To Whom it May Concern,
Please see the attached drawings for updates regarding comments received 6-15-2021.
1. Response to Building comment 30. Fenestration U-factor skylight.
The skylight notes have been added to sheet A-601. It includes notes for max. U-value
of .55 and NFRC labels attached at time of inspection. The skylight is a pre-assembled
unit. Skylight tag was added to plans and elevations.
2. Response to Building comment 30. Fenestration U-factor windows and doors.
V The new window and doors notes have been added to sheet A-601. It includes notes for
max. U-value of .28 and NFRC labels attached at time of inspection. The doors and
windows are pre-assembled units. Door and window tags were added in plans and
elevations.
3. Response to Building comment 90. Architectural Plans Revised.
V The snowmelt plans have been adjusted on sheet A-002 to show existing and proposed
snowmelt for the project. The plans include the areas that will be relocated and added
for new snowmelt. The upper level snowmelt has been shown as proposed snowmelt. A
new Remp. form was completed to include the areas of additional snowmelt.
Mechanical plans and schedules were updated to show the new snowmelt areas. See
sheets M001 and M101 for revised snowmelt areas.
4. Response to Building comment 90. Architectural Plans Revised
The existing snowmelt areas have been adjusted on sheet A-002 to correspond with the
areas from the original permit plans (0188.2017.ARBK). The existing snowmelt area is
shown as 710 sq.ft.
5. Response to Building comment 90. Architectural Plans Revised.
Details 1/A-505 and 5/A-505 include notes for foundation wall min. R-values per 2015
IECC.
RECEIVED
BUILDING 314-D,ASPEN AIRPOST BUSINESS CENTER ASPEN,CO 81611 T:970.429.1286 0 7/3 0/2 0 21
ASPEN
BUILDING DEPARTMENT
G
11i
Galambos Architects Inc.
6. Response to Building comment 90. Mechanical Plans
V The AC unit has been relocated to be within the setbacks for the house. We will be
mounting the unit on the existing house on wall brackets. See Architectural plans and
Elevations on sheets A-004, A-102, A-202 for revised location. See Mechanical plan
M202 for mechanical unit location and mounting bracket specification.