HomeMy WebLinkAboutFile Documents.1010 E Hyman Ave.0056-2020-BRES (6) 1010 E Hyman Building Comments 1
bonniem (4)
File Name: 1010 EAST HYMAN 07_06_2020 PERMIT
o REVISED.pdf Update the window and door
�I ICI Author: bonniem schedule to identify the locations
Subject: PlanCheck where safety glazing is required
1 Page Label: A10.0 (E) EXT DOOR&WINDOW SCHEDULE per R308.4
& PROPOSED Note the proposed U-factor for
Color: • the new windows and doors
Al Y: 20.1179 in (must be .28 or lower per Table
X: 21.8993 in R402.1.2 as amended by
Creation Date: 9/22/2020 10:28:44 AM Ordinance 40, 2016.
Date: 9/22/2020 10:32:17 AM
Checkmark: Unchecked
Lock: Unlocked COMPLETED: SEE SHEET A10.0
Status:
Document Width: 10.3507 in
Document Height: 0.8349 in
Length:
Unit: Count
Measurement: 1 Count
Capture: No
Page Index: 21
Space:
nmmmmumnmm File Name: 1010 EAST HYMAN 07 06 2020 PERMIT If firepit is to be installed as part
nnmmmnmmmin — —
mo nmmnn m7 � "�� REVISED.pdf
nmi mnnmmmmn Author: bonniem of this permit, provide a cut
Subject PlanCheck sheet for the device and include
Page Label: UPPER/ROOF FLOOR PLAN fire pit on A3.1; or remove from
Color: • plans entirely.
Y: 12.8764 in
X: 14.8273 in
o., Creation Date: 9/22/2020 10:34:02 AM
_ Date: 9/22/2020 10:36:40 AM
Checkmark: Unchecked DONE HAS BEEN REMOVED FROM PLAN
Lock: Unlocked ENTIRELY
Status:
Document Width: 5.8823 in
Document Height: 2.9416 in
Length:
Unit: Count
Measurement: 1 Count
Capture: No
Page Index: 8
Space:
RECEIVED
11/18/2020
ASPEN
BUILDING DEPARTMENT
File Name: 1010 EAST HYMAN 07_06_2020 PERMIT Provide a detail for the new
Nir REVISED.pdf
Author: bonniem glass railing. Glass guards must
p Subject: PlanCheck comply with one of the following:
[Eiiwa
Pa a Label: LOWER/MAIN LEVEL FLOOR PLAN Have a top cap supported by at
��� �� Coor: ■ least 3 panes of glass; have a
111►\ "'� Y: 10.6010 in top cap supported independent
1 1 of the glass; or in the case of no
X: 14.7348 in
- nwn s■ top
Creation Date: 9/23/2020 9:13:04 AM cap, be at least two plies of
Date: 9/23/2020 9:15:37 AM equal thickness glass laminated
Checkmark: Unchecked together. Provide details
Lock: Unlocked demonstrating compliance with
Status: one of the above as well as
Document Width: 3.7072 in method of attachment and
Document Height: 2.8937 in support. Must support a point
Length: load of 2001bs. Please note that
Unit: Count many glass support
Measurement: 1 Count DONE SEE DETAIL#4 manufacturers require a top cap;
Capture: No SHEET A8.0 if you exceed their design you
Page Index: 7 will need a stamped engineered
Space: design. (Ordinance 40, 2016)
File Name: 1010 EAST HYMAN 07_06_2020 PERMIT This appears to be a detail for
REVISED.pdf
Author: bonniem snowmelt at grade rather than a
Subject: PlanCheck roof section. Please clarify
Page Label:A8.0 WALL& ROOF DETAIL&ASSEMBLIES where this detail will be used.
Color: •
Y: 8.7905 in
X: 3.9900 in
Creation Date: 9/23/2020 9:28:16 AM DETAIL#2 SHEET A8.0 IS TO BE USED AT THE ROOF
Date: 9/23/2020 9:30:40 AM SNOWMELT
Checkmark: Unchecked DETAIL#3 SHEET A8.0 IS TO BE USED AT THE
Lock: U
Lock: Unlocked PAVING SNOWMELT AT GRADE
Status:
Document Width: 5.3174 in
Document Height: 5.0001 in
Length:
Unit: Count
Measurement: 1 Count
Capture: No
Page Index: 19
Space:
RECEIVED
11/18/2020
ASPEN
BUILDING DEPARTMENT