HomeMy WebLinkAboutFile Documents.688 Spruce St.0119-2020-BRES (30) THe Mozingo CODE The Mozingo Code Group, LLC GROUP LLC 261 W 79th Ct Denver, CO 80221 sdmozingo@mozingocodegroup.com PLAN REVIEW REPORT PROJECT 688 Spruce Street PROJECT LOCATION Aspen, CO DATE OF REVIEW December 21, 2020 REVIEW BASED ON PLANS DATED 10/16/2020 Architectural 08/20/2020 Structural REVIEW CONTACT Shaunna Mozingo, President The Mozingo Code Group LLC sdmozingo@mozingocodegroup.com DESIGN TEAM COMMENT RESPONSES IN RED ON FOLLOWING PAGES, AND SUPPLEMENTAL INFORMATION IS INCLUDED AT END OF DOCUMENT. RREC5AVBD 127 /20D21 ASPCSHEN BUIB®MN61dING (VENT 688 Spruce Street, Aspen First Review PROJECT INFORMATION ARCHITECT: CCY Architects STRUCTURAL ENGINEER: KL&A Engineers MECHANICAL ENGINEER: Resource Engineering Group ELECTRICAL ENGINEER: Resource Engineering Group CODES USED FOR REVIEW (as amended by Aspen) 2015 International Building Code 2015 International Mechanical Code 2015 International Plumbing Code 2015 International Energy Conservation Code 2020 National Electrical Code BUILDING INFORMATION New SFD Total Floor Area: 4930 Notice This cursory plan review is based on the codes noted herein and represents a list of corrections necessary to comply with the requirements contained within them. This review is not a building permit. The local jurisdiction is responsible for issuing the appropriate permits based on this review. The approval of plans and specifications does not permit the violation of any section of any federal, state or local regulations. All comments in this report are based on the information provided on the drawings and supporting documentation provided for review. The Mozingo Code Group, LLC does not accept any responsibility for any condition that was not known at the time of this report. We reserve the right to amend this report if additional information is received. This report does not purport to review, interpret, apply, or certify compliance with the accessibility requirements set forth within the Americans with Disabilities Act (ADA). The application, interpretation and enforcement of the ADA are vested with the Federal Department of Justice. Applicants are encouraged to seek professional review to ensure compliance with the ADA. RECEIVED 12/28/2020 REIVED BOILio.�39lA�T 021 Mozingo Code Group, LLC /z ASPEN BUILDING DEPARTMENT 688 Spruce Street, Aspen First Review REVIEW COMMENTS The items noted below with a comment number (B-1, B-2 etc.) are items that need to be corrected to show compliance with the applicable codes. Please provide a written response indicating where the corrections are made on the plans. This will speed up the review process. Additional plan review comments may be added once revised plans are received for review. BUILDING CODE COMMENTS B-1 Refer to Sheets A202: Please specify how the glass guard behind the moveable screen meets the requirements of IRC Section R308.1 and its subsections, as amended by the City of Aspen. Please also provide construction details and specifications for the glass guard. Railing has been redesigned to typical horizontal I steel bar railing, see detail 10/A-530, and Structural Details. DETAIL 1 ON A520? B-2 Please specify where on the plans the provisions for IRC Section R309.6 Electric Vehicle Charging, as adopted by the City of Aspen, can be found. Sheet E-102 mentions an EV charging station in the garage but that is the only thing provided. INFORMATION WAS INCLUDED IN ELECTRICAL PLANS ALREADY B-3 Refer to Electric plans, Sheet E102: Plans contain a note that there will be pre-wiring for a future elevator. Separate permit required for future installation of an elevator per IRC Section R321.4 as amended by the City of Aspen. ELEVATOR IS NOT BEING DESIGNED OR INSTALLED AT THIS TIME. 10+ YEARS IN THE FUTURE B-4 Refer to Sheet A502: Please specify how all of the exterior wall coverings will meet the wall covering requirements of Table R703.3(1). There are no details in the architectural s/ or structural plans. Please also specify how the anchored stone veneer will meet the requirements for anchorage, air spaces, weepholes, etc of Section R703.8. The details say to refer to the structural plans, but the structural plans say it is per the architectural plans. ADDED NOTES TO STONE VENEER. ANCHORS AND FASTENERS ARE NOW SHOWN IN ASSEMBLIES. B-5 Refer to Architectural Sheet A-500: Please specify how any enclosed rafter spaces '1e meet the roof ventilation requirements of IRC Section R806.1 as amended by the City of Aspen. HOT ROOF ASSEMBLY DOES NOT REQUIRE ROOF VENTS. B-6 Refer to architectural, mechanical, electrical, and structural plans: Please specify how the 23.41 KW solar array meets the requirements of IRC Sections R902.4, R907 or R909, and R324. Sheet A-112 says to reference the mechanical plans but there are no specifications located within the mechanical plans. There is a small mention of the electric requirements in the electric plans but no specifications or details. The structural plans do mention in a comment that the roof load did take into consideration the PV array. Please also see electric comments below. C��C DESIGN-BUILD SOLAR ARRAY.ADDED NOTE TO ROOF PLAN THAT SOLAR A ARRAY TO BE FIELD COORDINATED TO MEET ALL IRC REQUIREMENTS STRUCTURAL COMMENTS 12/28/2020 ASPEN S-1 Refer to Structural plans Sheet S-001: Please clarify why Seismic Design Categg9ll 'G DEPARTMENT was used instead of C, IRC Table R301.2(1) as amended by Aspen. Please alsq�larifIVED 3IPage ALL STRUCTURAL Mozingo Code Group, LLC 03/11/2021 COMMENTS ADDRESSED ON PAGE 8 OF THIS PDF ASPEN BUILDING DEPARTMENT 688 Spruce Street, Aspen First Review why an elevation of 5280 was used instead of 7400, or if it has any bearing on the calculations. Also please complete the notes in the Design Criteria table as they are incomplete or reference wrong codes and standards. S-2 Refer to Structural Sheet S-122: Please specify the proper description for Keyed note <1> as it is missing. The note applies at Grids C and D. S-3 Refer to Architectural Sheet A130: The plans call for a pulldown stair to access storage in the garage attic. Please clarify whether the attic has been designed for loads associated with storage and provide details for pulldown stair framing. S-4 Refer to Architectural Plans, Sheet A-425: Please provide details for the west outdoor room screen wall that is shown on the plans. MECHANICAL CODE COMMENTS M-1 Refer to Mechanical Plans: Please provide heating and cooling load calculations in accordance with IMC Section 312.1. There is a "total zone heat loss" summary but nothing to show how those losses were calculated. Also, Sheet M001 lists design conditions with a winter outdoor temperature of-20 and summer outdoor temperature of 95. Aspen's design temperatures are -15 and 82. Please be sure that the load calculations submitted use these design temperatures and revise Sheet M001 accordingly. / See M001 Summary M-2 Refer to Mechanical Plans: Please provide ventilation calculations per IMC 403.3.2.1 through 403.3.2.3, as amended by the City of Aspen. Also, please specify the combination mechanical ventilation strategy used to meet the requirements of IMC 403.1, as amended by the City of Aspen. The plans show ERVs and exhaust fans in the controls sequence on Sheet M204 and a "max cfm" of 120 on Sheet M201 equipment schedule. Ventilation calculations are needed to show that the 120cfm is needed. See M001 Summary M-3 Refer to Mechanical and Plumbing Plans: Please provide water heating and space heating sizing calculations in accordance with IMC 1002.2.1 to ensure the combined systems will each be met. See M001 Summary RECEIVED 1211b1F ED 4 I IASv Mozingo Code Group, LLC BUILDINCCEEMIIOD21 ASPEN BUILDING DEPARTMENT 688 Spruce Street, Aspen First Review M-4 Refer to Mechanical Sheets: Exhaust fans are required in bathrooms and toilet compartments, not just the toilet compartments. Please provide exhaust fans in all rooms containing showers and/or tubs in accordance with M403, as amended by the City of Aspen. / See M001 Summary M-5 Refer to Electric Sheet E102: Please provide details and/or specifications for the patio heaters referenced in the electric sheets. / Not Part of Mechanical System PLUMBING CODE COMMENTS f See Response Letter, page 11 of this PDF P-1 No plumbing sheets submitted. Refer to Architectural Sheet A-110 and Mechanical Sheet M101, project note #19: Plans show a hot tub (by others) but no other information has been submitted for the plumbing, electric, mechanical or energy efficiency of the hot tub. Please provide additional information in order to verify compliance. P-2 Refer to Sheet A110 and mechanical plans: Please provide gas pipe sizing calculations with your design in accordance with IFGC Section 402. Please note that the mechanical plans show boilers for both the home heating/water heating as well as for the snow melt. The gas pipe sizing needs to include all appliances. There is an outdoor bbq, outdoor heating and fireplace as well as multiple gas appliances within the home. On Sheet M001, there is a comment that the lines have been sized for a capacity of 1090 MBH. This may not be accurate with all appliances included in the calculation. ENERGY CODE COMMENTS EN-1 Refer to Mechanical and Architectural plans: The plans specify prescriptive Energy Code compliance. Please specify how the plans will comply with the followina thermal envelope requirements: We are now pursuing RESCheck compliance. See Report, Uploaded into Salesforce a. Slab Edge Insulation: There is a requirement tor K]u insulation b tor neatea slabs) for a depth of 4 feet at all slabs less than 12" below grade. Please specify how the slabs that are less than 12" below grade will meet the requirements of R402.2.10. (this requirement is in addition to the under slab insulation required for radiant slabs). b. Please clarify if the R13 insulation in Wall 6 and Wall 7 is truly continuous or cavity insulation. The plans say"ci" but the wall is a framed wall and this is closed cell sprayed being used. Will it be sprayed between the framing members s.� 5 I E2, 2✓8/2020 Mozingo Code Group, LLC 03/11/2021 ASPEN BUILDINGPOMENT BUILDING DEPARTMENT 688 Spruce Street, Aspen First Review or continuously over the top of the framing members? If it is continuous, the detail is incorrect on Sheet A505. RE: ASSEMBLIES. ADDED NOTE TO CLARIFY Ely;2 Please specify how the hot water piping will meet the pipe insulation requirements of IECC Section R403.5.3 4 See M001 Specs EN-3 Please specify how the fans used for the whole house mechanical ventilation system meet the efficiency requirements of IECC Section R403.6.1 as amended by the City of Aspen. EN-4 Please specify how the balan ed ventilation system meets the requirements as set forth in IECC Section R403.6.2, as dded by the City of Aspen. EN-5 Please specify how the sn w elt system controls will meet the requirements of IECC R403.9. Equipment, Approaches, and Controls are professionally engineered within the guidelines of applicable codes. Equipment, ELECTRICAL CODE COMMENTS Rates, and Controls are all provided for review. Please provide specific comments/issues to address if they exist heet E001 Project Information — Per Sec. 8.24.010 of city Amendments, correct to 2020 NEC as adopted by state October 1, 2020, most current edition. Electrical Specifications— C.1 — ...per NECA 1. What is the reason for this reference? Sheet E002 One-Line Diagram —Anticipated 75kVA transformer—Justify size. Max 312.5 amps. Too small for calculated load from Load Calculation; CT Meter and Disconnect—Article 230.85 requires an Emergency Disconnect. Provide confirmation that the Disconnect will meet one of the design provisions from 230.82 (1) — (3) or an additional EM disconnect is required; Main Distribution Panel — Future Elevator in question. It has been included in the load calculation and is not noted as future; Tesla Gateway— Is there a current solar system in for review? Need product specifications for all Tesla Gateway, Generation Panel, Tesla Powerwall, AC Combiner, Solar Panels, Array disconnects, and associated OCPD's for the system. Where is the Rapid Shutdown for PV as required per 690.12? General notes for this page — 2. Verify all loads have been included in Load Calculation. List of additional equipment is not reflected in the Load Calculation. Detail notes for this page — 11. - ...to be rated 220A—This rating conflicts with one-line. Load Calculation —Area 5,756 SF differs from Architectural Plans Cover Sheet G-000 at 4,930 SF; Use of Art. 220.82 is based on known nameplate values. Load for Future Steam Showers and Assumed Patio Heaters in question; From Sheet M201 ASHP-1 &ASHP-2 are 31 amps at 230 volts. This value is only 14,880 VA as applied. Load calculation shows 19,215 VA; Only pumps 3, 8, and 9 are shown. From Sheet M204 Pumps 4, 5, 6, and 7 should be added based on use; Architectural Sheet A-10 show a Self-Contained Hot Tub. This load is not reflected; Where are the product specification sheets for all known values of equipment used? RECEIVED See Response Letter, pages 9-10 of this PDF REGENED 6IPage Mozingo Code Group, LLC 03/i1DPir:21021 BUILDING DEPARTMENT ASPEN BUILDING DEPARTMENT 688 Spruce Street, Aspen First Review Feeder Schedule — Feeder Note 2 —Ground to increase per 250.102 (C)(1) as this is a Supply- Side Bonding Jumper and not an Equipment Ground. Feeder Notes 6 & 7 — Feeders to be provided pending receipt/ review of PV Tesla system. Load Calculation EM-1 — Range at 1,750 VA while Range in Load Calculation is 1,725 VA. Why are these different?; Why are Pumps 4 & 7 accounted for when not on Load Calculation? Sheet E101 Provide General Note for page to require all 125-volt to 250-volt receptacles located on the lower level to be GFCI protected per 2020 NEC 210.8 (A)(5). Outdoor Kitchen/BBQ —AG receptacles are also required to be weatherproof per NEC 406.9 (A) & (B). PDR near Wet Bar— Missing EF-1? Sheet E102 Kitchen —Appears to have a built in Island from Sheet A-111. Provide general note to provide island receptacles as calculated from 2020 NEC 210.52 (C)(2). Garage— Garage Door receptacles to be GFCI protected per 210.8 (A)(2). Master Bath — Heated towel bars not included in Load Calculation. Sheet E103 Not reviewed. Pending PV submittal/ review. RECEIVED 12/28/2020 ASPEN BUILDING DEPARTMENT RECEIVED 7 ' Page Mozingo Code Group, LLC 03/11/2021 ASPEN BUILDING DEPARTMENT Goldfarb Residence—688 Spruce Street,Aspen CO Structural Design Review Comment Responses S-1 a. The lateral design is based on the IBC,which calls for a different Seismic Design Category than the IRC. In this case and for this code,we find that SDC B is appropriate. Please see attached for an "ATC Hazards by Location" printout of the determination of the IBC design category. j. Using the elevation 5280 for this elevation factor is a KL&A standard and is a conservative assumption. Using the site elevation of—7900 would result in a reduced lateral load. An updated S-001 General Notes sheet has been included to provide this missing information S-2l This keyed note should read "Provide double joist to serve as collector." Omission of the text for this keyed note was in error. S-3 A load key region has been added to S-003 to provide loading direction to the premanufactured truss designer, and an updated version of this sheet has been included. Note that it is the premanufactured truss designer's responsibility to design the attic/roof structure at this location. S-4 VElevations and details for the outdoor room screen wall have been developed and are included on S-300. RECEIVED 03/11/2021 ASPEN BUILDING DEPARTMENT FIFIF- REG R E S O U R C E ___,,,„ E N G I N E E R N G GROUP Shuanna Mozingo President The Mozingo Code Group 261W 79th Ct Denver, CO 80221 sdmozingo@mozingocodegroup.corn January 15, 2021 Regarding: 688 Spruce Street - Plan Review Report(Dec 21, 2020) Dear Shaunna: Please see electrical code comment responses below. E001: Sheet E001 Project Information—Per Sec. 8.24.010 of city Amendments, correct to 2020 NEC as adopted by state October 1, 2020, most current edition. EVrical Specifications—C.1 — ...per NECA 1. What is the reason for this reference? REG Response: Updated for NEC 2020 compliance. NECA 1 is a standard for electrical installation and further defines specifications not detailed in the NEC. Sheet E002 One-Line Diagram—Anticipated 75kVA transformer—Justify size. Max 312.5 amps. Too small for calculated load from Load Calculation; CT Meter and Disconnect—Article 230.85 requires an Emergency Disconnect. Provide confirmation that the Disconnect will meet one of the design provisions from 230.82 (1)—(3) or an additional EM disconnect is required; Main Distribution Panel—Future Elevator in question. It has been included in the load calculation and is not noted as future; Tesla Gateway—Is there a current solar system in for review?Need product specifications for all Tesla Gateway, Generation Panel, Tesla Powerwall, AC Combiner, Solar Panels, Array disconnects, and associated OCPD's for the system. Where is the Rapid Shutdown for PV as required per 690.12? s/ REG Response: Transformer sizing is per utility. Documentation updated for clarity regarding transformer and disconnect. The elevator load is displayed in the equipment schedule as ELE-1 which states "Future Elevator—Estimated". PV design per others. General notes for this page—2. Verify all loads have been included in Load Calculation. List of additional equipment is not reflected in the Load Calculation. REG Response: Updated notes for clarity. HVAC loads are included in the "Heating and Air Conditioning Load" section of the load calculation. Detail notes for this page— 11. - ...to be rated 220A—This rating conflicts with one-line. REG Response: Updated Load Calculation—Area 5,756 SF differs from Architectural Plans Cover Sheet G-000 at 4,930 SF; Use of Art. 220.82 is based on known nameplate values. Load for Future Steam Showers and Assumed Patio Heaters in question; From Sheet M201 ASHP-1 &ASHP-2 are 31 am C E IVE ID 230 volts. This value is only 14,880 VA as applied. Load calculation shows 19,215 VA; 0 1 Consulting Engineers • Mechanical • Structural • Energy 0 3 11 2 0 21 Crested Butte&Golden Colorado • reginc.com ASPEN BUILDING DEPARTMENT pumps 3, 8, and 9 are shown. From Sheet M204 Pumps 4, 5, 6, and 7 should be added based on use; Architectural Sheet A-10 show a Self-Contained Hot Tub. This load is not reflected; Where are the product specification sheets for all known values of equipment used? REG Response: Updated where applicable per discussion with City of Aspen code review. Please reference new notes regarding loads included in HVAC calculation which clarify that "Heating and Air Conditioning Load" also includes associated air handlers and pumps in addition to the Heat Pumps. Feeder Schedule—Feeder Note 2—Ground to increase per 250.102 (C)(1) as this is a Supply-Side Bonding Jumper and not an Equipment Ground. Feeder Notes 6 & 7—Feeders to be provided pending receipt/review of PV Tesla system. VREG Response: Updated Ground sizing. Feeder 6 and 7 per PV installer. Load Calculation EM-1 —Range at 1,750 VA while Range in Load Calculation is 1,725 VA. Why are these different?; Why are Pumps 4 & 7 accounted for when not on Load Calculation? REG Response: Load Calculations updated. Pumps 4 and 7 are included in the HVAC calculation for the general building load. They are explicitly called out for the emergency load in order to provide clarity to the installer. Added additional notes to plan set for clarity. Sheet E 101 Provide General Note for page to require all 125-volt to 250-volt receptacles located on the lower level to be GFCI protected per 2020 NEC 210.8 (A)(5). V REG Response: Updated Outdoor Kitchen/BBQ—AG receptacles are also required to be weatherproof per NEC 406.9 (A) & (B) V REG Response: Updated for clarity PDR near Wet Bar—Missing EF-1? V REG Response: No, confirmed with Mechanical. Sheet E102 Kitchen—Appears to have a built in Island from Sheet A-111. Provide general note to provide island eceptacles as calculated from 2020 NEC 210.52 (C)(2). REG Response: Updated Garage—Garage Door receptacles to be GFCI protected per 210.8 (A)(2). REG Response: Updated note to clarify EC responsibility to provide GFI breakers where applicable. Master Bath—Heated towel bars not included in Load Calculation. VREG Response: Updated Sheet E103 Not reviewed. Pending PV submittal/review. N(t Please feel free to contact to me with any follow questions or comments. Sincerely, Kristine Thompson, PE RECEIVED Consulting Engineers • Mechanical • Structural • Energy 0 3 11 2 0 21 Crested Butte&Golden Colorado • reginc.com ASPEN BUILDING DEPARTMENT Fr"- R EG RESOURCE _Ai E N C I N E E R INC GROUP Shuanna Mozingo President The Mozingo Code Group 261W 79th Ct Denver, CO 80221 sdmozingo@mozingocodegroup.com (January 06, 2021) Regarding: 688 Spruce Street - Plan Review Report(Dec 21, 2020) Dear Shaunna: Please see plumbing code comment responses below. P-1 No plumbing sheets submitted. Refer to Architectural Sheet A-110 and Mechanical heet M101,project note#19: Plans show a hot tub (by others)but no other information has been submitted for the plumbing, electric, mechanical or energy efficiency of the hot tub. Please provide additional information in order to verify compliance. REG Response: REG was asked to provide water service sizing only. The Permit Authority, City of Aspen, does not require plumbing plans for residential permit applications. Please consult Architect and/or Spa Designer for additional information pertaining to spa system design and compliance. P-2 Refer to Sheet A110 and mechanical plans: Please provide gas pipe sizing calculations with your design in accordance with IFGC Section 402. Please note that the mechanical plans show boilers for both the home heating/water heating as well as for the snow melt. The gas pipe sizing needs to include all appliances. There is an outdoor bbq, outdoor heating and fireplace as well as multiple gas appliances within the home. On Sheet M001, there is a comment that the lines have been sized for a capacity of 1090 MBH. This may not be accurate with all appliances included in the calculation. REG Response: REG was asked to provide gas service sizing only. This sizing is provided on sheet M001 in the Gas Design Conditions section. Service sizing has been updated to reflect equipment selections made for CD plan set. A gas appliance schedule has been provided on M201 with a breakdown of all gas appliances identified on Architectural and Mechanical floor plans. Please feel free to contact to me with any follow questions or comments. Sincerely, Cal Fenerty RECEIVED Consulting Engineers • Mechanical • Structural • Energy 03 11 2 21 Crested Butte&Golden Colorado • reginc.com ASPEN BUILDING DEPARTMENT