HomeMy WebLinkAboutFile Documents.731 E Durant Ave.0031-2023-BRES (9) HealthSa f e
INSPECTIONS
HealthSafe Inspections Inc
390 Apple Drive
Basalt CO 81621
970-920-2100
Jim Baker CDPHE Asbestos Building Inspector#13437
Ben Baker CDPHE Asbestos Building Inspector#25863
ASBESTOS REPORT
DATE
01/19/2023
CLIENT
Day a‘t -
\1\10
c/o Storm Designs Ltd 03/31/2p23
PO Box 5314 am
Snowmass Village, CO 81615
PROPERTY ADDRESS of INSPECTION
Chateau Chaumont#7, 701 East Durant Avenue,Aspen, Colorado 81611
Chateau
Chaumont
731 E. Durant
•
RECEIVED
1 02/16/2023
ASPEN
BUILDING DEPARTMENT
CLIENT BACKGROUND & PLANS
The Client, Day, is planning a renovation-remodel-demolition of the bedroom closets and
powder room south wall, which will have impacts of disturbance, detachment,
deconstruction, demolition, and disposal(5D) of drywall building materials, of which
some are suspect asbestos containing materials (ACM). Prior to 5D, Day is required to
have an asbestos inspection by a State of Colorado CDPHE certified asbestos inspector
who will collect bulk samples of the suspect ACM and have those samples analyzed at a
certified laboratory for asbestos content. Day hired HealthSafe Inspections, Inc.
(hereinafter, HealthSafe) via Storm Designs Ltd to perform a limited asbestos inspection
for the bedroom closets and south powder room wall.
VISUAL INSPECTION & LABORATORY FINDINGS
An inspection was conducted by Ben Baker of HealthSafe on Wednesday, January 04,
2023, with Cherie Storm of Storm Designs Ltd present during the initial survey,
inspection and sample collecting.All suspect ACM were identified by homogenous
materials and sampled randomly respective to the scope of those materials slated for 5D.
The suspect ACM collected and analyzed by EPA 600 Method PLM analysis are the
following:
1. Orange Peel Surfacing Texture, a homogeneous spray-applied surfacing
material/texture [samples 1-3: OP-1,2,3], collected randomly from the SW
bedroom closet east wall, SE bedroom closet east wall, and entryway north wall,
respectively,using the AHERA random sampling grid# 15. This surfacing
material/texture is friable and located on the ceilings and walls of the bedroom
closets and the south powder room wall. The estimated impact area of 5D is more
than 10 sf,but less than 1,000 sf(±150 sf), requiring a minimum of at least three
surfacing/texture material samples. The PLM analytical estimated results: 2%
Chrysotile asbestos in samples 2 and 3 with EPA 400 Point Count results:
<0.25% and 0.50%,respectively.
2. Drywall System Joint Compound: a homogeneous miscellaneous seam taping
compound requiring at least two samples [samples 4-5: JC-1,2], collected from
the SW bedroom closet NE corner and the SE bedroom closet NE corner,
respectively. This material is friable and applied to the condo interior drywall
system. The PLM analytical estimated results: 3% Chrysotile asbestos in both
samples. This material is given a total composite concentration with the drywall
system as a whole (see paragraph#3 below).
3. Drywall System, a homogeneous taped and joint compounded drywall system
(classified as a miscellaneous material as a complete integral system) [samples 6-
7: J-1,2], collected from the SW bedroom closet NE corner and the SE bedroom
closet NE corner, respectively. These composite layered taped and joint
compounded drywall materials are friable and located on the ceilings and walls of
the condo interior with an orange peel applied surfacing material/texture. The
estimated impact area of 5D is more than 10 sf,but less than 1,000 sf(1150 sf),
requiring a minimum of at least two composite core samples of all layers. The
rCO'itt RECEIVED
,31/2023 2 02/16/2023
fa sol
ASPEN
BUILDING DEPARTMENT
PLM analytical estimated results: 3% Chrysotile asbestos in the joint compound
of both samples with entire composite EPA 400 Point Count results: <0.25%.
A total of 7 suspect homogeneous ACM bulk samples were collected: 7 samples were
analyzed by EPA 600 PLM analytical methods and 4 of those samples were analyzed by
EPA 400 Point Count Method by a NVLAP accredited laboratory in accordance with
Colorado State Regulation 8 for the presence of asbestos mineral fibers.
See supporting Hayes Microbial Consulting, Inc. data report#23000404_3.
HEALTHSAFE CONCLUSIONS
• There is asbestos in the orange peel surfacing material/texture that does NOT
require abatement confirmed at<1%by EPA 400 Point Count Method. However,
Federal OSHA regulations shall apply when working with asbestos hazards even
at trace concentrations.
• There is asbestos in the drywall system joint compound that does NOT require
abatement confirmed at<1%by EPA 400 Point Count Method. However, Federal
OSHA regulations shall apply when working with asbestos hazards even at trace
concentrations.
• See EPA 40 CFR 763.121 Worker Protection Rule, OSHA 29 CFR 1910.134
Respirator Protection Standard, OSHA 29 CFR 1910.1001 General Industry
Standard and OSHA 29
Sincerely Submitted,
Ben Baker ,ei,\
' t
We p23
3/31/2
feitototi.
REC WED
3 02/16/2023
ASPEN
BUILDING DEPARTMENT
_ .
1
t i
I
, AO
r�03i3
3
1�2�2
cow!.
RECEIVED
4 02/16/2023
ASPEN
BUILDING DEPARTMENT
COLORADO & FEDERAL ASBESTOS REGULATIONS SUMMARY
Regulation No. 8 Part B—Asbestos of the Colorado Department of Public Health and
Environment(CDPHE),Air Quality Control Commission requires a State-certified
Asbestos Building Inspector to inspect and collect bulk samples of all suspect asbestos
containing materials (ACM) or suspect asbestos containing building materials (ACBM)
prior to their disturbance, removal or demolition and disposal. The suspect materials shall
be analyzed by a NVLAP accredited laboratory by polarized light microscopy(PLM)
using EPA 600 analytical method.A material which is estimated to contain more than 1%
asbestos is classified as ACM/ACBM and regulated by the State and Federal
governments.Any friable (able to crush or reduce to powder by finger pressure) asbestos
with trace amounts of asbestos fibers or less than 1%must be point-counted using EPA
400 analytical method to prove that it is indeed less than 1%; if not, it must be classified
as ACM/ACBM and shall be treated as a State and Federal regulated material.Any
friable asbestos containing material (greater than 1% asbestos concentration) or
ACM/ACBM that could be rendered friable during its removal or demolition and disposal
shall require an asbestos abatement by a certified asbestos abatement contractor to
remove and dispose of the material(s).
A Colorado State (CDPHE) issued asbestos abatement permit is required for the
following trigger levels of ACM/ACBM:
1. Residential buildings of four or fewer units--if more than 32 square feet of any
surface coverage (e.g., gypsum wallboard or drywall and associated applied surfacing
materials/textures, acoustic sprays,joint compounds,plaster, etc.), 50 feet of asbestos
covered or asbestos insulated pipe or any material which would fill a 55-gallon drum is
going to be disturbed, removed or disposed of, an asbestos abatement permit is required.
2. Residential complexes with more than four residential units, public access areas to a
residential building, commercial and retail buildings, public and civic buildings,
industrial buildings--if more than 160 square feet of surfacing materials, 260 linear feet
or more than 35 cubic feet(NESHAP) or 55-gallon drum(CDPHE) of suspect
ACM/ACBM is going to be disturbed, removed or disposed of, an asbestos abatement
permit is required under NESHAP and by the CDPHE. See note below on OSHA.
The regulations require an absolute minimum of 3 samples (EPA suggests 9)per
homogenous suspect surfacing and TSI materials and an absolute minimum of 2 samples
of homogenous miscellaneous materials or any number of"samples sufficient to
determine whether a material is ACM" (Reg8.IV.D.3). More samples are required based
on surface area or volume. These are minimums; the asbestos building inspector has the
field responsibility to determine homogenous materials and the number of samples to
collect per material; more than the minimum number of samples may be necessary at the
discretion of the inspector.An assessment of friability and functional space conditions of
the materials are also the inspector's field responsibilities. RECEIVED
5 02/16/2023
ASPEN
BUILDING DEPARTMENT
OSHA compliance is required for all employers and employees no matter the
quantity of asbestos present with strict regulations regarding 10 sf or more of TSI or
friable surfacing materials, and therefore it does not matter what the quantity or
State trigger levels are: all suspect ACM/ACBM shall be inspected and tested for
asbestos prior to their disturbance, removal and disposal for worker protection and
safety. See EPA 40 CFR 763.121 Worker Protection Rule, OSHA 29 CFR 1910.134
Respirator Protection Standard, OSHA 29 CFR 1910.1001 General Industry Standard and
OSHA 29 CFR 1926.1101 Construction Standard regulations when dealing with asbestos
hazards.
Note: County or City regulations may be more stringent.
RECEIVED
6 02/16/2023
ASPEN
BUILDING DEPARTMENT
4 H AY E S
MICROBIAL CONSULTING #23000404
Analysis Report prepared for We would like to thank you for trusting Hayes Microbial for your analytical needs!
We received 7 samples by FedEx in good condition for this project on January 5th, 2023.
HealthSafe
The results in this analysis pertain only to this job, collected on the stated date, and should not be used
Inspections in the interpretation of any other job. Information supplied by the customer can affect the validity of
results. These results apply only to the samples as received. This report may not be duplicated,except in
full,without the written consent of Hayes Microbial Consulting, LLC.
390 Apple Drive
Basalt, CO 81621 All information provided to Hayes Microbial is confidential information relating to our customers and their
Phone: (970) 920-2100 clients. We will not disclose,copy,or distribute any information verbally or written,except to those
designated by the customer(s). We take confidentiality very seriously. No changes to the distribution list
will be made without the express consent of the customer.
This laboratory bears no responsibility for sample collection activities, analytical method limitations,or
Day your use of the test results. Interpretation and use of test results are your responsibility. Any reference to
Chateau Chaumont #7 health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial. In no event, shall
701 E. Durant Ave. Hayes Microbial or any of its employees be liable for lost profits or any special, incidental or
Aspen, CO 81 61 1 consequential damages arising out of the use of these test results.
Collected: January 4, 2023 / /
Received: January 5, 2023 —4 1 g *-4--
Reported: January 16, 2023
Steve Hayes,BSMT(ASCP)
Laboratory Director { �
Hayes Microbial Consulting,LLC.
23
J��SED STgT 03 I
31I1G0 0
FS td�,w ,,� ` mi
aL ° sa
_' 0 Y° �� DPH
g J �
Zo o, �Y% J.
FZ�. ,..: ConofPobl[DePartmen[
PROM --- Zta,�ae�t� RECEIVED
EPA Laboratory ID: VA01419 Lab ID: #188863 DPH License: #PH-0198
02/16/2023
Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com Page: 1 of 4
ASPEN
BUILDING DEPARTMENT
Ben Baker #23000404
HealthSafe Inspections Day
390 Apple Drive Chateau Chaumont#7
Basalt,Co 81621 701 E. Durant Ave. Asbestos PLM Bulk
(970) 920-2100 Aspen,CO 81611 EPA 600/R-93,M-4/82-020
# Sample Material Description Non-Asbestos Fibers Asbestos Fibers
1 OP-1 Texture/White None Detected
2 OP-2 Texture/Tan 2%Chrysotile
3 OP-3 Texture/Tan 2%Chrysotile
4 JC-1 Joint Compound/Tan 3%Chrysotile
5 JC-2 Joint Compound/Tan 3%Chrysotile
6 J-1 Joint Compound/Tan 3%Chrysotile
Drywall/White 3%Cellulose Fibers None Detected
7 J-2 Joint Compound/Tan 3%Chrysotile
Drywall/White 3%Cellulose Fibers None Detected
3
O3I3112p2
sang
Collected:Jan 4,2023 Received: Jan 5,2023 Reported: Jan 16,2023 Revision: 3 RECEIVED
Project Analyst: Date: Reviewed By: e:
H AY E ffe�/�/� �Q /16/2023
Angie Llatas-Campos, ,4 01 19 2023 David McDonald,PHR Pa / l`�P`�'1!/Lf 01 - 19 -2023
0MICROBIAL CONSULTING __ i _
3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com BUILD AsFQI ING DEPARTMENT
Ben Baker #23000404
HealthSafe Inspections Day
390 Apple Drive Chateau Chaumont#7
701 E
Basalt,CO 81621 E. Durant Ave. Asbestos 400 Point Count
(970) 920-2100 Aspen,CO 81611
# Sample Material Description Total Points Non-Asbestos Fibers Asbestos Fibers
2 OP-2 Texture/Tan 400 <0.25%unrysotiie
Lab Note:Asbestos Observed Not Within Counting Field of View
3 OP-3 Texture/Tan 400 0.50%Chrysotile
6 J-1 Composite:JC/DW/Off-White 400 <0.25%Chrysotile
Lab Note:Asbestos Observed Not Within Counting Field of View
7 J-2 Composite: DW/JC/Off-White 400 <0.25%Chrysotile
Lab Note:Asbestos Observed Not Within Counting Field of View
1.„0\tt\N 3
03/31/2p2
Sam
Collected:Jan 4,2023 Received: Jan 5,2023 Reported: Jan 16,2023 Revision: 3 RECEIVED
0 Project Analyst: Date: Reviewed By: e:
H AY E ff��/�/� �Q /16/2023
Angie Llatas-Campos, ! ,4 01 - 19 -2023 David McDonald,PHR Po 6 l`��`�'1,!/Lf 01 - 19 -2023
MICROBIAL CONSULTING __ li1�t
3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com BUILDING DFEPARTMEt4T
Ben Baker #23000404
HealthSafe Inspections Day
390 Apple Drive Chateau Chaumont#7
701 E
Basalt,CO 81621 E. Durant Ave. Asbestos Analysis Information
(970) 920-2100 Aspen,CO 81611
Analysis Details All samples were received in acceptable condition unless otherwise noted on the report.This report must not be used by the client to claim product certification,
approval,or endorsement by AIHA,NIST,NVLAP,NY ELAP,or any agency.The results relate only to the items tested. Hayes Microbial Consulting reserves the right to
dispose of all samples after a period of 60 days in compliance with state and federal guidelines.
PLM Analysis All Polarized Light Microscopy(PLM) results include an inherent uncertainty of measurement associated with estimating percentages by PLM.
Materials with interfering matrix,low asbestos content,or small fiber size may require additional analysis via TEM Analysis.
TEM Analysis Analysis by TEM is capable of providing positive identification of asbestos type(s) and semi-quantitation of asbestos content.
Definitions 'None Detected'-Below the detected reporting limit of 1%unless point counting is performed,then the detected reporting limit is .25%.
New York ELAP Per NY ELAP198.6(NOB),TEM is the only reliable method to declare an NOB material as Non-Asbestos Containing.
Any NY ELAP samples that are subcontracted to another laboratory will display the name and ELAP Lab Identification number in the report page heading of those
samples.The original report provided to Hayes Microbial Consulting is available upon request.
tOkt.112p23
03/3 0000
ymi
RECEIVED
H AY E S 02/16/2023
MICROBIAL CONSULTING 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@a hayesmicrobial.com C +4 of
BUILDINGASP DEPARTMENT
•
HealthSafe Inspection's SHIP: FEDEX - ENV PO ASBESTOS
DATE: 01 05 2023
390 Apple Drive
_ -- MICROBIAL CONSULTING Basalt, CO 81621
817E 1598 8558
Job Number: Job Name: Dc, 1111111111111011111111111111I1ii1111I1 23000404
Collector: (den 134er C�Gt 6 h,t,mpvc ` ? Mobile: 970-(,/g-/I 7 Email: healthsafeinspections@gmail
Date Collected:5/lo•yl)_3 / )- 4 lie,' j`ffe,, Cc �'/ Note:L(, 6wr.bgIce( I3'33i,? �a'l.co'n_��
Analysis Type • Analysis Methods • • Turnaround Times •
PLM Bulk EPA 600 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day
Point Count 400 Point,1000 Point 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day
Vermiculite CARB 435 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day
TEM Air EPA AHERA,NIOSH 7402 - Same Day 1 Day 2 Day 3 Day 5 Day
Bulk Chatfield - Same Day 1 Day 2 Day 3 Day 5 Day
• Wipe ASTM D6480-05 - Same Day 1 Day 2 Day 3 Day 5 Day
Microvac ASTM D5755-09 - Same Day 1 Day 2 Day 3 Day 5 Day
PCM �I Air NIOSH 7400 I - Same Day I 1 Day I 2 Day �, 3 Day -I 5 Day
. — .�:+=o _ _ _- .-.e..-- ...R.___�1J._..-- _•.-_._-._._ate _sr I._--���..s -..--
#1 Group Number Sample Name Analysis Type Turnaround Volume/Area ! Stop (+)
1 Uf'-/ • _ he';
2 Up
3
e.' 3
4 Tc -/ I
5 JC- 2.
6 j- 1
7 j- a V/ \,/
8 .
9
10
11
3
12 icoti% -13 \40
13
_wologe
14 ca san`''
15
16
7 1 ECEIVED
Released by.,,, Date: Received By: Date:
Hayes Microbial Consulting.LLC. 3005 East Boundary Terrace,Suite F.ivlidlothian,VA.23112 (804)562-3435 contact@hayesrnicrohial.com Form 20,FIV.f 111;1A/14)23
Chain of Custody
ASPEN
BUILDING DEPARTMENT
..•ii•1.1.. V •*AveV•1�11e,• • •:$5:104. " 41.4,;:1•1� •� ien:0•1.) ••i�•�1�1•;:;1%;�:416��1; .Q:,,44;g:.�g �r dill���:�.��,
,.ii�llllljllji•. •ii1i1�►111/1/j/l/ji•+ :ii.i1►►11111111/1/i. ;iili•j►111111111%/l. liilil►�1111111111/i1 :'i1i►�1111111j�1•I. .��ii1►1111111 1 1 1/6, ..i�i►►1/1/1//11Pn, .C��i1►111111111%•'. :i•i1►I�Ii%�
••. /.11�°.�,��1\►I�QN/ '000,, 41l\III►►11�111j;:h. .4;t1�►1�/�1/1 101.•,•�111►1;i4/11%1///::...4, ,III/l/////��,q��\II0`....401/� ,, 1q,..,/1//11 f,fr;•,alt:0�0.11/11/1/ „:l���:111.!��S,
. A.,///Gnu\,1,0i011i111///b,4\A10:•144,9,,tj%;,,,,'h►11HOIll/l//4AZ\;�4h►1b',4'40 /j,,iit. ,*,,11i11i,,,,��C\:��,,,:el1111 iA4.; ^\b;,,!):1 11,1',4/�\.�yh 0./,..11/Ili!!/ \.�:1�1 S°
14�E:.6••//N�.B!,,1�/N1r;l�'..//^,%.� ,Ijn1111!1�4,'^///` i`ti'i11111,1,!l,:'�//N�\\'��'i1'11•Irir!l,i!..//l`\ �;,�1'l/1••r�!��:////�l`Y;�141r•lr,,lr, ///^\,\. .!I/irlr'JI� .///^\`1,�,,1�11Nr�;�r',///�\~ll ���.�
..-=s_7////\\lic!�!,;l•S'Ifi;,;//I\N; §§1:;l 4/0Aii% :.:,,,,;5.///ice 1; ;11:::' /0111�\ 14:'- J/,,, Illv!,;::;,t. ,I$;' \l•��,!.N:;,: /////N\l��';,ig•: 'eozI 11.:\Sir'
•:::G-:;��:/i^\h\I';�;;;::„'////j�II :;p;ar,;://///^II �}.,../1/// INI\,;,:qor•'/////�\I111\•'Tt. /Ii///�\II�\V,;1'r /////s!�II\Il\•,;;::.,. /////�'-.`�\I\I\�.;;'P.;r'/I//L:, ���ww\�..
i/ . �lggk, //,;, I .,rj?+; //r \IlN //r:: % //i \W\\ /r \l ;.\\l /r 1 /. ..w�1;'
';Sidi • v _ M a
=`�"�= ' i i;ICU'l� i ttltig.. 'UljillUiifiU'ItUt�U,istg i*,% ' a ;', "<67� H tvj..) ni tU'1tU'ikok7, ifU'ititi t} rIU'illltti,ij z{JUIfUII k`' ;:_:
.����\ VI 1 . IV•V/V IV VIV•V IV• �Iy �. 1 •V♦-.V•V V•V•VIVrVr V• IV V V•V• `.� y:=-� ==1.,
v`v� .vvvaOL� ../vv v C�i v .vvvvvv'vv `v�
• --_-1 pF COS ((c ??>::;t ,..•
%
SA:=.- 1.-':*f-,--Aj,' ,,, ca..-47,i o ,,--,e....,.. ..,,,,,-__;,-.F.,%-zw:
•k\NIt,S !) Colorado Department e
=: if:1i* of Public Health ((m', i .:
)) and Environmentmc, ==
__=__ _ 7;) ASBESTOS ____==__
; '� CERTIFICATION* `�
` /iii�i
A This certifies that a,1i =•
y:= , ' % (icy;. -
Benjamin L Baker (`c
4.
��,���= `» (� ;mac,,:,.-:;
:: » ((
Certification No.. 25863 �«:
i �
ice%�;:: '1=- •0 :y;C1=� �2.
«c<c<>:-�= has met the requirements of 25-7-507, C.R.S. and Air QualityControl ,t0;,.' 4
• _-=_� r?a Commission Regulation No. 8, Part B, and is hereby certified by the « '""...
'%==='- -,.. � state of Colorado in the following discipline: c = '�e•
=' -s. � Building Inspector* :,-'="'/
===` ° --
..._ -\ a)) Issued: August 31, 2022 1� 3 (cc`"°) -_ , ,..;# 3-,;, -«
,�y .__` i) \i' 03/3.1"/2132
(ii` _ 'Z1
)) Expires: September 25, 2023 -
'ZZ = (t` 3:•
►•.• - i�ce, Kc _:���.ice.
'.� This certificate is valid only with the possession of a ::•
•.:11," :;::f! � current Division-approved training course certification `�i:"
7 „\��<(.. -- in the discipline specified ahove. �� �>���;_,
Autho ize °19/APCD Representative ; .,/.
(Cr.,:
I.� ;;.:.•\ � �
1►� , ;i � !'i
__�•�=
' ` _-SEAL (C -
�.
.
� .
1���"• •�- I.I.�•I�n1.a"Yr1 47,..1��1I j IY11r1►�./I���1 . �r�I�I.•S.,48•/�rI� I�•MAI�• iI� 1♦1I�I r1Ir'FraT . ►♦1�n� ' • .,;`•��,�.-,.•� �: i i•t� � nu Itti faalInlRAMME �NIMnl �ERTaINNN ;i �tr7: ,nunT= ;:- . \ ► _ 4:1y \ :: ��• r;
N1 � i
L /{ � • \ /p /: \ i /�� \ \�"/�i///' \PY/0r. :'\ \ YG1� ' \\. V//P1:::,� \��i//�i�r�.�
�:.��=.�NV//!/':4:,.; \V,�r/✓,ir1pS/.•y,,;,;\\\ � f/r,1.r1,:i.;,,`A'wO//rgoi::„;' \9V"�,,y;••1p;1 \\ /0.0, :eiti y// r,r,,yrlrl,,l,,.\\ I/r/'yyy0,#.,„� //; ,!1♦•��. \\\\',i �1Hl11e4!//�ir',..We 1k`l-�/Pir'0{ Nleo`AV,G,r,40:•N \ tild//4.#111\,�',/ri/10 4,4 \ �w!:i,.p,*:.qI1,*,. ir,�/i/i11•:,,Ai'V4;:•0 ,/7••��; \ !//10j11:111 \�•'!4l1l0Q1i1ii 11110/1�0V'Igee#/I� �$I1i1 ;i�i:•YisN1t� )• igete10/� �, rd0j1:04.1 IS /�e..j.4011 � �i:/ri
ySgel�� $10 � ii: � ►)* � 4 : : :
BUILDING DEPARTMENT
�..i.•D1,q...--'-�: fvr' ..,.• •.,.;; :.� � ..r L.- '-', `� IV I ^'---I•I'.�,.'.��/.••.Y..:r-4y ri-�% 4iffet -.: ••itl�ir'1_-I• 1
.1. ,,-4 .,•,rJ► I �� r 11 .P94''"r+ ' " r. t \. �!/,.*-.C+ I, Ip '' M' m s ./• r i'h 1-1-h /riuV i1�..,r,•9.I
{� \`\ /. , .�a\uM.,lL.II p :'01� ��/I.`y"47i'l,�V,3� r9.A/�/.;.,,+��, -�'1�=��'`�••i'j�a •�.��. /.. �/.''��rh� \A���r9..r�i/ 'I�n;'¢a 7i�i.; .y�' • ./.
▪ �V.y11. 11 .1/!r.1ly ONO, /. ./LI 1. .� �VIr // ./,/, .G/�. 44� .Q►!d, . './%r!'iV Ve.�+C►S./• .Y•n �.,Irdi/• �i ll,I A. .�♦.i�.t�\i %'/,IrP '�i�y .r lfll/r;�► �i�'`�l� rlrr<I%%I:�w;r
�1, •4t.1e, 'sit'". '��: .hap, 'A: 0 i i .y#P, :0/ . •4�'' I! .!I S!:.• IIIP. 'IN`r aI ,,. 111 -01", d., :, ,,l 4.,1 'la.P:• :,I �., tit''•+,1., ,..I :,
n: r16,•dPI16.,A1 .••• ••• :1�:!1' I •'.. d^• 1��.:.Ip I •'. .r'-• i1�;:.l,Ir III;:::111'r .•pe•A.". i 1� :/Pr/ .•Q... .r:/•. -i i I�::::IiPI .W,.. .��`. ,i 1�:.,�il'r .•�.�. ..:P•. .rlll...y/„
,, � ylr,,!n .�.�...r:qi•, 1 • .rV ..S•O.nr \� . 11!n .-.4..0:�/ ♦, ��lln .•.+.._Q,!r. p,lll.rl•Ilr,r �... /,/. y,lll.p .�,..O :r,. 4.111.Ir ��, .0.,!, 411e/.p• �.•/._0 :rr. n„11,111 a .
11 11/1 .'�.. ./. I II III •\..I r .Ili„1 11 •\..• r.!. 1'.'I111 •�... ,:/. r11.II I,1111Z.1 I,(11 1 •r�i r.! III.1 1,11.111 .\.•1••r O,r.�/. rr.Illr,11.111 •1..IV.r•••,r r.!/• II\.1„111.Ir1 •�... ../ 1. „I r.11 \v
q•� .,. I.Rq: Ie1• e.. .ir ., 1` .I ....Io ..r. ,I A.,••!. .r. ,I .p,. r. —f�a !r. ., rrr .) "vr� C'!r. II�'�, w
r„ �7i,if ,\.
.Ins• �I
��,` "I.I
a
1
• •t
If
MM MM A '�
�
o. �.`ll I Ina.•./• •. A. Im-II 44t
�d• �'. `:I;ts': c.• ,. .e .'tom ram,, a
•V „P d. a.P :: i�'P','C P°P z.__ S P t i t"i,,ri1 4�1 t Aft',aTt_.:, P° P -Jr.,,r,._ ::t P, P"PJ. Ai,'r ,r.;t ,, .
,Pr .ttiP,t, ,JitilltJt"i,i 0 i i,, P; PI h,P i,rP, , P,P, ,PP,.9,t:r I ivP/t,tu,'4,P',P, ,P, P Ul.l; c ',vS
k' 1,f -`,f C'_ -��"/_`✓.-V:i,\Vim:/\�-v�- �:/-�/\i /-✓L/ f�.�v��•. i•"\ ,�• f�l�/_/�-'.�/�./V„u▪ 'v-\/ „, mil..,, •f i
�• v. .;,, --U .� `/" r-�.J`-._. " l` /•�._! '/�- `�- '�'-/'�� �~����./�,„:;. .ice`\�i\�j'`�ff. ''%�Ci.;
''� -„,-,--" S ='� :-.." -\.�• 1 /'u �N /\./'�.r�../ ,.i `t •,1
_ = i-.`-i-\ -i�f`J"v -"-.'!ti��..i1-.'�-�-�l `r_.' / _ y _�` `-'^��S,i'����^�i �N ;�...r`../"�1�i. -▪` +s
p � t_ �l�1�i✓�^i`r�- 1�/\�l�/ -�i�_1�� i Fes•' - C0 ..%'�l ,._,./�-/� �„i l/�-ti'�.��,, r *�:_-_-���.4•
7 s. ..• ✓ - ,,-2-`%'.�`. \ -.✓^/mil ��=..n '. :n / � 0 ::`/ ,./�./i�:_/, ;11- .i'\--f,-, n•i'•,-/Th1,/,. ; •/rr ..,*I
w' 9.. ..ti//_��;�,-... �„„„. /. .`✓ice.%�-_i:��i-_ _; * , A;' -* -`:%- �:„—,, „✓i ✓"\Jv„�N`/ . .r-i. .i ce ..,a•
• �i "•4 1 1 �\i�'%' ,%l,—,_„./-'�� �/ ✓lam -',. _ - `-� f f•`/ 1 �...„ l:i'V`l\ :'..,• r
....,...t„,.:,,.t..t.l-.e..eAzr-
•i�': :.:i - ��-'i-`%'�,✓ ",`���. l / /�✓ �1'./�/ ,_/"./` n/'�/10'
i n_ j�' / �%-�.���. i f~%\`%^./'�i: l- '�`•%,`�'='�f�.i �'l� �iir:_i-'�. �a •=!O•ci'z �� Colorado Department �� ✓�., . .„ c: I
,.....,...,,
-�,,,, .�U-... --- �� ✓� of Public Health -- -:_/-
; . 41
- -`,v.1� �1 and Environment �-s -% '^: .- ...,/ ;
mil`✓- /'�/' /�.1� -'✓`.11.'. .:.Z ._ �• ^l.-� \/ti/ti_/�-i-`...' �/-�
.���/-,�"'�.l- 'ti���\"\-�i'. _� -�_� i� � n �_ � -�_/'� ;-� -. --.....!\ --�/,`/'-,:-_ � - �116 .eve`•
r v _'\�i�- ram. { rr.
� i = ti- » =- ASBESTOS CONSULTING FILM
�,.�: .��,`�.� This certifies that � �� :s -
� • +� • 1 �� rtii. "- �• -ti��� V �
, am HealthSafe Inspections Inc • tea
sr , -
,
f. ......._ ..,.... ati • ••••• •• •iv,,,,..:,,,,,...... t:„.: � � _, Registration No.: ACC 18234 ,�%ar:stz._....:J.2s.:,, ,-E- T,..... �
(11 g.i.S-4:SM ,F.:'
has met the registration requirements of 25-7-507, C.R.S. and the Air Quality Control •t st
om =i
�f Commission Regulation No. 8, Part B, and is hereby authorized to perform asbestos consulting a.
• !r ;
r ;w^ activities as required under Regulation No 8, Part B, in the state of Colorado i• ` ' `r,
t# c ��_�•
c• / ✓�. xppp �- ._--��� r.i•ter iv• y i��� �—
• !�\� /•• -" 11 u.- -'- -\/ .l. ..'_'`./"'.� ."v •.lam✓�.-:- •- N ▪ .
I ▪ TgeA pi . Issued: May 12, 2022 31 12�23 ��� , ::� �. ; • ;:f;3':::::75
.
• '�, 4. r. Expires: May 14, 2023 p3I j
if:Lel3.
/ w ��� ��� uthorized ArCL1 Representative ; ' .`� 1
cleaCA
'YA` SEAL ��
/,.` I c,: .4 rx nt. S_ .t. ,4 ,,4` 4''4 S"'d'.d d'4, ................. 4Aab' d.,:.4A'..'M' �<.4..4., t,t d,S,4tAd',t'4'. t' !-44 f'.-t':'a , 4 'i. i ''' 4 S 1 d` fi-ii_6.Rfl-(_t.+;l-r ':'�`•-c.
��� ., ,• d`4 E 47 4 t S n3�s 4 d 4 E4G ;!, 4 �.J .t. �S„z ,k.. 'i;,"r3 i .. "$ , w.0
y: !•+r. y T .T I.It A T I ' J, :'I' •i, )"14..., DT a `any 0.,.� vN r s �.'
''fit • "' , L At ''\ �. 4• Vy R
t:a
...................................I I\rlr t%y�•
/" l
�• r r.J►i• �, I111 I'l r �. •.... . ii.".•r r1 JI r .d 1. .•i err I \ .d"1. 1•'•••••••!''�•.r.':',:n:o'L.�. IPI,I r,.� rp(11 b p.'.%:::; ':A / a IU
ri11'e""PYII, .r. .. Ire r!�.. .�..s.:.7Rr.... re 1;1' ...R-� r�,l.l•• i•.tf';?��,:,, .PIi4'i'rrel I.dd�IP,I^ •+i�%`C'`:'•'•.•• ✓e16,1 .,•.. .. n ,r I.4". •./ -:4• I IJJA.A •dv• ::v o - '`}r''��
r<<��/, :';1�A .I�.��y.•�. I/p%y;1�1r ....4
r.,I�p. Irl/ Il,yo .�;��%• '/:ryi' 1., .�N�y.. .i0t:•:'li i11,:.,1�, .,G♦ •�.• '�' 1,. .y c�. j::j I 1i.. •:v •�. ;,.I, Ill...yp 1.; ..rQ.�. �I,1' �! f /
\.. ;111.11,1., . 'l,.4000,.:$ .4� !.'d040. r" — II +. /I,: 049: . dllp4':40, 00,4,00.$1� , ,,� A i� , cf 1 �.r1 t Iddl.l..1r S,. r..• ,.t:w,:
jj��.,l j�:., rur .•1�r9�\r O.�E%'` .a." \Q\! i . 4.• ,t \�.�. .j- a fir .F�;�r!,.I.-.�..I Ir, u ./ .\ab,H �., ?r J,%I,, ,. .yrrF.••+. iI•'` ��. .,,��ZiZ: .. I r%rA/ '1\..ab'.=-.'�Pr�EE/, 'N�,.�'.
�. A•E. ,11.r1\. 2^.ai v,..,.>_a4 1.•g'•\1I,r.r.1•1%. \ i•11• ^- .toto/ •'.1 .0.. 40: /r1.___ !•`. �.� P4v .)ri E. k4gitt. 6' •p i b' l 'SIL?'—;,�. °':;i'1.AI rr 1�IZ.s i
/�'I'Irr'lil • •►%�• •;:(,e .:/�' rI \ .n':+ .O r r r•,��•L.�Ii• ':�I/Dlrr: ..r�11�•.' ,.':��r1iw1♦ �►.IIb� .. '�r•Ir/ry7��C11'�.•..1 ":. i%/./r /9�i:�1� :.dVim- .4 04,4• I_i ./•n y� Wit,
2di•; .03.7•.,g,0.- .�;:::.\r.1••+ J''x��.;: ,;.�kI`I+•,•l..►1.1/ �.� •4/••+.%.4.. •.It•..► ••..4 ..• ,.�__..�� 4.•,.. fir_•-.��.. 44+1,.•pk�. f�'�•\441�•...��►�i�/ ';.�` 441.�!.-,1 xr� �J
BUILDING DEPAR i MEN 1