Loading...
HomeMy WebLinkAboutFile Documents.1010 E Hyman Ave.0056-2020-BRES (6) 1010 E Hyman Building Comments 1 bonniem (4) File Name: 1010 EAST HYMAN 07_06_2020 PERMIT o REVISED.pdf Update the window and door �I ICI Author: bonniem schedule to identify the locations Subject: PlanCheck where safety glazing is required 1 Page Label: A10.0 (E) EXT DOOR&WINDOW SCHEDULE per R308.4 & PROPOSED Note the proposed U-factor for Color: • the new windows and doors Al Y: 20.1179 in (must be .28 or lower per Table X: 21.8993 in R402.1.2 as amended by Creation Date: 9/22/2020 10:28:44 AM Ordinance 40, 2016. Date: 9/22/2020 10:32:17 AM Checkmark: Unchecked Lock: Unlocked COMPLETED: SEE SHEET A10.0 Status: Document Width: 10.3507 in Document Height: 0.8349 in Length: Unit: Count Measurement: 1 Count Capture: No Page Index: 21 Space: nmmmmumnmm File Name: 1010 EAST HYMAN 07 06 2020 PERMIT If firepit is to be installed as part nnmmmnmmmin — — mo nmmnn m7 � "�� REVISED.pdf nmi mnnmmmmn Author: bonniem of this permit, provide a cut Subject PlanCheck sheet for the device and include Page Label: UPPER/ROOF FLOOR PLAN fire pit on A3.1; or remove from Color: • plans entirely. Y: 12.8764 in X: 14.8273 in o., Creation Date: 9/22/2020 10:34:02 AM _ Date: 9/22/2020 10:36:40 AM Checkmark: Unchecked DONE HAS BEEN REMOVED FROM PLAN Lock: Unlocked ENTIRELY Status: Document Width: 5.8823 in Document Height: 2.9416 in Length: Unit: Count Measurement: 1 Count Capture: No Page Index: 8 Space: RECEIVED 11/18/2020 ASPEN BUILDING DEPARTMENT File Name: 1010 EAST HYMAN 07_06_2020 PERMIT Provide a detail for the new Nir REVISED.pdf Author: bonniem glass railing. Glass guards must p Subject: PlanCheck comply with one of the following: [Eiiwa Pa a Label: LOWER/MAIN LEVEL FLOOR PLAN Have a top cap supported by at ��� �� Coor: ■ least 3 panes of glass; have a 111►\ "'� Y: 10.6010 in top cap supported independent 1 1 of the glass; or in the case of no X: 14.7348 in - nwn s■ top Creation Date: 9/23/2020 9:13:04 AM cap, be at least two plies of Date: 9/23/2020 9:15:37 AM equal thickness glass laminated Checkmark: Unchecked together. Provide details Lock: Unlocked demonstrating compliance with Status: one of the above as well as Document Width: 3.7072 in method of attachment and Document Height: 2.8937 in support. Must support a point Length: load of 2001bs. Please note that Unit: Count many glass support Measurement: 1 Count DONE SEE DETAIL#4 manufacturers require a top cap; Capture: No SHEET A8.0 if you exceed their design you Page Index: 7 will need a stamped engineered Space: design. (Ordinance 40, 2016) File Name: 1010 EAST HYMAN 07_06_2020 PERMIT This appears to be a detail for REVISED.pdf Author: bonniem snowmelt at grade rather than a Subject: PlanCheck roof section. Please clarify Page Label:A8.0 WALL& ROOF DETAIL&ASSEMBLIES where this detail will be used. Color: • Y: 8.7905 in X: 3.9900 in Creation Date: 9/23/2020 9:28:16 AM DETAIL#2 SHEET A8.0 IS TO BE USED AT THE ROOF Date: 9/23/2020 9:30:40 AM SNOWMELT Checkmark: Unchecked DETAIL#3 SHEET A8.0 IS TO BE USED AT THE Lock: U Lock: Unlocked PAVING SNOWMELT AT GRADE Status: Document Width: 5.3174 in Document Height: 5.0001 in Length: Unit: Count Measurement: 1 Count Capture: No Page Index: 19 Space: RECEIVED 11/18/2020 ASPEN BUILDING DEPARTMENT