HomeMy WebLinkAboutFile Documents.300 S Spring St.0054-2021-BCHO0054-2021-BCHO_300 S Spring 200_BuildingComment1
Subject: PlanCheck
Page: [2] 20067-e-e2.0
Author: justinh
Color:
File Name: 90.300 Spring.CO1 Sheets.20210816.pdf
If you use the space by space
lighting power allowances you
need to break the office up into
the relevant spaces (office,
restroom, etc.), otherwise you
should be using the building
area method which has offices at
.82 W/sq.ft.
I only measure 780 sq.ft. of
interior office space per the
drawings.
90.300 Spring.CO1 Sheets.20210816.pdf (6)
Subject: PlanCheck
Page: [2] 20067-e-e2.0
Author: justinh
Color:
File Name: 90.300 Spring.CO1 Sheets.20210816.pdf
The open/common office space
is required to be provided with
either a time switch control
switch or occupancy sensor per
IECC 405.2.2. Note how you will
be providing compliant controls
for the main space.
Subject: PlanCheck
Page: [2] 20067-e-e2.0
Author: justinh
Color:
File Name: 90.300 Spring.CO1 Sheets.20210816.pdf
Use the driver/transformer
wattage for your strip light as
required by IECC C405.4.1
Subject: PlanCheck
Page: 1
Author: justinh
Color:
File Name: 90.300 Spring.CO1 Sheets.20210816.pdf
I only measure 780 sq.ft. of
interior gross area, which would
be 8 occupants. Revise the
occupant load calculation.
Subject: PlanCheck
Page: 1
Author: justinh
Color:
File Name: 90.300 Spring.CO1 Sheets.20210816.pdf
2020 NEC is our currently
adopted electrical code, please
revise.
OFFICE201CARPET
(E)
(E)
A
A
A
A
D V
If you use the space by space
lighting power allowances you
need to break the office up
into the relevant spaces
(office, restroom, etc.),
otherwise you should be
using the building area
method which has offices at
.82 W/sq.ft.
I only measure 780 sq.ft. of
interior office space per the
drawings.
OFFICE
201
CARPET
A
A
A
A
The open/common office space is required to be
provided with either a time switch control switch or
occupancy sensor per IECC 405.2.2. Note how you will
be providing compliant controls for the main space.
A
A
A
A
Use the
driver/transformer
wattage for your strip
light as required by
IECC C405.4.1
CODE JURISDICTION:
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL PLUMBING CODE
2015 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL FUEL GAS CODE
2015 INTERNATIONAL FIRE CODE
2017 NATIONAL ELECTRIC CODE
OCCUPANCY (EXISTING TO REMAIN):
BUSINESS (B) = 838 SF
OCCUPANT LOAD:
BUSINESS = 100 GROSS
838 SF / 100 = 9 OCCUPANTS
CONSTRUCTION TYPE (EXISTING):
CONSTRUCTION TYPE V-B
FIRE RESISTANCE RATING REQUIREMENTS:
CONSTRUCTION TYPE V-B
STRUCTURAL FRAME: NR
BEARING WALLS, EXTERIOR: NR
BEARING WALLS, INTERIOR: NR
NON-BEARING WALLS, EXTERIOR: NR
NON-BEARING WALLS, INTERIOR: NR
FLOOR CONSTRUCTION: NR
ROOF CONSTRUCTION: NR
BUILDING CODE ANALYS
BUILDING HEIGHT AND AREA :
EXISTING TO REMAIN
EXIT ACCESS TRAVEL DISTANCE:
GROUP B OCCUPANCY: 300' MAX (21'-6" PROVIDED
DEAD END CORRIDOR:
I only measure 780
sq.ft. of interior gross
area, which would be
8 occupants. Revise
the occupant load
calculation.
CODE JURISDICTION:
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL PLUMBING CODE
2015 INTERNATIONAL MECHANICAL CODE
2015 INTERNATIONAL FUEL GAS CODE
2015 INTERNATIONAL FIRE CODE
2017 NATIONAL ELECTRIC CODE
OCCUPANCY (EXISTING TO REMAIN):
BUSINESS (B) = 838 SF
OCCUPANT LOAD:
BUSINESS = 100 GROSS
838 SF / 100 = 9 OCCUPANTS
CONSTRUCTION TYPE (EXISTING):
CONSTRUCTION TYPE V-B
FIRE RESISTANCE RATING REQUIREMENTS:
CONSTRUCTION TYPE V-B
STRUCTURAL FRAME: NR
BEARING WALLS, EXTERIOR: NR
BEARING WALLS, INTERIOR: NR
NON-BEARING WALLS, EXTERIOR: NR
NON-BEARING WALLS, INTERIOR: NR
BUILDING CODE ANALYS
2020 NEC is our
currently adopted
electrical code,
please revise.
COMCheck has been updated.
Note has been added to place all
common place lighting on time clock.
Linear Strip has been removed.
CCA - OCCUPANT LOAD REVISED
CCA - CODE REFERENCE REVISED
Subject: PlanCheck
Page: 3
Author: justinh
Color:
File Name: 90.300 Spring.CO1 Sheets.20210816.pdf
Electrical plan only shows a
single downlight in the restroom.
CENTER WALL
FIXTURE OVER
VANITY
ANSI RESTROOM
(E)
205
1' - 6"2' - 6"Q EQ 1' - 6"
EQ EQ
2' - 0"
2' - 0"
Electrical plan only
shows a single
downlight in the
restroom.
CCA - LAYOUT REVISED