HomeMy WebLinkAboutFile Documents.205 E Durant Ave.0127-2023-BRES (18)Design No. L513
February 4, 2022
Unrestrained Assembly Rating — 1 Hr.
Finish Rating — 28 Min.
This design was evaluated using a load design method other than the Limit States Design
Method (e.g., Working Stress Design Method). For jurisdictions employing the Limit States
Design Method, such as Canada, a load restriction factor shall be used — See
Guide BXUV or BXUV7
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions
employing the UL or cUL Certification (such as Canada), respectively.
1. Subflooring — Min 3/4 in. thick wood structural panels, min grade "Underlayment" or "Single
Floor". Face grain of plywood or strength axis of panels to be perpendicular to joists with joints
staggered.
2. Adhesive — Elastomeric adhesive per American Plywood Association Specification AFG-01,
applied in 3/8 in. diam beads to top of joists and 1/4 in. diam beads to T& G panel joints.
05/14/2024
justinh
see item 10D for RSIC-1 listing in
this assembly
3. Battens — Nom 6 by 22-1/2 by 5/8 in. thick pieces of gypsum board (Item 11) centered under T &
G panel joints and fastened with staples (Item 4) spaced 7 in. OC along each edge. The battens and
staples (Item 4) are optional when any of the optional finish flooring systems are used.
4. Staples — Formed of 16 SWG (0.062 in. thick) steel with 1-1/8 in. legs and 1/2 in. crown, driven
flush with gypsum board batten strips.
5. Finish Flooring System — (Optional) — One of the following flooring system may be used over
the subflooring. If a finished flooring system is used, the batten strips and staples may be omitted.
System No. 1
Vapor Barrier — (Optional) — Nom 0.030 in. thick commercial asphalt saturated felt.
Finish Flooring — Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having
a minimum compressive strength of 1800 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
UNITED STATES GYPSUM CO — Types LRK, HSLRK, CSD
USG MEXICO S A DE C V — Types LRK, HSLRK, CSD
Floor Mat Materials* — (Optional) - Floor mat material loose laid over the subfloor. Refer to
manufacturer's instructions regarding the minimum thickness of floor topping over each floor mat
material.
UNITED STATES GYPSUM CO — Types SAM, LEVELROCK® Brand Sound Reduction Board,
LEVELROCK® Brand Floor Underlayment SRM-25
Alternate Floor Mat Materials* — (Optional) — Nom 3/8 in. thick floor mat material loose laid
over the subfloor. Floor topping thickness shall be as specified under Floor Topping Mixture.
GRASSWORX L L C — Type SC50
Alternate Floor Mat Material* — (Optional) - Floor mat material nominal 3/8 in. thick loose laid
over the subfloor. Floor topping shall be a min 3/4 in. thick.
System No. 2
Finish Flooring — Floor Topping Mixture* — Min 1-1/2 in. thickness of floor topping mixture
having a min compressive strength of 1000 psi and a cast density of 100 plus or minus 5 pcf. Foam
concentrate mixed 40:1 by volume with water and expanded at 100 psi through nozzle. Mixture shall
consist of 1.4 cu feet of preformed foam concentrate to 94 lbs Type I Portland cement, 300 lbs of
sand with 5-1/2 gal of water.
ELASTIZELL CORP OF AMERICA — Type FF
System No. 3
Vapor Barrier — (Optional) — Nom 0.030 in. thick commercial asphalt saturated felt.
Floor Mat Materials* — (Optional) — Floor mat material nom 5/64 in. (2 mm) thick adhered to
subfloor with Hacker Floor Primer. Primer to be applied to the surface of the mat prior to the
placement of a min 1 in. of floor-topping mixture.
HACKER INDUSTRIES INC — Type Hacker Sound-Mat
Alternate Floor Mat Materials — (Optional) — Floor mat material nom 1/4 in. (6 mm) thick
adhered to subfloor with Hacker Floor Primer. Primer to be applied to the surface of the mat prior to
the placement of a min 1-1/4 in. (32 mm) of floor-topping mixture.
HACKER INDUSTRIES INC — Type Hacker Sound-Mat II.
Alternate Floor Mat Materials — (Optional) — Floor mat material nom 1/8 in. (3 mm) thick loose
laid over the subfloor. Floor topping thickness shall be a min of 3/4 in. (19 mm)
HACKER INDUSTRIES INC — FIRM-FILL SCM 125
Alternate Floor Mat Materials — (Optional) — Floor mat material nom 1/4 in. (6 mm) thick loose
laid over the subfloor. Floor topping thickness shall be a min of 1 in. (25 mm)
HACKER INDUSTRIES INC — Type FIRM-FILL SCM 250, Quiet Qurl 55/025
Alternate Floor Mat Materials — (Optional) — Floor mat material nom 3/8 in. (10 mm) thick loose
laid over the subfloor. Floor topping thickness shall be a min of 1-1/4 in. (32 mm)
HACKER INDUSTRIES INC — FIRM-FILL SCM 400, Quiet Qurl 60/040
Alternate Floor Mat Materials — (Optional) — Floor mat material nom 3/4 in. (19 mm) thick loose
laid over the subfloor. Floor topping thickness shall be a min of 1-1/2 in. (38 mm)
HACKER INDUSTRIES INC — Type FIRM-FILL SCM 750, Quiet Qurl 65/075
Metal Lath (Optional) — For use with 3/8 in. (10 mm) floor mat materials, 3/8 in. expanded steel
diamond mesh, 3.4 lbs/sq yd placed over the floor mat material. Hacker Floor Primer to be applied
prior to the placement of the metal lath. When metal lath is used, floor topping thickness a nom 1-
1/4 in. over the floor mat.
Finish Flooring — Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having
a min compressive strength of 1100 psi. Mixture shall consist of 6.8 gal of water to 80 lbs of floor
topping mixture to 1.9 cu ft of sand.
HACKER INDUSTRIES INC — Firm-Fill Gypsum Concrete, Firm-Fill 2010, Firm-Fill 4010, Firm-Fill
High Strength, Gyp-Span Radiant, Firm-Fill 3310
System No. 4
Vapor Barrier — (Optional) — Nom 0.030 in. thick commercial asphalt saturated felt.
Finish Flooring — Floor Topping Mixture* — Min 1-1/2 in. thickness of floor topping mixture
having a min compressive strength of 1000 psi and a cast density of 105 plus or minus 5 pcf. Foam
concentrate mixed 40:1 by volume with water and expanded at 100 psi through nozzle. Mixture shall
consist of 1.2 cu feet of preformed foam concentrate to 94 lbs Type I Portland cement, 300 lbs of
sand with 5-1/2 gal of water.
AERIX INDUSTRIES — Floor Topping Mix
System No. 5
Deleted
System No. 6
Finish Flooring — Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having
a min compressive strength of 1000 psi. Mixture shall consist of 5 to 8 gal of water to 80 lbs of floor
topping mixture to 2.1 cu ft of sand.
ULTRA QUIET FLOORS — UQF-A, UQF-Super Blend, UQF-Plus 200
System No. 7
Vapor Barrier — (Optional) — Nom 0.030 in. thick commercial asphalt saturated felt.
Finish Flooring — Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having
a minimum compressive strength of 1500 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
MAXXON CORP — Type Maxxon Standard and Maxxon High Strength
Floor Mat Materials* — (Optional) — Floor mat material loose laid over the subfloor. Refer to
manufacturer's instructions regarding the minimum thickness of floor topping over each floor mat
material.
MAXXON CORP — Type Encapsulated Sound Mat.
Floor Mat Reinforcement — (Optional) - Refer to manufacturer's instructions regarding regarding
minimum thickness of floor topping for use with floor mat reinforcement.
Metal Lath — (Optional) — 3/8 in. expanded galvanized steel diamond mesh, 3.4 lbs/sq yd loose
laid over the floor mat material.
Fiber Glass Reinforcement - (Optional, Not Shown) - 0.015 in. thick PVC coated non-woven
fiberglass mesh, 0.368 lbs/sq yd loose laid over the floor mat material.
System No. 8
Finish Flooring — Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having
a min compressive strength of 1000 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
FORMULATED MATERIALS LLC — Types FR-25, FR-30, and SiteMix
Alternate Floor Mat Material* — (Optional) Floor mat material nominal 2 - 9.5 mm thick loose laid
over the subfloor. Floor topping shall be a min of 3/4 in.
FORMULATED MATERIALS LLC — Types M1, M2, M3, Elite, Duo, R1, and R2
System No. 9
Finish Floor — Mineral and Fiber Board* — Min 1/2 in. thick, supplied in sizes ranging from 3 ft by
4 ft to 8 ft by 12 ft. All joints to be staggered a min of 12 in. with adjacent sub-floor joints.
HOMASOTE CO — Type 440-32 Mineral and Fiber Board
System No. 10
Finish Flooring — Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having
a min compressive strength of 1000 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
ARCOSA SPECIALTY MATERIALS — AccuCrete® Types NexGen, Green, Prime and PrePour,
AccuRadiant®, AccuLevel® Types G40, G50 and SD30
Alternate Floor Mat Material* — (Optional) - Floor mat material nominal 2 - 9.5 mm thick loose
laid over the subfloor. Floor topping shall be a min of 3/4 in.
ARCOSA SPECIALTY MATERIALS — AccuQuiet® Types D13, D-18, D25, DX38, EM.125, EM.125S,
EM.250, EM.250S, EM.375, EM.375S, EM.750, and EM.750S.
System No. 11
Vapor Barrier — (Optional) — Nom 0.030 in. thick commercial asphalt saturated felt.
Finish Flooring — Floor Topping Mixture* — 3/4 in. thickness of floor topping mixture having a
min compressive strength of 2100 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
System No. 12
Subflooring — Min 15/32 in. thick wood structural panels, min grade "C-D" or "Sheathing". Face
grain of plywood or strength axis of panels to be perpendicular to the joists with joints staggered.
Vapor Barrier — (Optional) — Commercial asphalt saturated felt, 0.030 in. thick.
Vapor Barrier — (Optional) — Nom 0.010 in. thick commercial rosin-sized building paper.
Finish Flooring* — Min 3/4 in. thickness of any Floor Topping Mixture bearing the UL Classification
Marking as to Fire Resistance. See Floor- and Roof-Topping Mixtures (CCOX) category for names of
Classified Companies. Refer to the manufacturer’s instructions accompanying the material and/or
contact the manufacturer’s technical support for specific mix design and minimum thickness
recommended for use with eligible floor mat(s).
Floor Mat Materials* — (Optional) — Nom. 1/4 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 3/4 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 55/025 and Quiet Qurl 55/025 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 3/8 in. thick loose laid
over the subfloor. Floor topping thickness shall be a minimum of 1 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 60/040 and Quiet Qurl 60/040 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 3/4 in. thick loose laid
over the subfloor. Floor topping thickness shall be a minimum of 1-1/2 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 65/075, Quiet Qurl 65/075 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 1/8 in. thick loose laid
over the subfloor. Floor topping thickness shall be a minimum of 3/4 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 52/013 and Quiet Qurl 52/013 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 1/4 in. entangled net core
with a compressible fabric attached to the bottom loose laid over the subfloor. Floor topping
thickness shall be a minimum of 1 in.
KEENE BUILDING PRODUCTS CO INC — Quiet Qurl 55/025 MT and Quiet Qurl 55/025 N MT
System No. 13
Subflooring — Min 23/32 in. thick T&G wood structural panels, min grade "Underlayment" or
"Single-Floor". Face grain of plywood or strength axis of panels to be perpendicular to the trusses
with end joints staggered 4 ft. Panels secured to trusses with construction adhesive and No. 6d
ringed shank nails spaced 12 in. OC along each truss. Staples having equal or greater withdrawal and
lateral resistance strength may be substituted for the 6d nails.
Gypsum Board* — One layer of nom 5/8 in. thick, 4 ft wide gypsum board, installed with long
dimension perpendicular to joists. Gypsum board secured with 1 in. long No. 6 Type W bugle head
steel screws spaced 12 in. OC and located a min of 1-1/2 in. from side and end joints. The joints of
the gypsum board are to be staggered a minimum of 12 inches from the joints of the subfloor.
GEORGIA-PACIFIC GYPSUM L L C — Type DS
Floor Mat Materials* — (As an alternate to the single layer gypsum board) — Floor mat material
loose laid over the subfloor.
MAXXON CORP — Type Encapsulated Sound Mat.
Gypsum Board* — (For use when floor mat is used) Two layers of nom 5/8 in. thick, 4 ft wide
gypsum board, installed with long dimension perpendicular to joists on top of the floor mat material.
Gypsum board secured to each other with 1 in. long No. 6 Type G bugle head steel screws spaced 12
in. OC and located a min of 1-1/2 in. from side and end joints. The joints of the gypsum board are to
be staggered a minimum of 12 inches in between layers and from the joints of the subfloor.
GEORGIA-PACIFIC GYPSUM L L C — Type DS
System No. 14
Finish Flooring — Floor Topping Mixture* — Min 3/4 in. thickness of floor topping mixture having
a min compressive strength of 1000 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
DEPENDABLE LLC — GSL M3.4, GSL K2.6, GSL-CSD and GSL RH.
Floor Mat Materials* — (Optional) — Nom. 1/4 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 3/4 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 55/025 and Quiet Qurl 55/025 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 3/8 in. thick loose laid
over the subfloor. Floor topping thickness shall be a minimum of 1 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 60/040 and Quiet Qurl 60/040 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 3/4 in. thick loose laid
over the subfloor. Floor topping thickness shall be a minimum of 1-1/2 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 65/075, Quiet Qurl 65/075 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 1/8 in. thick loose laid
over the subfloor. Floor topping thickness shall be a minimum of 3/4 in.
KEENE BUILDING PRODUCTS CO INC — Type Quiet Qurl 52/013 and Quiet Qurl 52/013 N
Alternate Floor Mat Materials* — (Optional) — Floor mat material Nom. 1/4 in. entangled net core
with a compressible fabric attached to the bottom loose laid over the subfloor. Floor topping
thickness shall be a minimum of 1 in.
KEENE BUILDING PRODUCTS CO INC — Quiet Qurl 55/025 MT and Quiet Qurl 55/025 N MT
System No. 15
Vapor Barrier — (Optional) — Commercial asphalt saturated felt, 0.030 in. thick.
Vapor Barrier — (Optional) — Nom 0.010 in. thick commercial rosin-sized building paper.
Finish Flooring* — Min 3/4 in. thickness of any Floor Topping Mixture bearing the UL Classification
Marking as to Fire Resistance. See Floor- and Roof-Topping Mixtures (CCOX) category for names of
Classified Companies.
Floor Mat Materials* — (Optional) — Nom 3/32 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 3/4 in.
PLITEQ INC — Type GenieMat RST02
Floor Mat Materials* — (Optional) — Nom 3/16 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 3/4 in.
PLITEQ INC — Type GenieMat FF03NP
Floor Mat Materials* — (Optional) — Nom 1/4 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 3/4 in.
PLITEQ INC — Type GenieMat FF06
Floor Mat Materials* — (Optional) — Nom 3/8 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 1 in.
PLITEQ INC — Type GenieMat FF10
Floor Mat Materials* — (Optional) — Nom 3/4 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 1-1/2 in.
PLITEQ INC — Type GenieMat FF17
Floor Mat Materials* — (Optional) — Nom 1 in. thick loose laid over the subfloor. Floor topping
thickness shall be a minimum of 1-1/2 in.
PLITEQ INC — Type GenieMat FF25
System No. 16
Finish Flooring* — Floor Topping Materials — Min 3/4 in. to 1-1/2 in. thickness of any Floor
Topping Mixture bearing the UL Classification Marking as to Fire Resistance with a minimum
compressive strength of 1500 psi.
See Floor- and Roof-Topping Mixtures (CCOX) category for names of Classified Companies. Refer
to the manufacturer’s instructions accompanying the material and/or contact the manufacturer’s
technical support for specific mix design and minimum thickness recommended for use with eligible
floor mat(s).
Floor Mat Materials* — (Optional) — Floor mat material nom 1/8 in. to 3/4 in. thick. Loose laid over
the subfloor. When used, Acousti-flor CSM (crack suppression mat) is loose laid over the floor mat
material. Floor topping material thickness is dependent on thickness of floor mat used.
WALFLOR INDUSTRIES INC — Type Acousti-flor, Acousti-flor CSM. Floor topping thickness
depends on products used as follows:
Acousti-flor (1/8 in. thick) - Floor topping thickness shall be a minimum of 3/4 in.
Acousti-flor (1/4 in. thick) - Floor topping thickness shall be a minimum of 1 in.
Acousti-flor (3/8 in. thick) - Floor topping thickness shall be a minimum of 1 in.
Acousti-flor (3/4 in. thick) - Floor topping thickness shall be a minimum of 1-1/2 in.
Metal Lath — (Optional) — Expanded steel diamond mesh, 2.5 lb / sq yd loose laid over floor mat
material.
Fiberglass Mesh Reinforcement — (Optional) — Coated non-woven glass fiber mesh grid loose
laid over floor mat material.
System No. 17
Finish Flooring - Floor Topping Mixture* — Min 1 in. thickness of floor topping mixture having a
min compressive strength of 4500 psi. Refer to manufacturer's instructions accompanying the
material for specific mix design.
SIKA DEUTSCHLAND GMBH — Type SCHONOX AP Rapid Plus
System No. 18
Vapor Barrier — (Optional) - Commercial asphalt saturated felt, 0.030 in. thick.
Vapor Barrier — (Optional) - Nom 0.010 in. thick commercial rosin-sized building paper.
Finish Flooring - Floor Topping Mixture* — Min 3/4 in. thickness of any Floor Topping Mixture
bearing the UL Classification Marking as to Fire Resistance. See Floor- and Roof-Topping Mixtures
(CCOX) category for names of Classified Companies. Refer to the manufacturer’s instructions
accompanying the material and/or contact the manufacturer’s technical support for specific mix
design and minimum thickness recommended for use with eligible floor mat(s).
Floor Mat Materials* — (Optional, Not Shown) - Floor mat material loose laid over the subfloor.
Refer to manufacturer's instructions regarding the minimum thickness of floor topping over each
floor mat material.
LOW & BONAR INC — EnkaSonic® by Colbond a member of the Low & Bonar group Types 125,
250, 250 Plus, 400, 400 Plus, 750, and 750 Plus.
Floor Mat Reinforcement — (Optional) - Refer to manufacturer's instructions regarding minimum
thickness of floor topping for use with floor mat reinforcement.
Metal Lath — (Optional) — Expanded steel diamond mesh, 2.5 lb / sq yd loose laid over floor mat
material.
Fiberglass Mesh Reinforcement — (Optional) — Coated non-woven glass fiber mesh grid loose
laid over floor mat material.
6. Wood Joists — Min 2 by 10, spaced 24 in. OC and effectively fireblocked in accordance with local
codes.
7. Horizontal Bridging — Used in same joist bay as ceiling damper (Item 8), when ceiling damper is
employed. Wood 2 by 4 in. secured between joists with nails.
8. Ceiling Damper* — (Optional) — Max nom area shall be 198 sq in. Max rectangular size shall be
12 in. wide by 16-1/2 in. long. Max height of damper shall be 8-3/4 in. Aggregate damper openings
shall not exceed 99 sq in. per 100 sq ft of ceiling area. Damper installed in accordance with the
manufacturers installation instructions provided with the damper. A steel grille (Item 12) shall be
installed in accordance with installation instructions.
AIR KING VENTILATION PRODUCTS — Series FRAS, Series FRAK, Series FRAKV
CENTRAL VENTILATION SYSTEMS CO L L C — Models C-S/R-HC(-A), C-RD-HC(-A)
GREENHECK FAN CORP — Model CRD-1WJ
METAL-FAB INC — Models MSCDHC, MRCDHC
METAL INDUSTRIES INC — Models CD-S/R-HC, CD-S/R-HC-A, CD-RD-HC, CD-RD-HC-A
NCA MFG INC — Models CD-S/R-HC, CD-S/R-HC-A, CD-RD-HC, CD-RD-HC-A
BRISK MFG INC — Model BMI-50-CRD-S/R-WT
PRICE INDUSTRIES LTD — Models CD-S/R-HC, CD-RD-HC
RUSKIN COMPANY — Model CFD7
UNITED ENERTECH CORP — Models C-S/R-HC(-A), C-RD-HC(-A)
9. Batts and Blankets* — (Optional, Not Shown) — For use with Steel Framing Members* (Item
10C only) and Gypsum Board* (Item 11A only) or for use with Steel Framing Members* (Item 10
only) and Gypsum Board* (Item 11E only) - Any thickness mineral wool or glass fiber insulation
bearing the UL Classification Marking for Surface Burning Characteristics, having a flame spread
index of 25 or less and a smoke spread index of 50 or less. Insulation fitted in the concealed space,
draped over steel framing members/gypsum board ceiling membrane.
9A. Batts and Blankets* — For Use With Items 10G and 11C only — Glass fiber insulation draped
over the resilient channel/gypsum panel ceiling membrane. Max. 3-1/2 in. thickness of glass fiber
insulation bearing the UL Classification Marking as to Surface Burning Characteristics and/or Fire
Resistance having a min. density of 0.5 pcf.
9B. Batts and Blankets* — (Optional, Not Shown) — For use with Steel Framing Members* (Item
10K only) and Gypsum Board* Item 11D only) - min. 3-1/2 in. thick min. density 0.9 lb/ft3 unfaced
fiberglass batt insulation bearing the UL Classification Marking for Surface Burning Characteristics,
having a flame spread value of 25 or less and a smoke spread value of 50 or less. Insulation fitted in
the concealed space, draped over steel framing members/gypsum board ceiling membrane and light
fixture protection.
10. Resilient Channels — Formed of No. 25 MSG galv steel spaced 16 in. OC perpendicular to joists.
Channels butted at splice, centered on joist and fastened to each joist with 1-7/8 in. long 6d cement-
coated nails. Additional resilient channels positioned so as to coincide with end joints of gypsum
board (Item 11), spaced 8 in. from other channels. Additional channels shall extend beyond each side
edge of board.
10A. Steel Framing Members* — (Not Shown) — As an alternate to Item 10, main runners nom 12
ft long spaced 48 in. OC. Cross tees nom 4 ft long installed perpendicular to main runners and
spaced 16 in. OC. Additional cross tees located 8 in. from and on each side of gypsum board end
joints. Main runners suspended by min 12 SWG galv steel hanger wires spaced 48 in. OC. Hanger
wires to be located adjacent to main runner/cross tee intersections. Hanger wires wrapped and twist-
tied on 16d nails driven into the side of joists at least 5 in. above the joist bottom face.
ROXUL USA INC. D/B/A ROCKFON — Types 650, 650C, 670, 670C
10B Steel Framing Members* — (Not Shown) — As an alternate to Item 10, main runners nom 12
ft long, spaced 48 in. OC. Ends of main runners at walls to rest on wall angle, without attachment,
with 1/2 to 3/4 in. end clearance. Primary cross tees (1-1/2 in. wide across flange) or cross channels,
nom 4 ft long, installed perpendicular to main runners and spaced 16 in. OC. Additional primary
cross tees or cross channels required at each gypsum board end joint and 8 in. from and on each
side of gypsum board end joint.
ARMSTRONG WORLD INDUSTRIES INC — Type DFR-8000
10C. Steel Framing Members* — (Not Shown) — As an alternate to Item 10, main runners, cross
tees, cross channels and wall angle as listed below:
a. Main Runners — Nom 10 or 12 ft. long, 15/16 in. or 1-1/2 in. wide face, spaced 4 ft OC. Main
runners suspended by min 12 SWG galv steel hanger wires spaced 48 in. OC. Hanger wires to be
located adjacent to main runner/cross tee intersections. Hanger wires wrapped and twist-tied on 16d
nails driven in to the side of joists at least 5 in. above the bottom face.
b. Cross Tees — Nom 4 ft. long, 1-1/2 in. wide face, installed perpendicular to the main runners,
spaced 16 in. OC. When Batts and Blankets* (Item 9) are used, cross tees spaced 16 in. OC. Additional
cross tees or cross channels used at 8 in. from each side of butted gypsum board end joints. The
cross tees or cross channels may be riveted or screw attached to the wall angle or channel to
facilitate the ceiling installation.
c. Cross Channels — Nom 4 ft. long, installed perpendicular to main runners, spaced 16 in. OC.
When Batts and Blankets* (Item 9) are used, cross channels spaced 16 in. OC.
d. Wall Angle or Channel — Painted or galv steel angle with 1 in. legs or channel with 1 in. legs, 1-
9/16 in. deep attached to walls at perimeter of ceiling with fasteners 16 in. OC. To support steel
framing member ends and for screw-attachment of the gypsum board.
CGC INC — Type DGL or RX.
USG INTERIORS LLC — Type DGL or RX.
10D. Steel Framing Members* — (Not Shown) — As an alternate to Item 10, furring channels
and Steel Framing Members* as described below:
a. Furring Channels — Formed of No. 25 MSG galv steel, 2-9/16 in. or 2-23/32 in. wide by 7/8 in.
deep, spaced 16 in. OC perpendicular to joists. Channels secured to joists as described in Item b.
Ends of adjoining channels overlapped 6 in. and tied together with double strand of No. 18 SWG
galv steel wire near each end of overlap.
b. Steel Framing Members* — Used to attach furring channels (Item a) to joists (Item 6). Clips
spaced 48 in. OC., RSIC-1 and RSIC-1 (2.75) clips secured to alternating joists with No. 8 x 2-1/2 in.
coarse drywall screw through the center grommet. RSIC-V and RSIC-V (2.75) clips secured to
alternating joists with No. 8 x 1-1/2 in. coarse drywall screw through the center hole. Furring
channels are friction fitted into clips. RSIC-1 and RSIC-V clips for use with 2-9/16 in. wide furring
channels. RSIC-1 (2.75) and RSIC-V (2.75) clips for use with 2-23/32 in. wide furring channels.
Adjoining channels are overlapped as described in Item a. As an alternate, ends of adjoining
channels may be overlapped 6 in. and secured together with two self-tapping No. 6 framing screws,
min 7/16 in. long at the midpoint of the overlap, with one screw on each flange of the channel.
Additional clips required to hold furring channel that supports the gypsum board butt joints, as
described in Item 11.
PAC INTERNATIONAL L L C — Types RSIC-1, RSIC-V, RSIC-1 (2.75), RSIC-V (2.75)
10E. Steel Framing Members* — (Not Shown) — As an alternate to Item 10. For use in corridors or
rooms having a maximum width dimension of 14 ft. Steel framing members consist of grid runners,
locking angle wall molding and hanger bars. Locking angle wall molding secured to walls with steel
nails or screws spaced max 24 in. OC. Slots of locking angle wall molding parallel with hanger bars to
be aligned with tabbed cutouts in bottom edge of hanger bars. Hanger bars spaced max 50 in. OC
and suspended with No. 12 AWG steel hanger wires spaced max 48 in. OC. Adjoining lengths of
hanger bar to overlap 12 in. and to be secured together and suspended by a shared hanger wire. A
min clearance of 1/4 in. shall be maintained between the ends of the hanger bars and the walls. Grid
runners cut-to-length and installed perpendicular to hanger bars and spaced max 16 in. OC with
additional grid runners installed 8 in. OC at gypsum board end joints. Grid runners parallel with walls
to be spaced max 16 in. from wall. Ends of grid runners to rest on and engage slots of locking angle
wall molding with a clearance of 3/8 in. to 1/2 in. maintained between each end of the grid runner
and the wall. Bulb of grid runner to be captured by tabbed cutouts in bottom edge of hanger bars.
ARMSTRONG WORLD INDUSTRIES INC — Type DFR-8000-SS
10F. Steel Framing Members* — (Not Shown) — As an alternate to Item 10. Main runners nom 12
ft long, spaced 72 in. OC. Cross tees, nom 6 ft long, installed perpendicular to main runners and
spaced 24 in. OC. Additional 6 ft long cross tees required at each gypsum board end joint with
butted gypsum board end joints centered between cross tees spaced 8 in. OC. The main runners and
cross tees may be riveted or screw-attached to the wall angle or channel to facilitate the ceiling
installation.
ARMSTRONG WORLD INDUSTRIES INC — Type DFR-8000
10G. Resilient Channels — (Not Shown)- As an alternate to Item 10. Resilient channels, formed from
No. 25 MSG galv steel and shaped as shown, spaced 12 in. OC perpendicular to joist. Channels
overlapped 4 in. at splices and secured to each joist with 1-1/4 in. Type S screws. Min end clearance
of channels to wall to be 1/2 in. Additional resilient channels positioned so as to coincide with end
joints of gypsum board (Item 11B and 11C). Channels oriented opposite at wallboard butt joints
spaced 6 in. OC.
10H. Steel Framing Members* — (Not Shown) — As an alternate to Items 10, 10A, 10B, 10C, 10D,
10E, 10F, 10G furring channels and Steel Framing Members* as described below:
a. Furring Channels — Formed of No. 25 MSG galv steel, 2-3/8 in. wide by 7/8 in. deep, spaced 16
in. OC perpendicular to joists. Channels secured to joists as described in Item b. Ends of adjoining
channels overlapped 6 in. and tied together with double strand of No. 18 SWG galv steel wire near
each end of overlap.
b. Steel Framing Members* — Used to attach furring channels (Item a) to joists (Item 6). Clips
spaced 48 in. OC., GenieClips secured to alternating joists with No. 8 x 2-1/2 in. coarse drywall screw
through the center grommet. Furring channels are friction fitted into clips. Adjoining channels are
overlapped as described in Item a. As an alternate, ends of adjoining channels may be overlapped 6
in. and secured together with two self-tapping No. 6 framing screws, min 7/16 in. long at the
midpoint of the overlap, with one screw on each flange of the channel. Additional clips required to
hold furring channel that supports the gypsum board butt joints, as described in Item 11.
PLITEQ INC — Type GENIECLIP
10I. Steel Framing Members* — (Not Shown) — As an alternate to Item 10, furring channels and
Steel Framing Members as described below.
a. Furring Channels — Formed of No. 25 MSG galv steel, 2-5/8 in. wide by 7/8 in deep, spaced 16 in
OC, perpendicular to joists. Channels secured to joists as described in Item b.
b. Steel Framing Members* — Used to attach furring channels (Item a) to the wood joists (Item 2).
Clips spaced at 48" OC and secured to the bottom of the joists with one 2 in. Coarse Drywall Screw
with 1 in. diam washer through the center hole. Furring channels are then friction fitted into clips.
Ends of channels are overlapped 6" and tied together with double strand of No. 18 AWG galvanized
steel wire. Additional clips are required to hold the Gypsum Butt joints as described in Item 11.
STUDCO BUILDING SYSTEMS — RESILMOUNT Sound Isolation Clips - Type A237 or A237R
10J. Steel Framing Members* — (Not Shown) — As an alternate to Item 10. Main runners nom 12 ft
long, spaced 72 in. OC. Main runners suspended by min 12 SWG galv steel hanger wires spaced 48
in. OC. Cross tees, nom 6 ft long, installed perpendicular to main runners and spaced 24 in. OC.
Additional 6 ft long cross tees required at each gypsum board end joint with butted gypsum board
end joints centered between cross tees spaced 8 in. OC. The main runners and cross tees may be
riveted or screw attached to the wall angle or channel to facilitate the ceiling installation.
USG INTERIORS LLC — Type DGL or RX.
10K. Steel Framing Members* — (Not Shown) — As an alternate to Item 10 Main runners nom 12 ft
long, spaced 48 in. OC. Cross tees, nom 4 ft. long, installed perpendicular to main runners and
spaced 24 in. OC. Additional 4 ft. long cross tees required at 6 in. from each side of butted gypsum
board end joints. When Batts and Blankets* (Item 9B) are used, cross tees spaced 16 in. OC with
additional cross tees 8 in. away from each side of butted gypsum board end joints. The cross tees
shall be riveted with 1/8 in. dia. rivets to the wall angle and to the main tee where the cross tee does
not align with slot in the main tee. Galvanized steel wall angle with 1-1/2 in. legs attached to walls at
perimeter of ceiling with fasteners at 16 in. OC. to support steel framing member ends and for screw-
attachment of the gypsum board.
CERTAINTEED CORP — Types DWS12-13-20, DWS4.16-13-20, DWS4-13-20, DWS2-13-20,
DWS2.16-13-20 and DWA1.5-1.5
CERTAINTEED CORP — Types EZDWS12-13-18, EZDWS4.16-13-18, EZDWS4-13-18, EZDWS2-13-18,
EZDWS2.16-13-18 and DWA1.5-1.5
10L. Framing Members* — (Not Shown) — As an alternate to Item 10. Main runners nom 12 ft long,
spaced 72 in. OC. Main runners suspended by min 12 SWG galv steel hanger wires spaced 48 in. OC.
Cross tees, nom 6 ft long, installed perpendicular to main runners and spaced 16 in. OC. Additional 6
ft long cross tees required at each gypsum board end joint with butted gypsum board end joints
centered between cross tees spaced 8 in. OC. The main runners and cross tees may be riveted or
screw attached to the wall angle or channel to facilitate the ceiling installation.
ROXUL USA INC. D/B/A ROCKFON — Type 670C
10M. Steel Framing Members* — (Not Shown) — As an alternate to Item 10, furring channels and
Steel Framing Members as described below.
a. Furring Channels — Formed of No. 25 MSG galv steel, 2-1/2 in. wide by 7/8 in deep, spaced 16 in
OC, perpendicular to joists. Channels secured to joists as described in Item b.
b. Steel Framing Members* — Used to attach furring channels (Item a) to the wood joists (Item 2).
Clips spaced at 48" OC and secured to the bottom of the joists with one 2-1/2 in. Coarse Drywall
Screw with 1 in. diam washer through the center hole. Furring channels are then friction fitted into
clips. Ends of channels are overlapped 6" and tied together with double strand of No. 18 AWG
galvanized steel wire. Additional clips are required to hold the Gypsum Butt joints as described in
Item 11.
REGUPOL AMERICA — Type SonusClip
10N. Steel Framing Members* — (Optional, Not Shown) — As an alternate to Item 10.
a. Furring Channels — Formed of No. 25 MSG galv steel, nominal 2-1/2 in. wide by 7/8 in. deep,
spaced 16 in. OC, perpendicular to the joists. Channels secured to Cold Rolled Channels at every
intersection with a 3/4 in. TEK screw through each furring channel leg. Ends of adjoining channels
overlapped 12 in. and fastened together with two double strand No. 18 SWG galv steel wire ties, one
at each end of overlap, or with two 3/4 in. TEK screws in each leg of the overlap section. Two furring
channels positioned 3 in. OC, 1-1/2 in. on each side of gypsum board (Item 11) end joints, each
extending a min of 6 in. beyond both side edges of the board.
b. Cold Rolled Channels — 1-1/2 in. by 1/2 in., formed from No. 16 ga. galv steel, positioned
vertically and parallel to joists, friction-fitted into the channel caddy on the Steel Framing Members
(Item 10Nc) and secured with two 3/4 in. TEK screws. Adjoining lengths of cold rolled channels
lapped min. 12 in. and secured along bottom legs with four 3/4 in. TEK screws and wire-tied together
with two double strand 18 SWG galv steel wire ties, one at each end of overlap.
c. Steel Framing Members* — Spaced 48 in. OC. max along joist, and secured to the joist on
alternating joists with two, #10 x 1-1/2 in. screws through mounting holes on the hanger bracket.
PAC INTERNATIONAL L L C — Type RSIC-SI-CRC EZ Clip
10O. Steel Framing Members* — (Optional, Not Shown) — As an alternate to Item 10.
a. Furring Channels — Formed of No. 25 MSG galv steel, nominal 2-1/2 in. wide by 7/8 in. deep,
spaced 16 in. OC perpendicular to joists and friction fit into Steel Framing Members (Item 10Ob).
Ends of adjoining channels overlapped 6 in. and tied together with double strand of No. 18 SWG
galv steel wire near each end of overlap or with two TEK screws along each leg of the 6 in. overlap.
Two furring channels positioned 6 in. OC, 3 in. on each side of gypsum board (Item 11) end joints.
Butt joint channels held in place by strong back channels placed upside down, on top of, and
running perpendicular to primary furring channels, extending 6 in. longer than length of gypsum side
joint. Strong back channels spaced maximum 48 in. OC. Strong back channels secured to every
intersection of primary furring channels with four 7/16 in. pan head screws, two along each of the
legs at intersections. Butt joint channels run perpendicular to strong back channels and shall be
minimum 6 in. longer than length of joint, secured to strong back channels with 7/16 in. pan head
screws, two along each of the legs at intersection with strong back channels.
b. Steel Framing Members* — Used to attach furring channels (Item 10Oa) to joists. Clips spaced
48 in. OC and secured along joist webs at each furring channel intersection with min. 3/4 in. long
self-drilling #10 x 1-1/2 in. screws through each of the provided hole locations. Furring channels are
friction fitted into clips.
PAC INTERNATIONAL L L C — Type RSIC-S1-1 Ultra
10P. Steel Framing Members* — (Optional, Not Shown) — Used as an alternate method to attach
resilient channels to structural members. A resilient sound isolation accessory shall be used at each
attachment point of the resilient channels and spaced max 24 in. O.C. Channel ends butted and
centered under the structural members and attached with one accessory at each end. Additional
accessories used to hold resilient channels that support the gypsum board end joints. The accessory
envelops the mounting edge of the resilient channel. The accessory and resilient channel are
fastened to the structural members with the screws supplied with the accessory and per the
accessory manufacturer's installation instructions. Gypsum Board butt joints staggered minimum 24
in. OC and Gypsum Board screws spaced 8 in. OC when used.
PAC INTERNATIONAL L L C — Types RC-1 Boost
11. Gypsum Board* — Nom 5/8 in. thick by 4 ft wide gypsum board. When resilient channels (Item
10) are used, gypsum board installed with long dimension perpendicular to resilient channels and
edge joints located between wood joists. Gypsum board secured to resilient channels with 1 or 1-1/4
in. long Type S bugle head screws spaced 12 in. OC in field and 8 in. OC along end joints. End joints
of gypsum board similarly fastened to additional resilient channels positioned at end joint locations.
Screws located 3/4 in. from side joints and 1/2 in. from end joints.
When Steel Framing Members* (Items 10A, 10B or 10C) are used, gypsum board installed with long
dimension perpendicular to cross tees with side joints centered along main runners and end joints
centered along cross tees. Gypsum board secured to cross tees with 1 in. long Type S bugle head
screws spaced 12 in. OC in the field and 8 in. OC along end joints. Gypsum board also secured to
main runners with 1 in. long Type S bugle head screws midway between cross tees. Screws along
sides and ends of boards spaced 3/4 to 1/2 in. from board edge. End joints of the sheets shall be
staggered with spacing between joints on adjacent boards not less than 4 ft OC.
When Steel Framing Members* (Items 10D, 10H) are used, gypsum board installed with long
dimension perpendicular to furring channels and side joints of sheet located beneath joists. Nom 1
or 1-1/4 in. long Type S bugle head screws are driven through channel spaced 12 in. OC in the field.
Gypsum board butt joints shall be staggered min. 2 ft. within the assembly, and occur between the
main furring channels. At the gypsum board butt joints, each end of each gypsum board shall be
supported by a single length of furring channel equal to the width of the gypsum board plus 6 in. on
each end. The two furring channels shall be spaced approximately 3-1/2 in. OC, and be attached to
underside of the joist with one clip at each end of the channel. Screw spacing along the butt joint to
attach the wallboard to the furring channels shall be 8 in. OC.
When alternate Steel Framing Members* (Item 10E) are used, gypsum board sheets installed with
long dimension (side joints) perpendicular to the grid runners with the end joints staggered min 4 ft
and centered between grid runners which are spaced 8 in. OC. Prior to installation of the gypsum
board sheets, backer strips consisting of nom 7-3/4 in. wide by 48 in. long pieces of gypsum board
are to be laid atop the grid runner flanges and centered over each butted end joint location. The
backer strips are to be secured to the flanges of the grid runners at opposite corners of the backer
strip to prevent the backer strips from being uplifted during screw-attachment of the gypsum board
sheets. Gypsum board fastened to grid runners with drywall screws spaced 1 in. and 4 in. from the
side joints and max 8 in. OC in the field of the board. The butted end joints are to be secured to the
backer strip with No. 10 by 1-1/2 in. long Type G laminating screws located 1 in. from each side of
the butted end joint and spaced 1 in. and 4 in. from the side joints and max 8 in. OC in the field of
the board.
When alternate Steel Framing Members* (Item 10F) are used, gypsum board sheets installed with
long dimension (side joints) perpendicular to the 6 ft long cross tees with the end joints staggered
min 4 ft and centered between cross tees which are spaced 8 in. OC. Gypsum board side joints may
occur beneath or between main runners. Prior to installation of the gypsum board sheets, backer
strips consisting of nom 7-3/4 in. wide pieces of gypsum board are to be laid atop the cross tee
flanges and centered over each butted end joint location. The backer strips are to be secured to the
flanges of the cross tees at opposite corners of the backer strip to prevent the backer strips from
being uplifted during screw-attachment of the gypsum board sheets. Gypsum board fastened to
cross tees with drywall screws spaced 1 in. and 4 in. from the side joints and max 8 in. OC in the field
of the board. The butted end joints are to be secured to the backer strip with No. 10 by 1-1/2 in.
long Type G laminating screws located 1 in. from each side of the butted end joint and spaced 1 in.
and 4 in. from the side joints and max 8 in. OC in the field of the board.
When Steel Framing Members (Item 10I) are used, one layer of nom 5/8 in. thick, 4 ft wide gypsum
board is installed with long dimensions perpendicular to furring channels. Gypsum board secured to
furring channels with nom 1 in. long Type S bugle-head steel screws spaced 8 in. OC in the field of
the board. Gypsum board butted end joints shall be staggered minimum 48 in. and centered over
main furring channels. At the gypsum board butt joints, each end of each gypsum board shall be
supported by a single length of furring channel equal to the width of the gypsum board plus 3 in. on
each end. The two support furring channels shall be spaced approximately 3 in. in from joint. Screw
spacing along the gypsum board butt joint and along both additional channels shall be 8 in. OC.
Additional screws shall be placed in the adjacent section of gypsum board into the aforementioned 3
in. extension of the extra butt joint channels as well as into the main channel that runs between. Butt
joint furring channels shall be attached with one RESILMOUNT Sound Isolation Clip at each end of
the channel.
When alternate Steel Framing Members* (Item 10J and 10L) are used, gypsum board sheets
installed with long dimension (side joints) perpendicular to the 6 ft long cross tees with the end
joints staggered min 4 ft and centered between cross tees which are spaced 8 in. OC. Gypsum board
side joints may occur beneath or between main runners. Prior to installation of the gypsum board
sheets, backer strips consisting of nom 7-3/4 in. wide pieces of gypsum board are to be laid atop the
cross tee flanges and centered over each butted end joint location. The backer strips are to be
secured to the flanges of the cross tees at opposite corners of the backer strip with hold down clips
to prevent the backer strips from being uplifted during screw-attachment of the gypsum board
sheets. Gypsum board fastened to cross tees with 1 in. drywall screws spaced 1 in. and 4 in. from the
side joints and max 8 in. OC in the field of the board. The butted end joints are to be secured to the
backer strip with No. 10 by 1-1/2 in. long Type G laminating screws located 1 in. from each side of
the butted end joint and spaced 1 in. and 4 in. from the side joints and max 8 in. OC in the field of
the board.
When Steel Framing Members (Item 10M) are used, one layer of nom 5/8 in. thick, 4 ft wide
gypsum board is installed with long dimensions perpendicular to furring channels. Gypsum board
secured to furring channels with nom 1 in. long Type S bugle-head steel screws spaced 8 in. OC in
the field of the board. Gypsum board butted end joints shall be staggered minimum 48 in. and
centered over main furring channels. At the gypsum board butt joints, an additional single length of
furring channel shall be installed and be spaced approximately 3 in. from the butt joint (6 in. from the
continuous furring channels) to support the floating end of the gypsum board. Each of these shorter
sections of furring channel shall extend one joist beyond the width of the gypsum panel and be
attached to the adjacent joists with one SonusClip at every joist involved with the butt joint.
When Steel Framing Members (Item 10N) are used, nom 5/8 in. thick, 4 ft wide gypsum board,
installed as described in Item 11. Adjacent butt joints staggered minimum 48 in. OC.
When Steel Framing Members (Item 10O) are used, nom 5/8 in. thick, 4 ft wide gypsum board,
installed as described in Item 11. Butt joints staggered minimum 24 in. OC.
AMERICAN GYPSUM CO — Type AG-C
CERTAINTEED GYPSUM INC — Type C
CGC INC — Type C
CERTAINTEED GYPSUM INC — Type LGFC-C/A
GEORGIA-PACIFIC GYPSUM L L C — Types 5, C, DAPC, TG-C
NATIONAL GYPSUM CO — Types eXP-C, FSK-C, FSW-C, FSW-G
PABCO BUILDING PRODUCTS L L C, DBA PABCO GYPSUM — Type C, PG-3 or PG-C
PANEL REY S A — Types PRC, PRC2
THAI GYPSUM PRODUCTS PCL — Type C
UNITED STATES GYPSUM CO — Type C
USG BORAL DRYWALL SFZ LLC — Type C
USG MEXICO S A DE C V — Type C
11A. Gypsum Board* — For use when Batts and Blankets* (Item 9) and Steel Framing
Members* (Item 10C) are used. Nom 5/8 in. thick, 4 ft wide gypsum board installed with long
dimension perpendicular to cross tees with side joints centered along main runners and end joints
centered along cross tees. Fastened to cross tees with 1 in. long Type S bugle head screws spaced 8
in. OC in the field and 8 in. OC along end joints. Fastened to main runners with 1 in. long Type S
bugle head screws spaced midway between cross tees. Screws along sides and ends of boards
spaced 3/8 to 1/2 in. from board edge. End joints of the sheets shall be staggered with spacing
between joints on adjacent boards not less than 4 ft OC.
CGC INC — Type C, ULIX
UNITED STATES GYPSUM CO — Type C, ULIX
USG BORAL DRYWALL SFZ LLC — Type C
USG MEXICO S A DE C V — Type C
11B. Gypsum Board* — For use when Batts and Blankets* (Item 9) and Resilient Channels (Item
10G) are used. Nom 5/8 in. thick, 4 ft wide gypsum board installed with long dimension
perpendicular to resilient channels. Nom 1 in. long No. Type S bugle head screws are driven through
channel spaced 8 in. OC. End joints of gypsum board similarly fastened to additional resilient
channels positioned at end joint locations.
CERTAINTEED GYPSUM INC — Type C
11C. Gypsum Board* — For use when Batts and Blankets* (Item 9A) and Resilient Channels (Item
10G) are used. Nom 5/8 in. thick, 4 ft wide gypsum board installed with long dimension
perpendicular to resilient channels. Nom 1 in. long No. Type S bugle head screws are driven through
channel spaced 8 in. OC. End joints of gypsum board similarly fastened to additional resilient
channels positioned at end joint locations.
AMERICAN GYPSUM CO — Type AG-C.
11D. Gypsum Board* — For use when alternate Steel Framing Members* (Item 10K) are used - 1/2
in. thick, 4 ft. wide; installed with long dimension parallel to main runners and perpendicular to the 4
ft. long cross tees with the end joints centered between cross tees which are spaced 6 in. OC. Sheets
are attached to cross tees with screws spaced 8 in. OC on the ends and 12 in. OC in the field with
additional screws located 1-1/2 in, from the side edges. Sheets are attached to the main tees with
screws spaced 8 in. OC with additional screws located 4 in. OC from the edges. Screws on the sides
are located 1/2 in. from the side edge of the gypsum board. When Batts and Blankets* (Item 9B) are
used - 5/8 in. thick, 4 ft wide; installed with long dimension parallel to main runners and
perpendicular to cross tees and attached with screws spaced 8 in. OC on the ends and 8 in. OC in the
field with additional screws located 1-1/2 in. from the side edges. Sheets are attached to main tees
with screws spaced 8 in. OC with additional screws located 4 in. OC from the side edges. Screws on
the sides located 3/4 in. from the side edge of the gypsum board, and screws at the end of the
gypsum board located 1/2 in. from the board ends. Joints to be covered with paper tape and joint
compound.
CERTAINTEED GYPSUM INC — Type C
11E. Gypsum Board* — (As an alternative to Item 11) Nom 5/8 in. thick, 48 in. wide gypsum board
installed, as described in Item 11, with max screw spacing 8 in. OC. When insulation is used
resilient/furring channels spaced max. 16 in. OC.
CGC INC — Type ULIX
UNITED STATES GYPSUM CO — ULIX
12. Finishing System — (Not Shown) — Vinyl, dry or premixed joint compound, applied in two
coats to joints and screw-heads. Nom 2 in. wide paper tape embedded in first layer of compound
over all joints. As an alternate, nom. 3/32 in. thick veneer plaster may be applied to the entire surface
of the gypsum board.
13. Grille — Steel grille installed in accordance with the installation instructions provided with the
ceiling damper.
14. Discrete Products Installed in Air-handling Spaces* — Automatic Balancing Valve/Damper —
(Not Shown - Optional) — For use with item 8, Ruskin Company's Model CFD7 damper (CABS).
Ceiling damper to be provided with plenum box per damper manufacturer's instructions with side
outlet only. Entire assembly to be installed into any UL Class 0 or Class 1 flexible air duct in
accordance with the instructions provided by the automatic balancing valve/damper manufacturer.
METAL INDUSTRIES INC — Model ABV-4, ABV-5, ABV-6
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions
employing the UL or cUL Certification (such as Canada), respectively.
Last Updated on 2022-02-04