Loading...
HomeMy WebLinkAboutInspection.675 E Durant Ave.0038-2024-BCOM CTL I THOMPSON 11111 Spray-Applied Fire-Resistive Material Information Project No.: GS06891.000E-395 Date of Measurements: 11/19/2024 Project: Little Nell Hotel - Parking Garage Report No.: 2 Client: AHG Parent Co LLC Technician: TDD Contractor: Alpha Insulation and Waterproofing, Inc Location of Measurements: Level P1 Substrate Information Required UL Required UL Thickness Design Thickness Design (Inches.) (Inches.) 1. Primary Beam Varies 263 Column 263 El Secondary Beam Varies 263 ❑ Fluted Floors ❑ Bar Joists ❑ Other Restrained: Submittal given by: Alpha Insulation and Waterproofing, Inc Substrate Condition Painted: 1. Oiled: ❑ Scale: ❑ Type of Fire-Resistive Material: Cafco Blaze-Shield II HS Measurements Performed Thickness Measurement: 1.1 Density Taken: • Bond Taken: ❑ Required Average Density: 15 pcf Required Strength: psf Remarks: As requested,a site visit was made to inspect spray applied fireproofing that was installed on repair areas at the Little Nell Hotel Parking Garage.Thickness measurements and density determination samples were taken today. Thickness measurements and density of spray-applied fireproofing met or exceeded the submitted project specifications. Lids were set to spray-applied fireproofing for bond testing,we will return to the site in 28-days to perform bond pull test. RECEIVED 11/20/2024 234 Center Drive 1 Glenwood Springs,Colorado 816011 Phone: 979-945-2809 Fax:970-945-7411 ASPEN BUILDING DEPARTMENT IIIII Thickness and Density of Sprayed Fire-Resistive Material Applied to Structural Members(ASTM E605) Project No.G506891.000E-395 Date of Measurements: 11/19/24 Project: Little Nell Hotel-Parking Garage Technician: TDD Thickness of Material on Beam or Column r 1 I \--1.1) V V • IF lir Ilr V V v V V V Req. Avg. Avg. Member Type 1 2 3 4 5 6 7 8 9 10 11 12 (In.) (In.) Column at D.1/8 line 28/16 25/16 24/16 21/16 22/16 25/16 19/16 21/16 22/16 17/16 19/16 23/16 22/16 N/A 26/16 22/16 23/16 18/16 20/16 19/16 25/16 23/16 22/16 16/16 24/16 17/16 Primary Beam,along 8 19/16 19/16 17/16 18/16 20/16 18/16 18/16 18/16 20/16 X X X 19/16 18/16 line,from D.1 to E.5 18/16 20/16 20/16 18/16 19/16 19/16 20/16 17/16 20/16 X X X Secondary beam,along 20/16 20/16 18/16 17/16 20/16 17/16 19/16 19/16 20/16 X X X 19/16 18/16 8.5 line,from F.5 to H.1 20/16 20/16 17/16 19/16 20/16 18/16 19/16 20/16 20/16 X X X Primary beam,along 8 21/16 19/16 21/16 17/16 20/16 18/16 19/16 20/16 19/16 X X X 19/16 19/16 line,from Ito 1 20/16 18/16 19/16 19/16 19/16 20/16 19/16 21/16 19/16 X X X Secondary beam, 20/16 19/16 19/16 19/16 21/16 21/16 18/16 21/16 21/16 X X X 20/16 19/16 along 8.5 line,from I 21/16 20/16 18/16 17/16 21/16 21/16 18/16 20/16 18/16 X X X Remarks: Thickness measurements performed today meet or exceed submitted project specifications. RECEIVED 11/20/2024 ASPEN BUILDING DEPARTMENT 234 Center Drive)Glenwood Springs,Colorado 81601)Phone:979-945-2809 Fax:970-945-7411 Density Determination For Sprayed Fire-Resistive Material ASTM E 605 Project No.: GS06891.000E-395 Date of Measurements: 11/19/2024 Project: Little Nell Hotel-Parking Garage Technician: TDD Required Dens Average: 15 pcf Individual: 15 pcf Location Weight(g) Volume(cm3) Density(pcf) Secondary beam,along 8 line,between I and J lines 48.69 190 16 RECEIVE( Average(pcf) 16 11/20/2024 ASPEN Remarks: Density of spray-applied fireproofing meets or exceeds project specifications. BUILDING DEPARTMENT 234 Center Drive l Glenwood Springs,Colorado 81601 I Phone: 979-945-2809 Fax: 970-945-7411