � , Is � O I `IJ I�D,y_�. J First Floor Mechanical Plan L - - - J/ .0 CFM- 'e1iYi' %l»iF'"41 Q I t T w s� ^I^r^I e 1 1 Lj - ' 12"X4" �� Lj� J 1 1150 CFM El:,.) /22 RA3 155"x5" O O O G M 102 CAD First Floor Mechanical Plan 1/4" = 1'-0" _ - -91/4.=1'-0" — 2968„o. I 7 I 6 I 5 I 4 I 3 I 2 I 1 1 I , 1 6 I 5 I 4 I 3 I 2 I 1 I / / a"oa pam a o E� r m T 1.2 T 3 �" 5 � ISSUNCE / / 2020-09-04 Permit Set H I' i i 0 LOCAL MOWER PROJECT NOTES 1FRIDAY DESIGN Po Box 7925 O / �, Lw aEwcEN.C�081812 • At I 1 I Dashed line represents outline of in-floor radiant heating zone.See Hydronic Schedule for CONTACT:DE.K SKALA° ASP ��������������������� I/ • �� 1— additional information.Omit radiant tubing under refrigerators,coolers,freezers or other E .555 r appliances.Omit radiant tubing from mechanical,wine storage or AN spaces,typ. E awE simile I� , \, I ,/ \ O Install boiler per manufacturer's recommendations,Including:access clearances,vent GREEN BUD BLUE s E 202 �, -�" I-- -I \ , \ \ pipe sizes/materials,system fill water quality,electrical t disconnect.Slope vents back to CONTACT: NE EL'.9 . HLST boiler.Provide condensate neutral Cation kit and route to nearest floor drain/sinkin coNr ®O 1 ,\ \ /-' \" Mechanical Room. sENDONAS. ecsr.SUITE 202 --—-- -—-- ® O3 for in label equi m air with ID tags shown in these plans and provide appropriate access ASPEN,C081611 RA1 200 CFM RA located above bathroom door \ for Installation and maintenance,yp./ CONTACT:SARA ADAMS 30"x5„ \ 4/Symbol represents a typical flush-mounted radiant zone manifold with access panel. ®75 CFM -----� ,\/ \ -----� 4 HIGH COUNTRY ENGINEERING v ` Arrows denote recommended access direction.Coordinate locations and access panel 1517 BtAKE AVENUE SUITE 101 O ° '30"x1" detailing with Architect,typ. GLENWOOD TEL 9709252855 SPRINGS, ®2::CFM— �® — — \ \ / CONTACT:ROGER NEAL 81801 I I _�\� r <5> Hatched area represents outline of in-slab radiant snowmelt zone.Sea Snowmelt Zone „ .,,,,ik„M,E,E„o,„,Ep 36x5I .___ DN \ I I / N Schedule for additional information,typ. — _Bed2ro�om 5-1 _ —limo 8"x4" I I \ \ ,- /, / O for uinao TEL: 9703ENGINEERINGGROUP RESOURCEBELLE 9.1216 • VIEW g S wm moisture and temperature sensor location,place control wire in conduit to allow CRESTED Bum,co a 224 zm1 I TEL: AUGUST fo replacement of sensor. O III I I ! Bath / % <7> Coordinate grille,diffuser and sensor locations and elevations with Architect and Interior Grva8� u�Gusr Rasu000soN HARPER --—1-i /- v Designer.typ. �� im WALKER STTRREET.7E noNu Ili - /pI 9 ® NEW YORK5 NEW YORK 10013 Box out duct boot _ 8 Install temperature sensors on intedor walls,away from sources of heat.Coordinate final corvrncr5cnawrvn GERncI I I 0 I O Provide cable actuated balancing damper at each take-off from trunk duct or a maximum snwssrs�asz7 I l ;i of 10'from grille.Mount damper actuator(end of cable)behind face of grille.typ. BTvOKLVNe NEW YORK 11222 corvrAcr NwTT Emml 15 D I ■� 4t, Ducts routed in drop ceiling structure above. D emuoa.TV:!"vwr L — — — — — — 11— — II� Ducts routed in drop ceiling cavity above. a757W ST KEN CARcoesurnrvSUWEN.KENRARYLAVENUE,SURE F308 LITILETON.3COLORAG08012J Provide 1/2"min.duct liner in rectangular ducts,or per acoustical reportcorvTncreEvEaErr vERscHavE�� ���®��� �� •������ recommendations,whichever is more restrictive.Ducts to be 26 ga ruin.,continuous for .uwEnc...LT..' Oentire system.Duct dimensions shown are inside clear,typ.Air-side equipment must haveErectangular duct for 10'downstream/upstream of unit supply/return connections before RENws Acousncs trensitioning to round duct is permitted. NEW PORK,NY 10014TE z 11�I Provide chase for ducts lNtrom below C L s46ssso223s CONTACT:RYANGRAYS ie vnzerccrni F14 from lower level thru roof Insulate OA duct with a minimum of 2"duct wrap(R-6)to avoid condensation. Install air-side equipment per manufacturer's)and acoustical report recommendations. ii3oi w��oo13.DESIGNS UITE 510 Provide 1"min.deflection springs rated for unit weight as vibration isolation,electrical GOLDEN,,COLORADO 80403 \ disconnect,condensate drain,flexible duct connections at adequate coil,Ater —CONTACT ANDY LACELLE Mechanical room exhaust terminationgip motor access,and condensate drain(where required).Where needed,coordinate ceiling access panel in field and with Architect,typ. Boiler vent terminations with concentric vent kit 15 Provide 4'of flex duct or acoustical lining at duct connections to grilles. \ 16. Fireplace system by others.Provide exhaust,combustion,and make-up air as necessary \`\ — — I— — 1 — — — — —E — I— — — — — — — p — — for the specified equipment to meet code and manufacturer requirements.typ-�C 1 17 Space reserved for hydronic equipment(pumps,radiant manifolds,valves,expansion/ \ I.\\\ tanks and appurtenances.) ^ I 18 Terminate vents a minimum of 36"above adjacent grade.Maintain minimum separation of N 10 linear feet between EA vent terminations and OA intakes. rr� 19 Spa design and detailing by others. �� a�LLa,o»An� G c _�OQ,p00 UCFtiT I1 •PJ �••'' rrl Provide 1"acoustical liner on �' RA duct per aco 'cal report P 1600 CFM 38880 D.5 —�r rPili =,r yII I D.5 �il' E�,� Angle top corn St to align with roof plane „_ ti- ® ,,5 ONAI. M � `11`\A1l`�-I . —le I "fir' 1 1 1 \�`i1 I ,II Route kitchen hood exhaust to dormer above bedroom al — 0anc s 023 ,---1�- x z �lv, ;� 200 CFM ,r 66" M. RA7 1 Wan II `1" , O 3s^x5^ 1 � 1 1 234 W Francis 1 1 ,`U 1 ., = I \y y 250 cF -Bedroom_ _ — I `1 — — — — — — — — — Hatched area represents mechanical mezzanine �`w t:til r above ceiling,accessed from hall ceilin In Stud , r1�I.•_1 g" y \ y , I!��`,I'ICI 36-x5' RA high on vertical face,aligned with I A R E G `i6"z101EM 1 CROUP \ `I `I 1 80 ,sei Remote fan for kitchen hood suspended from roof framing c°N E E a I N c `,i',��1I 1 ® and located above hall,provide vibration isolation per ,, `I 1, I e Acoustical report dated 11-26-22 Manifold in mechanical mezzanine on wall face ,its•yr•�w ,,.. IP I reginc.com•970.349.1216 where ceiling below steps up above the bathroom r,►'� 41 r.�� O®— _ O J Consulting �� 4'. . m1L 225 CFM— T.. g Engineers B , rp���ryy RA1 i /! I B Mechanical•Structural•Energy 36x6" 28 , I r 1 efficiency susta nobility simplicity �- •, \ 12'xs" SA diffuser high on vertical face,aligned with RA t� 1 I!_II!_12 x6' 'r '1,-'1, I ussiaz sl��..1� °� ILI I ® 0 ` — — — —SALE!' e 2020-09-04 Permit se (�� p , O SA above cabinets N I - ®Al I • ) 250 CFM I 2020-12-17 80%CD Check Bet et 3 Iti IlL.,i la Q®�0 2021-02-21 CD Che CD ko 36"z5" I 2021-02-21 CD Check set 27 I 2021-08-02 CO B p s'xs° et 20210104 COA Building Permit Dressing Room 2022-01-04 COA Building Permit 1 2022-02-04 For Construction Bathroom Nit //��_2_022-04-08 For Construction ��I '26' - 971 I I 023-02-21 For Construction — FA1 75 CFM! ` `w� I RA in ceiling of hallway I 023-04-26 Bulletin 04 30"x1" I L `Ii'� Access hatch in ceiling,coordinate detailing with Architect l36 �~t- I r e1® —14 lem �o 0 I g-r®al� rd am 16 1 I I 1 — it 96 $ OJ J.• 'S P S tt�4,Amonsl61elaie7l'. — J err sti`si ien�eutmennin�ea 1 r Second Floor Mechanical 4P1e19ei ii iNil i e1[j L L _ _ J �, Plan e�Caler�a/1 gg� m®api�e 9111®®1411IIIIMINIMIV11E� -L1 d ��/ ,r,,/,r/,r — — - — — — — — — — 1 1 .^"I it GI'�i' of I IH -Itll I 0 2 3 0 © O M103 ® ED Second Floor Mechanical Plan _•1/4"=1'0. '''''". No. 2988 I 7 I 6 I 5 I 4 I 3 I 2 I 1 I I T I a I 6 I 4 I 5 I 2 I I I T ,�Eoa,oawamE�w.�oA,.ATa.o,sr�ir�. - 2020-09-04 Permit Set I I I 1 m1 Jm : ' : 7928 PRCHIECT PO BOX aE swxo ASPEN,00 S.S O 81611 TEN BUD E202 H-sue I I I TEL.0...3675 H-1 I CONTACT BHERI SANZONE I ' � �a.Illp� J li M-4 I-I-rI- " .a1� -- I - - - - 17. BeNooN DRAMs 1 ,'� I I =-�-F 300 S.SPRING ST,SUITE 202 I li ASPEN,,CO 81611 ConneOA duct to 1 I I 0 LL _L 4 1Coordinate duct routing in field with steel column in this area }- - - I i CONTACT:sAan owls 1 -- - I I -..HGx.ER Mechanical .c9 - .r®iii O I�I i - I " HIGH COUNTRY ENGINEERING 1517' .� Wine Cellar I $ 1 �'. 'f - O - 'a XB"-- I - - - - - CONTACT: :AVENUE AL 101 XTEL.GLENWOOD SPRINGS,CO 8160 0 � o a a a a as�n C � T"�v oE�wE4L 0 ® �.-��� I L. © .j p r rl 1 it -RESOURCE ENGINEERINGG B�i 1 FCu-11 'f- 1 1 � ® L, a B I I I e� I H r— — 426BEC.STE"ueu coS°n GROUP �91 L 1 I Y I CON GP 20°x2a�;5ii' I L , I Route SA duct 1 I 90 a��1�6THA6z000BONH HARPER EL: LF . -MD 2-"- I below beam I I 1 BSERVATORE NTERNABONAL WALKER120 STREET,TE I I - - - 1 - L - _ _ III ITEL:212 NEW YORK NEW YORK 10013 N11 CONTACT CARL3NA GERACI 74 I pri I / 1 w- I 7 _� J Theater e>"wE TTON I I I 2Jog duct down below steel beam O enooKLVNeEw cone n 2z 1 tltl Hall 1 A- - - - - _ in drop above Powder Room,locate SA CONEIM.TACT:MATT EMI I I I Bedroom O di"user ce tered high on face of wall along ceiling 0 o ��. Laundry _t�k- I 10 ° 1APA WEST KEN CARYL AVENUE,SU.F308 1 1 NCLOSURE CONSULTING LTC -� I- NIE ETNwCOL ORAD03012J I ar - Rough in a,&iona!control wire CONTACT:EVERETT VERSCHAVE nc A I I �4 "' I - - 'Pow er 1� for secon,=ry temperature �•5 I _= I V 1 Room sensorttheo ostat location 3 I I L 5___I A J ® TEL 696 660 2236 014 I F 70"X5" CONTACT:RYAN GRAYS(GLOTZBECKER) Ij I I — �� SPACAN55... - I I Route ductwork around steel column 11301 W 03RD DR.SUITE DESIGNS — I I - _!_ r, I I 1� GD�EN,6CGLGR DG6�63 I L 1 I 1201 Bedroom I � �, - EL rz3.ga.aia6 1 CONTACT:ANOT ACEL f I 1 - I +0 \� g�, " " " ""'�, ®FCU2 System; 1/4" = 1'-0" 1 - -Route SA duct I• I 380 CFM \ \ I below beam I 1 I I RA1 3o'xs° -CH-2 C — J I- x J - - J I CH-1_,„U 3 3�H-4� r 111 i6'x10 �_�_� N BT- _ -I I - Electrical/AV RA1 380 CFM O Hall �'x ��III�12 30x8 .,....- �I 9 c 0 - ww I� LITHj `O SA1 380 CFM r gICFM 4-� I 30"x8" r SA1 '_o, .....l..„..1.•ous'r'••., hD.5 1 D.5 1 A�Iuulu1111111 Sx,DI� °'r v I 11 'f r Power Q I 8"x16" , V-1 Roo Mechanical) t I/ LQ.. (3�1- �"'I 1 T T FCU-3-System ��1. ONAIE_N_���r��rs�.�rs� er, I CD 1/4" = 11-011iiir 04-26-2023 I L - J 1 Bedroom I ra:*: . ye . B ®5 / �//- E 234 W Francis M I1 ' 1 lliii �H-4 L rr R E G 8"x16" A 1 t FCU4 J. I - I I Connecto rT— I 1 Bath I d m 1. I. .- L FM. - - J HINT O L 1 w1 ' L - reginacomc R97QSa9.121B J - L I I e>_ 8,1 .:; Consulting Engineers B ___.., //'/// ��= I -- I ..� : B Mechanical•Structural•Energy .w .- .. ®,� I - 8 J ���� - efficient t bilit simplicity 7- , \ 1 I .mzuz\ = I )�~ rr2 02 l l ; J s+{1 iiioi J J O efficiency yls�mP tv © 1� I•�-I 1 }J I Electric heat trace in window wells,typ. L ��� _ "'"'�� - - ��� — — — �/ m I Gym I I - 1 I.a ) 2020-09-04 Permit Set r edroom I ....: III 12 - I I I -I I' _ 2020-12-04 80%CD Seen set 0 ♦♦♦.♦♦ - 202-02-11 OD he Set ♦♦.�.♦ 2021-02-21 CD Check Set 2 • I I .....•o• I — I I _ I I 2021-03-n co Set 7. I �::.= - 'I IME illin II% - 2021-04-02 COA Building Permit r- 2022-01-04 COA Building Permit ( C ` I '/" 2022 02-04 For Consbucbon Amr. i I r I8 For Construction J 1 I I 1 Batlhl %A\2023-02-2211 For Consbuction — _ I I ) Bedroom I 5 023-0426 Bulletin04 ..: sundry I 1 2L11 1 I 1I ® I 1 I 10 H- ) I 1 r1 %3' L J I 1 1 L f I I 1 I f G - - - i m r I i I , I ! 1 I Fan Coil Systems FCU-1 System - 1 i :'I o m� a CD 1/4" = 1'-0" 1 ED FCU-4 System M301 1/4" = 1'-0" 2 3 40 P�.a. -•1/4•=1'-0" 2968 xo I 7 I 6 I 5 I 4 I 3 I 2 I 1 I I I 3 I 5 I 4 I 3 I 2 I 1 I 2020-09-04 Permit Set IRBO Y DESIGN11.2 BGx 7928PEN.C081612I 0.309.0696 REK SKALKO EE EGREEN BLOI I 12� 5 s SUITE 202 �75 CFM ASPEN,CO 81611 SA2 I I - J1 "x6" 9 r ZONE c 12,x6, I] XT 1 © ^ TEL . /Y sAN ��y/{2 L- _ ®i-- CH-1_,_CH 3 IJ I, I- 000V LJ 1-1 H_4 pi7`•r -�l 3005 sPRIN°ST.SUITE 202 �1 300S. PRINGGST 53 Connect to Li I11 XT �* + CH 2 CHh l _ r CONTACG. T I L r ® I CONTACT 9ARAPRAMS FCU-5�, OA duct 1 L — — Tg — _I= 1 RI Mechanical 1 I - o - _ AF�3 SA2 175 CFM I GLENW0i00S AVENUE+ GLErvwoo AVENUc coa,6o SIIIIKILlik/MEP V 7 - \T/- - A,F-2 12"xe H 2 TEL ROGERNEAL .- ' 1 ,H-4 RESOURCE ENGINEERING GROUP N CO 81224 I M" zo2 �\ O I, �e-z Ij Conned to IL 9 0. .uurrne m21CRESTED 6 HSAS DODSONH HARPER I. 11 OA dud L CONTACT.AUGUST I Mechanical 1 I UDBSERvnrOIRE INTERNAnONAL 1 120WALKER STREET.TE ill .4463 FOIL-6W. r NEW YORK5NEW YORK 10013 CONTACT:DARLINA GERACI O I.` dil MD-2 3..,.....1 eNEEUTTON II DHW-1 N I RCP BROOKLYN.NEW YORK 11222 II' I CONTACT:MATT EMI D JI 12"x6" 12"x6" II.:DHW-2 - EIMMOPE ENCLOSURE E CONSULTING uc II- 1 O aPPuaO 5l:` 6-2 11737 WEST KEN CARYL AVENUE SUITE F308 0123 TEL'3LITTLETON3.1863 D0 S00 Laundry 1 12"x6' F corvTncr6EVEaE1T VERscRAVE $,, X7-4. ' I W,n� wL1 1 1 lI �1, I EREMOS ACOUSTICS a,i I H_g il.`/ lI I 1230 BROADWAY SUITE 202 L YORK,NY 014 L''643 650 2235 TE I I CONTACT:RYAN GRAYS(GLOTZBECKER) SPA CONSULTMIT COLORADO POOL11301 w aBRO DRO ESIGNS C SUITE 610 II GOLDEN,,COLORADO 80403 TEL CONTACT ANDY LACELLE irg 1 1.2 1 13.8146 _ �"� Fcu-6 1, fell 9 i \�\ ', r _ J Laundry 1 CD1FCU-5 System0 FCU-6 System �''? I O , x 1/4" = 1' 0" 1/4" = 1'-0" H 1 -H,s, �I -3-IL24 - /, I I tt 1 I I Wine Cellar I I I c OI I - - L - 0 rOPpOo llOf-ti 1i I I r I- I ;,......;:sp�OpU9Ti"'y".yF�I�rrTA / T 40 I "sssao ,. 1 I Route SA duct �l " I I below beam/ " \/ONAt.0' - - P �I L - - - - - - - .... 04-26-2023 /� FCU-7 I I ����®: 234 W Francis V ..1-. L !� ®�� - _ 6d Hall I ri, , _ 0 I I I I � t 1 1 �� :_ D.5 pM MI rE .1. . _ _ D.5 CROUP 1- re inacom•970.349.1216 ConsI I I I �� — II L 1 I k I -.— Ir —7 B Mecghan Mechanical of Energy B I �� _ gv Ji I 300 CFM �� T I I _ Go errciency I susta nabJny I simplicity Bath © — , 36"x5" Bedroom I I Bedroom IaI r _ -1 Laundry li,ir 70 I !I1 `,� - - I © - 1 1 s> I _ 1v I v T 1 L ��1J 11 4— 1 1 — —p"® r J 2020-09-04 80%CD 1 I I �% F , zma z- 80%CD CheckSet SA diffuser high on wall Q - 0 I • I A 2021-02-21 CD Check Set I I I L L_ - - - - ©* `° 2021-03-10 CD Set '= I ®� 11 I I 2021-04-02 COA Building Permit .... I __ - _ _ I 12 x61 �11 RA1 1 ' I 200 CFM 2o22-0221 For Consvuckon 2022-01-04 COA Baking Permit 150 CFM i = I ( RA1 I_ -L -.- 30 x5 11W 2022-04-08 For ConsWcBon I I _ q 1 - I I r 1 3o^x5^ v-1 /a zo2&oz-21 ForConsvu bon I I I FLI I T ,'� ,- I J 1 _ _\ s 023-04-26 Bulletin 04 l l.. - it I I10 - _s ate. — (; — 10x6 � O Fan Coil Systems CDFCU-7 System CD1FCU-8 System A 1/4" = 1'-0" 1/4" = 1'-0" M302 pp.pp xo. - -9/4"=1'-0" 2988 I T I 6 I 5 I 4 I 3 I 2 I 1 I I 7 I 6 I 5 I 4 I 3 I 2 I 1 I ,:cm,,,,..,,nag,.2,,,og,ziaiaiiz,,,.. T 3 _..... 2020-09-04 Permit Set 1FRIDAY DESIGN PO BOX 7928 ASPEN.CO 81612 REK SKALKO I IL I BLV GREEN BLD E I_ — —\ — L _`n E 30055PR CO 81611 SUITE 202 L TEL 990 945.8675 CONTACT:SHERI SANZONE ei�O�O�� xe.o"K�Ea"Arw 3005 SPRING S.SUITE 02 ������� ASPEN CO 81611 .l w 1eee�le _� I I^,� MD-2 _E� __ _ Jr O CONTACT25ARA PRAMS 0 0- M2u27 I W�II� �® 1�4P�.�:���� MIL ENGINE. I 400 CFM n I I•^ 1517BlAKEAVENUE,U.HIGH COUNTRY E101 RA1 C n ect OA toRA of Laundry FCU,provide -I -I L GLErvw000 6PR Ncs co at6°t 10 54"x5" motorized OA damper at connection to main coNinci�aoceR NEAL OA trunk 14"X10"I I I14'x10" 000000 MEP acor _RESOURCE ENGINEERING GROUP 426 01 CRESTED LLEVIEW AVE,SUITE 2CRESTEDBUTTE,CO 81224 ' DT AUGUST DDN DBTHABZDDDBDNHARPER FCU-9 I I I I I I I Bedroom I oosvrovATOIRE INTERNATIONAL Q I O I A WALKER STREET.. III NEW YORK NEW YORK 10013 M302 _:.I I I Bedroom ! /o-�� TEL 212 255 4 463 ,�aI V� — — — — — CONTACT CARL NA GERACI r Laundry I I 10 �, I I I BNwE Tory kayo r®1t ,,: sr ST 527 BROOKLY®200 CFM I I '_"Q—w, .L� 0" CONTACT: NEW YORK 11222 J I 17 p —v W— I/ RAi 150 CFM 200 CFM (} I coea"'Ac9 CONSUL-DM M°A°iTEMM �a.�■}y El 30"z5" I' D "A}, x.N�k % `I Mechamc�l. 1� 30'k5" II_ o A'rs'EO ENCLosuRE CONSULTING uc set II I rol L /W�i 30x5 - wGr rcEry cnmLAVENUE sunE F366 O I . 0- TELLETON.1863 D08012J ! 91 o I i 4 —:'a CONTACT:EVERETT VERSGNVE Route ductwork around steel column - ISA `a swm«wsu,.w,. Cr I O I 12 x� liEREi I: - ®� WTI REMOSAcousres NEW YORK,NY 10014 I 1 - E270 BROADWAY SUITE 202 ®ZOO CFM_ - - I_ T 6 _ \/ C IL 8 CONTACTOR AN GRAYE(GLOTZBECKER) � � I30"x5 r SA1 I-- I — `IYIG COLD N6u20'Ix10" _I ® CONTACT'ANDY IACELL0 38146 I Route SA du co.300 CFMS I - - I below beam, i I - I 30"c8' I I Provide temp sensor for Ice SA in wall at floor,rotated to fit wall width machine closet in RA duct RA in ceilina_.- \ \ OFCU-9 System C) FCU-10 System N 1/4" = 1'-0" 1/4" = 1'-0" C MN It SIGIUTURE to CO V•.•JpUST F�I 38880 Pr erRGom Phi . D.5 ` ' D.5 `�' '� /oNALENG�-, 14 I' I !L FCU-12 r.. 7II 1 r - - ��i I ��.04 26 2023 I I 1 II • •, I 9l Illi 234 W Francis Spa Loun. Q 11 �� I I r ®��� © _ JI��'�� hanlcal4 i� — GI m hl • -iiv ® �i I 12 r .® �i7J1 m �" - I ��� ' REG L ,,,gip y— _. I O Massage .a s o V e�r =1��� _ T1 Q sa I AilCROUP 0 49 N 6 Saun: r�1 1 II reginacom•970.349.1216 p 1 1111■N mum I W•IIII Consulting Engineers Amm. P1 Mechanical•Structural•Energy 1 Yt� 1 B ' 1 I Shower/Steam — B y sus y simplicity _ I 16 I f I� �fFiclenc [a nabdlt I ci C .� I Massage O i! _1 I'?I'S f r I ,`I 0 17 2020-09-04 Pam sat 2020-12-04 80%CD Check set 4 ii- 'B I ' ®200 CFM *.a. 2020-12-17 ao%cD set V �' 1 B l`j V-3 v® ®I �� ^ 2021 02 1 CD Check Set I 2021-03-10 CD Se 30"x5 L _ ® ng Permit 22022 01-04 COA Building Permit I 20 I 1 P -7 f 4' ,2�e022 04-08 For Construction - L JI I�- - i - Ly'f023-0221 For Construction Tvlechanlcal ,.'r 5 023-0426 Bulletin 04 O i/.41 r ivv --I,i r 411 O ) OFCU-11 System O FCU-12 System Fan Coil Systems 1/4" = 1'-0" 1/4" = 1'-0" M303 2968- I 7 I 6 I I 4 I 3 I 2 I 1 I I , I B I 5 I 4 I 3 I 2 I ( I O Y O ISSUANCE pam woEI E m r O2022-06-10 COA BUILDING PERMIT - I 1 e PO BOX DESIGN ASPEN,CO 81812 TEL. 896 ACT:D REK SKAU(O Ai n,.r 4' BLUES SUITE 202 E D.rJ - - - _ �!1 II, - D.5 1 C OOQ\ - - _ Powder Room- - E ,II \_� TEL 91. �4 CONY _ aSAN20NE .EEEEJ, I L BENDON AD I tf�� � 11.117 NG ST.SUITE 202 I I -- 1111 I 400 CFM Il=v� - - elan II 'FCU 1 H I ® 48"x5" I CONTACT:ARAAD000 11' © ;:- -el �1—uIII "I I r — — — — HIGH COUNTRY ENGINEERING _��_ Q JP OI -hanl cal 4 'I I I 1517 BLAKE AVENUE SUITE 101 GLENWOOD SPRINGS,CO Powder Room 100 CFM --- a ® �a \ / �%"I I I I TEL ROGERR NEAL a1ao1 SMIKMUU EP ENGINEER V �� I� ® I I L —426RESOURCE BELEVIEW NE,SUIT GROUP 14 Il\.�� ?..___,-", W. e I O I F/-1 ICREs ED BUTTE 81224TCON ALT461216SCO RE NI®3i1 -31�1�,,WoreIt��R I !� I I I I — — — — LIGHTING DESIGN. LOBSERVATORE INTERNATIONAL HARPER ®150CFM Aim J W T1I I �I � I Al I I I Sauna mWALKERsmEE 7E 24"x5" Spa Lounge 13 I I Gym 15 NEW YORK NEW YORK 10013 1 ...,.,ii ..,:. . ., - J I coHincrScnRi3NA CERAa ' . . - I ONEBUTTO — — — — — I I I �\ BROOKLYNNBE WEST ST CO W YORK 11222 0 Massage e I / II• - """'' - - I L -,- C \ col`rvENV6o"'Acaanwrr EMm D T7 I I ri a - - _ \mil / CONSULTANT o A.D.ENcwsuaE CONSULTING uc ® vV-3 I I I V31 ® ® 11757LITTL TEST KEN CARYL AVENUE SURE F308 'Sauna_ A "�YI 15 I I �� I 1 I y I 4e"x4„ i' i — I CONTACT:EVEaTrVERSCHAVE I I Shower/Steam I m L J ; ,ca,n«wLT,NT I I I 16 J d t 1 - ��o CFM. 30"X4" ll I'��q�i 11A EREN1os ACOUSTICS / I 1�Kr FC 14_ TEL YORK,NY 696 650 2235 10014 TE 202 4 J CONTACT RYAN GRAYS(GLOTZBECKER) -0 — _ i . 20' eC nIC2 3� — 11301 WD43RD DROSUITE 61 � 1 :1 i f�1 f ,1 1 0, , ,, ,ti F (�v//�'7�/vim -7 48 4 E GOLDEN,�(\//�'7�/�� LL 10j— - - - �_ IL J I 11 I I`i I- I 11I I 11 I I I I"'-i•I i f I l•.I I I 1 I "I I I 11 i f I COLORADO 80403 oc �V • I r',` CO I.NTLACT.ANDY LACELLE O 0 O O �• CD, \ N , \ 1/4" = 1'-0" O 1/4" = 11-0" N A3 c C r-�Pp00 UCFP h 4•,.s,7•.•cilia .2 ak MUF ,38880 T�s 1°'~jONALE_NG\-_ 5 I M202 111 i 04-26-2023 11 'IL - _Bedroom- ' i �I!s �L, �I �ia„ 200 CFM I ,® I RA7 234 W Francis \I��®• 'IN I 28 I IRM I ��i � 36"x5" ti I I E I, I -250 CFM Bedroom �J � E 36"x5" 28 R E G � ► x lzx ' CROUP a N 1. 225 CFM p N I ROUP r +RA1 2 9. p_ H-• LL11,� - 36"x5' - ee�r-s. �_'► ,FCU-i6 J -��1\\ , 1� �M _ Y181Jt I `M _ I L 91 Consulting Engineers16 B Q ®o„1vt4 a al I , 1 v B Mechanical•Structural• •9E Energy �\ — — — — — — — — % �� efficient talnabilit simplicity -��SA above cabinetsi Y sus y simP ry �\ � U 15 �V® (® ®250 CFM I _ _ - gas �1 _ ' z �IFij 1� II „ 12x6 \— D I y "'!jam_ _ iNt ili ,Yjl} I Q 27 I ✓ `� ,v® 2020-12-04 80%CDC zozo-lz-04 ao%cDcneu set Dressing Room - -2 2020-12-17 80%CD Set �Bafhr00 i \i I I I 2021-02-21 CD Check Set �26z. I 0 27 2021-03-10 CD Set _ �� RA in ceiling of hallway I I 2021-04-02 COA Building Permit ` I Dressing Room 2022-01-04 COA Building Permit Access hatch in ceiling,coordinate detailingwith Architect I 1 _ _ _ _ _ Bathroom, - 2022-04-08 For Construction �//� lip. �IQ I \ 'r /I �26�� i= I 2022-04-08 For Construction \7 4 III _`� .K I /A\2023-02-21 For Construction Access hatch in ceiling,coordinate detailing with Architect �-5 023-04-26 Bulletin 04 1.2 Fan Coil Systems A OFCU-1 5 System O FCU-16 System A 1/4" = 1 0 1/4" = 1 0 M304 I 7 I 6 I 5 I 4 I 3 I 2 I 1 I