HomeMy WebLinkAboutFile Documents.433 E Hyman Ave.0041-2024-BCOM (5) ARCHITECT/ENGINEER
0041 -2024-BCOM_BuildingComments_1 RESPONSES IN BLUE
90.Architectural FULL Set 433 Hyman Ave 20240924.pdf(13)
rag & bone Subject: PlanCheck •
2023 NEC and ICC Al .1-2017
Page Index: 1
Page Label: 1-COVER COVER SHEET
Author: nickt
Color: •
1 'wrtiw p -' File Name: 90.Architectural FULL Set 433 Hyman Ave UPD D ON
N-^m6 �: 20240924.pdf 1-CrVER SHEET
-.a
Subject: PlanCheck
rag & bone All as amended by Y OF
81611 Page Index: 1
Page Label: 1 COVER COVER SHEET ASPEN MUNICP' CODE
=`- Author: nickt TITLE 8
Color: •
=i —? File Name: 90.Architectural FULL Set 433 Hyman Ave UPD' "ED ON
mum. ` 20240924.pdf
_L- ; — 4 1- , •VER SHEET
Subject: PlanCheck
Page Index: 3 This sheet shows a,:ditional
-- " Page Label: 3-COVER LIGHT FIXTURE&LOW VOLTAGE fixtures not show on the lighting
SCHEDULES plans or comch- k. Revise to
w � .. ,°°° m• °-•— a"" Author: nickt coordinate. Mir, t be simplest to
�•�
Color • only have on- lighting plan and
= """ File Name: 90.Architectural FULL Set 433 Hyman Ave light sched e to avoid this
20240924.pdf problem.
SCHED 4 LE ON SHEET E101
UP! A ED TO COORDINATE
Subject: PlanCheck
Page Index: 4 Indicate occupancy e above
Page Label:A1.00 EGRESS PLAN &ANALYSIS (R2).
sit Author: nickt
Indicate occupancy type Color: ■
above(R2). File Name: 90.Architectural FULL Set 433 Hyman Ave UPDATE N
20240924.pdf SHEET A1.00
4NALY5
„�o _.,P_m, Subject: PlanCheck
Page Index: 4 Type of constru ion is VA
art.SSr,.a--.°.,.= Page Label:A1.00 EGRESS PLAN &ANALYSIS
Author: nickt
messirmoIMEN 2= o Color: ■
a' n File Name: 90.Architectural FULL Set 433 Hyman Ave UPDA D ON
20240924.pdf SHE T A1.00
RECEIVED
10/22/2024
ASPEN
BUILDING DEPARTMENT
Liy Q Subject: PlanCheck
f As discussed d ring the
%% Page Index: 4
Page Label:A1.00 EGRESS PLAN &ANALYSIS presubmittal eting, please
Author: nickt address eve thing that was
lawn°"ff.-- Color: • included o the building checklist
I sent you
File Name: 90.Architectural FULL Set 433 Hyman Ave
-0- 20240924.pdf
Subject: PlanCheck
Page Index: 4 The floor/ceiling assembly above
o „ P Page Label:A1.00 EGRESS PLAN &ANALYSIS must be 2 hour fire and ST 0
Author: nickt sound rated. I emailed y a 3
_... Color: • page document indicaf g the
"� File Name: 90.Architectural FULL Set 433 Hyman Ave previously approved sembly
20240924.pdf for the ceiling with a building
checklist after th presubmittal
" _ meeting on 8/ /24. Please
A DETAIL PROVIDED include the f and sound rated
& ADDRESSED ON assembly' dicated in that
docume printed on the plans.
SHEET A1.05 RCP Pleas indicate on the plans that
thi assembly must be used for
patching any holes/disturbance
in the rated lid.
Ir'.,R i Subject: PlanCheck
�°° Any new ceiling fr ing dropped
Page Index: 4
- ", Page Label:A1.00 EGRESS PLAN &ANALYSIS below the rate eiling must be
Author: nickt non-combu ' le or fire retardant
„.,�- , Color: • treated od.2021 IBC 803.13
7:;;;= File Name: 90.Architectural FULL Set 433 Hyman Ave
ftff[f: 20240924.pdf
ADDRESSED NOTE #7
wON SHEET A1.05 RCP
Subject: PlanCheck
Page Index: 4 Provide a door and door
Page Label:A1.00 EGRESS PLAN &ANALYSIS hardware schedule.
Author: nickt
Color: • DOOR SCH ULE
File Name: 90.Architectural FULL Set 433 Hyman Ave
20240924.pdf PROVIDE ON
SHEET -COVER
Subject: PlanCheck
Page Index: 9 This she ditional
Page Label: A1.05 REFLECTED CEILING PLAN fixtur not shown on lighting
_,
1Author: nickt pla or comcheck. Revise o
Color: ■ co rdinate. Might le t to
ght be simple File Name: 90.Architectural FULL Set 433 Hyman Ave o y have one lighting and
""°"°`"` 20240924.pdf lig schedule id this
® problem.
i
<L E11111 ��,.
SHEET E101 UPDATED
TO COORDINATE
1`\,[d-a 4. r)
10/22/2024
ASPEN
BUILDING DEPARTMENT
Subject: PlanCheck
Page Index: 9 Not an existing sl .This is
Page Label:A1.05 REFLECTED CEILING PLAN actually a 2 ho fire rated wood
Author: nickt framed floor/ iling assembly
Color: • with gyp mbrane.As
- li i—� File Name: 90.Architectural FULL Set 433 Hyman Ave mentio d in previous note, use
w e,�I 20240924.pdf the
chinembly I provided for
UPDATED ON g.
--- I r..., :,-, ® a SHEET A1.05
Subject: PlanCheck
me ex Page Index: 12 Indicate bench heigh must be
Page Label:A-2.01 FITTING ROOM ENLARGED PLANS& 17-19")per ICC A .1-2017
ADA BEN=N ELEVATIONS 903.5.
Author: nickt
Indicate bench height - Color: ■ UPD ED ON
ICCA117�1-2017Pe File Name: 90.Architectural FULL Set 433 Hyman Ave
!-- 9 mMI 20240924.pdf SH ET A2.01
1_Iaiwg--..I „Area..
L \ = Subject: PlanCheck
d Page Index: 12 Indicate this door is remain in
:=.:"M°°T'°" Page Label:A-2.01 FITTING ROOM ENLARGED PLANS& a fixed open pos on or remove
r ELEVATIONS the curtain. 2 1 IBC 1010.1,
‘• Author: nickt 1010.1.7.
IM:f 1—..-Mi i Color: ■
File Name: 90.Architectural FULL Set 433 Hyman Ave DATED ON
"E' �" i 20240924.pdf
pdf
SHEET A2.01
90.Electrical FULL Set 433 Hyman Ave 20240809 (1).pdf(3)
Subject: PlanCheck
Page Index: 1 2023 NEC
Page Label: E-001.00 ELECTRICAL COVER SHEET
Author: nickt
--7CAl15NA ELECiRICFL CODE-2 Color: ■
File Name: 90.Electrical FULL Set 433 Hyman Ave 20240809 UP TED ON
Ecomiii (1).pdf EET E-001
Subject: PlanCheck
Page Index: 3 Include these lights in the
Page Label: E-101.00 ELECTRICAL LIGHTING NEW WORK c eck.
--_ PLAN
1 Author: nickt
w--- = Color: ■
- File Name: 90.Electrical FULL Set 433 Hyman Ave 20 40809
(1).pdf
c —1.1 - UPDATED 0
SHEET E-10
RECEIVED
10/22/2024
ASPEN
BUILDING DEPARTMENT
Subject: PlanCheck
Page Index: 3 Provide cutsheets showing
Page Label: E-101.00 ELECTRICAL LIGHTING NEW WORK fixture wattage and listing by a
PLAN nationally recognized testing lab.
Author: nickt
- Color: ■
File Name: 90.Electrical FULL Set 433 Hyman Av 20240809
(1).pdf
•
INCLUDED IN
REV #1
RESUBMISSION
RECEIVED
10/22/2024
ASPEN
BUILDING DEPARTMENT