134 E Bleeker St. — Fire Suppression Calculations
To: Joanna S. Schaffner
County Planner/Zoning
530 E. Main Street
Suite 205
Aspen, CO 81611
970-920-5105
From: Richard Goulding, P.E., M.B.A.
Principal Engineer
592 Highway 133
Carbondale CO, 81623
Ph: 970-948-7474
Fax: 866-876- 5873
cc:
Date: 1/6/2021
Re: 134 E Bleeker St, Aspen CO Building Permit COA Comments
The purpose of this memorandum is to summarize the methodology and results of
RFE's hydraulic headloss model pertaining to the available fire suppression flow for 134
E Bleeker St, Aspen CO.
Relevant Fire Protection Calculation information was provided to RFE containing the
residual pressure, system flow demand, and required pressure at the residence. RFE's
model considers the geometry and sizing of the water service pipe as well as the above-
mentioned parameters provided by the Fire Protection Calculations and calculates the
total headloss due to friction.
A 1.5in Copper Type K pipe was tested given a required flow rate of 42.73 gpm and a
residual pressure of 110 psi. The resulting total frictional headloss subtracted from the
residual pressure is more than the required pressure at the residence. This indicates
that a 1.5in diameter water service line is sufficient to supply the necessary pressure to
the residence.
Pac)RECEIYED
07/23/2021
ASPEN
BUILDING DEPARTMENT
FjROARING FORK
ENGINEERING
134E Bleeker By: ILG
Aspen,CO 81611 Ck'd By.- ROG
pipe Pipe Pipe Pipe Nom. Pipe Date: 1/6/2021
Material Thickness Lining Diameter ID
Type Class Type (Inches) (Inches)
Copper Type K/L Unlined 1.5 148
Hydraulics Calculations for Fire
Suppression Line Size
Flow Segment:"Description of segment or other identifying remarks'
Item Existing/ Flow Pipe Pipe Pipe Pipe Nom. Pipe K-Section Flow Vel.Head K Length Pipe C HL
Future Rate Material Thickness Lining Diameter ID Area Velocity Va2/2g
(gpm) Iris) Type Class Type (inches) (inches)'(ft) (sf) (fps) (ft) (ft) (ft)
fait 43 0.10 Copper -ype K., Unlined 1 1/2 148 0.12 0.01 796 C.98 I 0.98
Pipe Pun 43 0.10 Copper Type K,:r Unlined 1 1/2 308 0.12 0.01 ].96 C.98 ]1 135 13.11
Exit 43 0.10 Copper Type K/L Unlined 1 1/2 1.48 0.12 0.01 7.96 0.98 1 0.98
Pipe and Fitting Friction Head Losses 15.08 ft
Radon of Safety 1.51 ft
Total Friction Headloss 16.58 ft
7.19 psi
Residual Pressure Available 110 psi
Total Pressure at House 102.81 psi
Required Pressure at House 11.03 psi