ASBESTOS REPORT
DATE
07/27/2023
CLIENT
Steve & Beth Nuehoff
c/o Demesne Aspen
402 E AABC
Aspen, CO 81611
PROPERTY ADDRESS of INSPECTION
918 South Mill Street,Aspen, Colorado 81611
!F:7
usivir
411 - t ILL STREET
RECEIVED
09/20/2023
1 ASPEN
BUILDING DEPARTMENT
CLIENT BACKGROUND & PLANS
The Clients, Steve and Beth Nuehoff, have failing outdoor patios over living space in the
above-referenced duplex, which require of disturbance, detachment, deconstruction,
demolition, and disposal (5D) of interior drywall building materials, of which some are
suspect asbestos containing materials (ACM). Prior to 5D, Steve and Beth are required to
have an asbestos inspection by a State of Colorado CDPHE certified asbestos inspector
who will collect bulk samples of the suspect ACM and have those samples analyzed at a
certified laboratory for asbestos content. Steve and Beth hired HealthSafe Inspections,
Inc. (hereinafter, HealthSafe)via Demesne Aspen to perform a limited asbestos
inspection for the drywall below these outdoor patios.
VISUAL INSPECTION & LABORATORY FINDINGS
An inspection was conducted by Ben Baker of HealthSafe on Wednesday, July 19, 2023,
with Richard Mullen of Demesne Aspen present during the initial survey, inspection and
sample collecting.All suspect ACM were identified by homogenous materials and
sampled randomly respective to the scope of those materials slated for 5D. The suspect
ACM collected and analyzed by EPA 600 Method PLM analysis are the following:
1. Orange Peel Surfacing Texture, a homogeneous spray-applied surfacing
material/texture [samples 1-5: OP-1,2,3,4,5], collected randomly from the parking
garage ceiling south-center, east unit second-level ADU space kitchen ceiling near
the NE light fixture, east unit entry-level master bedroom closet ceiling near the
HVAC vent,west unit second-level east bedroom en-suite bathroom under the
vent fan cover, and west unit entry-level master bathroom ceiling under the vent
fan cover, respectively. Samples were collected evenly distributed throughout the
duplex in areas slated for impacts of 5D. This surfacing material/texture is friable
and located on the ceilings and walls of the living spaces underneath the outdoor
patios. The estimated impact area of 5D is more than 1,000 sf, but less than 5,000
sf(±1,200 sf), requiring a minimum of at least five surfacing/texture material
samples. The PLM analytical estimated results: NONE DETECTED.
2. Drywall System Joint Compound: a homogeneous miscellaneous seam taping
compound requiring at least two samples [samples 6-7: JC-1,2], collected from
the parking garage ceiling south-center and west unit entry-level master bathroom
SE corner, respectively. This material is friable and applied to the interior drywall
system beneath the outdoor patios. The PLM analytical estimated results: NONE
DETECTED.
3. Drywall System, a homogeneous taped and joint compounded drywall system
(classified as a miscellaneous material as a complete integral system) [samples 8-
9: J-1,2], collected from the parking garage ceiling south-center and west unit
entry-level master bathroom SE corner, respectively. These composite layered
taped and joint compounded drywall materials are friable and located on the
ceilings and walls of the living spaces beneath the outdoor patios with an orange
peel applied surfacing material/texture. The estimated impact area of 5D is more
than 1,000 sf, but less than 5,000 sf(±1,200 sf), requiring a minimum of at leaDDst C
EIVELI
09/20/2023
2
ASPEN
BUILDING DEPARTMENT
two composite core samples of all layers. The PLM analytical estimated results:
NONE DETECTED.
A total of 9 suspect homogeneous ACM bulk samples were collected, and 9 samples were
analyzed. The bulk samples were analyzed by EPA 600 PLM analytical methods by a
NVLAP accredited laboratory in accordance with Colorado State Regulation 8 for the
presence of asbestos mineral fibers. There is NO asbestos in all 9 samples.
See supporting Hayes Microbial Consulting, Inc. data report#23029261_1.
HEALTHSAFE CONCLUSIONS
• There is NO asbestos in any of the suspect building materials slated for 5D in this
patio repair project. NO asbestos abatement will be required for any of the
building materials.All building waste and debris can be disposed of in any landfill
which accepts normal, non-hazardous building waste.
Sincerely Submitted,
Ben Baker
UI
vP DN
uP
vP
6
First-Level Entry Level
(Garage)
vP DA, uP DN
Second Level
_ECEIVED
09/20/2023
3 ASPEN
BUILDING DEPARTMENT
COLORADO & FEDERAL ASBESTOS REGULATIONS SUMMARY
Regulation No. 8 Part B—Asbestos of the Colorado Department of Public Health and
Environment(CDPHE),Air Quality Control Commission requires a State-certified
Asbestos Building Inspector to inspect and collect bulk samples of all suspect asbestos
containing materials (ACM) or suspect asbestos containing building materials (ACBM)
prior to their disturbance,removal or demolition and disposal. The suspect materials shall
be analyzed by a NVLAP accredited laboratory by polarized light microscopy (PLM)
using EPA 600 analytical method.A material which is estimated to contain more than 1%
asbestos is classified as ACM/ACBM and regulated by the State and Federal
governments.Any friable (able to crush or reduce to powder by finger pressure) asbestos
with trace amounts of asbestos fibers or less than 1%must be point-counted using EPA
400 analytical method to prove that it is indeed less than 1%; if not, it must be classified
as ACM/ACBM and shall be treated as a State and Federal regulated material.Any
friable asbestos containing material (greater than 1% asbestos concentration) or
ACM/ACBM that could be rendered friable during its removal or demolition and disposal
shall require an asbestos abatement by a certified asbestos abatement contractor to
remove and dispose of the material(s).
A Colorado State (CDPHE) issued asbestos abatement permit is required for the
following trigger levels of ACM/ACBM:
1. Residential buildings of four or fewer units--if more than 32 square feet of any
surface coverage (e.g., gypsum wallboard or drywall and associated applied surfacing
materials/textures, acoustic sprays,joint compounds, plaster, etc.), 50 feet of asbestos
covered or asbestos insulated pipe or any material which would fill a 55-gallon drum is
going to be disturbed, removed or disposed of, an asbestos abatement permit is required.
2. Residential complexes with more than four residential units, public access areas to a
residential building, commercial and retail buildings, public and civic buildings,
industrial buildings--if more than 160 square feet of surfacing materials, 260 linear feet
or more than 35 cubic feet(NESHAP) or 55-gallon drum (CDPHE) of suspect
ACM/ACBM is going to be disturbed, removed or disposed of, an asbestos abatement
permit is required under NESHAP and by the CDPHE. See note below on OSHA.
The regulations require an absolute minimum of 3 samples (EPA suggests 9)per
homogenous suspect surfacing and TSI materials and an absolute minimum of 2 samples
of homogenous miscellaneous materials or any number of"samples sufficient to
determine whether a material is ACM" (Reg8.IV.D.3). More samples are required based
on surface area or volume. These are minimums; the asbestos building inspector has the
field responsibility to determine homogenous materials and the number of samples to
collect per material; more than the minimum number of samples may be necessary at the
discretion of the inspector.An assessment of friability and functional space conditions of
the materials are also the inspector's field responsibilities. RECEIVED
09/20/2023
4 ASPEN
BUILDING DEPARTMENT
OSHA compliance is required for all employers and employees no matter the
quantity of asbestos present with strict regulations regarding 10 sf or more of TSI or
friable surfacing materials, and therefore it does not matter what the quantity or
State trigger levels are: all suspect ACM/ACBM shall be inspected and tested for
asbestos prior to their disturbance, removal and disposal for worker protection and
safety. See EPA 40 CFR 763.121 Worker Protection Rule, OSHA 29 CFR 1910.134
Respirator Protection Standard, OSHA 29 CFR 1910.1001 General Industry Standard and
OSHA 29 CFR 1926.1101 Construction Standard regulations when dealing with asbestos
hazards.
Note: County or City regulations may be more stringent.
RECEIVED
09/20/2023
5
ASPEN
BUILDING DEPARTMENT
a% HAYES
MICROBIAL CONSULTING #23029261
Analysis Report prepared for We would like to thank you for trusting Hayes Microbial for your analytical needs!
We received 9 samples by FedEx in good condition for this project on July 20th, 2023.
HealthSafe
The results in this analysis pertain only to this job, collected on the stated date, and should not be used
Inspections in the interpretation of any other job. Information supplied by the customer can affect the validity of
results. These results apply only to the samples as received. This report may not be duplicated,except in
full,without the written consent of Hayes Microbial Consulting, LLC.
390 Apple Drive
Basalt, CO 81621 All information provided to Hayes Microbial is confidential information relating to our customers and their
Phone: (970) 920-2100 clients. We will not disclose,copy,or distribute any information verbally or written,except to those
designated by the customer(s). We take confidentiality very seriously. No changes to the distribution list
will be made without the express consent of the customer.
This laboratory bears no responsibility for sample collection activities, analytical method limitations,or
Steve & Beth Nuehoff your use of the test results. Interpretation and use of test results are your responsibility. Any reference to
91 8 S Mill St health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial. In no event, shall
Aspen, CO 81 61 1 Hayes Microbial or any of its employees be liable for lost profits or any special, incidental or
consequential damages arising out of the use of these test results.
Collected: July 19, 2023
Received: July 20, 2023
Reported: July 27, 20234-41g *-4--
Steve Hayes,BSMT(ASCP)
Laboratory Director
Hayes Microbial Consulting,LLC.
2�J��SED STq TFS>v 6'�ey�an,,� ms
2 0 Q e�y, DPH
G'�.� � \ ConneRicut Department
q(PROSE gutioaiasab of Public Health RECEIVED
EPA Laboratory ID: VA01419 Lab ID: #188863 DPH License: #PH-0198 09/20/2023
Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com POWEril 4
BUILDING DEPARTMENT
Ben Baker #23029261
HealthSafe Inspections Steve & Beth Nuehoff
390 Apple Drive 918 S Mill St
Basalt,CO 81621 Aspen,co 81611 Asbestos PLM Bulk
(970) 920-2100 EPA 600/R-93,M-4/82-020
# Sample Material Description Non-Asbestos Fibers Asbestos Fibers
1 OP-1 Paint-like/White/Tan None Detected
2 OP-2 Joint Compound/Tan None Detected
3 OP-3 Joint Compound/White None Detected
Joint Compound/White None Detected
4 OP-4 Joint Compound/White None Detected
5 OP-5 Joint Compound/White None Detected
6 JC-1 Joint Compound/White None Detected
7 JC-2 Joint Compound/Gray None Detected
Joint Compound/White None Detected
8 J-1 Drywall/ Pink 5%Synthetic Fibers None Detected
2% Fiberglass
Joint Compound/White None Detected
RECEIVED
Collected:Jul 19,2023 Received: Jul 20,2023 Reported: Jul 27,2023
H AY E S 09/20/2023
Project Analyst: /, �, Date: Reviewed By: Date:
Mark Bergstrom,�`�,/fAl' P /f��� 07 27 2023 Brian Keith, 0723
QMICROBIAL CONSULTING _ l l BUILDING D A TfvfEMT
3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com age:2 or 4
Ben Baker #23029261
HealthSafe Inspections Steve & Beth Nuehoff
390 Apple Drive 918 S Mill St
Basalt,Co 81621 Aspen,co 81611 Asbestos PLM Bulk
(970) 920-2100 EPA 600/R-93,M-4/82-020
# Sample Material Description Non-Asbestos Fibers Asbestos Fibers
9 J-2 Drywall/Gray 5%Cellulose Fibers None Detected
2% Fiberglass
Tape/Tan 98%Cellulose Fibers None Detected
Joint Compound/White None Detected
Lab Note: Between Layers of Paint
Joint Compound/White None Detected
Lab Note:Top/Bottom of Drywall Tape
Collected:Jul 19,2023 Received: Jul 20,2023 Reported: Jul 27,2023 RECEIVED
ED
H AY E S Project Analyst Date Reviewed By:000V 2 O/2 O 2 3
Mark Bergstrom,�� � � 07 - 27 -2023 Brian Keith, 07-27-2023
MICROBIAL CONSULTING ASPEN
3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com BUILDING D! TIME
Ben Baker #23029261
HealthSafe Inspections Steve & Beth Nuehoff
390 Apple Drive 918 S Mill St
Basalt,Co 81621 Aspen,co 81611 Asbestos Analysis Information
(970) 920-2100
Analysis Details All samples were received in acceptable condition unless otherwise noted on the report.This report must not be used by the client to claim product certification,
approval,or endorsement by AIHA,NIST,NVLAP,NY ELAP,or any agency.The results relate only to the items tested. Hayes Microbial Consulting reserves the right to
dispose of all samples after a period of 60 days in compliance with state and federal guidelines.
PLM Analysis All Polarized Light Microscopy(PLM) results include an inherent uncertainty of measurement associated with estimating percentages by PLM.
Materials with interfering matrix,low asbestos content,or small fiber size may require additional analysis via TEM Analysis.
TEM Analysis Analysis by TEM is capable of providing positive identification of asbestos type(s) and semi-quantitation of asbestos content.
Definitions 'None Detected'-Below the detected reporting limit of 1%unless point counting is performed,then the detected reporting limit is .25%.
New York ELAP Per NY ELAP198.6(NOB),TEM is the only reliable method to declare an NOB material as Non-Asbestos Containing.
Any NY ELAP samples that are subcontracted to another laboratory will display the name and ELAP Lab Identification number in the report page heading of those
samples.The original report provided to Hayes Microbial Consulting is available upon request.
RECEIVED
H AY E S 09/20/2023
ASPEN
MICROBIAL CONSULTING 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@a hayesmicrobial.com BUILDINUE:P4RT 1ENT
SHIP: FEDEX - ENV SO �SHI S :7
Health Safe Inspection's DATE: 07-20-2023 NI
. . i 1 81-C 964C 9895IIIIIIIIII
.
�� ; :: l_ � ..: �� .1-:::-: �._� 390 Apple Drive
==r" MICROBIAL CONSULTING Basalt, CO 81621 1�������������������������������������� 73F329261
Job Number: Job Name:,5 retie � 13et11 fit' /I/velior
Collector: Be, Baker q le' 5 Ai, // 51- Mobile: 970-920-210D Email: healthsafeinspections@gmail
Date Collected: 7 1 3 L >,� d Note c b �6ak�� c 3�J emu / v:
Analysis Type • Analysis Methods • • Turnaround Times
PLM Bulk EPA 600 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day
Point Count 400 Point,1000 Point 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day
Vermiculite CARB 435 ••' 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day
TEM Air EPA AHERA,NIOSH 7402 - Same Day 1 Day 2 Day 3 Day 5 Day
Bulk Chatfield - Same Day 1 Day 2 Day 3 Day 5 Day
• Wipe ASTM D6480-05 - Same Day 1 Day 2 Day 3•Day 5 Day
Microvac ASTM D5755-09 - Same Day 1 Day 2 Day 3 Day 5 Day
PCM Air NIOSH 7400 - Same Day 1 Day 2 Day 3 Day 5 Day
# Group r n L Number Sample Name Analysis Type Turnaround Volume/Area Stop(+)
1 G P i ''L Ai C. 1),,
2
3 'MEE 0 ? 2- I ,
UP 3
4 0 ID.
J-I
l
12
10
15
16
17
1
Released by: �2 A Date: 43 Received By: 1 Date: `7 23
4
Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F.Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobiaLcom Form 420,Rev.B,M rch 23,2019
Cht �ialy
BUILDING DEPARTMENT
�a.1•jj•,.. V .o1eis.• •�•1•il'e .t ;:fe:�•0•1• r ./,�•///1�1• `v ►��.I0."0 �•.iA7,;;;$f•.. .;:i ��.�����, w�;�♦��1�:tiVi r •�'�1����/����,
'•ii►1111111�%i'. •it►i►//1/1/1////1%i�, :'i•i►11111111111%I• :�i�i'j111111111�%1• :`i•iQ�111111111%/i, :'i'i�111111111j�11i• .��ii►11111111/1%/n, .�i'il•►IIIIIIi1Pn, .'.'�i'i►1►IIIIIIIIi•i,, :i.i►IIIIi:�.
•• 0,11$0;..•alit. .01110)....\`y1111QNl 4 I;... 01 4.4.41 :•.`\h'NHI$1I....`I►11►Nlll I I1.,,\y 1►IN11 11.3•. \ 1 0440. r I. \ 1►Nlll 11 1`i l:•/
•O-J1t/Gnu�\11 N11111/bn,t\1111HI/llt/1/S'n.\�y111►►HNll1✓1/4^n��\�1111►IP1111/11G'n���h4►4��'11j11/1/1.'r\\�2��Ii►I1i11�1�11%I%i'�'����i1i►�•'�I�/i11%1%i����\��y11/�h1//111�1%�/��%��\22��11►/1��.
.w�:�•JrI/1^\\�11,��/l1'/I/IIItI//^\���1,11111111111 III/ \\.�.II�I1111/j1I�/ 1 Z y�11 H111/��.'1 \ `�!I,IhN/1r l,/.//1��. yl Nh.�li.,.1/^1�.���1 •N 1 r:, / 11 r ,t/r,,l/^\,• I I_��
• .l mac_•: !I n, it:.0,r?://I •..0:0�!r;;itot,• ,,,I. .:t!r /11^��\''W!,"ll�...4 //,k ��,/,O., 1/! 1.�i S;4A'.t; , !Il/\O\\!tit�•1.'.Q''� 111/nllI�;���ll•:?'/,o11/N\I��':����:
•::r=:�IIn\��'t��'.:iV,�',:.ljlln\i•R�;t.;0::d�,:./llll�\II•�\';;':•k.•a�'1✓/ \I'�\�;1,;�::,:.'/III�\�.`\,�f�;.',q�'.�j11j1/`I�\\,,;.,.,':;:,1111In`.i•�,a,t;:;:'://1/j�\II\\,;f;�'.�;:•/liI^\I\�w�\w�.
S•11^\i►\\\d�;r;.;: 1IIli/�.\►►\\V.',:nS�:•/II11:•'-`�►IN\�,�::Yr: /I/11�\II\\\•,yNo,: /II/1�\I�N\.�;,..:: //��\\\N\,;:•:rr I//it!`a`\\\\,•,:'r� ///r.::::�\►\\I\•,r,'N: I/!r< +�.�w�\\•..
i.
:I�'`'''I lititsil :;tita!['��U�iv.vLii Js iiiiVUIiUIlU1164 L4 i ''L I' RIU44 1"PitliI'11hUIIU1117U1 lIUI itig} rI�J�iVii 4 i 411.1 IU i 6.1 , _:•
. -,\ V• • / VIV•V/V IV VIV: IV• �•y �y • •V••IV.V V•V.V•V.V.V• I, V V.V. `." �.. y:=� ==1.,
; 'vim . .vvaLI ../vv v v .vv.,vv.•,vv G
...............
ce:�Z7`=_ - �C ::.
•=c;�= % r\ ) 0•COS Kc :>•;: '..
ice(«(1.d: E. --'= 1. , ..y =—•
IW
tW
*cli
� Cam'•,'`` )»>>.
•=�\ _, Colorado Department t<.r-.
of Public Health cc =°•.
)) and Environment ..
qa »`•'•
=__ _ ;; ASBESTOS ( ____==_
') CERTIFICATION* (e
/iieisi
?)) This certifies that �,1 == =< •
y,= , ' (icy =,e
Benjamin L Baker (`c•��, `» ( :;;:;mac,,:,.
::_ )) c(
1 Certification No.. 25863 �.:-«:
'''''• '' :: =' has met the requirements of 25-7-507, C.R.S. and Air QualityControl »»Y�...
_--:_ r?a Commission Regulation No. 8, Part B, and is hereby certified by the « '""...
'%==='- -,.•._ state of Colorado in the following discipline: c
. i)
=• '• -� Building Inspector* Ellf::*..::::-:::::-?,-::::;:i2::!41.:4''
.==����` ill-
_ '--� Issued: August 31 2022 '%%;�.
>) Expires: September 25, 2023 (« '-s.
---� ir
%/ cc-, �:�
►•.• - • _ >�• iki �� ((C __�=�.ice.
'%! !mil) * C:•"-__ �..
'.� This certificate is valid only with the possession of a ...
�ii % :_., Cis?+ ..�;;���.•
..;,.... ;.:f! � c•urrent Division-approved training course certification ems:"
"\�\e«r\ in the discipline specified above. (� �>����;_,
Autho ize APCD representative ,, .,i.
.p.:.. SEAL =-_ ,o.'
.'����"i ?' ..•n•n•n• •..Inln•n• • •G�r\...,,.•^�4 .�iJ••.'�n•n•�a.•�.• n•ni.• .n• 1 r►•r^• •r�..r:.n�.,—'' �=�=
;;-',4• • , ii :.;1a'tnlifitl�Ago�ni�rIt o i tiitalln}Ir In llr��. + a� +an�Gn�ar_�n►I Ira 11fi11r�Nr �. _� ;i �lr 1.1 I. „-._
i�
• G:
h
.i�
..
�Ni'I/I/�Gd}: \�I/I/I t'S'.•t,;;A%11*/I//,/;. \►\\ iiONi i.:;.:.\\\\�,i ig,V: \\\\\YIi/l/n'.y0:;'.\1\\`'Yl/�/,G;• ) i 1t,(0:11,�\1�i ll�1 r��..
�.�-__:►NV///r,��.0•„i; \\.VI/✓,'i'O,y,.; �\ VI,r rraj��;,�� \\\\1N///tr,'r',i/,,.: \\\ \VjI//i.,y'��rl�i�� \\ \/1//{.p 1.1. n \\ V/r r,,�.l.�s���\\���y///.. ••I•,..,\�\�//1/� � D�
♦•�w.�.��\\\V//!Sr'110/�i•'1'�c\\\V// yi 0.41�1�`�.\\\�//,�J/'••N.�1`C•�V/G r' /�� •y1'io\►y/L;r�'d/l'•11111�f c\\\\//�5,'/i/11�/''Itio\\\y//�5,.,�'0•r/r/,�l`,�V\�T��/�id;i//;•:i�1 .,1J✓rrl,,,,i� 0,�
.•.O- 11\C�\VIlfi;I60.4:4'4'-`l\/,/p�1.r,1N1\I\��1ti�Pir'0{i1N11111\�y�%/' /i'::"Iik1\\�w�/j/Ij .#10j11111i\%*ri/'t11,/1 j10k\ :'%,"1/� ;":..0►1��►\,�h�;/./ irt40..i11111\��v'isi•Ilr; ��i•'
!���1//1�1\\�;•"!/ii 1i1j/►//II�IIj1\\�;••'!ri�i11i1Q/i11/1►1�1�\ii•'%�/i�i�l/ri►/1/1111i\��•'4: i�/1'i//1//1111\i1-�;/i1i.IfiN1/1111\��•'ir/�j11�/1/'/�1//1�11\�,':rdj�ilj'�,'1111�11\\i-'S�/i�ii11///►111�111\\►.iw�/��ji1/1�Ir%i�
:y►7�/�/�►�►tte':iity,:�tibi:�•�'1::i/�1�1141A ";;�:1//'/'/�1�•e gee:*//�/�1$1)• ;i�i/11�4,01•1: '.;elii//►11it; '•+;►•/•////►�1 0 ;►11//�//��1��!I'`�•ttj/1///�±•
"+` "'` BU r GDEPA' V 1