HomeMy WebLinkAboutFile Documents.401 Castle Creek Rd.0018-2024-BCOM (9)SMOKE ALARMS AND
CARBON MONOXIDE
DETECTORS REQUIRED
THROUGHOUT DWELLING
UNIT PER CITY OF ASPEN
MUNICIPAL CODE 8.15
These plans must be kept at the
building site or inspection
delays may occur. Construction
shall conform to these plans. All
changes shall be approved by
the building official.
Field Plan Set Must Be Printed In Color
SEPARATE PERMITS ARE
REQUIRED FOR ELECTRICAL,
PLUMBING, MECHANICAL, OR
FIRE SPRINKLER WORK
It should be known that this review shall
not relieve the applicant of their
responsibility to comply with the
requirements of the City of Aspen
Municipal Code. Pursuant to
Sec.26.104.050, any permit or approval
issued in error or otherwise not in
conformity with the requirements of this
Title, shall be void. Similarly, any permit
or approval issued in reliance upon or
as a result of, a materially false
statement or representation made in
the process of obtaining the permit or
development approval shall, likewise,
be void. Any person having received a
void or voidable permit or approval
shall not be relieved from having to
comply with all applicable terms and
conditions of this Title and the City shall
not be estopped from fully enforcing
same.
bobn
04/24/2024ZONING
It should be known that this review shall
not relieve the applicant of their
responsibility to comply with the
requirements of the City of Aspen
Municipal Code. Pursuant to
Sec.26.104.050, any permit or approval
issued in error or otherwise not in
conformity with the requirements of this
Title, shall be void. Similarly, any permit
or approval issued in reliance upon or
as a result of, a materially false
statement or representation made in
the process of obtaining the permit or
development approval shall, likewise,
be void. Any person having received a
void or voidable permit or approval
shall not be relieved from having to
comply with all applicable terms and
conditions of this Title and the City shall
not be estopped from fully enforcing
same.
FIRE
SPRINKLERS
REQUIRED
2021 IBC 601 Fire Resistive Requirements for
Type of Construction: ____
Primary Structural Frame: ____hr
(columns, beams, girders, etc)
Exterior Bearing Walls: ____hr
Interior Bearing Walls: ____hr
Floors/Ceilings: ____hr
Roof : ____hr
Unless noted otherwise for occupancy separation or fire
separation distance.
IB
2
2
2
2
1
READ THIS OR FAIL YOUR INSPECTION!
Dropped Ceilings and Soffits beneath fire rated
assemblies
2021 IBC 803.13
This applies to the attachment of finishes or furring to any
assemblies that are required to be either fire-rated or
non-combustible and is separate from the fire-rated
assembly requirement.
1. Dropped Ceilings & Soffits: If dropped 1 ¾
inches or less, do one of the following:
-Fill spaces with Class A material.
-Fill spaces with inorganic or non-combustible material.
-Fire block 8 feet in all directions.
2. Dropped Ceilings & Soffits: If dropped greater
than 1 ¾ inches:
Framing members, hangers, and other assembly
members must be non-combustible. You may not
use wood.
In Type III and V construction only, you may use fire
retardant treated wood or non-combustible framing.
3. Dropped Ceilings & Soffits below Heavy
Timber T&G ceilings, do all of the following:
-One layer 5/8” type X gypsum board directly
attached with minimum level one finish.
-Drop ceiling according to item 1 or 2 above as
applicable.
(City Policy)
THE FOLLOWING INSPECTIONS MAY NOT BE SCHEDULED UNTIL
the building code official has received and approved the following:
FINAL MECHANICAL, ELECTRICAL, AND PLUMBING INSPECTIONS:
1. Preliminary Comissioning Report for new heating, cooling and duct systems that are
part of the alteration (2021 IECC C503.3, C408)
2. Functional testing of new lighting control systems that are part of the alteration (2021
IECC C503.5, C408.3)
2. Letter of transmittal from the building owner or authorized agent acknowledging that
they have received the Preliminary Commissioning Report.
2021 IECC C408.2.4.1
05/17/2024
justinh
APPLICATION ACCEPTED DATE: 2024-04-18 PERMIT NUMBER: 0018-2024-BCOM
COMMUNITY DEVELOPMENT DEPARTMENT
BUILDING PERMIT COVERSHEET
PROPERTY INFORMATION
ADDRESS: 401 CASTLE CREEK RD UNIT:
PARCEL ID: 273512307801 LEGAL DESCRIPTION: ASPEN VALLEY HOSPITAL SUB
OWNER: ASPEN VALLEY HOSPITAL DISTRICT
PERMIT CONTRACTOR: HASELDEN CONSTRUCTION LLC
DESCRIPTION OF WORK Creation of Nuc-Med Suite in existing hospital space. Includes Nuc-Med / CT Imaging, N.M. Tech workspace and
Contracts Media Prep Area for a total of 687 SF.
USE OF BUILDING Commercial FIRE SPRINKLER REQUIRED? Yes
CLASS OF WORK Commercial FIRE SPRINKLER TYPE NFPA 13
BUILDING TYPE (IRC) REQUIRED SPECIAL
INSPECTIONS
CONSTRUCTION TYPE IB ENERGY CODE COMPLIANCE COMCheck UA Alternative
OCCUPANCY GROUP (IBC) I-2 WORK CHANGES BUILDING
FOOTPRINT? No
CODE EDITIONS 2021 IBC TOTAL SPA SQ.FT.
OTHER CODE EDITIONS
2021 IBC, 2021 Aspen Energy Code,
2021 IPC, 2021 IMC,2021 IFGC,
2021 IFC, 2021 IFC, 2021 IEBC,
2017 A117.1 ANSI, 2023 NEC
TOTAL SNOWMELT SQ.FT.
HISTORIC PROPERTY? No TOTAL POOL SQ.FT.
FIRE SPRINKLER EXISTING? Yes