HomeMy WebLinkAboutFile Documents.341 Park Ave.0072-2022-BRES (10) HealthSa f e
INSPECTIONS
HealthSafe Inspections Inc
390 Apple Drive
Basalt CO 81621
970-920-2100
Jim Baker CDPHE Asbestos Building Inspector#13437
Ben Baker CDPHE Asbestos Building Inspector#25863
ASBESTOS REPORT
DATE
05/01/2022
CLIENT
Near
c/o Giant Construction
PROPERTY ADDRESS of INSPECTION
341 Park Avenue,Aspen, Colorado 81611
•
RECEIVED
06/08/2022
1 rowel)
1/2022 J
` ` """ ASPEN
mp
BUILDING DEPARTMENT
CLIENT BACKGROUND & PLANS
The Client,Near, is planning a renovation-remodel-demolition of drywall materials to
expand a window/doorway opening and create a new opening for a small window near
the front door, which will have impacts of disturbance, detachment, deconstruction,
demolition, and disposal(5D) of drywall building materials, of which some are suspect
asbestos containing materials (ACM). Prior to 5D, Near is required to have an asbestos
inspection by a State of Colorado CDPHE certified asbestos inspector who will collect
bulk samples of the suspect ACM and have those samples analyzed at a certified
laboratory for asbestos content. Near hired HealthSafe Inspections, Inc. (hereinafter,
HealthSafe) to perform via Judd Clarence at Giant Construction for a limited asbestos
inspection for these areas slated for 5D impacts.
VISUAL INSPECTION & LABORATORY FINDINGS
An inspection was conducted by Ben Baker of HealthSafe on Thursday,April 19, 2022,
with Judd Clarence present during the initial survey, inspection and sample collecting.All
suspect ACM were identified by homogenous materials and sampled randomly respective
to the scope of those materials slated for 5D. The suspect ACM collected and analyzed by
EPA 600 Method PLM analysis are the following:
1. Skip Trowel Surfacing Texture, a homogeneous trowel-applied surfacing
material/texture [samples 1-3: ST 1,2,3], collected randomly from the entry east
wall under the junction box cover place, living room SE corner, and living room
SW corner, respectively, using the AHERA random sampling grid#14. This
surfacing material/texture is on the ceilings and walls of the house main floor. The
estimated impact area of 5D is more than 10 sf,but less than 1,000 sf(±75 sf),
requiring a minimum of at least three surfacing/texture material samples. The
PLM analytical estimated results: NONE DETECTED.
2. Drywall System Joint Compound: a homogeneous miscellaneous seam taping
compound requiring at least two samples [samples 4-5: JC-1,2], collected from
the living room SE corner and SW corner, respectively. This material is applied to
the house main-floor drywall system. The PLM analytical estimated results:
NONE DETECTED.
3. Drywall System, a homogeneous taped and joint compounded drywall system
(classified as a miscellaneous material as a complete integral system) [samples 6-
7: J-1,2], collected from the living room SE corner and SW corner, respectively.
These composite layered taped and joint compounded drywall materials are on the
ceilings and walls of the house main floor with a skip trowel applied surfacing
material/texture. The estimated impact area of 5D is more than 10 sf, but less than
1,000 sf(±75 sf), requiring a minimum of at least two composite core samples of
all layers. The PLM analytical estimated results: NONE DETECTED.
A total of 7 suspect homogeneous ACM bulk samples were collected, and 7 samples were
analyzed. The bulk samples were analyzed by EPA 600 PLM analytical methods by a
RECEIVED
keven5 06/08/2022
2 10/21/2022 J
FORCCMCOACIANCE ASPEN
BUILDING DEPARTMENT
NVLAP accredited laboratory in accordance with Colorado State Regulation 8 for the
presence of asbestos mineral fibers. There is NO asbestos in all 7 samples.
See supporting Hayes Microbial Consulting, Inc. data report#22014578_1.
HEALTHSAFE CONCLUSIONS
• There is NO asbestos in any of the suspect building materials slated for 5D.NO
asbestos abatement will be required for any of the building materials.All building
waste and debris can be disposed of in any landfill which accepts normal, non-
hazardous building waste.
Sincerely Submitted,
Ben Baker
3a 3ai.
,,
, 111
Ja
RECEIVED
rf� 06/08/2022
3 21/2022 J
` co°"comewra ASPEN
mp
BUILDING DEPARTMENT
k
' __ r A
, „.,...
.........- WI 1
_______
,_______ _
, 1 r 7_,.r. -,- .
1
”74 H Y 2 � ,I_ _ . _
p4yr rib! I
t"Il i4
-#
At
COLORADO & FEDERAL ASBESTOS REGULATIONS SUMMARY
Regulation No. 8 Part B—Asbestos of the Colorado Department of Public Health and
Environment(CDPHE),Air Quality Control Commission requires a State-certified
Asbestos Building Inspector to inspect and collect bulk samples of all suspect asbestos
containing materials (ACM) or suspect asbestos containing building materials (ACBM)
prior to their disturbance, removal or demolition and disposal. The suspect materials shall
be analyzed by a NVLAP accredited laboratory by polarized light microscopy(PLM)
using EPA 600 analytical method.A material which is estimated to contain more than 1%
asbestos is classified as ACM/ACBM and regulated by the State and Federal
governments.Any friable (able to crush or reduce to powder by finger pressure) asbestos
with trace amounts of asbestos fibers or less than 1%must be point-counted using EPA
400 analytical method to prove that it is indeed less than 1%; if not, it must be classified
as ACM/ACBM and shall be treated as a State and Federal regulated material.Any
friable asbestos containing material (greater than 1% asbestos concentration) or
ACM/ACBM that could be rendered friable during its removal or demolition and disposal
shall require an asbestos abatement by a certified asbestos abatement contractor to
remove and dispose of the material(s).
RECEIVED
rlf� 06/08/2022
4 10/21/2022 J
` c°"w ASPEN
mp
BUILDING DEPARTMENT
A Colorado State (CDPHE) issued asbestos abatement permit is required for the
following trigger levels of ACM/ACBM:
1. Residential buildings of four or fewer units--if more than 32 square feet of any
surface coverage (e.g., gypsum wallboard or drywall and associated applied surfacing
materials/textures, acoustic sprays,joint compounds,plaster, etc.), 50 feet of asbestos
covered or asbestos insulated pipe or any material which would fill a 55-gallon drum is
going to be disturbed, removed or disposed of, an asbestos abatement permit is required.
2. Residential complexes with more than four residential units, public access areas to a
residential building, commercial and retail buildings, public and civic buildings,
industrial buildings--if more than 160 square feet of surfacing materials, 260 linear feet
or more than 35 cubic feet(NESHAP) or 55-gallon drum(CDPHE) of suspect
ACM/ACBM is going to be disturbed, removed or disposed of, an asbestos abatement
permit is required under NESHAP and by the CDPHE. See note below on OSHA.
The regulations require an absolute minimum of 3 samples (EPA suggests 9)per
homogenous suspect surfacing and TSI materials and an absolute minimum of 2 samples
of homogenous miscellaneous materials or any number of"samples sufficient to
determine whether a material is ACM" (Reg8.IV.D.3). More samples are required based
on surface area or volume. These are minimums; the asbestos building inspector has the
field responsibility to determine homogenous materials and the number of samples to
collect per material; more than the minimum number of samples may be necessary at the
discretion of the inspector.An assessment of friability and functional space conditions of
the materials are also the inspector's field responsibilities.
OSHA compliance is required for all employers and employees no matter the
quantity of asbestos present with strict regulations regarding 10 sf or more of TSI or
friable surfacing materials, and therefore it does not matter what the quantity or
State trigger levels are: all suspect ACM/ACBM shall be inspected and tested for
asbestos prior to their disturbance, removal and disposal for worker protection and
safety. See EPA 40 CFR 763.121 Worker Protection Rule, OSHA 29 CFR 1910.134
Respirator Protection Standard, OSHA 29 CFR 1910.1001 General Industry Standard and
OSHA 29 CFR 1926.1101 Construction Standard regulations when dealing with asbestos
hazards.
Note: County or City regulations may be more stringent.
RECEIVED
ere 06/08/2022
5 10/21/2022 J
FORCOOtGOACJANCE
ASPENjimp
BUILDING DEPARTMENT
a% HAYES
MICROBIAL CONSULTING #22014578
Analysis Report prepared for We would like to thank you for trusting Hayes Microbial for your analytical needs!
We received 7 samples by FedEx in good condition for this project on April 20th,2022.
HealthSafe
The results in this analysis pertain only to this job, collected on the stated date, and should not be used
Inspections in the interpretation of any other job. This report may not be duplicated, except in full,without the written
consent of Hayes Microbial Consulting, LLC..
390 Apple Drive This laboratory bears no responsibility for sample collection activities, analytical method limitations,or
Basalt, CO 81621
your use of the test results. Interpretation and use of test results are your responsibility. Any reference to
Phone: (970) 920-2100 health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial. In no event, shall
Hayes Microbial or any of its employees be liable for lost profits or any special, incidental or
consequential damages arising out of the use of these test results.
Near
341 Park Ave 44( nAspen, CO 81611 *„..6&_,...
Collected: April 19, 2022 Steve Hayes,BSMT(ASCP)
Received: April 20, 2022 Laboratory Director
Reported: April 27, 2022 Hayes Microbial Consulting,LLC.
ciED ST,4
�07 /AL�o,4,,001
w
1 tia
, 1 ,
DPH
� \+T CnnuDpme
4C pROjE Health
Pubhc RECEIVED
EPA Laboratory ID: VA01419 Lab ID: #188863 DPH License: #PH-0198
06/08/2022
Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com Page: 1 of 3
ASPEN
BUILDING DEPARTMENT
Ben Baker #22014578
HealthSafe Inspections Near
390 Apple Drive 341 Park Ave
Basalt,CO 81621 Aspen,co 81611 Asbestos PLM Bulk
(970) 920-2100 EPA 600/R-93,M-4/82-020
# Sample Material Description Non-Asbestos Fibers Asbestos Fibers
1 ST-1 Brittle/Cream None Detected
2 ST-2 Brittle/Cream None Detected
3 ST-3 Brittle/Cream None Detected
4 JC-1 Joint Compound-like/Cream None Detected
5 JC-2 Joint Compound-like/Cream None Detected
6 J-1 Drywall/White/Brown 5%Cellulose Fibers None Detected
Joint Compound-like/Cream None Detected
Joint Compound/Drywall/Cream/Brown 5%Cellulose Fibers None Detected
Lab Note:Composite of Drywall&Joint Compound.
7 J-2 Drywall/White/Brown 5%Cellulose Fibers None Detected
Joint Compound-like/Cream None Detected
Joint Compound/Drywall/Cream/Brown 5%Cellulose Fibers None Detected
Lab Note:Composite of Drywall&Joint Compound.
Collected:Apr 19,2022 Received:Apr 20,2022 Reported:Apr 27,2022 RECEIVE 1J
(IIID H A V E S Project Analyst: Date: Reviewed By 66/O 8/2 0 2 2
MICROBIAL CONSULTING Darien Williams, jam,, k Q `�%'"43 04- 27 -2022 Samuel Settle, It � __ t 04-27-2022
3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com BUILDING V 2 of 33T
Ben Baker #22014578
HealthSafe Inspections Near
390 Apple Drive 341 Park Ave
BBasalt,CO 81621 Aspen,CO 81611
Basal Asbestos Analysis Information
920-2100
Analysis Details All samples were received in acceptable condition unless otherwise noted on the report.This report must not be used by the client to claim product certification,
approval,or endorsement by AIHA,NIST,NVLAP,NY ELAP,or any agency.The results relate only to the items tested. Hayes Microbial Consulting reserves the right to
dispose of all samples after a period of 60 days in compliance with state and federal guidelines.
PLM Analysis All Polarized Light Microscopy(PLM) results include an inherent uncertainty of measurement associated with estimating percentages by PLM.
Materials with interfering matrix,low asbestos content,or small fiber size may require additional analysis via TEM Analysis.
TEM Analysis Analysis by TEM is capable of providing positive identification of asbestos type(s) and semi-quantitation of asbestos content.
Definitions 'None Detected'-Below the detected reporting limit of 1%unless point counting is performed,then the detected reporting limit is .25%.
New York ELAP Per NY ELAP198.6(NOB),TEM is the only reliable method to declare an NOB material as Non-Asbestos Containing.
Any NY ELAP samples that are subcontracted to another laboratory will display the name and ELAP Lab Identification number in the report page heading of those
samples.The original report provided to Hayes Microbial Consulting is available upon request.
RECEIVED
H AY E S 06/08/2022
MICROBIAL CONSULTING 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com ASPpUI 3 of 3
BUILDING DEPARTMENT
H AY E S Hea6thSafe inspections SHIP: FEDEX - ENV PO ASBESTOS
Q390 Apple Drive
N DATE: 04-20-2022
MICROBIAL CONSULTING basalt, CO 81621 8136 1033 6123
11111111111111111 IIIIII111111IIIIIIIIIII 22014578
Job Number: Job Name: !Meaty
Collector: 8a1 a Mobile 970-920 2100 Email: heJu c...cueii ispections@gmail
I _ - --- E'dl �ct�i�r 3 Li 1 Pollk illit
Date Collected: 0 t- , fa-)- s CO Fi6/l_ Note:Cc h4",/.b11 er../71Yv)f•.:v1.cc -._-_-_—_—_-
Analysis Type Analysis Methods Turnaround Times
PLM 1Bulk EPA 600 3 Hour 1 Same Day 1 Day 2 Day 3 Day 5 Day—
Point Count 400 Point,1000 Point 3 Hour I Same Day 1 Day 2 Day 3 Day 5 Day
Vermiculite CARB 435 3 Hour Same Day 1 Day T 2 Day 3 Day 5 Day
TEM Air EPA AHERA,NIOSH 7402 - Same Day 1 Day 2 Day 3 Day 5 Day
Bulk Chatfield - Same Day 1 Day 2 Day 3 Day 5 Day
Wipe ASTM D6480-05 - Same Day I 1 Day 2 Day 3 Day 5 Day
Microvac ASTM D5755-09 - Same Day 1 Day 2 Day 3 Day 5 Day
PCM Air NIOSH 7400 - Same Day 1 Day 2 Day 3 Day 5 Day
# Group Number Sample Name Analysis Type Turnaround Volume/Area Stop (+)
1 ST_/ Pc_Ai 5 IJaL
2 _ - - -- -CT-a ________) — -
3 sT-3
4 Je -►
5 Jc 3_ I .
6 T- i
7 J-)_ %/
8
9
10
11
12 .
13
14
15 •
16 RECEIVED
17
Released by: j _ Date: 0,1 A 9 720- Received By: 'S1Y�(_ kitig Datt14022
Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com Form'##2'00,Rev.3,March 23,2019
A SieZ I1 Custody
BUILDING DEPARTMENT
�"�1��r. 1 f" k�'�� '._' �I�h�Y� � ( Y,7 �2�2.1{a�; ''� )k�� ?b �,1� ��
< �o r" `%r q I".rj441,' .'r{( {� �; r it ,' . 7
(D)f+z �16 .)l' r �I;r�{i �� ��C ei. � ) ��t.�'i'p, .•v� � f Sr I r,'d,N"'"1�. ,A��i�'t•�'n r )i.(f °" ;7,�� e`�4F� �1.,7 SU
/ p•r�,,i. o o rt,., e v st i,f .7e",0..,s.. } ..,o k. {t i la.n,,i, {s V. { v. s 1 till ��i 7..V.. -
' ' }ep�''1,'!. I .Ere :iet'n.t•i' 7Y t l' }4. •• 7 , :L,+h .. .,t
rt. 1 = 3rr ,• M art' ,......7� r.4 s 4) " , ' x i V���, t .a � . e q.,t, _ , L ,05 > .L ._ . J. .L e a. 014, 1.. _ L VR'IIt+2°
-
1 ,l ,1,1 1,,,7,,,,t,v,;.v,t,,,,, ,t,t,,,I,I,f,r,i(,,t I,;t,t r,t,1,t,l,t,,,,P',Co, ,,, V.,1,1,0,1 V,it„ ;,,i,1:1,l,,,l,l,1 ,t,r,1,1,1,t;,,S., ,0 r{,,,,,1,1 O,I;,1,4 t I t,{ ,r,,t;l,l,V,l,t"I,,,t,l; ,t,t,t,t° )
-,$s �� 0040 c�
, \ z‘!....,:„-it-szta.z...1.:,
vi�.� 4ry+� p t ,(— R L
EiD. e , ,,J876 &"� G
,,, ' r1 Colorado Department .`N., ,
z of Public Health , le_ ` and Environment =S`���:��♦ I
'D;... : ASBESTOS CONSULTING FIRM .. itil''' '
4
ti. � This certifies that F
r.
HealthSafe Inspections, Inc. =, . �,
01, � e � ark)
" Registration No. AC 18234 .4,1
IN R. y r
j% �fi has met the registration requirements of 25-7-507, C.R.S. and the Air Quality Control :i-7
\S% j.j. Commission Regulation No.8,Part B,and is hereby authorized to perform asbestos consulting
�,. As; activities as required under Regulation No 8, Part B, in the state of Colorado. . ° s
_ Issued: April 12,2021 F
r Expires: May 14,2022 jui___ r S
C;
) t t,t t t SAKE'L:y,t"'I'I I l l .{l'IA 74.,7 7'11 1't, tf I I ;t"' ir1'1 I7,t 1 0 I t/t I,:rtAt -I?I p: t.{1 IT!I'.I`t'1 t t S",t't'i! l I tI 6'.IA till'! I t t t',I'I t(P •A.t l t u i t - I
i-. y,� -�1 �/
— .a xJT `xi! TI •"r , T ,^ 0T. %,,,,
. • T , W11 L 'I i _
—r I 1 1 1 1 11 I I
= ,(fry ( i,', Y p { i [ - > % i -i i. yy ^%°5',
. t�% �1.d, l,1i'A?i,.°Yy ;4 i1Ylttl t�l''111 • 41, Y. ni'f',A;� Y.:Y!� 14s 1.6 .i-..,-Ap r.k.,'tli3O,}S�'i.,:i 11ii .%.%�_,. „t 1 � )
7 'rrrlyi �'• '.l rl� R A it6 N. ..�:,,•S,t,t✓lv A.:...• y>'I th r ! si - 'SrciiOr �i N I 7 IN �'
r,r/I r..r '. 5':i 4 t ,,i5. i,#' 01,6 k_. �l1, cl',t)3 'Sr5 ��' —di rosoiAtt e• ,' N.N. r-,b..!liti � :. 'gd k t '4?1 14X�C t, 'Izo e•� I. r W i 1 0kM,7Vq,' -Jt f di -- 0.' ,1 ...r �.Ds.. .1
BUILDING DEPARTMENT
i Ii1i1�..� ♦..•1�1/KOT, V ♦�1•1//44 *Y 41§;;1 y P .•i11;;;Vo i i.,p 1 �� i i�.�0 �: i i;.�1 i i i;;$1 : �i 4;:;:
••i�f�lj/jl�ijif:. ��11f1f/////�►i�i �'�1\/If/f1//1/.i�i• .��\►off///►/1►�r�r'. �����1�//1/111driv.���Iff//1/1/�/i���.\�Ilf►/1/►1�/�.i v�1��f�/1//1/i�ri;��\�//��1//►1��•��\►�1f////►+��.'
•:•:1:•4'4,t3llrri..�.�\\11611►►:.,..;,;);.,BLit I/k,••jjdpi,._•440:441►►QOi1%. Agit it4,40I�dIPi,,:�\111 g,41lllrn.�q\�1;1144,...I 1;;;,,�\\\I�INI►0I/0,;;;;i.,..4, 11/►►►►0I;;ii.:`\\\11j1►\4::
':::•zii/lif;e/jn J�\1111�/j6111,/jnJ�11111111.rj/d�♦,�.ir\J\\111!1I/N.,11 i�'/�nJ\\1111111111♦,/il��/,', -�,A 111/1♦�♦�tiKi�J\\11111,r♦j/ll,i�,/An Vs,,;1111♦♦/,111��/,//nJ\\111?11i♦l/j11,,11;"; n\J\\111..�*.•s
yo••.��i,�.//J^\\�`.111�•IlilDlil�'..irr^\l •`!Il�liil♦O�A',r�j�\\���Id�l♦111,�',''�rr�\\0�11!111/1♦lll,lili r�^\\,�.��11j11�1/l/lf�ii.r�ll a�l!llili/li'1,,irr^\ �11i♦♦II♦ii'�.J^\\ �)•�liill��;l'ylrr\\�:_���.
ii/..IrJ{/\\\\\,;�,i�y.♦.;.,y IrrrA\\\\,..�,�:♦.S'r,rrrrh`\\\.,��, ♦ �rrr^\\\ ,,b,S':;� rr I\\\ ,,r rr�\\ r�\\\ ,�,,�♦I,,�•� rrr�\\� I�� .., r h\
,i/i,'/•r .1 M:#4,;•IiPi�\�\\',' Ir 11 \\\ .:::r,I;;;1 ^1\\\�:•:#;.,,,,�Jrr0W.'s;.0°;;iiia.�.\\ `t 1,,:;,„'Iiii0M�\\,'1::.:;. fir 4141,111 t:yiiiri4t=��:•
—i�i�Z::,!�',:�N\ ':',S'::r•/iJrr�;_;�\1 '¢;'/irfri.:,.�\\1 •r/rJ✓ ; �\\\ rr/irrri��N\ ;./irf✓��N r:/rrrr�;�\�\ •�/rJir,;��N\ ',hrp, �����-•
�- l
�..
l
�% r,;til
y r
_____ " y:;Hill 1f Il1((Ulli�'J!' I'ikl�tUii iii N:t'II"tt1J111t1�1 1..u..
lJf 9 ' Ui 'U11U1!"14UItl'Jlltul IU1NtliJI't' N IttJ1t` rr(�tt'
�.�..,__—��'•:..: 'V Z j , Y .. S H y.'1 V./ Y, S ',,, I��,�V . Y V ...„ V U Y V iH� V
�. _��—"\ •; V.VI YV V♦V♦V. ♦VY ......♦ ♦ i V.I♦1./1 ♦ ♦•'LY VIZ4♦V.V♦VI'Ci ♦ ♦VI Y ♦V.V. ♦V1V /,���..,
•.:-_ _ v ♦vv ......11v'wv _ v� �i'•�I' ..rvvv ry wt'' v vv �.�
-',ice%i� •�)) /)
*Ifigfik.i.iii
.•
. 040
•ems••.== /} �, :_ %+
Vall
�'i� Al; !'`' �� �, * -AA pot * �i�L�
Colorado Department cc'`` ..•
►.• -- tip '
' of Public Health -
%tit-.• and Environment t _=
...
:= _`= - '' ASBESTOS „ .
:.
-�r,1,ZO�' CERTIFICATION*
This certifies that
rz,%. '' � ,..
=s' ' Benjamin L Baker c<c' ,+.•1
:. - )) c� -
="" o Certification No.: 25863 t" `•r� =
(ic'': --a:
�•'. '•` has met the requirements of 25-7-507, C.R.S. and Air Quality Control
___ , Commission Regulation No. 8, Part B, and is hereby certified by the t( ..
, -=
�� state of Colorado in the following discipline: tic_ ,,;� •
>> Building Inspector* ea; = •
;
c-r.t:s;:i:::::,-." >> 4 ::
is r:....
4W Issued: August 19 2021 "
':'==,== :'• . Expires: September 25, 2022 $
h tCC :;:sue fss,
'.b 1'lv:== i• o�_11 ��..
(( „��V
"I%,`'" *This certificate is valid onlywith the possession ofa 1`_'•:�
�,�.,L' ) current Division-approved training coarse certification ,���%i�,..,
•���•<.,. 7)) in the discipline specified above. %•.
_- Authorized I Representative (i Aie.-;y:4
4r y - ...r.♦n♦,./P n.�.n ♦�... �.i.♦�.�n•.r�•..na ...,ANC"... n �r, ♦ ♦....�.. ♦n♦i:.�r., ^,'^I - h:��������%
<,, ,ICIOSIIInit tl(sill' :t•�'fi�115111151 f It�a RII IAN(�I11tRIRiI IINIfaltl �',i 1,111t 1IA101 1M01,tf'(it•F,. 111? Inntl'ix ,
..�\���•\•�=='i{r .�,,N�►"jrr {,�Nh` j/r CNN..i/r .�;t,,.,;;1\i\i-` {�,.•,.\N��:: i/�s N\\�:_. I �,y:'r;.,N\I....:�{rl,;,.:;•„•.1+,\,
����.�Y\�rrl�/, �t''•' ,�,�\�rr/// ,,.,;r,.♦.�.\r�✓JrI// „�`,�I\�Irr//(:r:ti���'rII/(.::..p.„��.\\�/�///, ; 2•,•h �IIL/,,'S'':.�•;���.��\�,'�rrD,/, n•...•:�.�\11\Vii''%:i•
. ..��VII{{;l,t'i�l♦i♦y111; 0;,,"1:.INit,,,.1101 ;,,,,, 'iW�,�i�\ 11%;J,':.Ilyl� \.1V//{�ii�'.:::47i �a��yfle,,,, i,% //;':•0,".iit;n14411.► itii ,�:11, / ,_-�16t
y���J1Iq.:�\�/1{ %�t11j1�1,111i:4�\\Iirrllll��rll♦111I,:.�\V�J•,Ill♦�N�1'q',�,��.//{ ylill/ll��//♦1I,i.�\V/{%%�/1j�//1�/11�`y.�`�//!j.I/ll���l '1�1,�\�/l�:/II♦j11Nj1 ;,���/{r ,II .�♦ili i����/I{ l'� i�
;..•i�►►�ii'k '////1jIH�l�►111111+���%i{/lllllr��►.11111►1+� ,%,"llh►I►,111,V-1?;1;1;i'0,4 ;1101(, /I/t111��►►11111,1\�� �;/�l�lll�ll'I i1,1\✓Gr�/40',�11/H�I1�+� Y:.yi/ /ln►r•:y+c�c: •,i//�, (f.il•
•'•�10:t►tt' .��i$�1111�1►11��::::' .��I��11111,111�1)�::` .i�/�•I/i/1►�11i'0 ♦�i'e•///1/111' „ 11:0/►/►1 dp." .�///ll{►.1► 1 t�=�?_•.ti`S/I/N.1410:. `;N Illicit t. /I ti .
•i�11/1/1/0.' •1d11/N/:- .�111/11/1i• A111111111:- A�1/111111- .d'111:,.. -p• J.11t4.0� : a-........�1>" �1�....to.-
1/11.to.-�. ������4._..��...'
.�.�:• � ��1�• :}� .�.�.1� � 1�.��. � t:1�:♦ � ��1�11 :� ��1�� 14�iIi.:• j� �.1:� I'+�l !.1:
ASPS
nEviiiremliLDING DEPARTMENT