HomeMy WebLinkAboutFile Documents.555 E Durant Ave.0025-2022-BRES (19) 0025-2022-BRES_555 E DURANT AVE 4A_BuildingCommentl
90. Architectural Plans.20220216.pdf(7)
Subject: PlanCheck DWELLING SEPERATION WALL NEEDS TO BE
Page Label: 9
Author: linzhid DEFINED.
Color: I PROVIDE WALL TAG and STC.
File Name: 90. Architectural Plans.20220216.pdf This is W-2(sheet A-501)and has an STC of 52.A wall tag has been added in plan
(sheet A-101)and the cut sheet showing the STC has been added to A-504.
Subject: PlanCheck
Page Label: 9 SPECIFY SETUP OF MECHANICAL EQUIPMENT
Author: linzhid (HEATING & HOT WATER, ETC)
Color: •
File Name: 90. Architectural Plans.20220216.pdf This set up has been added and is shown on A-101.
Subject: PlanCheck
Page Label: 9 NOTATE WHERE ELECTRICAL PANEL IS
Author: linzhid LOCATED
Color: •
File Name: 90. Architectural Plans.20220216.pdf The electrical panel has been added and is shown on A-101.
Subject: PlanCheck PROVIDE DOCUMENTATION FOR SOUND
Page Label: 12
Author: linzhid RATING
Color: ■ This documentation has been added to A-504.
■ File Name: 90. Architectural Plans.20220216.pdf
Subject: PlanCheck
Page Label: 12 F-1 NEEDS TO REFERENCE THE CORRECT GA
`�'"a Author: linzhid FILE, GA 5406 DOES NOT MATCH
Color: • F-1 and R-1 have been corrected (A-501)and replaced with:
`-I..,. File Name: 90. Architectural Plans.20220216.pdf C-1 is the GA File 5406.
F-1 is now the existing floor assembly with a sound isolation mat.
--^---'----- Subject: PlanCheck PLEASE ALSO PROVIDE A FLOOR ASSEMBLY
Page Label: 14
°pro Author: linzhid SOUND ISOLATION MAT
Color: ■
The sound isolation mat for the floor assembly has been added to
____ . _ File Name: 90. Architectural Plans.20220216.pdf A-503.
Subject: PlanCheck IF USING DIMENSIONAL LUMBER, THIS
arPage Label: 14 ASSEMBLY WILL NOT WORK SINCE IT DOES
�`'_ Author: linzhid NOT HAVE STC 50
Color: ■
File Name: 90. Architectural Plans.20220216.pdf DEFINE IF USING ESR 1153 OR FIND NEW
ASSEMBLY FOR DIMENSIONAL
ESR 1153 has been removed(A-503).
We are using dimensional lumber so GA File 5406 is the correct
assembly;C-1 has been updated to show dimensional lumber(A-501);
4A is the top floor unit and has nothing above so does not need to
comply with STC rating.