HomeMy WebLinkAboutFile Documents.300 S Spring St.0054-2020-BCOM (13)The City of Aspen
These plans must be kept at the
building site or inspection
delays may occur. Construction
shall conform to these plans. All
changes shall be approved by
the building official.
Field Plan Set Must Be Printed In Color
SEPARATE PERMITS ARE
REQUIRED FOR ELECTRICAL,
PLUMBING, MECHANICAL, OR
FIRE SPRINKLER WORK
12/01/2020
sophiev
NO EXTERIOR LIGHTING IN SCOPE
OF WORK.
SEPERATE PERMIT IS
REQUIRED FOR ANY
SIGNAGE
COMcheck Software Version 4.1.1.0
Interior Lighting Compliance Certificate
Project Title:
2015 IECC
Project Type:Alteration
Construction Site:
300 SPRING STREET STE 200
ASPEN, CO 81611
Owner/Agent:
DAVID ROSENFELD
CCA
640 E HYMAN AVE
ASPEN, CO 81611
9709255590
DAVIDR@CUNNIFFE.COM
Designer/Contractor:
STANTON HUMPHRIES
AEC
9707488520
STAN@AEC-VAIL.COM
Project Information
Energy Code:
300 SPRING STREET STE 200
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1-OFFICE (Common Space Types:Office - Open Plan)785 0.98 769
769Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
OFFICE ( Common Space Types:Office - Open Plan 785 sq.ft.)
LED 1: A: DOWNLIGHT: Other:1 35 13 455
LED 2: C: VANITY LIGHT: Other:1 1 20 20
LED 3: L: LINEAR LED DRIVERS: Other:1 3 96 288
763Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting alteration project represented in this document is consistent with the
building plans, specifications, and other calculations submitted with this permit application. The proposed interior lighting
systems have been designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any
applicable mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES
Project Title:
Data filename:
300 SPRING STREET STE 200
P:\Current Projects\20067.00 - 300 Spring Street - Hanover Office
Remodel\Calculations\COMcheck\300 SPRING LIGHTING COMCHECK.cck
12/23/20Report date:
51 ofPage
STANTON HUMPHRIES, PE 12/23/20
01/07/2021
bonniem
0054-2020-BCOM
CJAR LLC
300 S Spring St 200
273718227116
2015 IBC 601 Fire Resistive Requirements for
Type of Construction: _VB_
Primary Structural Frame: _0___hr
(columns, beams, girders, etc)
Exterior Bearing Walls: __0__hr
Interior Bearing Walls: __0__hr
Floors/Ceilings: _0___hr
Roof : _0___hr
Unless noted otherwise for occupancy separation or fire
separation distance.
COMMERCIAL REFERENCES FROM 2015 IBC
EU = enclosed usable space under stairs shall be 1-hr construction or stair
enclosure rating. No access from stair enclosure.1011.7.3
SG = safety glazing required sec 2406
V = ventilation required, including from bathrooms. sec 1203.1, IMC 402 & 403
GR = guards, 42” min ht, 4” max opening sec 1015
HR = handrails 34”-38” ht sec 1014
AS = risers shall be solid in accessible egress stairs sec 1011.5.5.3
DS = Draft stopping / fire blocking 718
RD = Roof drainage 1503.4
STC = Sound transmission class not less than 50 at dwelling separations, sec
1207
PD = protect against decay, sec 2304.12
REFERENCES FROM 2015 IMC
AS = access and service space for maintenance req’d, sec 306
MA = kitchen hood make up air required, sec 508
ET = exhausts terminate 3’ from prop line and openings, 10’ from intakes,
501.3.1
IT= intake openings 10’ from lot line & contaminant sources (vents, streets),
401.4
D = fasten and seal all ductwork per 603.9
REFERENCES FROM 2015 IFGC
CA = combustion air not taken from bathrooms or storage, sec 303.3
REFERENCES FROM 2015 IECC
F = new or replacement glazing U factors may not exceed:
Fixed fenestration: U 0.29
Operable fenestration: U 0.37
Entrance doors: U 0.77
-Must have NFRC label or ASHRAE calcs, sec C402.4
REFERENCES FROM 2014 NEC
EP = electric panel ‘happy space’ 30”x36”x78”, not in storage, sec 110.26
FIRE
SPRINKLERS
REQUIRED