HomeMy WebLinkAboutFile Documents.134 E Bleeker St.0102-2020-BRES (41) I( Kumar&Associates,Inc.°
Geotechnical and Materials Engineers 5020 County Road 154
and Environmental Scientists Glenwood Springs,CO 81601
phone: (970)945-7988
fax:(970)945-8454
email:kaglenwood@kumarusa.com
An Employee Owned Company www.kumarusa.com
Office Locations: Denver(HQ),Parker,Colorado Springs,Fort Collins,Glenwood Springs,and Summit County,Colorado
SUBSOIL STUDY
FOR FOUNDATION DESIGN
PROPOSED FULL BASEMENT & CRAWLSPACE
UNDER EXISTING HOUSE
134 EAST BLEEKER STREET
ASPEN, COLORADO
PROJECT NO. 20-7-375.01
JUNE 14, 2021
PREPARED FOR:
BRET HIRSH
do EIGELBERGER ARCHITECTURE +DESIGN
ATTN: NICK CHAN
350 MARKET STREET, SUITE 309
BASALT, COLORADO 81621
nchan(&,ei2elber2er.com
RECEIVED
07/23/2021
ASPEN
BUILDING DEPARTMENT
TABLE OF CONTENTS
PURPOSE AND SCOPE OF STUDY - 1 -
PROPOSED CONSTRUCTION - 1 -
SITE CONDITIONS - 1 -
FIELD EXPLORATION - 1 -
SUBSURFACE CONDITIONS - 2 -
DESIGN RECOMMENDATIONS - 2 -
FOUNDATIONS - 2 -
FOUNDATION AND RETAINING WALLS - 3 -
FLOOR SLABS - 4 -
UNDERDRAIN SYSTEM - 4 -
SLOPE STABLIZATION - 5 -
SURFACE DRAINAGE - 5 -
LIMITATIONS - 6 -
FIGURE 1 - LOCATION OF EXPLORATORY BORING
FIGURE 2 - LOG OF EXPLORATORY BORING
FIGURE 3 - GRADATION TEST RESULTS
TABLE 1- SUMMARY OF LABORATORY TEST RESULTS
TABLE 2 - PERCOLATION TEST RESULTS
RECEIVED
07 /23 /2e21
Kumar&Associates,Inc.° Project No.20-7-375.01
ASPEN
BUILDING DEPARTMENT
PURPOSE AND SCOPE OF STUDY
This report presents the results of a subsoil study for a proposed full basement and crawlspace
addition under an existing residence to be located at 134 East Bleeker Street, Aspen, Colorado.
The project site is shown on Figure 1. The purpose of the study was to develop
recommendations for the foundation design. The study was conducted in accordance with our
proposal for geotechnical engineering services to Eigelberger Architecture +Design dated
May 15, 2020.
An exploratory boring was drilled to obtain information on the subsurface conditions. Samples
of the subsoils obtained during the field exploration were tested in the laboratory to determine
their classification and other engineering characteristics. The results of the field exploration and
laboratory testing were analyzed to develop recommendations for foundation types, depths and
allowable pressures for the proposed building foundation. This report summarizes the data
obtained during this study and presents our conclusions, design recommendations and other
geotechnical engineering considerations based on the proposed construction and the subsurface
conditions encountered.
PROPOSED CONSTRUCTION
The proposed basement and crawlspace will be constructed under the existing two-story
residence. Basement floor will be structural over crawlspace. Grading for the structure is
assumed to involve cut depths up to about 15 feet. We assume relatively light to moderate
foundation loadings, typical of the proposed type of construction.
If building loadings, location or grading plans change significantly from those described above,
we should be notified to re-evaluate the recommendations contained in this report.
SITE CONDITIONS
The subject site was developed with a two-story residence with a basement and detached garage
with a living area above the garage. The ground surface was relatively flat. Vegetation consists
of irrigated grass, small Blue Spruce and large Cottonwood trees.
FIELD EXPLORATION
The field exploration for the project was conducted on May 27, 2021. One exploratory boring
was drilled at the location shown on Figure 1 to evaluate the subsurface conditions. The boring
was advanced with 4-inch diameter continuous flight augers powered by a truck-mounted
45B drill rig. The boring was logged by a representative of Kumar&Associates, Inc.
21
Kumar&Associates,Inc.° Project No.20-7-375.01
\SPEN
BUILDING DEPARTMENT
-2 -
Samples of the subsoils were taken with a 1%-inch I.D. spoon sampler. The sampler was driven
into the subsoils at various depths with blows from a 140-pound hammer falling 30 inches. This
test is similar to the standard penetration test described by ASTM Method D-1586. The
penetration resistance values are an indication of the relative density or consistency of the
subsoils. Depths at which the samples were taken and the penetration resistance values are
shown on the Log of Exploratory Boring, Figure 2. The samples were returned to our laboratory
for review by the project engineer and testing.
SUBSURFACE CONDITIONS
A graphic log of the subsurface conditions encountered at the site is shown on Figure 2. The
subsoils consist of about 1/2 foot of topsoil overlying dense, slightly silty sand and gravel down to
the maximum explored depth of 26 feet. The soils were more sandy with depth.
Laboratory testing performed on samples obtained from the boring included natural moisture
content and gradation analyses. Results of gradation analyses performed on small diameter drive
samples (minus 11/2-inch fraction) of the coarse granular subsoils are shown on Figure 3. The
laboratory testing is summarized in Table 1.
No free water was encountered in the boring at the time of drilling and the subsoils were slightly
moist.
DESIGN RECOMMENDATIONS
FOUNDATIONS
Considering the subsurface conditions encountered in the exploratory boring and the nature of
the proposed construction, we recommend the new basement be founded with spread footings
bearing on the natural granular soils.
The design and construction criteria presented below should be observed for a spread footing
foundation system.
1) Footings placed on the undisturbed natural granular soils should be designed for
an allowable bearing pressure of 3,000 psf. Based on experience, we expect
settlement of footings designed and constructed as discussed in this section will
be about 1 inch or less.
2) The footings should have a minimum width of 16 inches for continuous walls and
2 feet for isolated pads.
3) Exterior footings and footings beneath unheated areas should be provided CEIVED
adequate soil cover above their bearing elevation for frost protection. Pla
07/23/2021
Kumar&Associates,Inc.° Project No.20-7-375.01
ASPEN
BUILDING DEPARTMENT
- 3 -
of foundations at least 42 inches below exterior grade is typically used in this
area.
4) Continuous foundation walls should be well reinforced top and bottom to span
local anomalies such as by assuming an unsupported length of at least 10 feet.
Foundation walls acting as retaining structures should also be designed to resist
lateral earth pressures as discussed in the "Foundation and Retaining Walls"
section of this report.
5) All existing fill, topsoil and any loose or disturbed soils should be removed and
the footing bearing level extended down to the relatively dense natural granular
soils. The exposed soils in footing area should then be moistened and compacted.
6) A representative of the geotechnical engineer should observe all footing
excavations prior to concrete placement to evaluate bearing conditions.
FOUNDATION AND RETAINING WALLS
Foundation walls and retaining structures which are laterally supported and can be expected to
undergo only a slight amount of deflection should be designed for a lateral earth pressure
computed on the basis of an equivalent fluid unit weight of at least 45 pcf for backfill consisting
of the on-site granular soils. Cantilevered retaining structures which are separate from the
residence (if any) and can be expected to deflect sufficiently to mobilize the full active earth
pressure condition should be designed for a lateral earth pressure computed on the basis of an
equivalent fluid unit weight of at least 40 pcf for backfill consisting of the on-site granular soils.
All foundation and retaining structures should be designed for appropriate hydrostatic and
surcharge pressures such as adjacent footings, traffic, construction materials and equipment. The
pressures recommended above assume drained conditions behind the walls and a horizontal
backfill surface. The buildup of water behind a wall or an upward sloping backfill surface will
increase the lateral pressure imposed on a foundation wall or retaining structure. An underdrain
should be provided to prevent hydrostatic pressure buildup behind walls.
Backfill should be placed in uniform lifts and compacted to at least 90% of the maximum
standard Proctor density at a moisture content near optimum. Backfill in pavement and walkway
areas should be compacted to at least 95% of the maximum standard Proctor density. Care
should be taken not to overcompact the backfill or use large equipment near the wall, since this
could cause excessive lateral pressure on the wall. Some settlement of deep foundation wall
backfill should be expected, even if the material is placed correctly, and could result in distress to
facilities constructed on the backfill. Backfill should not contain organics, debris or rock EIVED
k GC
than about 6 inches.
07/23/2021
Kumar&Associates,Inc.° Project No.20-7-375.01
ASPEN
BUILDING DEPARTMENT
-4 -
The lateral resistance of foundation or retaining wall footings will be a combination of the
sliding resistance of the footing on the foundation materials and passive earth pressure against
the side of the footing. Resistance to sliding at the bottoms of the footings can be calculated
based on a coefficient of friction of 0.50. Passive pressure of compacted backfill against the
sides of the footings can be calculated using an equivalent fluid unit weight of 425 pcf. The
coefficient of friction and passive pressure values recommended above assume ultimate soil
strength. Suitable factors of safety should be included in the design to limit the strain which will
occur at the ultimate strength, particularly in the case of passive resistance. Fill placed against
the sides of the footings to resist lateral loads should be a granular material compacted to at least
95% of the maximum standard Proctor density at a moisture content near optimum.
FLOOR SLABS
The natural on-site soils, exclusive of old fill and topsoil, are suitable to support lightly loaded
slab-on-grade construction. To reduce the effects of some differential movement, floor slabs
should be separated from all bearing walls and columns with expansion joints which allow
unrestrained vertical movement. Floor slab control joints should be used to reduce damage due
to shrinkage cracking. The requirements for joint spacing and slab reinforcement should be
established by the designer based on experience and the intended slab use. A minimum 4-inch
layer of free-draining gravel should be placed beneath basement level slabs to facilitate drainage.
This material should consist of minus 2-inch aggregate with at least 50%retained on the No. 4
sieve and less than 2%passing the No. 200 sieve.
All fill materials for support of floor slabs should be compacted to at least 95% of maximum
standard Proctor density at a moisture content near optimum. Required fill can consist of the on-
site granular soils devoid of vegetation, topsoil and oversized rock.
UNDERDRAIN SYSTEM
Although free water was not encountered during our exploration, it has been our experience in
the area that local perched groundwater can develop during times of heavy precipitation or
seasonal runoff. Frozen ground during spring runoff can create a perched condition. We
recommend below-grade construction, such as retaining walls, crawlspace and basement areas,
be protected from wetting and hydrostatic pressure buildup by an underdrain system.
The drains should consist of drainpipe placed in the bottom of the wall backfill surrounded above
the invert level with free-draining granular material. The drain should be placed at each level of
excavation and at least 1 foot below lowest adjacent finish grade and sloped at a minimu ° o
a suitable gravity outlet. Free-draining granular material used in the underdrain system s`o r
07 /23 /nn21
Kumar&Associates,Inc.° Project No.20-7-375.01
ASPEN
BUILDING DEPARTMENT
- 5 -
contain less than 2%passing the No. 200 sieve, less than 50%passing the No. 4 sieve and have a
maximum size of 2 inches. The drain gravel backfill should be at least 11/2 feet deep.
SLOPE STABLIZATION
The City of Aspen requires an engineered excavation slope stabilization plan if proposed
foundations are within 15 feet of neighboring structures or public travel ways. The plan is not
required if excavations are less than 5 feet below the existing grade or further than 15 feet from
travel ways and less than 15 feet deep. Slope bracing could be required depending on the
addition location, size and excavation depth. Slope bracing through use of a variety of systems
such as grouting, micro piles and soil nails should be feasible at the site. A shoring contractor
should provide design drawings to support the proposed excavation slopes where needed. Other
City requirements may also be applicable.
DRYWELL
Drywells and bio-swales are often used in the Aspen area for site runoff detention and disposal.
The Natural Resources Conservation Service has identified four hydrologic groups (HSG) in the
Aspen area and the site is located in Type B soil having a moderate infiltration rate. The results
of percolation testing performed in Boring 1,presented in Table 1, indicate an infiltration rate of
about 1 minute per inch. The bedrock is generally known to be relatively deep in this area and
groundwater level was not encountered to the boring depth of 26 feet. The drywell should have
solid casing down to at least basement level and perforation below that level.
SURFACE DRAINAGE
The following drainage precautions should be observed during construction and maintained at all
times after the proposed construction has been completed:
1) Inundation of the foundation excavations and underslab areas should be avoided
during construction.
2) Exterior backfill should be adjusted to near optimum moisture and compacted to
at least 95% of the maximum standard Proctor density in pavement and slab areas
and to at least 90% of the maximum standard Proctor density in landscape areas.
3) The ground surface surrounding the exterior of the building should be sloped to
drain away from the foundation in all directions. We recommend a minimum
slope of 6 inches in the first 10 feet in unpaved areas and a minimum slope of
2'/2 inches in the first 10 feet in paved areas. Free-draining wall backfill should be
covered with filter fabric and capped with at least 2 feet of the on-site soil l E IVE D
reduce surface water infiltration. 1
07/23/2021
Kumar&Associates,Inc.° Project No.20-7-375.01
ASPEN
BUILDING DEPARTMENT
- 6 -
4) Roof downspouts and drains should discharge well beyond the limits of all
backfill.
LIMITATIONS
This study has been conducted in accordance with generally accepted geotechnical engineering
principles and practices in this area at this time. We make no warranty either express or implied.
The conclusions and recommendations submitted in this report are based upon the data obtained
from the exploratory boring drilled at the location indicated on Figure 1, the proposed type of
construction and our experience in the area. Our services do not include determining the
presence, prevention or possibility of mold or other biological contaminants (MOBC)developing
in the future. If the client is concerned about MOBC,then a professional in this special field of
practice should be consulted. Our findings include interpolation and extrapolation of the
subsurface conditions identified at the exploratory boring and variations in the subsurface
conditions may not become evident until excavation is performed. If conditions encountered
during construction appear different from those described in this report, we should be notified so
that re-evaluation of the recommendations may be made.
This report has been prepared for the exclusive use by our client for design purposes. We are not
responsible for technical interpretations by others of our information. As the project evolves, we
should provide continued consultation and field services during construction to review and
monitor the implementation of our recommendations, and to verify that the recommendations
have been appropriately interpreted. Significant design changes may require additional analysis
or modifications to the recommendations presented herein. We recommend on-site observation
of excavations and foundation bearing strata and testing of structural fill by a representative of
the geotechnical engineer.
Respectfully Submitted,
Kumar& Associates,Inc =cQ,00 l E6/S '‘
i
James H. Parsons, P.E. s
Reviewed by: ..,
Daniel E. Hardin, P.E.
JHP/kac
cc: Eigelberger Architecture—Hannah Hunt Moeller—(hannahhunt@eigelberger.coRE C E IVE D
KL&A—Brett McElvain—(bmcelvain@klaa.com)
07/23/2021
Kumar&Associates,Inc.® Project No.20.7-375� PEN
BUILDING DEPARTMENT
/
/
. Two.RYPJ /tio,,,, \ \ \ CAN
TRASH .p er \ FED.RYP.)�
-' a:ENCLOSURE • 4•"L£A,39'6 -
*' '—RICIRIC Ai,.. )
as REBAR FOUND CI• R•YP.) _-0..699.RC65
BEARSS66°16'31"W 1.97 S Gj�� w
1. ELEC N� L
1.1
METER ` . —' RS REBAR R CAP FOUND
I • \ LS.IRL1EGIBLE
St RIDGE RIDGES ..
R/ �, `�79IS9' TORY r.• ;)
pK I ��!i�,i�- TWOUSE W GARAGE
1.`, G d HOUSE WITH GARAGE y
l• / 4.6 Bu44 RIDGE
WATER / I -"pNCS 791F.F' F . • d,�—.._
METER I -1X7E CHIMNEY j91.80' .
SEWER / •�1➢'� 7919.2'~� / ODRFJEWAY�
CLEANOUT .,
/ d '
GAS M / •i I d c c
METER 1 ,. I
/ 134 c 1 � `°yr
I IRIDGE EAST 7691.6' r aTREETf
/ 7919.9.Gh� �(ff-`fR.J� •77„ SIGN /a '`_
I 8/7.
' E.E.
/ I _ L / ,
W I/2 LOT R O I / 7994 7922IA,EY X3 I ig 7891.8 'a�#
ILJ1 .� ��T]� 'W lWgyi'� �$ /YS WELL / ' SSTONEIDEW_ /SHE SmEwALRITILEEI - //STONE / ,:...._ ..: -,'
/ PATIO /y �. /I `°, HALF '-I'� , WOOD/METAL /1 r/ / • / CK 65 / FENCE TRANSITION x
LJe r 6,5005.FW / )g9$
/^S` TWO STORY WOOD
/RIDGE FRAME HOUSE } I r `/>�' / 7916I /IW1TH BASEMENTRIDGEI {r,11
�ir I134 ESTBLFF¢FR STREET 7916.3' / + 6�JjLy
iFF.Wn!. �/ 1 789s.78' . ' i .. 3F
FENCE TRANSRION L 0/ 1894 (§
/
` � NI +7D ,
T� pg.
Rmc� %i I az
i REBAR FOUND 7916.7 • �/ r
IeLOW GROUND . / • xI .0'
J�09g 7895. / �r`_
�,.�y / BbftpMcg� tj t/
Sa9°26'Ot`W * //-- "�to II'
24s265' T T2 T3 r•.9 BORING- 1 — i STREET .
I.O.A.GPS N]S= ✓5 1 x l 7895.0' SIGN
:.G.
40NUMENT a7 a /1•W A1EP (;] 13 p r
40NUMENT 47 q
^J.
4 7d95.3'� 45,p0. _ 'I
47;A _ aS REBARd
CAP FOUND /
STONE / '�S L.S.f11LLEGIB /
-� STREET SIDEWALK J` 7BM EL=7894.J5' //
7� SIGN E,yz
MONUMENT a." �oy_R£7ET sae -r}
�g�� y
t is,
4-0`1ST�EE7 -
/
i
fri
e.
E 10 0 1 0
G
ao RECEIVED
„� APPROXIMATE SCALE—FEET
" 07L23/2021
20-7-375.01 Kumar & Associates LOCATION OF EXPLORATORY BORING Ig. 1
,o ASPEN
BUILDING DEPARTMENT
BORING 1
EL. 7 89 5' LEGEND
0 .' TOPSOIL; CLAY, SANDY, ORGANIC, FIRM, MOIST, DARK BROWN.
32/12 GRAVEL (GP-GM); SANDY, SLIGHTLY SILTY, COBBLES, TRANSITIONING
TO GRAVELLY SAND WITH DEPTH, MEDIUM DENSE TO DENSE,
SLIGHTLY MOIST TO MOIST, TAN.
5
,. : 14/12 DRIVE SAMPLE, 1 3/8-INCH I.D. SPLIT SPOON STANDARD
PENETRATION TEST.
64/12
WC=1.6 32/12 DRIVE SAMPLE BLOW COUNT. INDICATES THAT 32 BLOWS OF
+4=48 A 140-POUND HAMMER FALLING 30 INCHES WERE REQUIRED
:.:. :
200=12 TO DRIVE THE SAMPLER 12 INCHES.
10
50/1
NOTES
L' 1. THE EXPLORATORY BORING WAS DRILLED ON MAY 27, 2021
L WITH A 4-INCH DIAMETER CONTINUOUS FLIGHT POWER AUGER.
= 15
64/12 2, THE LOCATION OF THE EXPLORATORY BORING WAS MEASURED
0 o APPROXIMATELY BY PACING FROM FEATURES SHOWN ON THE
SITE PLAN PROVIDED.
3. 3. THE ELEVATION OF THE EXPLORATORY BORING WAS OBTAINED
BY INTERPOLATION BETWEEN CONTOURS ON THE SITE PLAN
20 PROVIDED.
27/12
4. THE EXPLORATORY BORING LOCATION AND ELEVATION SHOULD BE
0
CONSIDERED ACCURATE ONLY TO THE DEGREE IMPLIED BY THE
WC=3.9 METHOD USED.
+4=25
: 0
-200=5 5. THE LINES BETWEEN MATERIALS SHOWN ON THE EXPLORATORY
�� BORING LOG REPRESENT THE APPROXIMATE BOUNDARIES
25 o BETWEEN MATERIAL TYPES AND THE TRANSITIONS MAY BE
53/12 GRADUAL.
6. GROUNDWATER WAS NOT ENCOUNTERED IN THE BORING AT THE
TIME OF DRILLING.
7. LABORATORY TEST RESULTS:
30 WC = WATER CONTENT (%) (ASTM D 2216);
+4 = PERCENTAGE RETAINED ON NO. 4 SIEVE (ASTM D 6913);
-200 = PERCENTAGE PASSING NO. 200 SIEVE (ASTM D 1140).
21
E..2
r 20-7-375.01 Kumar &Associates LOG OF EXPLORATORY BORING 0 /�3?2021
ASPEN
BUILDING DEPARTMENT
HYDROMETER ANALYSIS SIEVE ANALYSIS
TIME READINGS U.S. STANDARD SERIES CLEAR SQUARE OPENINGS
24 HRS 7 HRS
100 45 MIN 15 MIN 6OMIN 19MIN 4MIN 1MIN #200 #100 #50#40#30 16 #10#8 #4 3/8" 3 4" 1 1 2" 3" 5"6" 8"0
90 10
80 20
70 - 30
60 40
G
50 - 50
z1
a 40 60 E
30 70
20 80
10 90
0 I I I I I I I I I I I I III I I I I III I I I I I III I I I I I I III 100
.001 .002 .005 .009 .019 .037 .075 .150 .300 .600 1.18 2.36 4.75 9.5 19 38.1 76.2 127 200
.425 2.0 152
DIAMETER OF PARTICLES IN MILLIMETERS
CLAY TO SILT SAND GRAVEL COBBLES
FINE MEDIUM COARSE FINE COARSE
GRAVEL 48 % SAND 40 % SILT AND CLAY 12 %
LIQUID LIMIT PLASTICITY INDEX
SAMPLE OF: Slightly Silty Gravel and Sand FROM: Boring 1 0 7.5'
HYDROMETER ANALYSIS SIEVE ANALYSIS
TIME READINGS U.S. STANDARD SERIES CLEAR SQUARE OPENINGS
24 HRS 7 HRS
100 45 MIN 15 MIN 60MIN 19MIN 4MIN 1MIN #200 #100 #50#40#30 #16 #10#8 #4 3/8" 3/4" 1 1 2" 3" 5I 6" 8"0
I
90 10
80 20
70 30
60 1 40
IQ -
tz
50 1 50
40 - 60
30 70
20 - 80
I
10 - 90
0 I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I T 100
.001 .002 .005 .009 .019 .037 .075 .150 .300 .600 1.18 2.36 4.75 9.5 19 38.1 76.2 127 200
v .425 2.0 152
DIAMETER OF PARTICLES IN MILLIMETERS
SAND GRAVEL
CLAY TO SILT COBBLES
FINE MEDIUM COARSE FINE COARSE
ry GRAVEL 25 % SAND 70 % SILT AND CLAY 5 %
LIQUID LIMIT PLASTICITY INDEX
These test results apply only to the
E SAMPLE OF: Slightly Silty Gravelly Sand FROM: Boring 1 0 20' & 25' samples which were tested. The
testing report shall not be reproduced,
2 except in full, without the written
Ls approval of Kumar & Associates, Inc.
lE Sieve analysis testl is performed in
accordance with A D6913, ASTM D7928,
i g ASTM C136 and/or TM D1140.
20-7-375.01 Kumar & Associates GRADATION TEST RESULTS 0 7%132021
ASPEN
BUILDING DEPARTMENT
I( i Kumar&Associates,Inc.°
Gumar&Aland Materials Engineers
and Environmental Scientists
TABLE 1
SUMMARY OF LABORATORY TEST RESULTS
Project No.20-7-375.01
SAMPLE LOCATION NATURAL NATURAL GRADATION ATTERBERG LIMITS UNCONFINED
MOISTURE DRY GRAVEL SAND PERCENT PLASTIC COMPRESSIVE
BORING DEPTH CONTENT DENSITY (%) (%) PASSING 200 S EVE LIQUID LIMIT INDEX STRENGTH SOIL TYPE
(ft) (%) (pcf) (%) (%) (psf)
1 7'/z 1.6 48 40 12 Slightly Silty Gravel and
Sand
20 & 25 3.9 25 70 5 Slightly Silty Gravelly
combined Sand
RECEIVED
07/23/2021
ASPEN
BUILDING DEPARTMENT
I( A Kumar&Associates,Inc.®
Gumar&Aland Materials Engineers
and Environmental Scientists
TABLE 2
PERCOLATION TEST RESULTS
PROJECT NO.20-7-375.01
HOLE NO. HOLE DEPTH LENGTH OF WATER DEPTH WATER DEPTH DROP IN AVERAGE
(INCHES) INTERVAL AT START OF AT END OF WATER LEVEL PERCOLATION
(MIN) INTERVAL INTERVAL (INCHES) RATE
(INCHES) (INCHES) (MIN./INCH)
76 64 12
64 54 10
54 483/4 5'/4
B-1 184 5 483/4 43 53/4
43 38 5
38 331/2 4'/z 1
Note: Percolation tests were conducted in a 4-inch diameter boring drilled on May 27, 2021. The average
percolation rate was based on the last three readings of the test.
RECEIVED
07/23/2021
ASPEN
BUILDING DEPARTMENT