HomeMy WebLinkAboutFile Documents.824 E HOPKINS AVE.0093-2021-BRES (6)These plans must be kept at the
building site or inspection
delays may occur. Construction
shall conform to these plans. All
changes shall be approved by
the building official.
Field Plan Set Must Be Printed In Color
SEPARATE PERMITS ARE
REQUIRED FOR ELECTRICAL,
PLUMBING, MECHANICAL, OR
FIRE SPRINKLER WORK
SMOKE ALARMS AND
CARBON MONOXIDE
DETECTORS REQUIRED
THROUGHOUT DWELLING
UNIT PER CITY OF ASPEN
MUNICIPAL CODE 8.15
RESIDENTIAL REFERENCES FROM 2015 IBC
CV/CS = crawl space ventilation sec. 1203.4. 18” x 24” access required
1209.1
EE = emergency escape required sec 1030
EU = enclosed usable space under stairs shall be 1-hr construction or stair
enclosure rating. No access from stair enclosure. ½” gypsum permitted for
stairs inside a single dwelling unit. 1011.7.3.
RV = roof and rafter ventilation required 1203.2
A = Attic Access 20” x 30” 1209.2
SA = smoke alarm (NFPA 72) required sec 907.2.11
CO = carbon monoxide detector req. per Aspen Municipal Code 8.15
SG = safety glazing required sec 2406
V = mechanical ventilation required sec 1203.1 & IMC 403 (bath fans and
whole house ventilation)
GR = guards, 42” min ht, 4” max opening. Guards within dwelling unit 36” min
ht sec 1015
HR = handrails 34”-38” ht sec 1014
DS = Draft stopping / fire blocking 718
RD = Roof drainage 1503.4
STC = Sound transmission class not less than 50 at dwelling separations, sec
1207
SI = Stairway Illumination 1205.4
PD = protect against decay, sec 2304.12
REFERENCES FROM 2015 IMC
DE = clothes dryer exhaust, sec 504. Makeup air req’d if over 200 CFM
AS = access and service space for maintenance req’d, sec 306
MA = make up air required if hood exhausts greater than 400 CFM, sec 505.2
ET = exhausts terminate 3’ from prop line and openings, 10’ from intakes,
501.3.1
IT= intake openings 10’ from lot line & contaminant sources (vents, streets),
401.4
D = fasten and seal all ductwork per 603.9
REFERENCES FROM 2015 IFGC
DV = direct vent req’d, sec 303.3
CA = combustion air not taken from bedrooms, bathrooms or
storage sec 303.3
OD = outdoor appliances must be listed for outdoor use, sec 303.6
REFERENCES FROM 2015 IECC
F = new or replacement fenestration shall not exceed 0.28 U-factor, NFRC
label required, Ordinance 40, 2016
L = 75% of lamps in permanently installed lights must be high efficacy, sec
R404.1
SE = Continuous air barrier required; all exterior joints, cracks, and holes to be
caulked, gasketed, sealed, table R402.4.1.1
REFERENCES FROM 2014 NEC
EP = electric panel 'happy space' 30"x36"x78", not in storage, sec 110.26
FIRE RATED HATS REQUIRED
Where floor/ceiling or roof/ceiling
assemblies are required to have a
fire-resistive rating, recessed fixtures shall
be installed such that the required fire
resistance will not be reduced (IBC 714.4.2)
READ THIS OR FAIL YOUR INSPECTION!
Furred & Dropped Ceilings, Soffits, and Walls
20015 IBC 803.13
This applies to the attachment of finishes or furring to any
assemblies that are required to be either fire-rated or
non-combustible and is separate from the fire-rated
assembly requirement.
Walls, Ceilings & Soffits: If furred 1 ¾ inches or
less, do one of the following:
4.Fill spaces with Class A material.
5.Fill spaces with inorganic or non-combustible material.
6.Fire block 8 feet in all directions.
Walls: If set out (furred) greater than 1 ¾ inches,
do one of the following:
4.Use a Class A finish material (such as drywall).
5.Use non-combustible framing.
6.Protect both sides with fire sprinklers.
Ceilings & Soffits: If dropped (furred) greater
than 1 ¾ inches:
Framing members, hangers, and other assembly
members must be non-combustible. You may not
use wood.
In Type III and V construction only, you may use fire
retardant treated wood or non-combustible framing.
•2 layers 5/8 SHEETROCK Brand 2 hour UL Des L541 B-10
FIRECODE C Core Gypsum Panels
– 2x10 wood joists 16 o.c.
– 3 mineral wool batt
– RC-1 channel or equivalent
13"
59 RAL-TL-90-40
69 RAL-IN-90-5
59 RAL-TL-90-40
Based on vinyl tile in
place of carpet/pad
37 RAL-IN-90-6
Ceiling Assembly
Description STC IIC
Accoustical
Test Number Rating Test Number
Fire
Figure 242
2x4 staggered framing
3 1/2" glass fiber insulation
Side 1: 5/8" Gypsum Board, 1/2 Fiberboard
Side 2: 5/8" Gypsum Board, 1/2" Fiberboard
STC 58
UA 2 hour
Chase Wall Assembly
06/23/2021
Silver Town Structures
307 AABC Unit N
Aspen, CO 81611
June 28, 2021
RE:
Jody Larner Apartment Remodel
830 East Hopkins, Unit 103
Aspen, CO 81611
Aspen Building Department
To whom it may concern:
I am writing this letter to confirm the involvement of Silver Town Structures as a
consultant with this remodel project. I have reviewed the proposed remodel plans provided by
Sophie Harvey Design dated. I also personally inspected the premises on June 24,2021. The
structure is a three story wood frame, multi family residence. The exterior has a timber framed
stair for access to each apartment. Unit 103 is located at the garden level at the West end of the
building. There are two units above and one adjacent unit towards the East. The floor at this
level is over a crawlspace.
At the time of my inspection, several openings had been cut in the drywall to expose the
framing conditions. Brad Smith representing Hendrickson Construction was present and pointed
out the proposed changes.
Based on the framing I was able to observe, it is likely that the proposed changes do not
interfere or alter the existing load-path. The structural integrity of this residence will not be
affected by the proposed changes. Framing conditions will be reassessed after demolition has
occurred. I have agreed to make myself available to consult when new information regarding the
structure allows for a better assessment. Any structural modifications necessary to allow for the
proposed remodel will be provided at that time.
Sincerely,
Hein Brutsaert P.E.
06/29/2021