Interior Lighting Compliance Certificate
Project Information
Energy Code: 2021 IECC
Project Title: Lebateau Gravity House Aspen
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
Additional Efficiency Package(s)
Credits: 10.0 Required 0.0 Proposed
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed
(ft2) Watts /ft2 Watts
1-Restaurant(Dining: Bar Lounge/Leisure) 876 0.80 701
Total Allowed Watts = 701
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
1-Restaurant (Dining: Bar Lounge/Leisure)
LED: Ll: Surface Mount Decorative: LED A Lamp 6W: 2 6 12 72
LED: L2: Wall Sconce Decorative: LED A Lamp 6W: 1 6 6 36
LED: L4: Surface Mount Decorative: LED A Lamp 9W: 2 7 18 126
LED: L5: Existing Spot Accent Downlight: LED MR 6W: 1 5 6 30
LED: L6: Existing Surface Mount: LED A Lamp 9W: 1 20 9 180
LED: L7: Existing Surface Mount: LED PAR 15W: 1 2 15 30
LED: L8: Surface 4ft Strip: LED Panel 36W: 1 2 36 72
LED: L9: Tape Light 2.3W/ft: Other: 1 60 2 138
LED: L10: Shelf Light: LED Undercabinet Unit 8W: 1 2 8 16
Total Proposed Watts = 700
Interior Lighting PASSES: Design 0.1% better than code
Interior Lighting Compliance
Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this per it application.The roposed interior lighting systems have been
designed to meet the 2021 IECC requirements in COMcheck rsion COMcheck b and to co ply with any applicable
mandatory requirements listed in the Inspection Checklist.
Carlton Fretwell, P.E. MAY 111013
Name-Title Sign re '•����■■■■„����. Date
.o O
'p•APO•• i
o . :ON • F1
i �i
4 5 r: o:
r; .
lk. MAY 22 2023:41/
Project Title: Lebateau Gravity House Aspen •.�%%NM- N'' Os ED
Re oEteEN
Data filename: •••�� �� ���•• gte/24/k( '23
ASPEN
BUILDING DEPARTMENT
irlA COMcheck Software Version COMcheckWeb
Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2021 IECC
Project Title: Lebateau Gravity House Aspen
Project Type: New Construction
Exterior Lighting Zone 4 (High activity metropolitan commercial district (LZ4))
Construction Site: Owner/Agent: Designer/Contractor:
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts / Wattage (B X C)
Patio Seating Area (Dining area) 451 ft2 0.95 Yes 428
Total Tradable Watts (a) = 428
Total Allowed Watts = 428
Total Allowed Supplemental Watts (b) = 900
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 900 watts may be applied toward compliance of both non-tradable and tradable
areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast Lamps/ # of Fixture (C X D)
Fixture Fixture Watt.
Patio Seating Area (Dining area, 451 ft2): Tradable Wattage
LED: L3: Wall Sconce 8W T10 LED: LED A Lamp 8W: 1 4 8 32
LED: L11: Wall Sconce Existing: LED A Lamp 9W: 1 3 6 18
Total Tradable Proposed Watts = 50
Exterior Lighting PASSES: Design 96% better than code
Exterior Lighting Compliance
Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The roposed exterior lighting systems have been
designed to meet the 2021 IECC requirements in COMchec ersion COMcheck eb and to co ply with any applicable
mandatory requirements listed in the Inspection Checklist
Carlton Fretwell, P.E. MAY 22 2023
Name-Title Sig ure ���„,�� Date
d,O ,i•,
i •0 i �k y:
11 • 4 5 r: o2
r•
P% Mpy212013•.4,41
Project Title: Lebateau Gravity House Aspen Rend
FigD
Data filename: Pi e/24/kOe23
ASPEN
BUILDING DEPARTMENT
COMcheck Software Version COMcheckWeb
Inspection Checklist
Energy Code: 2021 IECC
Requirements: 100.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans, specifications, and/or EComplies Requirement will be met.
[PR4]1 calculations provide all information Does Not
with which compliance can be
determined for the interior lighting ❑Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
C103.2 Plans, specifications, and/or Complies Requirement will be met.
[PR8]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the exterior lighting ['Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
C406 Plans, specifications, and/or Complies Requirement will be met.
[PR9]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the additional energy ❑Not Observable
efficiency package options. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) p�� yfp
Project Title: Lebateau Gravity House Aspen Re o aF te: /
Data filename: gtei241k(P23
ASPEN
BUILDING DEPARTMENT
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
C405.2.3. Spaces required to have light- ❑Complies Requirement will be met.
1 reduction controls have a manual ❑Does Not
[EL22]1 control that allows the occupant to
reduce the connected lighting load in ['Not Observable
a reasonably uniform illumination ENot Applicable
pattern >= 50 percent.
C405.2.1, Occupancy sensors installed in ❑Complies Requirement will be met.
C405.2.1. classrooms/lecture/training rooms, :❑Does Not
1 conference/meeting/multipurpose
[EL18]1 rooms, copy/print rooms, Not Observable
lounges/breakrooms, enclosed offices, ❑Not Applicable
open plan office areas, restrooms,
storage rooms, locker rooms,
corridors, warehouse storage areas,
and other spaces <= 300 sqft that are
enclosed by floor-to-ceiling height
partitions. Reference section language
C405.2.1.2 for control function in
warehouses and section C405.2.1.3
for open plan office spaces.
C405.2.1. Occupancy sensors control function in ❑Complies Exception: Requirement does not apply.
2 warehouses: In warehouses,the ❑Does Not
[EL19]1 lighting in aisleways and open areas is
controlled with occupant sensors that ['Not Observable
automatically reduce lighting power ❑Not Applicable
by 50%or more within 20 minutes of
when the areas are unoccupied.The
occupant sensors control lighting in
each aisleway independently and do
not control lighting beyond the
aisleway being controlled by the
sensor. Lights not turned off by
occupant sensors is done so by time-
switch.
C405.2.1. Occupant sensor control function in EComplies Exception: Requirement does not apply.
3 open plan office areas: Occupant ❑Does Not
[EL20]1 sensor controls in open office spaces ['Not Observable
>= 300 sq.ft. have controls 1) ❑Not Applicable
e
configured so that general lighting can pp
be controlled separately in control
zones with floor areas <= 600 sq.ft.
within the space, 2) general lighting in
each zone permitted to turn on upon
occupancy in control zone, 3)
automatically turn off general lighting
in all control zones within 20 minutes
after all occupants have left the
space, 4) are configured so that
general lighting power in each control
zone is reduced by>= 80%of the full
zone general lighting power within 20
minutes of all occupants leaving that
control zone.
C405.2.2, Each area not served by occupancy ❑Complies Requirement will be met.
C405. sensors(per C405.2.1.1) have time- ❑Does Not
1 switch controls and functions detailed
[EL21]2 in sections C405.2.2.1. ❑Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) ��
Project Title: Lebateau Gravity House Aspen Re c lEr te: / 2����
Data filename: 6 e/2LfikOO'23
ASPEN
BUILDING DEPARTMENT
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
C405.2.4, Daylight zones provided with ❑Complies Requirement will be met.
C405.2.4. individual controls that control the ❑Does Not
1, lights independent of general area
C405.2.4. lighting. See code section C405.2.3 ['Not Observable
2 Daylight-responsive controls for ❑Not Applicable
[EL23]2 applicable spaces, C405.2.3.1 Daylight
responsive control function and
section C405.2.3.2 Sidelit zone.
C405.2.5 Additional interior lighting power ❑Complies Requirement will be met.
[EL27]1 allowed for special functions per the ❑Does Not
approved lighting plans and is
automatically controlled and [Not Observable
separated from general lighting. ❑Not Applicable
C405.2.7 Automatic lighting controls for exterior ❑Complies Requirement will be met.
[EL28]1 lighting installed. Controls will be ❑Does Not
daylight controlled, set based on
business operation time-of-day, or [Not Observable
reduce connected lighting > 30%. ❑Not Applicable
i
C405.7 Low-voltage dry-type distribution ❑Complies Requirement will be met.
[EL26] electric transformers meet the ❑Does Not
minimum efficiency requirements of
Table C405.6. ❑Not Observable
❑Not Applicable
C405.8 :Electric motors meet the minimum EComplies Exception: Requirement does not apply.
ii
[EL27]2 efficiency requirements of Tables ❑Does Not
C405.7(1)through C405.7(4). ❑Not Observable
Efficiency verified through certification
under an approved certification ❑Not Applicable
program or the equipment efficiency
ratings shall be provided by motor
manufacturer(where certification
programs do not exist).
C405.9.1, :Escalators and moving walks comply ❑Complies Exception: Requirement does not apply.
C405.9.2 with ASME A17.1/CSA B44 and have ❑Does Not
[EL28]2 ;automatic controls configured to
reduce speed to the minimum ❑Not Observable
permitted speed in accordance with ❑Not Applicable
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
1
C405. Total voltage drop across the ❑Complies Requirement will be met.
[EL29] combination of feeders and branch ❑Does Not
circuits <= 5%.
❑Not Observable
I ❑Not Applicable
C405. At least 90%of dwelling unit ❑Complies Exception: Requirement does not apply.
[EL30] permanently installed lighting shall ❑Does Not
have lamp efficacy>= 65 Im/W or
luminaires with efficacy>= 45 Im/W ❑Not Observable
or comply with C405.2.4 or C405.3. ❑Not Applicable
C405.11, :50%of 15/20 amp receptacles ❑Complies Exception: Requirement does not apply.
C405.11.1 installed in enclosed offices, ❑Does Not
mii
[EL31]2 conference rooms, copy rooms, break
rooms, classrooms and workstations ❑Not Observable
and > 25%of branch circuit feeders ❑Not Applicable
for modular furniture will have
automatic receptacle control in
accordance with C405.11.1.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) c�� D
Project Title: Lebateau Gravity House Aspen Re c lEr te: / yf
Data filename: 6 e/245/fk(P23
ASPEN
BUILDING DEPARTMENT
Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, Furnished O&M instructions for ❑Complies Requirement will be met.
C408.2 systems and equipment to the ❑Does Not
2 building owner or designated
[F117]3 representative. ❑Not Observable
❑Not Applicable
C405.5.1 Exterior lighting power is consistent ❑Complies See the Exterior Lighting fixture schedule for values.
[F119]1 with what is shown on the approved ❑Does Not
lighting plans, demonstrating
proposed watts are less than or equal ❑Not Observable
to allowed watts. ❑Not Applicable
i
C408.1.1 Building operations and maintenance ❑Complies Requirement will be met.
[F157]1 documents will be provided to the ❑Does Not
owner. Documents will cover
manufacturers' information, ❑Not Observable
specifications, programming ❑Not Applicable
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
C408.2.5 Furnished as-built drawings for ❑Complies Requirement will be met.
[F116]3 electric power systems within 90 days ❑Does Not
of system acceptance.
❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to ❑Complies Requirement will be met.
[F133]1 ensure proper calibration, adjustment, ❑Does Not
programming, and operation.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3) � ��
Project Title: Lebateau Gravity House Aspen Re o11r t�: / 2���
Data filename: 6 ea/24/f2OF'23