Architectural Engineering Consultants, Inc.
An Office with LEEDTTMM Accredited Professionals
40801 US Hwy 6 & 24,Suite 214,Eagle-Vail, CO 81620 Post Office Box 8489,Avon, CO 81620
phone: 970-748-8520 email: stan@aec-vail.com:www.aec-vail.com
May 19, 2021
Mr. Joseph Spears
S2 Architects
Aspen, Colorado 81611
joseph@s2architects.com
Re: 634 W. Hopkins Aspen Residence
Dear Joseph,
This document is intended to show compliance of the remodel of the residence located at 634 W
Hopkins, Aspen, CO with the 2015 International Energy Conservation Code (2015 IECC). We propose to
use a prescriptive approach (U-factor alternative) per sections 402.1-402.3 and 403.2.1 of the 2015 IECC.
Project
The project at 634 W Hopkins is the remodel of a residence with a floor area of 4,850 sf. The heat load
calculations are performed using the Carrier Hourly Analysis Program and provides a more detailed and
accurate load than Manual J.
Building Envelope
The following table lists the mandatory minimum insulation and fenestration requirements for the project
climate zone (7). All new assemblies will meet the following requirements.
Fenestration
U-factor
Ceiling U-
factor
Wood frame
wall U-factor
Floor
U-factor
Basement wall
U-factor
Slab
U-factor
Code Minimums 0.28 (1) .026 .045 .028 .050 .055
Notes: 1) Fenestration SHGC requirements do not apply in climate zone (7)
2) 4 ft deep and R-15 edge insulation for heated slabs
Sincerely,
Dan Findley
Mechanical Engineer
MANUAL J DESIGN CONDITIONS
WINTER DESIGN CONDITIONS SUMMER DESIGN CONDITIONS
OUTDOOR TEMPERATURE -15 °F OUTDOOR TEMPERATURE 82 °F
INDOOR TEMPERATURE 70 °F INDOOR TEMPERATURE 75 °F
TOTAL HEAT LOSS 102,200 BTU/HR SENSIBLE HEAT GAIN 95,400 BTU/HR
LATENT HEAT GAIN 0 BTU/HR
TOTAL HEAT GAIN 95,400 BTU/HR
Zone Sizing Summary for WHOLE HOUSE
Project Name: 20076 - 634 W HOPKINS 05/19/2021
Prepared by: AEC 12:15PM
Air System Information
Air System Name WHOLE HOUSE
Equipment Class UNDEF
Air System Type SZCAV
Number of zones 1
Floor Area 4850.0 ft²
Location Eagle, Colorado
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM Sum of space airflow rates
Space CFM Individual peak space loads
Calculation Months Jan to Dec
Sizing Data Calculated
Zone Sizing Data
Maximum Design Minimum Time Maximum Zone
Cooling Air Air of Heating Floor
Sensible Flow Flow Peak Load Area Zone
Zone Name (MBH)(CFM)(CFM)Load (MBH)(ft²)CFM/ft²
Zone 1 95.4 7751 7751 Aug 1600 102.2 4850.0 1.60
Zone Terminal Sizing Data
No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space
Space Name Mult.(MBH)Load (CFM)(MBH)(ft²)CFM/ft²
Zone 1
001 - STAIR 1 0.8 Jul 1500 73 1.5 115.0 0.63
002 - MECHANICAL 1 0.4 Jul 1500 41 0.8 85.0 0.49
003 - CRAWL SPACE 1 0.7 Jul 1600 176 3.5 225.0 0.78
004 - LAUNDRY 1 2.6 Jul 1500 188 0.3 75.0 2.51
005 - OWNERS CLOSET 1 0.4 Jul 1500 27 0.5 55.0 0.49
006 - BEDROOM #1 1 2.0 Jul 1600 150 2.3 200.0 0.75
007 - BATH 1 0.3 Jul 1500 24 0.2 50.0 0.49
008 - BATH 1 0.3 Jul 1500 24 0.2 50.0 0.49
009 - BEDROOM #2 1 1.8 Jul 1400 135 2.7 195.0 0.69
010 - DEN 1 3.0 Jul 1500 217 2.1 260.0 0.83
011 - BUNK 1 2.3 Aug 1300 171 2.5 195.0 0.88
012 - BATH 1 0.5 Jul 1500 39 0.7 80.0 0.49
100 - GARAGE 1 6.0 Jul 1600 639 12.8 500.0 1.28
101 - MUDROOM 1 3.3 Jul 1700 239 2.9 200.0 1.20
102 - ENTRY 1 12.5 Jul 1700 914 10.9 210.0 4.35
103 - PWD 1 0.2 Jul 1500 15 0.1 30.0 0.49
104 - MAIN LEVEL DEN 1 6.2 Aug 1600 458 6.3 365.0 1.25
105 - BEDROOM #3 1 2.5 Jul 1400 181 2.2 235.0 0.77
106 - BATH 1 0.6 Jul 1400 44 0.6 60.0 0.74
107 - BATH 1 0.6 Jul 1100 44 0.3 80.0 0.56
108 - BEDROOM #4 1 4.0 Jul 1400 294 4.3 245.0 1.20
201 - OFFICE 1 4.4 Jul 1700 320 3.7 70.0 4.57
202 - PWD 1 0.2 Jul 1500 14 0.2 25.0 0.56
203 - LIVING 1 9.8 Sep 1500 722 10.0 240.0 3.01
204 - KITCHEN 1 25.5 Sep 1500 1873 19.7 645.0 2.90
206 - MASTER BEDROOM 1 7.5 Jul 1400 550 8.2 205.0 2.68
207 - MASTER BATH 1 2.4 Jul 1600 177 2.9 155.0 1.14
Hourly Analysis Program v4.50 Page 1 of 1