Loading...
HomeMy WebLinkAboutFile Documents.617 W Bleeker St.0062-2019-BRES (41)The City of Aspen These plans must be kept at the building site or inspection delays may occur. Construction shall conform to these plans. All changes shall be approved by the building official. Field Plan Set Must Be Printed In Color SEPARATE PERMITS ARE REQUIRED FOR ELECTRICAL, PLUMBING, MECHANICAL, OR FIRE SPRINKLER WORK External Energy Use Approved RREMP CREMP PERMIT #:_______________DATE:________ SNOWMELT:_____________________________ POOL: _____________________________ SPA: _____________________________ OFFSET:________________________________ REMP SHEET: __________________________ REVIEWED BY: _________________________ SNOWMELT SYSTEM AND EQUIPMENT MANDATORY REQ’S. All snowmelt systems shall meet the following: -Any portions in the Right of Way must be on a separate zone. A ROW permit and Permanent Encroachment License are required. -R10 insulation shall be installed under the area to be snow melted or R5 insulation shall be installed under and at the slab edges. (Ordinance 11 Series 2011) -Automatic controls installed for system shut off when pavement temperature is above 50°F and no precipitation is falling. (2009 IECC Sec. 403.8 & 503.2.4.5) -Automatic or manual controls installed for system shut off when outdoor temperature is above 40°F. (2009 IECC Sec. 403.8 & 503.2.4.5) -Inspection by testing hydrostatically at 1½ times max system design pressure, but not less than 100psi, for 15minutes. (2009 IMC Sec. 1208.1) MINIMUM BOILER AFUE: _________________ REFERENCES FROM 2015 IRC CV/A = crawl space ventilation required, sec. R408.1 Access required, R408.4 EE = emergency escape required sec R310.1 EU = enclosed usable space under stairs shall be ½” Gyp, sec R302.7 G/D = garage/dwelling separation, sec R302.5 and R302.6 STC = Sound transmission class not less than 45 at dwelling separations, app K RV = roof and rafter ventilation required, R806.1 A = attic access 22” x 30”, 30” headroom above, R807.1 SA = smoke alarms installed to NFPA 72 requirements, sec R314 CO = carbon monoxide detector per City Ordinance 41 series 2008 SG = safety glazing required, sec R308.4 GR = guardrails, 36” min ht, 4” max opening; req at 30” drop any point w/in 36” horizontally, sec R312 WFP = window fall protection- operable window <24” AFF & >72” above grade: use opening control device listed to ASTM F2090, sec R312.2 HR = handrails 34”-38” ht, sec R311.7.8 SI = stairway illumination, sec R303.7 PD = protect against decay, sec R317 REFERENCES FROM 2015 IMC V = bathroom and balanced whole house mechanical ventilation req. Ordinance 40, 2016 DE = clothes dryer exhaust, sec 504. Makeup air req’d if over 200 CFM AS = access and service space for maintenance req’d, sec 306 MA = make up air required if hood exhausts greater than 400 CFM, sec 505.2 ET = exhausts terminate 3’ from prop line and openings, 10’ from intakes, 501.3.1 IT= intake openings 10’ from lot line & contaminant sources (vents, streets), 401.4 D = fasten and seal all ductwork per 603.9 REFERENCES FROM 2015 IFGC DV = direct vent req’d, sec 303.3 CA = combustion air not taken from bedrooms, bathrooms or storage sec 303.3 OD = outdoor appliances must be listed for outdoor use, sec 303.6 REFERENCES FROM 2015 IECC F = new or replacement glazing shall not exceed 0.28 U-Value, NFRC label required, Ordinance 40, 2016 L = 75% of lamps in permanently installed lights must be high efficacy, sec R404.1 SE = Continuous air barrier required; all exterior joints, cracks, and holes to be caulked, gasketed, sealed, table R402.4.1.1 REFERENCES FROM 2014 NEC EP = electric panel 'happy space' 30"x36"x78", not in storage, sec 110.26 SMOKE ALARMS AND CARBON MONOXIDE DETECTORS REQUIRED THROUGHOUT DWELLING UNIT PER CITY OF ASPEN MUNICIPAL CODE 8.15 COMMUNITY DEVELOPMENT DEPARTMENT BUILDING PERMIT CONTACT SHEET CITY OF ASPEN 130 S. GALENA ST | ASPEN, CO 81611 ___________________________________ _____________________ _____________________ ________________________________________ __________________ _________ ____________ _______________________________________________________________________________________ Name Phone Cell Phone CityMailing Address E-mailAddress State ZIP OWNER ___________________________________ _____________________ ________________________Name Phone E-mail FOR PLAN REVIEW QUESTIONS ___________________________________ _____________________ ________________________Name Phone E-mail FOR INSPECTION QUESTIONS ___________________________________ _____________________ _____________________ ________________________________________ __________________ _________ ____________ _______________________________________________________________________________________ Name Phone Cell Phone CityMailing Address E-mailAddress State ZIP OWNER’S AUTHORIZED AGENT ___________________________________ _____________________ _____________________ ________________________________________ __________________ _________ ____________ _______________________________________________________________________________________ Name Phone Cell Phone CityMailing Address E-mailAddress State ZIP APPLICATION BEST CONTACT ___________________________________ _____________________ _____________________ ________________________________________ __________________ _________ ____________ _______________________________________________________________________________________ Name Phone Cell Phone CityMailing Address E-mailAddress State ZIP ARCHITECT OR DESIGNER OF RECORD ___________________________________ _____________________ _____________________ ________________________________________ __________________ _________ ____________ _______________________________________________________________________________________ Name Phone Cell Phone CityMailing Address E-mailAddress State ZIP CIVIL ENGINEER OF RECORD ___________________________________ _____________________ _____________________ ________________________________________ __________________ _________ ____________ _______________________________________________________________________________________ Name Phone Cell Phone CityMailing Address E-mailAddress State ZIP STRUCTUAL ENGINEER OF RECORD I hereby certify that I have read and examined this application and know the same to be true and correct. All provisions of laws and ordinances governing this type of work will be complied with whether specified herein or not. The granting of a permit does not presume to give authority to violate or cancel the provisions of any other state or local law regulating construction or the performance of construction. It is my responsibility to review the approved plans and any comments that are contained thereon and see that the structure and/or project is built in compliance with all applicable codes. ________________________________________________________ _____________________ContractorSignature Date INSPECTIONS: The General Contractor must schedule inspections online. Please visit www.aspenpitkin.com/Departments/Community-Development-Forms/ to do so. ___________________________________ _____________________ _____________________ ________________________________________ __________________ _________ ____________ _______________________________________________________________________________________ Name Phone Cell Phone CityMailing Address E-mailAddress State ZIP GENERAL CONTRACTOR Check if you are a tested owner builder (single-family homes only). You must take a test and complete the owner/building affidavit. (CITY USE ONLY) Owner builder approved by:________________________Date:______________________ Affidavit on file ADDRESS: ____________________________PERMIT NUMBER: _______________________________ August 2017 617 WEST BLEEKER STREET 0062-2019-BRES Monica Ponce de Leon/ Austin Kaa AK@MPDLSTUDIO.COM Monica Ponce de Leon/ Austin Kaa AK@MPDLSTUDIO.COM 248-644-0271SCHWARTZ, RACHEL K & MARK 248-321-8329 1061 COUNTRY CLUB ROAD BLOOMFIELD HILLS MI 48304 MARK@MSSSPHD.COM 212-691-6835MONICA PONCE DE LEON 617-426-0995 29 STANHOPE STREET, 3RD FLOOR BOSTON MA 02116 MPDL@MPDLSTUDIO.COM 212-691-6835AUSTIN KAA 949-933-3147 416 W. 13TH STREET SUITE 311 NEW YORK NY 10014 AK@MPDLSTUDIO.COM 212-691-6835MONICA PONCE DE LEON STUDIO INC./ MONICA PONCE DE LEON 617-426-0995 29 STANHOPE STREET, 3RD FLOOR BOSTON MA 02116 MPDL@MPDLSTUDIO.COM 970-340-4130ROARING FORK ENGINEERING/ RICHARD GOULDING 970-948-7474 592 HIGHWAY 133 CARBONDALE CO 81623 richardg@rfeng.biz 970-927-4363ALBRIGHT AND ASSOCIATES/ JACK ALBRIGHT 970-379-3244 402 PARK AVE. UNIT A BASALT CO 81621 jack@albright-associates.com 970.927.6714JANCKILA CONSTRUCTION INC./ PETE WAARANIEMI 970.319.3650 75 BUCKSKIN DRIVE CARBONDALE CO 81623 pete@janckilaconstruction.com 11/20/2019 FIRE SPRINKLERS REQUIRED 0 electric snowmelt; 75% AFUE spa0 TF 0062.2019.BRES X A0-04 SPECIAL INSPECTION REQUIRED: -Structural steel welding: Field & Shop -High strength bolting -Epoxy anchors -Intumescent paint -Spray applied fire resistive materials -Permanent micropiles Special inspection is required per 2015 IBC section 1704. Inspector to verify that copy of agreement for inspection program to be on the job site prior to performing any inspections. A copy of all Special Inspector field reports to be on the job site for inspectors' review if requested. Failure to comply may result in denial of inspection. Concrete, structural steel--Rf Sheet S0.1 SHEAR WALL INSPECTION REQUIRED 4/15/2020 957 sf 48 sf Ventilation flow rate: ALL OUTDOOR LIGHTING MUST COMPLY WITH THE CITY OF ASPEN LIGHTING CODE SECTION 26.575.150 07/30/2020 NFPA 13D 0062-2019-BRES JULES ASPEN LLC 617 W BLEEKER ST 273512444002 08/17/2020 TF/JH SEE CHANGE ORDER 0052-2022-BCHO for updated REMP info The City of Aspen These plans must be kept at the building site or inspection delays may occur. Construction shall conform to these plans. All changes shall be approved by the building official. SEPARATE PERMITS ARE REQUIRED FOR ELECTRICAL, PLUMBING, MECHANICAL, OR FIRE SPRINKLER WORK SPECIAL INSPECTION AND TESTING AGREEMENT To permit applicants of project requiring special inspection and\or testing per Section 1704 of the International Building Code (IBC). Project Address: __________________________________ Permit Number:______________________ BEFORE A PERMIT CAN BE ISSUED: The owner, or the engineer or architect of record, acting as the owner’s agent, shall complete two copies of this agreement and the attached Special-inspection and Testing Schedule, including the required acknowledgments. A pre-construction conference with the parties involved may be required to review the special-inspection requirements and procedures. APPROVAL OF SPECIAL INSPECTORS: Special inspectors may have no financial interest in the projects for which they provide special inspections. Special inspectors shall be approved by the building department prior to performing any duties. Special inspectors shall submit their qualifications and are subject to personal interviews for pre-qualification. Special inspectors shall display approved identification, as stipulated by the building official, when performing the function of special inspector. Special inspection and testing shall meet the minimum requirements of the International Building Code Section 1704. The following conditions are also applicable: A. Duties and Responsibilities of the Special Inspector 1. Signify presence at job site. Special inspectors should notify contractor personnel of their presence and responsibilities at the job site. If required by the building official, they shall sign in on the appropriate form posted with the building permit. Observe assigned work. The special inspector shall observe assigned work for conformance with the building department approved (stamped) design drawings, specifications, and applicable workmanship provisions of the International Building Code. Architect\engineer-reviewed shop drawings may be used only as an aid to inspection. For continuous special-inspection, the special inspector shall be on site at all times observing the work requiring special inspection. Periodic inspections, if any, must have prior approval based on a separate written plan reviewed and approved by the building department and the engineer or architect of record. 3. Report nonconforming items. The special inspector shall bring nonconforming items to the immediate attention of the contractor and note all such items in the daily report. If any item is not resolved in a timely manner or is about to be incorporated in the work, the special inspector shall immediately notify the building department by telephone or in person, notify the engineer or architect, and post a discrepancy notice. Provide timely reports. The special inspector shall complete written inspection reports for each inspection visit and provide the reports on a timely basis determined by the building official. The special inspector or inspection agency shall furnish these reports directly to the building official, engineer or architect of record, and others as designated. [IBC Sec. 1704.1.2] These reports should be organized on a daily format and may be submitted weekly at the option of the building official. These reports should include: a. Description of daily inspections and tests made with applicable locations, b. Listing of nonconforming items, c. Report on how nonconforming items were resolved or unresolved as applicable, d. Itemized changes authorized by the architect, engineer, and building official if not included in nonconforming items. 2. 4. 1 5. Provide Final Inspection Report. The special inspector shall submit a written final report documenting required special inspections and correction of any discrepancies noted in the inspections prior to the final building inspection. B. Owner Responsibilities. The project owner, the engineer or architect or record, or an agent of the owner is responsible for employing special-inspection services. The special inspector\agency shall not be in the employ of the contractor, subcontractor or material supplier. [IBC Sec 1704.1] In case of an owner\contractor, the special inspector\agency shall be employed as specified by the building official. C. Engineer or Architect of Record Responsibilities 1. Prepare special inspection program. The engineer or architect of record shall list the items for which special inspection is required; and shall indicate any items for which the IBC or the building official approves periodic inspection and the frequency of such inspections. Respond to field discrepancies. The engineer or architect of record shall respond to uncorrected field discrepancies in design, material, or workmanship observed by the special inspector. Review shop drawings and submit design changes. The engineer or architect of record shall acknowledge and review for conformance with the construction drawings those shop drawings that may detail structural information, shall submit to the building official and to the special-inspection agency written documentation of any verbally authorized deviations from the approved construction documents, and shall submit revised documents for building official approval as required. 2. 3. D. Contractor Responsibilities 1. Notify the special inspector. The contractor is responsible for notifying the special inspector or agency regarding individual inspections for items listed on the attached schedule and as noted on the building department approved plans. Adequate notice shall be provided so the special inspector has time to become familiar with the project. Provide access to approved plans. The contractor is responsible for providing the special inspector access to approved plans. Retain special inspection records. Upon request, the contractor is also responsible for retaining, at the job site, all special inspection records completed by the special inspector. 2. 3. E. Inspection of Fabricators 1. Fabrication of structural assemblies and members. Where fabrication of structural load-bearing members and assemblies is being performed on the premises of a fabricator’s shop, IBC Section 1704.2 shall require special inspection of the fabricated items. Fabrication and implementation procedures. The special inspector shall verify that the fabricator maintains detailed fabrication and quality control procedures that provide a basis for inspection control of the workmanship and the fabricator’s ability to conform to approved construction documents and reference standards. The special inspector shall review the procedures for completeness and adequacy relative to code requirements for fabricator’s scope of work. 2. F. Approved Fabricator Responsibilities 1. Fabrication exempt inspections. Special inspections are not required where work is done on the premise of a fabricator registered and approved to perform such work without special inspection. 2 SMOKE ALARMS AND CARBON MONOXIDE DETECTORS REQUIRED THROUGHOUT DWELLING UNIT PER CITY OF ASPEN MUNICIPAL CODE 8.150062-2019-BRES617 W BLEEKER 19-17310062-2019-BRES Justin Hahh 8/17/2020 Field Plan Set Must Be Printed In Color 08/17/2020 TF/JH TECHNICAL GUIDE ROOF BOARD 11/20/2019 DensDeck® Roof Boards For latest information and updates: Technical Service Hotline 1.800.225.6119 or www.gpgypsum.com CAUTION: For product fire, safety and use information, go to buildgp.com/safetyinfo. 2 Product Overview DensDeck® Roof Board DensDeck® Prime Roof Board Table of Contents Product Overview . . . . . . . . . . . . . . . .2 Architectural Specifications . . . . . . . .3 Standards and Classifications . . . . . . . . . . . . . . . . . . .3 Fire Resistance . . . . . . . . . . . . . . .3 Wind Uplift Resistance . . . . . . . . .5 Sound Control . . . . . . . . . . . . . . . .8 Sound Control Illustrations . . . . . . . . .9 Roof System Applications . . . . . . . . .11 Physical Properties . . . . . . . . . . . . . .13 Recommendations and Limitations for Use . . . . . . . . . . . . .14 Nearly 30 Years of DensDeck® Roof Boards – Proven Performance With billions of square feet installed in a complete range of roofing systems and climate extremes, DensDeck Roof Boards have proven their toughness and versatility. The unique construction has been shown to withstand delamination, deterioration, warping and job site damage far more effectively than paper-faced gypsum board and other conventional roofing products such as wood fiberboard and perlite. • Provides superior fire protection. • Resists fire and hail damage. • Holds up well under normal construction and maintenance foot traffic while stiffening and stabilizing roof decks. • Easy to install in all types of roof systems. • Ideal product for direct membrane application. • Tested within roofing systems for sound isolation. DensDeck® is designed to address persistent challenges inherent in commercial roofing assemblies: fire resistance, strength and dimensional stability when installed in a properly designed roof assembly. DensDeck is a fiberglass mat- faced, noncombustible (as described and tested in accordance with ASTM E136), nonstructural, gypsum core panel. Building on our 30-year history of market-driven innovation DensDeck Prime Roof Boards have now been enhanced with EONIC™ Technology, a patented system that delivers advanced moisture performance and mat-to-core bond strength. With this advancement, DensDeck Prime Roof Boards are now the only roof board with manufacturing specifications that include 5%1 total water absorption by weight and 1 gram2 surface water absorption performance on both sides of the board.3 Also improved is the boards critical mat-to-core bond strength which in independent testing4 averaged 23% stronger on the face and 192% stronger on the back when compared to DensDeck Prime Roof Boards before the enhancement. DensDeck Prime Roof Boards continues to provide a broader compatibility and higher performance with roofing adhesives. Face mat allows adhesives to be applied more uniformly and consistently and results in a stronger bond with the membrane. For fully adhered and self-adhered “peel & stick” roofing systems, as well as hot mopped, cold mastic and torch-applied modified bitumen roofs, DensDeck Prime provides a stronger, more economical installation by reducing the amount of mastic or adhesive, and potentially eliminating the field primer. Consult with membrane manufacturer for actual priming requirements. 1/2” and 5/8” DensDeck Prime Roof Boards are the first and only gypsum roof boards with a limited warranty for up to 90 days of exposure to normal weather conditions when applied vertically on parapet walls.* * For complete warranty details, visit www .DensDeck .com . 1Maximum value 2Nominal value 3Based on published manufacturing specifications as of December 1, 2017 4 Comparison based on independent testing conducted by PRI Construction Materials Technologies in October 2017 . ½” boards tested in accordance to AST C209 . Georgia-Pacific Gypsum and Sustainability Georgia-Pacific Gypsum’s definition of sustainability is meeting the needs of society today without jeopardizing our ability to do so in the future. We are committed to using resources efficiently to provide innovative products and solutions that meet the needs of customers and society, while operating in a manner that is environmentally and socially responsible, and economically sound. 11/20/2019 DensDeck® Roof Boards For latest information and updates: Technical Service Hotline 1.800.225.6119 or www.gpgypsum.com CAUTION: For product fire, safety and use information, go to buildgp.com/safetyinfo. 3 Many of our products contribute to LEED® and other green building codes, standards, or program credits or requirements. To find out more, please refer to the LEED calculator at www.buildgp.com/leedcalc.aspx. For general information on sustainability, visit www.buildgp.com/sustainability. Architectural Specifications Georgia-Pacific Gypsum’s 3-part guide specifications are downloadable, as rewritable Microsoft® Word documents, in both CSI and ARCOM MasterSpec® formats. Georgia-Pacific Gypsum specifications and 3-D Revit® compatible models can be found at www.gpdesignstudio.com. Downloadable specifications are also available online from Building Systems Design, Inc. at www.bsdsoftlink.com, and ARCOM Product Masterspec at www.masterspec.com. Code Compliance DensDeck Roof Boards are manufactured to meet ASTM C1177 and have the following approvals: • Florida Product Approved • Miami-Dade County Product Control Approved Standards and Classifications – Fire Resistance DensDeck® and DensDeck® Prime Roof Boards are excellent fire barriers over combustible and noncombustible roof decks, including steel decks. Roofing specifications for steel deck installations often require a fire barrier as the component applied above the metal to help control and limit the amount of fuel contributed to a fire beneath the roof. UL Fire Resistance Ratings. 5/8” (15.9 mm) DensDeck® Roof Boards are designated as Type DD by UL LLC and included in assembly designs investigated by UL for hourly fire resistance ratings. 5/8” (15.9 mm) DensDeck Fireguard roof boards may also replace any unclassified 5/8” (15.9 mm) gypsum board in an assembly in the UL Fire Resistance Directory under the prefix “P”. UL 790 Classification. DensDeck and DensDeck Prime Roof Boards have been certified by UL for use as a fire barrier over combustible and noncombustible decks in accordance with the ANSI/UL 790 and ULC S114 test standard. The UL classification includes a comprehensive Class A, B or C rating. This test method and resulting classification measures the external fire resistance of the roof system but does not include an investigation of fire resistance to internal sources directed at the underside of the roof system. For additional information concerning the UL 790 classification for DensDeck Roof Boards, consult the UL certifications directory under categories TGFU (Roofing Systems) and TGFU7 (Roofing Systems Certified for Canada). UL 1256 Classification. DensDeck and DensDeck Prime Roof Boards have also been certified by UL in roof deck constructions for internal (under deck) fire exposure in accordance with the ANSI/UL 1256 Steiner Tunnel test. The UL listing includes the use of ¼” DensDeck Roof Boards under foam plastic insulation. For additional information concerning the UL 1256 classification for DensDeck Roof Boards, consult the UL certifications directory under categories TGKX (Roof Deck Constructions), TIAR (Building Units) and TIAR7 (Building Units Certified for Canada). FM Class 1 Approvals. 1/4” (6.4 mm) DensDeck Roof Boards have passed testing under the FM Calorimeter Standard 4450 (Approval Standard for Class 1 Insulated Steel Deck Roofs) and have been approved by FM for insulated steel deck roofs when installed per FM guidelines. To achieve a Class 1 designation, the assembly must satisfy criteria for fire, wind uplift, foot traffic and hail damage resistance. For more information about FM Approvals and Class 1 assemblies, consult FM or RoofNav®, FM’s tool for roofing professionals. Please note, however, that the performance of a roof depends on all components used in the roofing assembly and how the components interact. ASTM C1177. 5/8” (15.9 mm) DensDeck and 5/8” (15.9 mm) DensDeck Prime Roof Boards are manufactured to meet the “Type X” requirements of ASTM C1177 for increased fire resistance beyond regular gypsum board. Flame Spread and Smoke Development. When tested in accordance with ASTM E84, UL723 and CAN/ULC-S102, DensDeck and DensDeck Prime Roof Boards had Flame Spread 0, Smoke Developed 0. Long-term fire protection of roofing systems is a key concern of the design authority, code officials and building owners. DensDeck Roof Boards will contribute to the fire-resistant characteristics of roof assemblies over time. “When using a low-slope membrane roof system, designers should include in their designs a suitable cover board that is consistent with an appropriate listing or approval from a code-approved testing agency. This recommendation is consistent with the guidelines already contained in The NRCA Roofing and Waterproofing Manual, Fifth Edition. Furthermore, for mechanically attached single ply membrane roof systems, designers of newly-installed roof systems are now recommended to include a noncombustible cover board that is consistent with an appropriate listing or approval from a code-approved testing agency. Examples of noncombustible cover boards include fiberglass mat-faced gypsum boards and gypsum roof boards.” (January 2006 NRCA/MRCA Technical Bulletin.) See: January 2006 NRCA/MRCA Technical Bulletin: Fire Testing of Membrane Roof Systems . 11/20/2019 DensDeck® Roof Boards For latest information and updates: Technical Service Hotline 1.800.225.6119 or www.gpgypsum.com CAUTION: For product fire, safety and use information, go to buildgp.com/safetyinfo. 4 Standards and Classifications – Fire Resistance continued The design assemblies in this guide are presented for illustrative purposes only. It is important that you consult a design professional and the appropriate fire resistance directory or test report for complete assembly information and related information. Georgia-Pacific Gypsum does not provide architectural, engineering or roofing system services. For additional fire safety information concerning Georgia-Pacific Gypsum’s products, visit www.buildgp.com/safetyinfo. UL Classifications A B C D E Typical UL Fire Barrier Board Classification on Noncombustible Decking A. UL Classified Roof Covering B. Min. 1/4” (6.4 mm) DensDeck® Prime Roof Board C. UL Classified Insulation D. Minimum 1/4” (6.4 mm) DensDeck Roof Board serving as an insulation thermal barrier underlayment and an acceptable code alternative to a thermal barrier. E. Classified Steel Deck A B C D E *Note: The UL 790 classification for DensDeck provides that the use of DensDeck roof boards as a barrier board over a combustible deck permits the use of any classified roofing system which would otherwise be limited to use over a noncombustible deck . When used, the insulation must consist of one of the types specified . For additional information, consult the UL certifications directory under category TGFU (Roofing Systems) . FM Approvals A B CD E The following are typical configurations with DensDeck® Roof Boards certified by UL for use as a fire barrier over combustible and noncombustible decks and are for illustration purposes only. Please consult UL for additional information. DensDeck Roof Boards are typically utilized in these constructions as an insulation underlayment. In some assemblies it will be used as an insulation overlayment or cover board (1/4” (6.4 mm), 1/2” (12.7 mm) or 5/8” (15.9 mm)). In other assemblies it will serve both of these roles in the same system. The following is a typical configuration of a roof deck for a FM Class 1 fire rating and is for illustration purposes only. Please consult FM or RoofNav (https://www.roofnav.com) for additional information. Typical UL Fire Barrier Board Classification on Combustible Decking* A. UL Classified Roof Covering B. Min. 1/4” (6.4 mm) DensDeck Prime Roof Board C. UL Classified Insulation (optional) D. Minimum 1/4” (6.4 mm) DensDeck Roof Board serving as an insulation thermal barrier overlayment with all joints staggered a min. of 6” (152 mm) from the plywood joints. E. Classified Wood Deck Typical Configuration of DensDeck Roof Boards (Class 1 Fire Rating) A. Membrane (various) B. Minimum 1/4” (6.4 mm) DensDeck Roof Boards Overlayment C. Rigid Foam Insulation D. Minimum 1/4” (6.4 mm) DensDeck Roof Boards Underlayment E. Metal Deck 11/20/2019 DensDeck® Roof Boards For latest information and updates: Technical Service Hotline 1.800.225.6119 or www.gpgypsum.com CAUTION: For product fire, safety and use information, go to buildgp.com/safetyinfo. 12 A B D Applications continued Wood Shake/Shingle Underlayment A. Wood Shake/Shingles B. Organic Felt C. Minimum 1/4” (6.4 mm) DensDeck Roof Board as a wood shake/shingle underlayment on a combustible deck assembly to achieve a UL Class A fire rating D. Combustible Deck C Vegetative “Green” Roof A. Growing Medium and Plants B. Moisture Retention Mat C. Drainage Layer D. Protection Fabric/Root Barrier E. Waterproofing Membrane F. Minimum 1/2” (12.7 mm) DensDeck Prime Roof Board G. Insulation H. Any Structural Deck Photovoltaic Roofing System A. PV Panels B. Roofing Membrane C. Minimum 1/4” (6.4 mm) DensDeck Prime Roof Board D. Insulation E. DensDeck (optional) F. Any Structural Deck A B E D F A B CDE G H F C Parapet Wall Substrate – DensDeck® Prime Roof Board preferred A. Coping B. Minimum 1/2” (12.7 mm) DensDeck® Prime Roof Boards* C. Nailer D. Concrete Masonry Unit (CMU) E. Adhered Flashing Membrane F. Nailer G. DensDeck or DensDeck Prime Roof Board H. Rigid Foam Insulation I. Any Structural Deck *Fastened 8” o .c . 1/2” for 16” metal stud spacing 5/8” for 24” metal stud spacing 5/8” minimum over wood framing, 24” maximum stud spacing A C D E F H G I B The highlighted green circle is intended to call attention to the recommended DensDeck board for that particular application . 11/20/2019 DensDeck® Roof Boards For latest information and updates: Technical Service Hotline 1.800.225.6119 or www.gpgypsum.com CAUTION: For product fire, safety and use information, go to buildgp.com/safetyinfo. 7 GP Fastener Patterns 12" 4' x 8' 12"24"12" 12" 72" 12" 4' x 8' 12"24"12" 12" 18" 12" 18" 18" 18" 4' x 8' 12" 18" 12" 18" 18" 18" 12"12"12"12" 4' x 8' 12"12"12"12" 12" 12" 24" 24" 24" 4' x 8' 12" 18" 12" 18" 18" 18" 4' x 8' 6"12"12"12"6"6"12"12"12"6" 6" 18" 18" 12" 18" 6" 18" 4' x 8' 6" 6" 4' x 8' 12"12"12"12" 12" 12" 12" 12" 24" 12" 12" 4' x 8' 12"12"12"12" 36" 6" 6" 36" 12" 12" 4' x 8' 12"24"12" 24" 24" 24" 4' x 8' 6" 6" 4' x 8' 6" 18" 18" 12" 18" 6" 18" 6"12"12"12"6"6"18"18"6"6"6"6"6"12"12" 6" 12" 6" 12" 6" 12" 12" 6" 12" 12" 12" 12" 12" 12" 12" 4' x 8' 12"24"12" 36" 12" 12" 36" 4 fasteners per board 8 fasteners per board 10 fasteners per board 12 fasteners per board 15 fasteners per board 18 fasteners per board 24 fasteners per board 9 fasteners per board 20 fasteners per board16 fasteners per board Note: Preliminary insulation or mechanically attached roof covering requires a minimum of 4 fasteners per 4’ x 8’ board in FM assemblies . 32 fasteners per board Other patterns are available from system manufacturers or testing agencies. Wind continued 5 fasteners per board 11/20/2019 DensDeck® Roof Boards For latest information and updates: Technical Service Hotline 1.800.225.6119 or www.gpgypsum.com CAUTION: For product fire, safety and use information, go to buildgp.com/safetyinfo. 5 Wind Uplift Information Wind uplift resistance of roofing assemblies is achieved by fastening and/or adhering the roofing components to the structural deck. Uplift resistance testing may be conducted by several independent laboratories, in accordance with FM 4470 and ANSI/UL 1897 test procedures. The test results show the tested (not design) pounds per square foot (PSF) uplift resistance which has been achieved. It is the responsibility of the roofing design authority to comply with code requirements and follow the guidelines in ASCE-7 or FM 1-28 and 1-29 to establish the appropriate design uplift resistance and safety factor. Several factors are considered to determine the design pressure required, including but not limited to, height of the building, ground roughness, exposure and importance factor. Once the design pressure is determined, the roofing assembly which meets this pressure, with the appropriate safety factor, is selected by the design authority. Roof System Attachment to Deck PSF Single Ply Fully Adhered Adhered 915 Multi-Ply Hot Asphalt Hot Asphalt 825 Multi-Ply Torched Hot Asphalt 825 Multi-Ply Torch Cap Hot Asphalt Base Hot Asphalt 840 Multi-Ply Torched Adhered 810 Vertical Pull Resistance Over Structural Concrete Deck The assemblies listed are a sample of the highest vertical pull values available through FM’s RoofNav® utilizing DensDeck® Roof Boards. The test method used was FM 1-52. It is important to note that the vertical pull results are for the entire roof assembly, not just the DensDeck Roof Boards. For a comprehensive list of vertical pull tests and additional information, please visit https://www.roofnav.com. Actual results may vary depending on moisture (see page 15), and other factors. Georgia-Pacific Gypsum makes no representations or warranties concerning the vertical pull or uplift resistance of any roof assembly or system. The vertical pull test measures the uplift resistance in pounds on a four square foot test area. A 2’ x 2’ assembly is adhered to a concrete deck and the uplift force is divided by four to get the pounds per square foot uplift resistance. System Components, Standards and Classifications – Wind Uplift Resistance Uplift Resistance Pressures Achieved With DensDeck® Through Independent Testing The following are typical roofing systems with examples of assemblies evaluated by FM, UL or other labs for wind uplift resistance. These systems are presented for illustration only, and the examples of wind uplift resistance are for the entire assembly tested, not just the DensDeck® Roof Boards. Actual results may vary depending on moisture (see page 15), and other factors. Georgia-Pacific Gypsum makes no representations or warranties concerning the vertical pull or uplift resistance of any roof assembly or system. (Check membrane manufacturers’ listing including FM, UL and other accredited labs for thousands of additional uplift assembly ratings with DensDeck products .) Fastener rates shown are for the field of the roof . Additional fasteners are required for perimeter and corner areas and require either additional designer authority calculations or uplift testing . Unless otherwise noted, all screws used in tests are polymer coated, FM approved, min . 12 gauge steel and plates are 3” (76 mm) diameter corrosion resistant steel . Tests were conducted over 22 gauge steel decks . For fastener requirements in wood or structural concrete decks, refer to FM Global Property Loss Prevention Data Sheet 1-29 . Components above vapor retarder bonded with cold mastics, hot asphalt or adhesives . Vapor Retarder Substrate System Type and Description B C F A G DE Wind-Uplift PSF Product # of fasteners (4’ x 8’ board) FM 1-90 5/8” (15.9 mm) DensDeck 8 FM 1-90 5/8” (15.9 mm) DensDeck Prime 8 A. Any Rated Adhered Membrane B. Min. 1/4” (6.4 mm) DensDeck Roof Board (optional) C. Insulation (optional) D. Vapor Retarder E. Min. 5/8” (15.9 mm) DensDeck Roof Board F. Classified Steel Deck G. Fastener (see chart) 11/20/2019 08/17/2020 TF/JH REScheck Software Version 4.7.0 Compliance Certificate Project Energy Code:2015 IECC Location:Aspen, Colorado Construction Type:Single-family Project Type:New Construction Conditioned Floor Area:6,457 ft2 Glazing Area 40% Climate Zone:7 (9922 HDD) Permit Date: Construction Site: 617 W. Bleeker Aspen, CO 81611 Owner/Agent: Rachel K & Mark Schwartz 1061 Country Club Road Bloomfield Hills, MI 48304 248-321-8329 MARK@MSSPHD.COM Designer/Contractor: Monica Ponce de Leon Monica Ponce de Leon Studio INC. 29 Stanhope Street 3rd Floor Boston, MA 02116 212-691-6835 MPDL@MPDLSTUDIO.COM 0062-2019-BRESPermit Number: Compliance: Passes using UA trade-off 18.9% Better Than Code Maximum UA:957 Your UA:776 The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules. It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home. Compliance: Envelope Assemblies Assembly Gross Area or Perimeter Cavity R-Value Cont. R-Value U-Factor UA Wall 1: Wood Frame, 16" o.c.3,768 20.0 6.0 0.042 80 Window 1: Metal Frame with Thermal Break:Double Pane 1,471 0.260 382 Door 1: Solid 335 0.350 117 Door 2: Glass 52 0.320 17 Basement Wall 1: Solid Concrete or Masonry Wall height: 12.0' Depth below grade: 12.0' Insulation depth: 12.0' 3,398 15.0 15.0 0.026 88 Ceiling 1: Flat Ceiling or Scissor Truss 507 49.0 0.0 0.026 13 Ceiling 2: Cathedral Ceiling 3,596 49.0 0.0 0.022 79 Name - Title Signature Date Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other calculations submitted with the permit application. The proposed building has been designed to meet the 2015 IECC requirements in REScheck Version 4.7.0 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist. Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 1 of 10 08/13/20Report date: AKAUSTIN KAA 08/13/20 08/17/2020 08/17/2020 justinh Inspection Checklist Requirements: 0.0% were addressed directly in the REScheck software REScheck Software Version 4.7.0 Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided. Energy Code: 2015 IECC Section # & Req.ID Pre-Inspection/Plan Review Plans Verified Value Field Verified Value Complies?Comments/Assumptions 103.1, 103.2 [PR1]1 Construction drawings and documentation demonstrate energy code compliance for the building envelope. Thermal envelope represented on construction documents. Complies Does Not Not Observable Not Applicable 103.1, 103.2, 403.7 [PR3]1 Construction drawings and documentation demonstrate energy code compliance for lighting and mechanical systems. Systems serving multiple dwelling units must demonstrate compliance with the IECC Commercial Provisions. Complies Does Not Not Observable Not Applicable 302.1, 403.7 [PR2]2 Heating and cooling equipment is sized per ACCA Manual S based on loads calculated per ACCA Manual J or other methods approved by the code official. Heating: Btu/hr_____ Cooling: Btu/hr_____ Heating: Btu/hr_____ Cooling: Btu/hr_____ Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 3 of 10 08/13/20Report date:08/17/2020 08/17/2020 justinh Section # & Req.ID Foundation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1 [FO4]1 Conditioned basement wall insulation R-value. Where interior insulation is used, verification may need to occur during Insulation Inspection. Not required in warm-humid locations in Climate Zone 3. R-_____ R-_____ R-_____ R-_____ Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [FO5]1 Conditioned basement wall insulation installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable 402.2.9 [FO6]1 Conditioned basement wall insulation depth of burial or distance from top of wall. _____ ft _____ ft Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2.1 [FO11]2 A protective covering is installed to protect exposed exterior insulation and extends a minimum of 6 in. below grade. Complies Does Not Not Observable Not Applicable 403.9 [FO12]2 Snow- and ice-melting system controls installed. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 4 of 10 08/13/20Report date:08/17/2020 08/17/2020 justinh Section # & Req.ID Framing / Rough-In Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.3.4 [FR1]1 Door U-factor.U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 402.1.1, 402.3.1, 402.3.3, 402.5 [FR2]1 Glazing U-factor (area-weighted average). U-_____U-_____Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.3 [FR4]1 U-factors of fenestration products are determined in accordance with the NFRC test procedure or taken from the default table. Complies Does Not Not Observable Not Applicable 402.4.1.1 [FR23]1 Air barrier and thermal barrier installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable 402.4.3 [FR20]1 Fenestration that is not site built is listed and labeled as meeting AAMA /WDMA/CSA 101/I.S.2/A440 or has infiltration rates per NFRC 400 that do not exceed code limits. Complies Does Not Not Observable Not Applicable 402.4.5 [FR16]2 IC-rated recessed lighting fixtures sealed at housing/interior finish and labeled to indicate ≤2.0 cfm leakage at 75 Pa. Complies Does Not Not Observable Not Applicable 403.3.1 [FR12]1 Supply and return ducts in attics insulated >= R-8 where duct is >= 3 inches in diameter and >= R-6 where < 3 inches. Supply and return ducts in other portions of the building insulated >= R-6 for diameter >= 3 inches and R-4.2 for < 3 inches in diameter. Complies Does Not Not Observable Not Applicable 403.3.5 [FR15]3 Building cavities are not used as ducts or plenums. Complies Does Not Not Observable Not Applicable 403.4 [FR17]2 HVAC piping conveying fluids above 105 ºF or chilled fluids below 55 ºF are insulated to ≥R- 3. R-_____R-_____Complies Does Not Not Observable Not Applicable 403.4.1 [FR24]1 Protection of insulation on HVAC piping. Complies Does Not Not Observable Not Applicable 403.5.3 [FR18]2 Hot water pipes are insulated to ≥R-3. R-_____R-_____Complies Does Not Not Observable Not Applicable 403.6 [FR19]2 Automatic or gravity dampers are installed on all outdoor air intakes and exhausts. Complies Does Not Not Observable Not Applicable 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 5 of 10 08/13/20Report date:08/17/2020 08/17/2020 justinh Section # & Req.ID Insulation Inspection Plans Verified Value Field Verified Value Complies?Comments/Assumptions 303.1 [IN13]2 All installed insulation is labeled or the installed R-values provided. Complies Does Not Not Observable Not Applicable 402.1.1, 402.2.5, 402.2.6 [IN3]1 Wall insulation R-value. If this is a mass wall with at least ½ of the wall insulation on the wall exterior, the exterior insulation requirement applies (FR10). R-_____ Wood Mass Steel R-_____ Wood Mass Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.2 [IN4]1 Wall insulation is installed per manufacturer’s instructions. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 7 of 10 08/13/20Report date:08/17/2020 08/17/2020 justinh Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 402.1.1, 402.2.1, 402.2.2, 402.2.6 [FI1]1 Ceiling insulation R-value.R-_____ Wood Steel R-_____ Wood Steel Complies Does Not Not Observable Not Applicable See the Envelope Assemblies table for values. 303.1.1.1, 303.2 [FI2]1 Ceiling insulation installed per manufacturer’s instructions. Blown insulation marked every 300 ft². Complies Does Not Not Observable Not Applicable 402.2.3 [FI22]2 Vented attics with air permeable insulation include baffle adjacent to soffit and eave vents that extends over insulation. Complies Does Not Not Observable Not Applicable 402.2.4 [FI3]1 Attic access hatch and door insulation ≥R-value of the adjacent assembly. R-_____R-_____Complies Does Not Not Observable Not Applicable 402.4.1.2 [FI17]1 Blower door test @ 50 Pa. <=5 ach in Climate Zones 1-2, and <=3 ach in Climate Zones 3-8. ACH 50 =_____ACH 50 =_____Complies Does Not Not Observable Not Applicable 403.3.4 [FI4]1 Duct tightness test result of <=4 cfm/100 ft2 across the system or <=3 cfm/100 ft2 without air handler @ 25 Pa. For rough-in tests, verification may need to occur during Framing Inspection. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable 403.3.3 [FI27]1 Ducts are pressure tested to determine air leakage with either: Rough-in test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the system including the manufacturer’s air handler enclosure if installed at time of test. Postconstruction test: Total leakage measured with a pressure differential of 0.1 inch w.g. across the entire system including the manufacturer’s air handler enclosure. _____ cfm/100 ft2 _____ cfm/100 ft2 Complies Does Not Not Observable Not Applicable 403.3.2.1 [FI24]1 Air handler leakage designated by manufacturer at <=2% of design air flow. Complies Does Not Not Observable Not Applicable 403.1.1 [FI9]2 Programmable thermostats installed for control of primary heating and cooling systems and initially set by manufacturer to code specifications. Complies Does Not Not Observable Not Applicable 403.1.2 [FI10]2 Heat pump thermostat installed on heat pumps. Complies Does Not Not Observable Not Applicable 403.5.1 [FI11]2 Circulating service hot water systems have automatic or accessible manual controls. Complies Does Not Not Observable Not Applicable 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 8 of 10 08/13/20Report date:08/17/2020 08/17/2020 justinh Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 403.6.1 [FI25]2 All mechanical ventilation system fans not part of tested and listed HVAC equipment meet efficacy and air flow limits. Complies Does Not Not Observable Not Applicable 403.2 [FI26]2 Hot water boilers supplying heat through one- or two-pipe heating systems have outdoor setback control to lower boiler water temperature based on outdoor temperature. Complies Does Not Not Observable Not Applicable 403.5.1.1 [FI28]2 Heated water circulation systems have a circulation pump. The system return pipe is a dedicated return pipe or a cold water supply pipe. Gravity and thermos- syphon circulation systems are not present. Controls for circulating hot water system pumps start the pump with signal for hot water demand within the occupancy. Controls automatically turn off the pump when water is in circulation loop is at set-point temperature and no demand for hot water exists. Complies Does Not Not Observable Not Applicable 403.5.1.2 [FI29]2 Electric heat trace systems comply with IEEE 515.1 or UL 515. Controls automatically adjust the energy input to the heat tracing to maintain the desired water temperature in the piping. Complies Does Not Not Observable Not Applicable 403.5.2 [FI30]2 Water distribution systems that have recirculation pumps that pump water from a heated water supply pipe back to the heated water source through a cold water supply pipe have a demand recirculation water system. Pumps have controls that manage operation of the pump and limit the temperature of the water entering the cold water piping to 104ºF. Complies Does Not Not Observable Not Applicable 403.5.4 [FI31]2 Drain water heat recovery units tested in accordance with CSA B55.1. Potable water-side pressure loss of drain water heat recovery units < 3 psi for individual units connected to one or two showers. Potable water- side pressure loss of drain water heat recovery units < 2 psi for individual units connected to three or more showers. Complies Does Not Not Observable Not Applicable 404.1 [FI6]1 75% of lamps in permanent fixtures or 75% of permanent fixtures have high efficacy lamps. Does not apply to low-voltage lighting. Complies Does Not Not Observable Not Applicable 404.1.1 [FI23]3 Fuel gas lighting systems have no continuous pilot light. Complies Does Not Not Observable Not Applicable 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 9 of 10 08/13/20Report date:08/17/2020 08/17/2020 justinh Section # & Req.ID Final Inspection Provisions Plans Verified Value Field Verified Value Complies?Comments/Assumptions 401.3 [FI7]2 Compliance certificate posted.Complies Does Not Not Observable Not Applicable 303.3 [FI18]3 Manufacturer manuals for mechanical and water heating systems have been provided. Complies Does Not Not Observable Not Applicable Additional Comments/Assumptions: 1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3) Project Title: Data filename: C:\Users\ak\Desktop\REScheck\617 W Bleeker.rck Page 10 of 10 08/13/20Report date:08/17/2020 08/17/2020 justinh