Loading...
HomeMy WebLinkAboutFile Documents.800 S Monarch St.0062-2021-BRES (9) 800 S Monarch Building Comments_Markup Summary 90.Architectural Plans.20210323 (1).pdf(6) 1 o Page Label: 7 As an R2 building, 3 stories or © I Author: bonniem Date: 11/8/2021 6:42:30 AM less above grade plane, this File Name: 90.Architectural Plans.20210323(1).pdf project falls into the residential a Y Subject: PlanCheck section of the IECC and - o ; T - f therefore will be subject to the ~ , Q Page Index: 7 L.„ '.,...„,....„ i , Checkmark: Checked R REMP mitigation fees. Please R Remp updated on sheet provide an updated R-REMP A-3.30 A3.30 and provided worksheet on A-3.30 and as a b b `` seperately separate document. ® � Page Label: 10 I Author: bonniem Penetrations into or through I Date: 11/8/2021 6:30:44 AM interior exit stairways are File Name: 90.Architectural Plans.20210323(1).pdf prohibited except for equipment and ductwork necessary to serve Subject: PlanCheck the interior exit stairway. (2015 Page Index: 10 penetration removed. new fl Checkmark: Checked routing through the ceiling IBC 1023.5) � ecmar goes/floor of the parking garage and Please clarify if this penetration utility room. meets the requirement in 1023.5 or the exception for membrane penetrations protected per 714.3.2 Page Label: 11 Author: bonniem Provide U-factor information for Date: 11/8/2021 7:00:16 AM new windows. New fenestration File Name: 90.Architectural Plans.20210323(1).pdf to have a u-factor of.28 or less .___-_____ _, — Subject: PlanCheck and be NFRC labeled per Table ®� 1m, Page Index: 11 NFRC label specification and R402.1.2 Checkmark: Checked U value requirement added for ►email q FAT `----- new windows on sheet A-4.00 Page Label: 13 Author: bonniem Provide listed/tested assembly ~ ~~ Date: 11/8/2021 6:16:15 AM or prescriptive calculation per rl i�� File Name: 90.Architectural Plans.20210323 (1).pdf Table 722.2.1.4(2)to verify 1 hr r r fire rating - = ; o s ,,, Subject: notAComment, please flatten Page Index: 13 Checkmark: Checked If using an assembly from the Gypsum Manual or UL, include UL 305 and installation the full installation instructions in instructions add to assembly the assemblies sheets. sheet. 'va E€ i-- 1 - Page Label: 14 Primary structural frame requires Author: bonniem 1 hour fire-resistance in type VA „ Date: 11/5/2021 11:59:01 AM construction (Table 601)Update File Name: 90.Architectural Plans.20210323(1).pdf + _ ` ""'° detail to show a 1 hour =_ _ w. = Subject: PlanCheck horizontal assembly below the == = = Page Index: 14 1 hr membrane added below Checkmark: Checked structural frame or other form of a type c drywall for f1 assembly individual encasement protection per 704.4 Page Label: 15 Author: bonniem Per 2015 IBC 11.This project Per 2015 IBC does not need to be accessible Date: 11/8/2021 6:01:16 AM 5''"4, ,„er tboraaa because the recreational ,aell;6eatl°"°, File Name: 90.Architectural Plans.20210323 (1).pdf ry�eaov�pea Subject: NotAComment, please flatten facilities do not serve any type A, (p,S IBC;;p:3, type B, or accessible units. ,,,g2) Page Index: 15 k°paare (2015 IBC 1104.3, 1110.2) tlaa,ea,„aGi Checkmark: Checked No corrections are needed, but g or inaPo"ing fw Nll 2 awesslb;0y the City of Aspen will not be .. ` c pliance. understood. reviewing or inspecting for full accessibility compliance. 90.Electrical & Lighting Plans.20210323.pdf(1) 3 COORDINATE LOCATION OF ALL APPLIANCES WITH OWNER PRIOR.p Page Label: [4] 20041-E1 (D-48)-E103 a°ppwl° Author: bonniem This project is required to meet Date: 11/5/2021 6:15:00 PM the requirements of the File Name: 90.Electrical &Lighting Plans.20210323.pdf residential sections of the 2015 �mia pmian is raamreammaa,na raawremanteama IECC, not commercial. The eCOMrovi illnot le Instead Subject: 75% high efficacy lamps The COMCM1eck provided will na be applicable Instead :° m°I)6ka,alllam°"^"ells"nPomana"' COMcheck provided will not be a same„ba„Ig„a�a lntlwallinganl.Naa Page Index: 4 12 404 e"irement on lM1 g gplans(2g,61ECG Checkmark: Checked applicable. Instead, a minimum of 75%of all lamps installed in See updated sheet with added permanent light fixtures must be table showing 100%as high high efficacy in dwelling units. efficacy Note this requirement on the lighting plans. (2015 IECC R404.1) 90.Mechanical & Plumbing Plans.20210323.pdf(1) Page Label: [7] 20041-M2(d-48)-M2.3 L Author: bonniem Penetrations into or through interior exit stairways are Date: 11/8/2021 6:30:17 AM File Name: 90.Mechanical & Plumbing Plans.20210323.pdf prohibited except for equipment Subject: PlanCheck and ductwork necessary to serve Page Index: 7 the interior exit stairway. (2015 ,, Checkmark: Checked IBC 1023.5) Please clarify if this penetration stair penetration removed. see meets the requirement in 1023.5 updated drawing for new location or the exception for membrane I and routing. penetrations protected per 714.3.2 90.Structural Plans.20210323.pdf(1) Page Label: 3 re � .�, u Author: bonniem Revise structural sheets to Date: 11/8/2021 6:38:10 AM include a special inspection Rev;,a °"are"base'°'net"tleaapacia""apac6°"special lnspe File Name: 90.Structural Plans.20210323.pdf program as required by the etl by[M1e alon agreement.Listeall items,M1e,require special Inspection an w„et„ert„eyreaalrepabotl;°°r�ntlna°aa special inspection agreement. n=pe"°n;nacc°r„an�w„„z6,61BG„g6 Subject: Special Inspection Program Provitlea spe"al inspecton agreement signetl by ell List all items that require special re,airaa°°^ia, Page Index: 3 Ial-l",a�o reement inspection and whether they Checkmark: Checked require periodic or continuous inspection in accordance with 2015 IBC 1705. Provide a special inspection structural sheets updated to agreement signed by all required indicate the special inspection parties. requirements. Special inspection https://www.cityofaspen.com/Do agreement is also executed and cumentCenter/View/5146/Specia provided. I-Inspection-Agreement