HomeMy WebLinkAboutFile Documents.134 E Bleeker St.0102-2020-BRES (45)E0-1 A.SUBSTITUTIONS: SUBSTITUTION OF SPECIFIED EQUIPMENT WILL BE ALLOWED THROUGH A PRIOR APPROVAL PROCESS INITIATED BY THE CONTRACTOR. CONTRACTOR SHALL SUBMIT INTENDED SUBSTITUTION AT LEAST FIVE DAYS PRIOR TO BID FOR APPROVAL FROM ENGINEER. SUBMITTAL SHALL INCLUDE CAPACITIES, DIMENSIONS AND OPERATING INSTRUCTIONS FOR EACH PIECE OF EQUIPMENT. SUBSTITUTION SHALL OCCUR AT NO COST TO THE OWNER. CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF APPROVED SUBSTITUTION AND SHALL INCUR ALL COSTS ASSOCIATED WITH THE SUBSTITUTION INCLUDING STRUCTURAL MODIFICATIONS, SPACE LAYOUT AND REDESIGN COSTS. SEE ALSO DIVISION I GENERAL REQUIREMENTS. EXAMINATION OF SITE, DRAWINGS, SPECIFICATIONS: A.EXAMINE CAREFULLY THE SITE AND CONDITIONS OF THE SITE. PROVIDE ALL NECESSARY EQUIPMENT AND LABOR TO INSTALL A COMPLETE WORKING SYSTEM WITHIN THE SITE CONDITIONS. B.EXAMINE THE DRAWINGS AND SPECIFICATIONS AND 5 DAYS PRIOR TO BIDDING REPORT ANY ERRORS, OMISSIONS, INCONSISTENCIES, AND CONFLICTS TO THE ENGINEER TO BE REMEDIED IN AN ADDENDUM TO THE PROJECT PRIOR TO BID TIME. C.DRAWINGS ARE DIAGRAMMATIC AND CATALOG NUMBERS GIVEN ARE FOR REFERENCE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE CAPACITY OF THE EQUIPMENT MEETS THE DRAWING REQUIREMENTS AND SHALL NOT DIMENSION FROM THE MECHANICAL, PLUMBING, OR PIPING DRAWINGS. D.THE LATEST ADOPTED VERSIONS OF THE INTERNATIONAL BUILDING CODES SHALL BE USED AS REQUIRED. THIS WILL ALSO INCLUDE THE LATEST ADOPTED VERSIONS OF THE MECHANICAL, PLUMBING AND ENERGY CONSERVATION CODES. ALL METHODS AND MATERIALS REQUIRED BY THESE CODES SHALL BE REQUIRED BY THESE SPECIFICATIONS UNLESS INDICATED OTHERWISE. OTHER APPLICABLE LOCAL CODES AND ORDINANCES SHALL BE AS REQUIRED AND IT SHALL BE THE CONTRACTOR’S RESPONSIBILITY TO BE KNOWLEDGEABLE OF THESE REQUIREMENTS. E.WHERE INSTALLATION PROCEDURES OR ANY PART THEREOF ARE REQUIRED TO BE IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE MANUFACTURER OF THE MATERIAL BEING INSTALLED, PRINTED COPIES OF THESE RECOMMENDATIONS SHALL BE FURNISHED TO THE ENGINEER PRIOR TO INSTALLATION. INSTALLATION OF THE ITEM WILL NOT BE ALLOWED TO PROCEED UNTIL THE RECOMMENDATIONS ARE RECEIVED. FAILURE TO FURNISH THESE RECOMMENDATIONS CAN BE CAUSE FOR REJECTION OF THE MATERIAL. 44”MOUNTING HEIGHT ABOVE FINISHED FLOOR TO CENTER OF DEVICE A AMPS A.D.ACCESS DOOR AAV AIR ADMITTANCE VALVE ABV ABOVE AC AIR CONDITIONING UNIT AC ABOVE COUNTER AD AREA DRAIN (SEE SYMBOLS) A.F.C.ABOVE FINISHED CEILING A.F.G.ABOVE FINISHED GRADE AIC AMPERE INTERRUPTING CAPACITY A.F.F.ABOVE FINISHED FLOOR AHU AIR HANDLING UNIT ALUM ALUMINUM AP ACCESS PANEL OR DOOR ATS AUTOMATIC TRANSFER SWITCH AV AUDIO / VIDEO AVG AVERAGE AWG AMERICAN WIRE GAGE BAS BUILDING AUTOMATION SYSTEM BB BASEBOARD BD BACK DRAFT DAMPER BFP BACK FLOW PREVENTOR BL BOILER BLDG BUILDING BLW BELOW BOB BOTTOM OF BEAM BOD BOTTOM OF DUCT BOP BOTTOM OF PIPE BSMT BASEMENT BTU BRITISH THERMAL UNIT C CHILLER CAP CAPACITY CB CIRCUIT BREAKER CBV CIRCUIT BALANCING VALVE CCT CORRELATED COLOR TEMPERATURE CKT CIRCUIT CFH CUBIC FEET PER HOUR CFM CUBIC FEET PER MINUTE CHWR CHILLED WATER RETURN CHWS CHILLED WATER SUPPLY CI CAST IRON CL CENTER LINE CLG CEILING CMU CONCRETE MASONRY UNIT CO CLEAN OUT COL COLUMN COMP COMPRESSOR CONC CONCRETE COND CONDENSATE CONN CONNECTION CONT CONTINUATION CONTR CONTRACTOR CRI COLOR RENDERING INDEX CT COOLING TOWER CT CURRENT TRANSFORMER CU CONDENSING UNIT CU COPPER CUH CABINET UNIT HEATER CVB CONSTANT VOLUME BOX CWR CONDENSER WATER RETURN CWS CONDENSER WATER SUPPLY DB DRY BULB DEPT DEPARTMENT DF DRINKING FOUNTAIN DIA DIAMETER DIAG DIAGRAM DIFF DIFFERENTIAL DISCH DISCHARGE DIV DIVISION DN DOWN DS DUCT SILENCER DWG DRAWING DX DIRECT EXPANSION (A)EXISTING EA EXHAUST AIR GRILLE/REGISTER EAT ENTERING AIR TEMPERATURE EC ELECTRICAL CONTRACTOR ECC ECCENTRIC EF EXHAUST FAN EFF EFFICIENCY EL ELEVATION ELEC ELECTRIC ELEV ELEVATOR EM EMERGENCY FUNCTION ENT ENTERING EMT ELECTRIC METALLIC TUBE EQ EQUAL EQUIP EQUIPMENT EQUIV EQUIVALENT ES END SWITCH ESP EXTERNAL STATIC PRESSURE ET EXPANSION TANK EWC ELECTRIC WATER COOLER EWT ENTERING WATER TEMPERATURE EX EXHAUST EXPAN EXPANSION EXT EXTERNAL F DEGREES FAHRENHEIT FA FREE AREA FC FAN COIL UNIT FC FOOTCANDLE FCV FLOW CONTROL VALVE FD FIRE DAMPER FD FLOOR DRAIN FIN FINISHED FLA FULL LOAD AMPS FLEX FLEXIBLE FLR FLOOR FOB FLAT ON BOTTOM FOT FLAT ON TOP FP FIRE PROTECTION FP FIRE PUMP FPM FEET PER MINUTE FPS FEET PER SECOND FS FLOW SWITCH FSD FIRE/SMOKE DAMPER FT FEET FXC FLEXIBLE CONNECTION GND GROUND GA GAUGE GAL GALLON GALV GALVANIZED GEC GROUND ELECTRODE CONDUCTOR GFCI / GFI GROUND FAULT CIRCUIT INTERRUPTER GC GENERAL CONTRACTOR GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GRS/LB GRAINS PER POUND H 2O WATER HB HOSE BIBB HD HEAD (SEE SCHEDULES) HP HEAT PUMP HP HORSEPOWER HR HOUR HT HEIGHT HTR HEATER HWR HEATING WATER RETURN HWS HEATING WATER SUPPLY HX HEAT EXCHANGER HZ HERTZ ID INSIDE DIAMETER IG ISOLATED GROUND IN INCHES INV INVERT JBOX JUNCTION BOX K KELVIN KW KILOWATT KVA KILO VOLT - AMPS L LENGTH LAT LEAVING AIR TEMPERATURE LV LAVATORY LB POUND LD LINEAR DIFFUSER LF LINEAR FEET LIN LINEAR LIQ LIQUID LM LUMEN LRA LOCKED ROTOR AMPS LV LOUVER LVG LEAVING LWT LEAVING WATER TEMPERATURE MBH THOUSANDS OF BTU PER HOUR MC MECHANICAL CONTRACTOR MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MD MOTORIZED DAMPER MDP MAIN DISTRIBUTION PANEL MED MEDIUM MFR MANUFACTURER MIN MINIMUM MISC MISCELLANEOUS MLO MAIN LUG ONLY MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED MUA MAKE-UP AIR UNIT N NEUTRAL NC NORMALLY CLOSED NEG NEGATIVE NIC NOT IN CONTRACT NL NIGHT / SECURITY LIGHT - DO NOT SWITCH NO NORMALLY OPEN NOM NOMINAL NTS NOT TO SCALE OA OUTSIDE AIR OBD OPPOSED BLADE DAMPER OC ON CENTER OCC OCCUPIED OCP OVER CURRENT PROTECTION OD OUTSIDE DIAMETER OL OVERLOAD ORD OVERFLOW ROOF DRAIN OZ OUNCE PBD PARALLEL BLADE DAMPER PD PRESSURE DROP PH PHASE POS POSITIVE PRESSURE POS POINT OF SALES PRV PRESSURE REDUCING VALVE PS PRESSURE SWITCH PSI POUNDS PER SQUARE INCH PT PRESSURE TRANSMITTER PTAC PACKAGED TERMINAL AIR CONDITIONER PV PLUG VALVE PVC POLYVINYL CHLORIDE QTY QUANTITY RA RETURN AIR GRILLE / REGISTER RCP REFLECTED CEILING PLAN RD ROOF DRAIN REL RELIEF REQD REQUIRED RF RETURN FAN RH RELATIVE HUMIDITY RHC REHEAT COIL RLA RATED LOAD AMPS RM ROOM RPM REVOLUTIONS PER MINUTE SA SUPPLY AIR GRILLE / REGISTER SC SHORT CIRCUIT SCA SHORT CIRCUIT AVAILABLE SCCR SHORT CIRCUIT CURRENT RATING SCH SCHEDULE SD SMOKE DAMPER SEF SMOKE EXHAUST FAN SF SUPPLY FAN SH SENSIBLE HEAT SH SHOWER SP STATIC PRESSURE SPD SURGE PROTECTION DEVICE SPEC SPECIFICATION SQ SQUARE SS STAINLESS STEEL SS SAFETY SHOWER STD STANDARD STL STEEL SYS SYSTEM TEMP TEMPERATURE TR TRANSFER GRILLE / REGISTER TR TAMPER RESISTANT TT TEMPERATURE TRANSMITTER TTB TELECOMMUNICATIONS TERMINAL BACKBOARD TYP TYPICAL TX TRANSFORMER UC UNDERCUT DOOR UH UNIT HEATER UNO UNLESS NOTED OTHERWISE UNOCC UNOCCUPIED UR URINAL V VOLTS VA VOLT AMPERE VA VALVE VAV VARIABLE AIR VOLUME UNIT VFD VARIABLE FREQUENCY DRIVE VRF VARIABLE REFRIGERANT FLOW VOLT VOLTAGE VTR VENT THROUGH ROOF W WIDTH W WATTS W/ WITH W/O WITHOUT WB WET BULB WC WATER COLUMN WC WATER CLOSET WG WATER GAUGE WP WEATHERPROOF WPIU WEATHERPROOF IN-USE WSR WITHSTAND RATING XFMR TRANSFORMER SUBSTITUTIONS: RESPONSIBLE DIVISION: UNLESS OTHERWISE INDICATED ALL HEATING, VENTILATING, AIR CONDITIONING, PLUMBING, AND OTHER MECHANICAL EQUIPMENT, MOTORS, AND CONTROLS SHALL BE FURNISHED, SET IN PLACE AND WIRED AS FOLLOWS: ITEM FURNISHED SET POWER CONTROL WIRED WIRED EQUIPMENT 23 23 26 -- COMBINATION MAGNETIC MOTOR STARTERS, MAGNETIC MOTOR STARTERS, VFD'S AND CONTACTORS 23(1)26 26(2)23 FUSED AND UNFUSED DISCONNECT SWITCHES, THERMAL OVERLOAD SWITCHES AND HEATERS, MANUAL MOTOR STARTERS 26 26 26 -- MANUAL-OPERATING AND MULTI-SPEED SWITCHES 23 26 26 26 CONTROLS, RELAYS, TRANSFORMERS 23 23 26 23 THERMOSTATS (LOW VOLTAGE) AND TIME SWITCHES 23 23 26 23 THERMOSTATS (LINE VOLTAGE) 23 23 26 26 TEMPERATURE CONTROL PANELS 23 23 26 23 MOTOR AND SOLENOID VALVES, DAMPER MOTORS, PE & EP SWITCHES 23 23(2)--23(2) PUSH-BUTTON STATIONS AND PILOT LIGHTS 23 23(2)-- 23(2) HEATING, COOLING, VENTILATION AND AIR CONDITIONING CONTROLS 23 23 26 23 EXHAUST FAN SWITCHES 23 26 26 23(2) SUBSCRIPT FOOTNOTES: 1.MOTOR STARTER TO INCLUDE CONTROL TRANSFORMER, HOA SWITCH, (1) NO AND (1)NC AUXILIARY CONTACT, AND “ON” AND “OFF” PILOT LIGHTS. 2.IF ITEM IS FOR LINE VOLTAGE, SET IN PLACE AND CONNECT UNDER DIVISION 26. WHERE FACTORY MOUNTED ON EQUIPMENT OR ATTACHED TO PIPING OR DUCTS AND USING LINE VOLTAGE FURNISH AND SET UNDER DIVISION 23, CONNECT UNDER DIVISION 26. ABBREVIATIONS: Bighorn Consulting Engineers, Inc. Mechanical & Electrical Engineers 386 Indian Road Grand Junction, CO 81501 Phone: (970) 241-8709 101 W 11th Street #109-C Durango, CO 81301 Phone: (970) 422-7676 SECURITY CAMERA SECURITY SYSTEM LEGEND ADA DOOR OPERATOR PUSH BUTTONHC T GFCI WP GFCI 44" D J F LA-7 J ROOM 100 BRANCH CIRCUIT PANELBOARD TELEPHONE TERMINAL BOARD ELECTRIC MOTOR FUSED SAFETY SWITCH / DISCONNECT COMBINATION MOTOR STARTER CONTACTOR CIRCUITRY HOMERUN: PANEL LA - CIR. #7 CONDUIT OR WIRE CONCEALED IN WALL/CLG. (SOLID LINE TYPE) CONDUIT OR WIRE UNDERFLOOR/UNDERGND. (CENTER LINE TYPE) CEILING JUNCTION BOX - SURFACE/FLUSH WALL JUNCTION BOX - SURFACE/FLUSH DUPLEX RECEPTACLE FLOOR MOUNTED RECEPTACLE SPLIT WIRED DUPLEX RECEPTACLE CEILING MOUNTED DUPLEX RECEPTACLE FOURPLEX RECEPTACLE FLOOR MOUNTED FOURPLEX RECEPTACLE APPLIANCE RECEPTACLE - 3 WIRE THERMOSTAT DRAWING KEY NOTES ROOM DESIGNATION GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE WITH A WEATHER PROOF COVER GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE MOUNTED AT 44" ABOVE FINISHED FLOOR FUSED DISCONNECT 100A = AMP RATING 2P = NUMBER OF POLES CIRCUIT BREAKER IN A PANEL BOARD PAD MOUNTED UTILITY TRANSFORMER M ELECTRICAL METER SHOWN ON ONE-LINE DIAGRAMS MAIN DISTRIBUTION GEAR ELECTRICAL POWER PANEL WITH MAIN LUG OR MAIN BREAKER PP1= PANEL NAME 225A MLO = MAIN LUG OR BREAKER SIZE 120/208V = PANEL VOLTAGE 3PH, 4 WIRE = PANEL PHASE, DISTRIBUTION TYPE 100 A 2 POLE FUSED DISCONNECT PP1 225A MLO 120/208V 3PH, 4W GROUND FAULT CIRCUIT INTERRUPTERGFCI USB RECEPTACLE WITH USB CHARGING CAPABILITES RECEPTACLE MOUNTED ABOVE COUNTERAC CW RECEPTACLE MOUNTED IN CASEWORK ELECTRIC HAND DRYER PP1 225A MCB 120/208V 3PH, 4W OPEN/CLOSE/STOP PUSH BUTTON RL F FLOW SWITCH PIR DETECTOR SMOKE DETECTOR - PHOTOELECTRIC REMOTE LAMP D DUCT DETECTOR CEILING MOUNTED SPEAKER FIRE ALARM HORN/STROBE FIRE ALARM STROBE FIRE ALARM HORN FIRE ALARM PULL STATION FIRE ALARM EQUIPMENT LEGEND TAMPER SWITCH FS PIR TS C INTERCOM PUSH TO CALL SWITCH CLOCK / PA SPEAKER WALL MOUNTED CLOCK ONLY COMMUNICATION LEGEND ABOVE THE CEILING PROJECTOR CONNECTION P WALL MOUNTED HDMI H 135°135° STANDARD HEAT DETECTOR HDMI PLAIN DATA OUTLET PROJECTOR WIRELESS ACCESS POINT ABOVE THE CEILING ROUND CEILING MOUNTED SPEAKER WAP PLAIN DATA OUTLET WITH MOUNTING HEIGHT80" SQUARE SPEAKERS S ELECTRICAL EQUIPMENT LEGEND ELECTRICAL DEVICE LEGEND S S S S S S S S S S S S S OS EMR A WALL MOUNTED SCONCE LIGHT FIXTURE RECESSED DOWNLIGHT CAN FIXTURE SURFACE CEILING OR PENDANT MOUNTED FIXTURE DOUBLE FACE EXIT SIGN, WALL AND CEILING MOUNTED SINGLE FACE EXIT SIGN, WALL AND CEILING MOUNTED WALL MOUNTED EMERGENCY LIGHT EMERGENCY EXTERIOR EGRESS FIXTURE SWITCHES LIGHT FIXTURES EM EX1 EX2 A A A DR D 4 3 2 LV TO MA SINGLE POLE SWITCH TWO POLE SWITCH THREE-WAY SWITCH FOUR-WAY SWITCH DIMMER SWITCH DOOR ACTIVATED SWITCH LOW VOLTAGE LIGHT SWITCH MANUAL MOTOR STARTER OS MA P PILOT LIGHT SWITCH AUTO ON / AUTO OFF LIGHT SWITCH A 3D 3 WAY DIMMER SWITCH - (4D INDICATES A 4WAY DIMMER) NOTES: SYMBOLS SHOWN ARE STANDARD. VARIATION AND/OR COMBINATIONS MAY BE USED ON THE PLANS. THIS LIST SHOWS STANDARD SYMBOLS AND ALL MAY NOT APPEAR ON THE PROJECT DRAWINGS; HOWEVER, WHEREVER THE SYMBOL ON THE PROJECT DRAWINGS OCCUR, THE ITEM SHALL BE PROVIDED AND INSTALLED. VARIATION AND/OR COMBINATION MAY BE USED ON THE PLANS. A NUMBER NEXT TO A RECEPTACLE OR DEVICE INDICATES A CIRCUIT NUMBER. AN UPPER CASE LETTER NEXT TO A SWITCH INDICATES THE FUNCTION OF THE SWITCH. A LOWER CASE LETTER INDICATES THE SWITCH CIRCUIT. AN UPPER CASE LETTER NEXT TO A LIGHT FIXTURE INDICATES THE TYPE OF FIXTURE. REFER TO THE LUMINAIRE SCHEDULE FOR FIXTURE SPECIFICATIONS. A LOWER CASE LETTER NEXT TO A LIGHT CORRESPONDS TO THE SWITCH DESIGNATION. OS CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH WALL MOUNTED DUAL TECHNOLOGY MANUAL ON / AUTO OFF VACANCY SENSOR SWITCH A 2'x4' LED TROFFER OR DIRECT/INDIRECT TYPE FIXTURE GRID, FLANGE OR SURFACE MOUNTED 1'x4' LED TROFFER OR DIRECT/INDIRECT TYPE FIXTURE GRID, FLANGE OR SURFACE MOUNTED 2'x2' LED TROFFER OR DIRECT/INDIRECT TYPE FIXTURE GRID, FLANGE OR SURFACE MOUNTED S S K T KEY OPERATED LIGHT SWITCH MANUAL ON / AUTO OFF DIMMING LIGHT SWITCH SSC SCENE CONTROL STATION SMS UNIT LIGHTING MANAGEMENT CONTROL STATION, LIGHTING LEGEND ELECTRIC DOOR STRIKEDS CARD READER FOR DOOR OPENERATORCR S SMO COMBINATION DATA/TELEPHONE FLOOR MOUNTED COMBINATION DATA/TELEPHONE CEILING MOUNTED COMBINATION DATA/TELEPHONE TELEVISION OUTLET DUAL TECHINOLOGY MOTION / OCCUPANCY SENSOR LIGHT SWITCH MANUAL ON - TIMED OFF LIGHT SWITCH WALL BRACKET LINEAR FIXTURE OPEN STRIP FIXTUREJ D MA MA CEILING MOUNTED DUAL TECHNOLOGY MANUAL ON / AUTO OFF VACUITY SENSOR DOOR HOLD - MAGNETIC HOLDDH FIRE ALARM CONTROL PANELFACP 1 GENERAL ELECTRICAL NOTES: 1.ALL ELECTRICAL WORK TO COMPLY WITH LATEST EDITION OF NEC, IECC AND ALL APPLICABLE GOVERNING CODES. 2.FIELD COORDINATION DURING CONSTRUCTION IS IMPERATIVE. CONTRACTORS BIDDING THIS WORK MUST MAKE REASONABLE ALLOWANCES FOR UNFORESEEN CONTINGENCIES. 3.ELECTRIC UTILITY TO ADVISE OWNER AND/OR THE ELECTRICAL ENGINEER PRIOR TO SERVICE MODIFICATION REQUIRING COST TO THE OWNER. WIRING: 1.ALL WIRING IS SHOWN DIAGRAMMATICALLY ON DRAWING, FIELD VERIFY ALL CONDITIONS PRIOR TO ROUGH-IN. 2.ALL CONDUITS AND CONVEYANCES SHALL BE CONCEALED. IN THE EVENT THAT A NEW DEVICE IS BEING INSTALLED IN AN EXISTING DRYWALL PARTITION, PROVIDE A CUT IN TYPE BOX AND FISH FLEXIBLE CONDUIT DOWN INSIDE THE WALL FROM ABOVE THE CEILING AND REPAIR THE DRYWALL AROUND THE CONDUIT. TRANSITION TO EMT ONCE ABOVE THE CEILING. 3.SIZES OF WIRE AND CABLES ARE BASED UPON COPPER CONDUCTORS, UNLESS OTHERWISE INDICATED. ALL CIRCUITS SHALL CONTAIN (2) #12 AWG WITH (1) #12 GND IN 1/2" CONDUIT UNLESS NOTED OTHERWISE. 4.ALL BRANCH CIRCUITS WITH HOME RUNS OVER 50 FEET, WILL BE SIZED ONE SIZE LARGER. 5.ALL PENETRATIONS IN OR THROUGH FIRE RATED PARTITIONS SHALL BE FIRE STOPPED IN SUCH A WAY THAT THE PENETRATION MATCHES THE FIRE RATING OF THE WALL. 6.THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL COORDINATION BETWEEN THE APPROPRIATE DISCIPLINES AND CONTRACTORS. 7.COORDINATE ALL DEVICE, FIXTURE AND HARDWARE COLOR SELECTIONS WITH THE ARCHITECT PRIOR TO MAKING SHOP DRAWING SUBMITTALS. 8.COORDINATE THE MOUNTING HEIGHTS OF ALL RECEPTACLES MOUNTED ABOVE COUNTERS, CASEWORK AND APPLIANCE RECEPTACLES WITH ARCHITECTURAL ELEVATIONS. 9.BRANCH CIRCUIT AND SPECIAL SYSTEMS WIRING FOR DEVICES ON WALLS IN FINISHED AREAS WHICH CANNOT BE CONCEALED SHALL BE INSTALLED IN SURFACE MOUNTED RACEWAY. 10.ALL EXPOSED CONDUITS, BOXES, ETC. IN ROOMS TO BE PAINTED SHALL BE PAINTED TO MATCH THE SURROUNDING SURFACE. EXPOSED CONDUITS, BOXES, ETC. IN ROOMS WHICH ARE NOT PAINTED MAY BE LEFT UN-PAINTED. EXPOSED CONDUIT, BOXES, ETC. ON THE EXTERIOR OF BUILDINGS SHALL BE PAINTED TO MATCH THE SURROUNDING SURFACE AS CLOSELY AS POSSIBLE. 11.THE CONTRACTOR IS RESPONSIBLE FOR PATCHING, PAINTING, REPAIRING OR REPLACEMENT OF ALL WALLS, CEILING OR OTHER BUILDING ELEMENTS WHICH ARE DISTURBED AS PART OF THE DEMOLITION AND/OR INSTALLATION OF ELECTRICAL WORK. 12.PROVIDE ELECTRICAL CONNECTION TO ALL FIRE, SMOKE, AND FIRE / SMOKE DAMPERS INCLUDING POWER AND FIRE ALARM. VERIFY EXACT SIZE AND FINAL LOCATION OF ALL DAMPERS WITH THE MECHANICAL CONTRACTOR. ALL ROOFTOP UNITS RATED AT MORE THAN 2000 CFM WILL BE OUTFITTED WITH A DUCT DETECTOR IN THE RETURN DUCT. ALL ROOFTOP UNITS RATED AT MORE THAN 15000 CFM WILL BE OUTFITTED WITH A DUCT DETECTOR IN BOTH THE SUPPLY AND RETURN DUCT AT ROOFTOP LEVEL AND IN THE RETURN DUCT AT EVERY LEVEL THAT IS SERVED. ELECTRICAL CONTRACTOR WILL PROVIDE A REMOTE TEST STATION AND ALL WIRING NECESSARY TO COMPLETE INSTALLATION. 13.REFER TO THE MECHANICAL EQUIPMENT SCHEDULE FOR ADDITIONAL REQUIREMENTS ASSOCIATED WITH PLUMBING AND HVAC EQUIPMENT AND OWNER/GENERAL CONTRACTOR FURNISHED EQUIPMENT. LUMINAIRES: 1.COORDINATE THE LOCATION OF ALL LIGHTING EQUIPMENT INCLUDING BUT NOT LIMITED TO THE LUMINAIRES, SWITCHES WITH THE ARCHITECTURAL, STRUCTURAL AND MECHANICAL DRAWINGS AND ALL OTHER TRADES AS REQUIRED. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLANS FOR DIMENSIONAL LOCATION OF LIGHT FIXTURES. 2.LIGHTING FIXTURES SHALL BE SUPPORTED FROM THE STRUCTURE ABOVE AND SHALL NOT BE SUPPORTED FROM THE T-BAR CEILING GRID. 3.THE ELECTRICAL CONTRACTOR IS TO CONFIRM THE LIGHT FIXTURES ORDERED WILL BE COMPATIBLE WITH THE CEILING TYPES AS SHOWN ON THE ARCHITECTURAL REFLECTED CEILING PLANS. NOTIFY THE ENGINEER OF ANY DISCREPANCIES PRIOR TO ORDERING THE FIXTURES. 4.VERIFY LUMINAIRE MOUNTING REQUIREMENTS AND OVERALL HEIGHT OF ALL PENDANT MOUNTED FIXTURES PRIOR TO ORDERING. 5.ALL LIGHT FIXTURES NEED TO BE COMPATIBLE WITH THE SWITCHES AND CONTROLS BEING PROVIDED. 6.THE LIGHTING PACKAGE SHALL BE APPROVED BY BOTH THE ARCHITECT AND ENGINEER AS APPROVED EQUAL BEFORE BID. NO LIGHT FIXTURE SHALL BE ORDERED UNTIL THE LIGHT FIXTURE SUBMITTAL PACKAGE HAS BEEN APPROVED IN WRITING BY THE ARCHITECT, GENERAL CONTRACTOR AND ELECTRICAL ENGINEER. 7.COORDINATE LUMINAIRE MOUNTING REQUIREMENTS PRIOR TO PLACING ORDER. EMERGENCY AND EXIT LIGHTS: 1.PROVIDE EMERGENCY AND EXIT SIGNS AS PER ALL GOVERNING CODES. 2.EXIT SIGNS CONNECTED TO A REMOTE EMERGENCY HEAD REQUIRE EXTRA BATTERY CAPACITY TO OPERATE THE REMOTELY LOCATED EMERGENCY HEAD FOR EGRESS AWAY FROM THE BUILDING. 3.REFER TO THE PLANS FOR THE NUMBER OF FACES REQUIRED AT EACH EXIT. FIELD ADJUST THE LOCATION OF THE EXIT SIGNS AND NUMBER OF FACES FOR THE BEST VISIBILITY POSSIBLE. 4.ALL LIGHTING FIXTURES DENOTED WITH "EM" SHALL BE PROVIDED WITH AN ENGINEER APPROVED EMERGENCY LED DRIVER OR INVERTER TO OPERATE THE FIXTURE IN AN EMERGENCY MODE TO MEET ALL CURRENT GOVERNING CODES AND WILL BE CIRCUITED TO THE UNSWITCHED SIDE OF THE LIGHTING CIRCUIT. 5.ALL LIGHT FIXTURES DESIGNATED WITH "EM" OR SPECIFIED WITH AN EMERGENCY FUNCTION SHALL BE PROVIDE WITH ONE OF THE FOLLOWING. a.INTEGRAL TEST SWITCH b.REMOTE INFRARED HANDHELD DEVICE c.INTEGRAL ELECTRONIC DEVICE THAT AUTOMATICALLY PERFORMS CODE REQUIRED TESTS. 6.ALL STAIRWELLS AND PATHS OF EGRESS TO THE EXTERIOR DOORS AND THE EXTERIOR PATH OF EGRESS AWAY FROM THE BUILDING SHALL RECEIVE EMERGENCY LIGHTING PER CODE. DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:08pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F CRAWLSPACE 00 PROPERTY LINE PR O P E R T Y L I N E PR O P E R T Y L I N E SETBACK SETBACK PROPERTY LINE SE T B A C K SE T B A C K PROVIDE LED STRIP LIGHTS TO PROVIDE ILLUMINATION FOR THE ENTIRE BASEMENT. SMOKE/CARBON MONOXIDE DETECTOR E1-1 LIGHTING - CRAWLSPACE PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:05pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F UP DN LAUNDRY 005 MUDROOM/SKI LOCKER 001 BEDROOM 2 002 BEDROOM 1 003 BATH 1 004 BATH 3 010 BEDROOM 3 011 CLOSET 1 106 BASEMENT GALLERY 009 BATH 2 012 RECREATION ROOM 008 HALL 007 R @ 0' - 7 27/32"18 CLOSET/WINE CELLAR 006 LIGHTS CHOSEN BY OTHERS. ELECTRICAL CONTRACTOR TO LIMIT LIGHT CIRCUIT AMPACITY TO 16A OR LESS PER LIGHT CIRCUIT. LIGHTING CONTROLS BY OTHERS. SMOKE/CARBON MONOXIDE DETECTOR UP S/C S/C S/C S/C S/C E1-2 LIGHTING - BASEMENT PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:06pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 A minimum of 75% of all lamps installed in permanent light fixtures must be high efficacy in dwelling units. (2015 IECC R404.1) 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F PROPERTY LINE PR O P E R T Y L I N E SETBACK OPEN TO BELOW KITCHEN 101 DINING/FAMILY ROOM 102 VESTIBULE 103 LIVING ROOM 104 GARAGE 107 DN UP DN LIGHTWELL COVER LIGHT WELL COVER POWDER 1 106 ENTRY 105 UP UP PROPERTY LINE PR O P E R T Y L I N E SETBACK PROPERTY LINE SE T B A C K SE T B A C K HOUSEKEEPING PAD FOR (4) MECHANICAL UNITS, SCREENING PROVIDED RE: LANDSCAPE PARKING SPACE 18' X 8'-6" 15R @ 0'-7 5/8" MUDROOM BENCH CLOSET TESLA ELECTRIC CAR CHARGER LIGHTS CHOSEN BY OTHERS. ELECTRICAL CONTRACTOR TO LIMIT LIGHT CIRCUIT AMPACITY TO 16A OR LESS PER LIGHT CIRCUIT. SMOKE/CARBON MONOXIDE DETECTOR MOUNTED ABOVE GARAGE DOOR MOUNTED ABOVE GARAGE DOOR S/C S/C S/C S/C S/C S/C S/C EL-01 EXISTING HISTORIC FIXTURE TO REMAIN EL-01 EL-01 EL-01 EL-01 EL-02 EL-02 E1-3 LIGHTING - MAIN LEVEL PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:06pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m REVIEWED FOR COMPLIANCE 10/05/2021 sarahy BY HPC 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F MASTER BEDROOM 204 MASTER BATH 205 OPEN TO BELOW GUEST BATH 207 MASTER CLOSET 201 BATH 4 202 DN DN GUEST BEDROOM 206 OPEN TO BELOW OPEN TO BELOW MASTER HALLWAY 203 OFFICE 208 UPPR O P E R T Y L I N E SETBACK SETBACK PROPERTY LINE SE T B A C K MA K E - U P GUEST CLOSET 210 KITCHENETTE 209 KING BED 15R @ 0'-7 5/8" NEW METAL RAILING NEW METAL RAILING LAUNDRY 211 LIGHTS CHOSEN BY OTHERS. ELECTRICAL CONTRACTOR TO LIMIT LIGHT CIRCUIT AMPACITY TO 16A OR LESS PER LIGHT CIRCUIT. SMOKE/CARBON MONOXIDE DETECTOR S/C S/C S/C EL-01EL-01 EL-01 EL-01 E1-4 LIGHTING - UPPER LEVEL PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:06pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F SETBACK SETBACK PR O P E R T Y L I N E PROPERTY LINE PROPERTY LINE SLOPE 13 1/2" : 12" SLOPE 10 1/2" : 12" SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SLOPE 10 1/2" : 12" SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SL O P E 3 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SLOPE 13 1/2" : 12" SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SL O P E 12 " : 1 2 " SL O P E 12 " : 1 2 " SL O P E 12 " : 1 2 " SLOPE 12" : 12" SLOPE 12" : 12" SLOPE 4" : 12"SLOPE 4" : 12" SL O P E 12 " : 1 2 " SL O P E 12 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " PR O P E R T Y L I N E SETBACK PROPERTY LINE SE T B A C K EXISTING PLUMBING FLUE VENT; TO BE USED HISTORIC CHIMNEY TO REMAIN; TO BE USED AS PLUMBING VENT EXISTING PENETRATION; TO BE USED FOR 6" ROUND PLUMBING VENT HISTORIC PENETRATION; NOT IN USE HISTORIC PENETRATION; NOT IN USE EXISTING PENETRATION; TO BE USED FOR 8" ROUND PLUMBING VENT HISTORIC PENETRATION; NOT IN USE EXISTING CHIMNEY TO BE USED FOR 6" VENT EXISTING PENETRATION TO BE USED FOR 8" EXHAUST PT-01 PT-02 E1-5 LIGHTING - ROOF PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:07pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F CRAWLSPACE 00 PROPERTY LINE PR O P E R T Y L I N E PR O P E R T Y L I N E SETBACK SETBACK PROPERTY LINE SE T B A C K SE T B A C K BP-1 FC 2 FC 1 H 1 H 1 S S SS BL 1 BL 2 BP-41 BP-42 BP-35,37 BP-39 BP-36,38 BP-40 S2 S2 44'' 44'' GENERAL NOTES: ·ALL 120V RECEPTACLES TO HAVE DUAL FUNCTION BREAKERS THAT PROVIDE ARC FAULT AND GROUND FAULT PROTECTION. ·ALL 120V 20A BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES TO USE COMBINATION AFCI BREAKERS. 1 MOUNTED UNDER COUNTER FLUSH POPUP COUNTERTOP RECEPTACLE HUBBEL RCT221W OR OWNER APPROVED EQUIVALENT WEATHER RESISTANT RECEPTACLE WEATHERPROOF IN USE COVER POWER FOR HOOD ABOVE GAS RANGE GARAGE DOOR OPENER DUPLEX IN CEILING POWER FOR IN FLOOR HEAT MAT. ASSUMED 14W/FT2 2 3 4 6 7 E2-1 ELECTRICAL - CRAWLSPACE PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:08pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F UP DN LAUNDRY 005 MUDROOM/SKI LOCKER 001 BEDROOM 2 002 BEDROOM 1 003 BATH 1 004 BATH 3 010 BEDROOM 3 011 CLOSET 1 106 BASEMENT GALLERY 009 BATH 2 012 RECREATION ROOM 008 HALL 007 R @ 0' - 7 27/32"18 CLOSET/WINE CELLAR 006 44''44'' 44'' 44'' 44'' 44'' WASHING MACHINE DRYER BASEMENT PANEL (BP) BP-2 BP-3 BP-3 BP-3 PARTIAL PARTIAL PARTIAL BP-4 BP-5 BP-6 BP-7 BP-8 BP-10,12 GENERAL NOTES: ·ALL 120V RECEPTACLES TO HAVE DUAL FUNCTION BREAKERS THAT PROVIDE ARC FAULT AND GROUND FAULT PROTECTION. ·ALL 120V 20A BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES TO USE COMBINATION AFCI BREAKERS. 44'' 44'' J7 MP-32,34 J7 MP-31,33 J7 MP-28,30 1 MOUNTED UNDER COUNTER FLUSH POPUP COUNTERTOP RECEPTACLE HUBBEL RCT221W OR OWNER APPROVED EQUIVALENT WEATHER RESISTANT RECEPTACLE WEATHERPROOF IN USE COVER POWER FOR HOOD ABOVE GAS RANGE GARAGE DOOR OPENER DUPLEX IN CEILING POWER FOR IN FLOOR HEAT MAT. ASSUMED 14W/FT2 2 3 4 6 7 E2-2 ELECTRICAL - BASEMENT PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:08pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F PROPERTY LINE PR O P E R T Y L I N E SETBACK OPEN TO BELOW KITCHEN 101 DINING/FAMILY ROOM 102 VESTIBULE 103 LIVING ROOM 104 GARAGE 107 DN UP DN LIGHTWELL COVER LIGHT WELL COVER POWDER 1 106 ENTRY 105 UP UP PROPERTY LINE PR O P E R T Y L I N E SETBACK PROPERTY LINE SE T B A C K SE T B A C K HOUSEKEEPING PAD FOR (4) MECHANICAL UNITS, SCREENING PROVIDED RE: LANDSCAPE PARKING SPACE 18' X 8'-6" 15R @ 0'-7 5/8" MUDROOM BENCH CLOSET TESLA ELECTRIC CAR CHARGER 3 3 44'' 44'' 44'' 44''44'' J 4 2 2 DW REF 6 UTILITY CT UTILITY METERMAIN PANEL (MP) DISCONNECT AND REMOVE EXISTING SERVICE. INSTALL NEW ELECTRICAL SERVICE. MP-2 MP-4 MP-5 MP-6 MP-7 MP-8MP-9 MP-11 MP-13 MP-14 MP-15 MP-16 FUSED DISCONNECT FC 3 EF 1 CU 1 CU 2 CU 3 CU 4 J TESLA CHARGER 11.5KW MP-40,42 COORDINATE LOCATION OF KITCHEN APPLIANCES IN FIELD. 44'' GD F F F F MP-39,41 MP-35,37 MP-36,38 MP-32,34 MP-10 3 44'' 3 MP-10 MP-23,25 S MP-44 S MP-43 GENERAL NOTES: ·ALL 120V RECEPTACLES TO HAVE DUAL FUNCTION BREAKERS THAT PROVIDE ARC FAULT AND GROUND FAULT PROTECTION. ·ALL 120V 20A BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES TO USE COMBINATION AFCI BREAKERS. UTILITY CT CABINET FUSED SERVICE DISCONNECT ELEVATION OF THE ELECTRICAL SERVICE1MOUNTED UNDER COUNTER FLUSH POPUP COUNTERTOP RECEPTACLE HUBBEL RCT221W OR OWNER APPROVED EQUIVALENT WEATHER RESISTANT RECEPTACLE WEATHERPROOF IN USE COVER POWER FOR HOOD ABOVE GAS RANGE GARAGE DOOR OPENER DUPLEX IN CEILING POWER FOR IN FLOOR HEAT MAT. ASSUMED 14W/FT2 FAN COIL HAS 2 CIRCUITS. 1 CIRCUIT FOR THE FAN & 1 CIRCUIT FOR ELEC HEATER 2 3 4 6 7 S2 8 8 MP-46,48 3 E2-3 ELECTRICAL - MAIN LEVEL PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:09pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m REVIEWED FOR COMPLIANCE 10/29/2021 sarahy BY HPC 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F MASTER BEDROOM 204 MASTER BATH 205 OPEN TO BELOW GUEST BATH 207 MASTER CLOSET 201 BATH 4 202 DN DN GUEST BEDROOM 206 OPEN TO BELOW OPEN TO BELOW MASTER HALLWAY 203 OFFICE 208 UPPR O P E R T Y L I N E SETBACK SETBACK PROPERTY LINE SE T B A C K MA K E - U P GUEST CLOSET 210 KITCHENETTE 209 KING BED 15R @ 0'-7 5/8" NEW METAL RAILING NEW METAL RAILING LAUNDRY 211 3 3 44'' 44'' MP-19 MP-20 MP-21 MP-21 PARTIAL PARTIAL FC 4 FC 5 S S 44'' 44'' 44'' 44'' MP-22MP-24,26 MP-12 MP-18 MP-27 MP-29 MP-31 MP-28 1 MOUNTED UNDER COUNTER FLUSH POPUP COUNTERTOP RECEPTACLE HUBBEL RCT221W OR OWNER APPROVED EQUIVALENT WEATHER RESISTANT RECEPTACLE WEATHERPROOF IN USE COVER POWER FOR HOOD ABOVE GAS RANGE GARAGE DOOR OPENER DUPLEX IN CEILING POWER FOR IN FLOOR HEAT MAT. ASSUMED 14W/FT2 2 3 4 6 GENERAL NOTES: ·ALL 120V RECEPTACLES TO HAVE DUAL FUNCTION BREAKERS THAT PROVIDE ARC FAULT AND GROUND FAULT PROTECTION. ·ALL 120V 20A BRANCH CIRCUITS SUPPLYING OUTLETS OR DEVICES TO USE COMBINATION AFCI BREAKERS. J 7 7 MP-45,47 J7 MP-49,51 J7 MP-53,55 8 8 S2 S2 MP-50,52 MP-54,56 E2-4 ELECTRICAL - UPPER LEVEL PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:09pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 EE CC B B AA D D F F SETBACK SETBACK PR O P E R T Y L I N E PROPERTY LINE PROPERTY LINE SLOPE 13 1/2" : 12" SLOPE 10 1/2" : 12" SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SLOPE 10 1/2" : 12" SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SL O P E 3 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SLOPE 13 1/2" : 12" SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SLOPE 13 1/2" : 12" SL O P E 12 " : 1 2 " SL O P E 12 " : 1 2 " SL O P E 12 " : 1 2 " SLOPE 12" : 12" SLOPE 12" : 12" SLOPE 4" : 12"SLOPE 4" : 12" SL O P E 12 " : 1 2 " SL O P E 12 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " SL O P E 13 1 / 2 " : 1 2 " PR O P E R T Y L I N E SETBACK PROPERTY LINE SE T B A C K EXISTING PLUMBING FLUE VENT; TO BE USED HISTORIC CHIMNEY TO REMAIN; TO BE USED AS PLUMBING VENT EXISTING PENETRATION; TO BE USED FOR 6" ROUND PLUMBING VENT HISTORIC PENETRATION; NOT IN USE HISTORIC PENETRATION; NOT IN USE EXISTING PENETRATION; TO BE USED FOR 8" ROUND PLUMBING VENT HISTORIC PENETRATION; NOT IN USE EXISTING CHIMNEY TO BE USED FOR 6" VENT EXISTING PENETRATION TO BE USED FOR 8" EXHAUST PT-01 PT-02 E2-5 ELECTRICAL - ROOF PLAN SCALE: 1/4"=1'-0" NORTH DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:10pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m (2)4"C-3#500KCMIL AL CABINET CT ONE-LINE DIAGRAM NOT TO SCALE FUSED MAIN DISCONNECT CLASS T FUSES 600 A 120/240V 1Ø NEMA 3R 42KAIC MAIN PANEL (MP) MCB 600 A 120/240V 1Ø NEMA 3R 10KAIC BASEMENT PANEL (BP) MCB 200 A 120/240V 1Ø NEMA 1 10KAIC (2)3"C-3#500KCMIL AL + #1/0 AL GND 1 2 3 2"C-3#250KCMIL AL + #4 AL GND 1 1 2 3 4 GROUND ROD #6 CU 4 UTILITY TRANSFORMER ASSUMED 150KVA 32900 SCA PANEL SCHEDULE - MP TYPE:PANELBOARD BUS SIZE:600 PHASES:1 NEUTRAL BUS:YES VOLTAGE:120/240 MAIN BRKR:600 WIRES:3 GROUND BUS:YES ENCLOSURE:NEMA3R MOUNTING:SURFACE SC RATING:10000 LOAD TYPE LOAD DESCRIPTION AMPS CKT#0/CKT#AMPS LOAD TYPE LOAD DESCRIPTION POLES LOAD LOAD POLES SUBFEED PANEL BP 200A 1 A 2 20A RECEPTACLE GARAGE ---2P 13949 1440 1P --- SUBFEED ------3 B 4 20A RECEPTACLE GARAGE DOOR OPENER ------13785 1500 1P --- RECEPTACLE GROUND LEVEL BATHROOMS 20A 5 A 6 20A RECEPTACLE LIVING RM ---1P 180 1260 1P --- RECEPTACLE DINING ROOM & VESTIBULE 20A 7 B 8 20A RECEPTACLE KITCHEN ISLAND ---1P 1080 540 1P --- RECEPTACLE GARBAGE DISPOSAL 20A 9 A 10 20A RECEPTACLE SERVICE RECEPTACLES ---1P 1200 720 1P --- MOTOR KITCHEN HOOD 20A 11 B 12 20A MECH YEAR ROUND FC-4 ---1P 1500 2616 1P --- RECEPTACLE KITCHEN 20A 13 A 14 20A RECEPTACLE KITCHEN ---1P 360 360 1P --- RECEPTACLE DISHWASHER 20A 15 B 16 20A RECEPTACLE REF/FREEZER ---1P 1200 900 1P --- SPACE ------17 A 18 20A MECH YEAR ROUND FC-5 ------0 2616 1P --- RECEPTACLE MASTER BEDROOM 20A 19 B 20 20A RECEPTACLE MASTER HALLWAY & CLOSET ---1P 1620 540 1P --- RECEPTACLE MASTER BATHROOMS 20A 21 A 22 20A RECEPTACLE WASHING MACHINE ---1P 540 1000 1P --- MISCELLANEOUS OVEN 50A 23 B 24 30A MISCELLANEOUS DRYER ---2P 4500 2500 2P --- MISCELLANEOUS ------25 A 26 ---MISCELLANEOUS --- ------4500 2500 ------ RECEPTACLE GUEST ROOM 20A 27 B 28 20A RECEPTACLE GUEST BATHROOM ---1P 1260 180 1P --- RECEPTACLE GUEST KITCHENETTE 20A 29 A 30 ---SPACE --- ---1P 1500 0 ------ RECEPTACLE GUEST KITCHENETTE 20A 31 B 32 35A MECH COOLING CU-4 ---1P 1500 2880 2P --- SPACE ------33 A 34 ---MECH COOLING --- ------0 2880 ------ MECH COOLING CU-2 35A 35 B 36 35A MECH COOLING CU-3 ---2P 2520 2400 2P --- MECH COOLING ------37 A 38 ---MECH COOLING --- ------2520 2400 ------ MECH COOLING CU-1 35A 39 B 40 60A MISCELLANEOUS TESLA CHARGER ---2P 2520 5750 2P --- MECH COOLING ------41 A 42 ---MISCELLANEOUS --- ------2520 5750 ------ MISCELLANEOUS EF-1 20A 43 B 44 20A MECH YEAR ROUND FC-3 ---1P 64 1308 1P --- MISCELLANEOUS FLOOR HEAT MASTER BATHRM 20A 45 A 46 20A MISCELLANEOUS FANCOIL HEATER ---2P 1000 1500 2P --- MISCELLANEOUS ------47 B 48 ---MISCELLANEOUS --- ------1000 1500 ------ MISCELLANEOUS FLOOR HEAT BATHRM 4 20A 49 A 50 20A MISCELLANEOUS FANCOIL HEATER ---2P 120 1500 2P --- MISCELLANEOUS ------51 B 52 ---MISCELLANEOUS --- ------120 1500 ------ MISCELLANEOUS FLOOR HEAT GUEST BATHRM 20A 53 A 54 20A MISCELLANEOUS FANCOIL HEATER ---2P 133 1500 2P --- MISCELLANEOUS ------55 B 56 ---MISCELLANEOUS --- ------133 1500 ------ SPACE ------57 A 58 ---SPACE --- ------0 0 ------ SPACE ------59 B 60 ---SPACE --- ------0 0 ------ SPACE ------61 A 62 ---SPACE --- ------0 0 ------ SPACE ------63 B 64 ---SPACE --- ------0 0 ------ SPACE ------65 A 66 ---SPACE --- ------0 0 ------ LOADS BY TYPE:LOADS BY PHASE: LOAD CONNECTED DEMAND DEMAND CONNECTED CONNECTED BALANCE TYPE LOAD (VA)FACTOR LOAD (VA)PHASE LOAD (VA)LOAD (AMPS)(PERCENT) LIGHTING 0.00 1.25 0.00 A 53948.00 449.57 A-B: 92.4 KITCHEN 0.00 1.00 0.00 B 58416.00 486.80 B-A: 92.4 PROCESS 0.00 1.00 0.00 C --------- RECEPTACLES 10000.00 1.00 10000.00 RECEPTACLES 20820.00 0.50 10410.00 TOTAL/AVERAGE 112364.00 468.18 92.4 MECH HEATING 0.00 1.00 0.00 MECH COOLING 20640.00 1.00 20640.00 MECH YEAR ROUND 20388.00 1.00 20388.00 NOTES: APPLIANCE 0.00 1.00 0.00 MISCELLANEOUS 39016.00 1.00 39016.00 1. THE LARGEST CONNECTED MOTOR LOAD IS INCLUDED IN MECHANICAL, PROCESS, OR MOTOR LOADS. MOTOR 1500.00 1.00 2250.00 SPARE 0.00 1.00 0.00 LARGEST MOTOR 1 ABOVE 0.25 1440.00 TOTAL 112364.00 103394.00 PANEL SCHEDULE - BP TYPE:LOADCENTER BUS SIZE:225 PHASES:1 NEUTRAL BUS:YES VOLTAGE:120/240 MAIN BRKR:200 WIRES:3 GROUND BUS:YES ENCLOSURE:NEMA1 MOUNTING:SURFACE SC RATING:10000 LOAD TYPE LOAD DESCRIPTION AMPS CKT#0/CKT#AMPS LOAD TYPE LOAD DESCRIPTION POLES LOAD LOAD POLES RECEPTACLE CRAWLSPACE RECPS 20A 1 A 2 20A RECEPTACLE MUDROOM & GALLERY ---1P 360 720 1P --- RECEPTACLE BASEMENT BATHROOMS 20A 3 B 4 20A RECEPTACLE BEDROOM 3 ---1P 900 900 1P --- RECEPTACLE BEDROOM 2 20A 5 A 6 20A RECEPTACLE BEDROOM 1 ---1P 900 1080 1P --- RECEPTACLE REC ROOM 20A 7 B 8 20A RECEPTACLE LAUNDRY ROOM ---1P 1080 1000 1P --- SPACE ------9 A 10 30A RECEPTACLE DRYER ------0 2500 2P --- SPACE ------11 B 12 ---RECEPTACLE --- ------0 2500 ------ SPACE ------13 A 14 ---SPACE --- ------0 0 ------ SPACE ------15 B 16 ---SPACE --- ------0 0 ------ SPACE ------17 A 18 ---SPACE --- ------0 0 ------ SPACE ------19 B 20 ---SPACE --- ------0 0 ------ SPACE ------21 A 22 ---SPACE --- ------0 0 ------ SPACE ------23 B 24 ---SPACE --- ------0 0 ------ SPACE ------25 A 26 ---SPACE --- ------0 0 ------ SPACE ------27 B 28 20A MISCELLANEOUS FLOOR HEAT BATH 3 ------0 336 2P --- SPACE ------29 A 30 ---MISCELLANEOUS --- ------0 336 ------ MISCELLANEOUS FLOOR HEAT BATH 2 20A 31 B 32 20A MISCELLANEOUS FLOOR HEAT BATH 1 ---2P 301 336 2P --- MISCELLANEOUS ------33 A 34 ---MISCELLANEOUS --- ------301 336 ------ MECH YEAR ROUND H-1 20A 35 B 36 20A MECH YEAR ROUND H-1 ---2P 1908 1908 2P --- MECH YEAR ROUND ------37 A 38 ---MECH YEAR ROUND --- ------1908 1908 ------ MECH YEAR ROUND FC-1 20A 39 B 40 20A MECH YEAR ROUND FC-2 ---1P 1308 1308 1P --- MECH YEAR ROUND BL-1 20A 41 A 42 20A MECH YEAR ROUND BL-2 ---1P 1800 1800 1P --- LOADS BY TYPE:LOADS BY PHASE: LOAD CONNECTED DEMAND DEMAND CONNECTED CONNECTED BALANCE TYPE LOAD (VA)FACTOR LOAD (VA)PHASE LOAD (VA)LOAD (AMPS)(PERCENT) LIGHTING 0.00 1.25 0.00 A 13949.00 116.24 A-B: 98.8 KITCHEN 0.00 0.00 0.00 B 13785.00 114.88 B-A: 98.8 PROCESS 0.00 1.00 0.00 C --------- RECEPTACLES 10000.00 1.00 10000.00 RECEPTACLES 1940.00 0.50 970.00 TOTAL/AVERAGE 27734.00 115.56 98.8 MECH HEATING 0.00 1.00 0.00 MECH COOLING 0.00 1.00 0.00 MECH YEAR ROUND 13848.00 1.00 13848.00 NOTES: APPLIANCE 0.00 1.00 0.00 MISCELLANEOUS 1946.00 1.00 1946.00 1. THE LARGEST CONNECTED MOTOR LOAD IS INCLUDED IN MECHANICAL, PROCESS, OR MOTOR LOADS. MOTOR 0.00 1.00 0.00 SPARE 0.00 1.00 0.00 LARGEST MOTOR 1 ABOVE 0.25 954.00 TOTAL 27734.00 27718.00 DATE: CHECKED BY: JOB NO: DRAWN BY: DATE:ISSUED FOR: SHEET NUMBER: 13 4 E A S T B L E E K E R S T R E E T SCALE:AS SHOWN 08/10/2020 PERMIT BCE BCE March 25, 2021 - 12:44:10pm 20-102 AS P E N , C O L O R A D O DO NOT REPRODUCE THESE DRAWINGS AND SPECIFICATIONS WITHOUT THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. THE DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF THE SERVICE AND SHALL REMAIN THE PROPERTY OF THE DESIGNER WHETHER THE PROJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. THESE DRAWINGS AND SPECIFICATIONS SHALL NOT BE USED BY ANYONE ON ANY OTHER PROJECTS FOR ADDITIONS TO THIS PROJECT BY OTHERS EXCEPT BY THE EXPRESSED WRITTEN PERMISSION OF THE DESIGNER. Bi g h o r n C o n s u l t i n g E n g i n e e r s , I n c . Me c h a n i c a l & E l e c t r i c a l E n g i n e e r s 38 6 I n d i a n R o a d Gr a n d J u n c t i o n , C O 8 1 5 0 1 Ph o n e : ( 9 7 0 ) 2 4 1 - 8 7 0 9 10 1 W 1 1 t h S t r e e t # 1 0 9 - C Du r a n g o , C O 8 1 3 0 1 Ph o n e : ( 9 7 0 ) 4 2 2 - 7 6 7 6 03-25-2021 10/05/2020 CD 03/25/2021 PERMIT COMMENT REVISION 1 E2-5 03/26/2021 05/1 9 / 2 0 2 1 bonn i e m