HomeMy WebLinkAboutFile Documents.931 Gibson Ave.0037-2019-BRES (35)ENGR Round 1 Comments 10-22-2019 Page: C201 PROPOSED BASINS Date: 10/21/2019 10:01:17 AM File Name: 931 Gibson - Civil Plans.pdf Please depict flow arrows. 931 Gibson - Civil Plans.pdf (22) Page: C300 GRANDING & DRAINAGE W/ LA Date: 10/21/2019 10:24:17 AM File Name: 931 Gibson - Civil Plans.pdf Please only depict trees that are to remain on the site plan for clarity. Page: C300 GRANDING & DRAINAGE W/ LA Date: 10/12/2019 3:34:18 PM File Name: 931 Gibson - Civil Plans.pdf Please verify water utility will not conflict with proposed landscaping. Several driplines appear to overlap the alignment. Page: C300 GRANDING & DRAINAGE W/ LA Date: 10/22/2019 10:53:19 AM File Name: 931 Gibson - Civil Plans.pdf Proposed contours result in a 20% slope for the driveway. Please adjust grading in this area to have a maximum slope of 12%. Page: C300 GRANDING & DRAINAGE W/ LA Date: 10/21/2019 10:15:48 AM File Name: 931 Gibson - Civil Plans.pdf Transition needs to be longer. Please extend the transition further east to the next remaining dripline. Please depict flow arrows. W W W W W W W W W W 93 6 0+75 0+7 5 0 FT 7 9 3 5 0 Please only depict trees that are to remain on the site plan for clarity. OSW W W W +(35. 5 ) 4 0 . 5 0+2 5 BACK OF SIDEWALK ALIGNMENT 0+00 7937.74 TW : 7 9 3 6 . 1 6 @SE T B A C K BW : 7 9 3 5 . 1 9 7937.84 7 9 3 6 7 9 3 7 Please verify water utility will not conflict with proposed landscaping. Several driplines appear to overlap the alignment. W W W W DRIVEWAY TRENCH MIN LENGTH: 26' DRAIN COLLECT PR:1.0 7937 WAY CENTERLINE ALINGMENT0+69 0+50 1.0 0 % 2.5 0 % TW: 7 9 3 6 . 2 5 @SETBACK TW:7936.25 BW:7934.61 TD : 7 9 3 2 . 6 5 +79 3 2 . 7 7 +79 3 2 . 6 5 +:7 9 3 2 . 7 7 +79 3 2 . 5 0 932 . 2 5 7 9 3 4 TD 1 CONNECTION INV OUT:7931.32 4" PVC INLET 3 RIM:7932.25 INV IN:7931.26 4" PVC INV OUT:7931.26 4" PVC INLET 2 RIM:7937.01 INV OUT:7933.01 4" PVC 0+ 0 0 Proposed contours result in a 20% slope for the driveway. Please adjust grading in this area to have a maximum slope of 12%. W W W W 0+75 1+0 0 1+2 5 0+7 5 1+0 0 1.50 FT 5.00 FT 1.0 0 % 5.0 0 % 7 9 3 5 -2. 0 % +79 3 3 . 5 5 +79 3 3 . 5 5 +79 3 3 . 2 5 79 3 3 7 9 3 4 PR3.4 AND 3.9 CONNECTION RIM:7933.18 INV IN:7930.23 4" PVC INV OUT:7930.23 6" PVC PR3.10 CO Transition needs to be longer. Please extend the transition further east to the next remaining dripline. Please see EX1, attached. This exhibit demonstrates that at a 10-ft driveway width, the slope does not exceed 12%. Per our meeting, this is acceptable. Flow arrows have been added to show discharge from higher elevations to lower elevations. The water service has been located as far as possible from the existing tree and is located under existing impervious driveway area. Per our meeting, this is acceptable. We have lengthened the transition and updated the alignment. We are now only depicting proposed trees and existing trees. 01/22/2020 Page: C300 GRANDING & DRAINAGE W/ LA Date: 10/21/2019 10:16:45 AM File Name: 931 Gibson - Civil Plans.pdf Several existing and proposed tree driplines appear to overlap the proposed sewer lateral alignment. Please verify utilities will not be installed directly over or in close proximity to proposed landscaping. Page: C301 GRANDING & DRAINAGE Date: 10/21/2019 10:18:28 AM File Name: 931 Gibson - Civil Plans.pdf Please depict all connections with sizing and slope information. Page: C301 GRANDING & DRAINAGE Date: 10/22/2019 10:48:05 AM File Name: 931 Gibson - Civil Plans.pdf A 2' full section of asphalt must be removed and replaced to allow for construction of curb & gutter. Please depict full removal limits and milling limits on plans for all asphalt cuts. Page: C301 GRANDING & DRAINAGE Date: 10/21/2019 10:18:33 AM File Name: 931 Gibson - Civil Plans.pdf Please show roof drains and downspouts on the drainage plan. Clearly show how runoff is routed to the BMPs. Page: C301 GRANDING & DRAINAGE Date: 10/21/2019 10:36:57 AM File Name: 931 Gibson - Civil Plans.pdf Floating sidewalk detail is included, but limits of installation are not included within plans. Please include stationing for beginning and end of floating sidewalk. OSW S W W W W W W W W W W W W W W W W W W NEW 2" TYPE K COPPER W NEW TAP MIN 18" FROM OL ABANDON EXISTING SERV -2.0 % -2.0 % 79 3 6 79 3 7 7937 69 DRIVEWAY CENTERLINE ALIGNME 0+00 BACK OF SIDEWA 0+00 0+2 5 0+5 0 FLOWLINE ALIGNMENT 0+00 0+2 5 0+5 0 1.00 FT 4.00 FT 0% -2.0 % -2. 0 % -4.3 % -4.6 % -2. 0 % 7937.26 7937.60 7937.51 7937.77 7937.74 7937.35 7937.27 7937.53 7937.61 7937.03 TW: 7 9 3 6 . 16 FT 7937.68 0+30 ROAD CROSS-SECTION 0+00 7937.57 7937.07 7937.84 7937.71 7937.34 793 7 7 9 3 6 7 9 3 7 PR3.11 CONNECTION ALT 2 RIM:7937.01 INV OUT:7933.01 4" PVC 10 CONNECTION ALT 2 7935.00 N:7932.37 4" PVC OUT:7932.37 4" PVC 0+0 0 Several existing and proposed tree driplines appear to overlap the proposed sewer lateral alignment. Please verify utilities will not be installed directly over or in close proximity to proposed landscaping. 5 % 1.0 0 % 00% +79 3 4 . 7 5 793 2 . 5 0 + 793 2 . 7 5 + TW : 7 9 3 Please depict all connections with sizing and slope information. W W 25.00 FT 1+4 1 1+2 5 1+5 11+5 0 79 3 2 PR3.7 CONNECTION A 2' full section of asphalt must be removed and replaced to allow for construction of curb & gutter. Please depict full removal limits and milling limits on plans for all asphalt cuts. W 7 7937 END DRIVEWAY CENTERLINE ALINGMENT0+69 2.5 0 % 7 9 3 5 TD : 7 9 3 2 . 6 5 +79 3 2 . 7 7 +:7 9 3 2 . 7 7 +79 3 5 . 2 5 0+ 0 0 Please show roof drains and downspouts on the drainage plan. Clearly show how runoff is routed to the BMPs. W W W W W W W W W 79 3 6 +75 0+5 0 0+7 5 7 9 3 5 0+30 Floating sidewalk detail is included, but limits of installation are not included within plans. Please include stationing for beginning and end of floating sidewalk. The requested information is provided on the pipe profiles. Per our meeting, this is acceptable. The proposed sewer service has been moved slightly to the west and is now outside of the existing drip line. We have depicted the 2' section. Gutters are shown, connections are called out. Per our meeting, our existing annotation is acceptable. Stationing has been updated to indicate location of floating sidewalk. 01/22/2020 Page: C301 GRANDING & DRAINAGE Date: 10/22/2019 7:49:54 AM File Name: 931 Gibson - Civil Plans.pdf How is drainage handled within window well? Window wells must be free draining or tie to the stormwater BMP. Please verify. Page: C400 DRIVEWAY PLAN & PROFILE Date: 10/21/2019 10:20:48 AM File Name: 931 Gibson - Civil Plans.pdf Surface appears to have hump on south side of sidewalk. Appears to possibly be a bottoming out issue for vehicles. Page: C400 DRIVEWAY PLAN & PROFILE Date: 10/21/2019 10:22:52 AM File Name: 931 Gibson - Civil Plans.pdf Flowline must be outside of walking surface. Please provide detail to ensure sidewalk is outside flow conveyance. Page: C402 FLOWLINE PLAN & PROFILE Date: 10/21/2019 10:26:56 AM File Name: 931 Gibson - Civil Plans.pdf Please call out beginning station and end station for transition. Page: C402 FLOWLINE PLAN & PROFILE Date: 10/21/2019 10:38:09 AM File Name: 931 Gibson - Civil Plans.pdf Road cross section is not in plans. Cross sections need to be included for all remaining trees on the eastern side of the property to understand tree impacts per email on 8/8/19. ABANDONED 10' HOLY CROSS ELECTRIC EASEMENT 10.00 FT 10.00 FT 13.68 FT 1.0 0 % 3. 6 5 % 2 1.0 0 % 7932 . 5 0 + TW: 7 9 3 2 . 5 0 79 3 2 79 3 2 PR2.0 AND 2.1 CONNECTION RIM:7931.83 CLEANOUT 4 PR3.5 AND 3.6 CONNECTION RIM:7932.48 INV IN:7930.38 6" PVC INV IN:7930.38 4" PVC INV OUT:7930.38 6" PVC CLEANOUT 4 RIM:7932.42 INV IN:7930.24 6" PVC INV OUT:7930.24 6" PVC DEPTH: 17.67' WQCV REQUIRED (FS=1.5): 199 CF 100-YR RETENTION REQUIRED: 614 CF VOLUME PROVIDED: 653 CF INV IN:7929.50 6" PVC INV IN:7929.50 6" PVC 1+0 0 E N D P I P E A 1+ 3 6 1+4 1 How is drainage handled within window well? Window wells must be free draining or tie to the stormwater BMP. Please verify. 7937 7938 2.00% -9.1 2 % Surface appears to have hump on south side of sidewalk. Appears to possibly be a bottoming out issue for vehicles. El e v a t i o n 7935 7936 7937 7938 2.00% 9.12 % E Flowline must be outside of walking surface. Please provide detail to ensure sidewalk is outside flow conveyance. W W NEW 2" TYPE K COPPER WATER SERVICE NEW TAP MIN 18" FROM OLD ABANDON EXISTING SERVICE PER COA STANDARDS DRIVEWAY CENTERLINE ALIGNMENT 0+00 FLOWLINE ALIGNMENT 0+00 1'. 2.TRA CUR 3.SIDE EAS 4' W 4.CUR 1.5' C ALLO 0+75 5.SIDE A 5' ALLO 0+75 Please call out beginning station and end station for transition. 0+30 Road cross section is not in plans. Cross sections need to be included for all remaining trees on the eastern side of the property to understand tree impacts per email on 8/8/19. The hump is approximately 1.5". We did not find bottoming out to be a problem. See C400. Flowline is at driveway station 0+1.00, end of sidewalk is at station 0+5.67. Based on our site visit with Engineering and Parks, we determined the acceptable sidewalk widths. The drawings have been revised to show these widths. Window wells will drain to the foundation drain system. A typical window well detail has been added to C500. Stationing has been added. 01/22/2020 Page: C402 FLOWLINE PLAN & PROFILE Date: 10/21/2019 10:26:07 AM File Name: 931 Gibson - Civil Plans.pdf How is conveyance addressed at tie in location? Project must tie into existing curb and gutter to the west. Please clarify. Page: C402 FLOWLINE PLAN & PROFILE Date: 10/22/2019 8:52:20 AM File Name: 931 Gibson - Civil Plans.pdf Spread must be examined with curb and gutter per email on 8/8. Please include exhibits as needed to ensure spread meets requirements in Table 4.1 of the URMP for a collection road. If spread is great than maximum, addition of an inlet maybe required. Page: C500 DETAILS 1 Date: 10/21/2019 10:35:27 AM File Name: 931 Gibson - Civil Plans.pdf Need to include detail for 18" curb and gutter with a 8.3% gutter cross slope. This cross slope maximizes capacity in smaller than standard gutter. Page: C600 UTILITIES Date: 10/12/2019 3:08:05 PM File Name: 931 Gibson - Civil Plans.pdf Clarify what is happening with the existing sewer lateral. Is the existing being removed and replaced? Page: C600 UTILITIES Date: 10/21/2019 10:29:41 AM File Name: 931 Gibson - Civil Plans.pdf Vertical separation between water service and sanitary main must be examined. 18" minimum separation at crossing. Please provide information on plans that demonstrate this is possible. Elevation of sanitary line must be included. 25.00 FT 1+4 1 1+5 11+5 0 79 3 2 How is conveyance addressed at tie in location? Project must tie into existing curb and gutter to the west. Please clarify. W W W W W W W W W W W W 79 3 6 79 3 7 0+5 0 0+75 0+2 5 0+ 5 0 0+7 5 1.00 FT FT -2. 0 % 793 793 7 9 3 5 0+ ROAD CROSS-SECTION 0+00 7 7 Spread must be examined with curb and gutter per email on 8/8. Please include exhibits as needed to ensure spread meets requirements in Table 4.1 of the URMP for a collection road. If spread is great than maximum, addition of an inlet maybe required. Need to include detail for 18" curb and gutter with a 8.3% gutter cross slope. This cross slope maximizes capacity in smaller than standard gutter. S W W W W W W W W W W W T T T T T T T T T T T SANITARY SEW MANHOLE 1.00 FT Clarify what is happening with the existing sewer lateral. Is the existing being removed and replaced? OSW S W W W W W W W W W W W W W W W W W W W W W W W W W T T T T T T T T T T T T T T T T T T N N A 7937 1.00 FT 4.00 FT 16 FT Vertical separation between water service and sanitary main must be examined. 18" minimum separation at crossing. Please provide information on plans that demonstrate this is possible. Elevation of sanitary line must be included. Per our site visit, we are no longer required to provide curb and gutter west of the property line. The sewer line will be removed and replaced. Spread has been analyzed. Calcs and discussion have been added to the report. See additional detail C500. Crossing detail provided on C501 as discussed during our meeting. 01/22/2020 Page: C600 UTILITIES Date: 10/21/2019 10:31:55 AM File Name: 931 Gibson - Civil Plans.pdf Please depict new telephone pedestal location as well as appropriate electrical infrastructure at tie in location. Is there a transform with capacity in this location? Please provide electrical capacity verification. Page: C600 UTILITIES Date: 10/21/2019 11:40:52 AM File Name: 931 Gibson - Civil Plans.pdf The fire suppression letter states a 1.5" is sufficient. Please adjust plans to utilize a 1.5" K-copper line. Page: COVER & INDEX Date: 10/22/2019 8:11:15 AM File Name: 931 Gibson Temp Shoring Plans.pdf Plans must be stamped and signed by a Colorado Professional Engineer. 931 Gibson Temp Shoring Plans.pdf (6) Page: NOTES & DETAILS Date: 10/22/2019 8:10:35 AM File Name: 931 Gibson Temp Shoring Plans.pdf Provide substantiation for all soil parameters. Also note, the coefficient of friction does not appear to reflect the recommended value in the soil report, which states, "Resistance to sliding at the bottoms of the footings can be calculated based on a coefficient of friction of 0.45." Page: PLAN VIEW Date: 10/22/2019 8:05:07 AM File Name: 931 Gibson Temp Shoring Plans.pdf How will excavation occur for the 20' deep drywell in this corner of the property? Please clarify. E E E E ECT V CT V CT ELECTRIC METER CATV PED EXISTING BOULDER WALL EEEEE Please depict new telephone pedestal location as well as appropriate electrical infrastructure at tie in location. Is there a transform with capacity in this location? Please provide electrical capacity verification. R W 2" TYPE K COPPER WATER SERVICE W TAP MIN 18" FROM OLD ANDON EXISTING SERVICE PER COA STANDARDS The fire suppression letter states a 1.5" is sufficient. Please adjust plans to utilize a 1.5" K-copper line. 195 Lodgepole Circle Parachute, Colorado 81635 970-903-3028 www.rocksolidblasting.com on A v e S h o r i n g d I n d e x SHEET INDEX 1. COVER AND INDEX 2. NOTES AND DETAILS 3. PLAN VIEW 4. PROFILE AND SECTIONS RING WALLS EN, COLORADO Plans must be stamped and signed by a Colorado Professional Engineer. 2 CONTINUOU #4 BAR A36 STEEL PLATE 8"x8"x1 " 1.0 GENERAL NOTES 1.1 Per H-P Kumar report dated 6/29/2017 and Kumar and Associates report dated 4/4/2019, soils to be retained are assumed to be dense silty sand with gravel and scattered cobbles. Subsurface conditions may be discovered at the time of construction that may require modifications to this design. Conditions may include, but are not limited to, groundwater, trash debris, soil shear strength, and grout/soil pullout resistance. 1.2 Concrete/Shotcrete: fc' = 4,000 psi, 28-day unconfined compressive strength Grout: fc' = 3,000 psi, 28-day unconfined compressive strength Reinforcement Steel: Fy = 60,000 psi 1.3 Soil Parameters: ɸ = 35° c = 10 psf ɣ = 125 pcf Qa = 15 psi 1.4 Soil Nails will be Williams Form Geo-Drill bar or All-Thread Bar or equivalent as indicated in plans. Williams Form Couplers will be used as necessary. 1.6 Verification and/or proof tests may be conducted as determined in the field by the Engineer. 1.7 Cement grout will be installed in sufficient quantity to fully encapsulate the bar to the collar of the hole. 1.8 Groundwater is not anticipated. If groundwater is encountered during excavation, the excavation shall to prevent the flow of water into the excavation or behind the support of excavation. 1.12 These plans are not to be used for the layout of the lot or the proposed house. Survey of the proposed footer locations shall be complete prior to RSS personnel mobilizing to the site. 1.13 Survey and layout of wall by others. Excavation by others. 1.14 The temporary shoring system has been designed for a minimum factor of safety of 1.3 and a maximum design life of 3 months. The designed shoring system should show no observable deflection on neighboring properties. 1.15 These shoring plans are based on an Architectural site plan by F&M Architects dated 6/20/2019 and a foundation plan by Silver Town Structures dated 5/15/2019. 2.0 SOIL NAIL CONSTRUCTION 2.1 Locations and quantities of nails are approximate and will be finalized during construction. 2.2 The slope will be excavated in 4 or 5-foot stages (by others). 2.3 Construction Sequence 2.3.1 Excavate wall location (by others). 23.2 Drill and grout Soil Nail. Provide substantiation for all soil parameters. Also note, the coefficient of friction does not appear to reflect the recommended value in the soil report, which states, "Resistance to sliding at the bottoms of the footings can be calculated based on a coefficient of friction of 0.45." ED 1:1 0+00 How will excavation occur for the 20' deep drywell in this corner of the property? Please clarify. PLANS ARE NOW STAMPED SEE RESPONSE 2. ON 2019-10-31 RSS response to City of Aspen Comments.pdf Drywell location (per sheet C301) and shoring has been added to plan set dated10/23/19. The transformer will be replaced as necessary. See note as discussed during our meeting. The Telephone Ped will be relocated to the SE corner. Size has been changed to 1.5". 01/22/2020 Page: PLAN VIEW Date: 10/22/2019 8:06:30 AM File Name: 931 Gibson Temp Shoring Plans.pdf Please depict location and depth of utilities located within vicinity proposed system. Page: PLAN VIEW Date: 10/22/2019 8:09:29 AM File Name: 931 Gibson Temp Shoring Plans.pdf Please verify with geotechnical engineer that 1:1 slope is achievable. Page: PLAN VIEW Date: 10/22/2019 8:06:09 AM File Name: 931 Gibson Temp Shoring Plans.pdf Wall location appears to be within drip-lines of existing trees. Please obtain approval from Parks Department to locate wall here or adjust design. Page: 2 Date: 10/12/2019 3:56:51 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Signature, stamp, and date required. 931 Gibson_Civil_20190830_Report.pdf (15) Page: 3 Date: 10/12/2019 3:56:05 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Correct link errors. 2+00 WALL C ATCHED EA AT 1:1 2+20 Please depict location and depth of utilities located within vicinity proposed system. DIG HATCHED AREA AT 1:1 Please verify with geotechnical engineer that 1:1 slope is achievable. 1-SID AROU 75 1+35.75 1+28.5 1+132' 2' DIG HATCHED Wall location appears to be within drip-lines of existing trees. Please obtain approval from Parks Department to locate wall here or adjust design. License No. Signature, stamp, and date required. ................................................... 5 ................................................... 5 ................................................... 5 ................................................... 6 ................................................... 6 ................................................... 6 ................................................... 6 ................................................... 6 ................................................... 6 ................................................... 6 .... Error! Bookmark not defined. ................................................... 7 ................................................... 7 Correct link errors. Utility locations have been added to plan set dated 10/23/19. The water line will be below the soil nail wall or sleeved through the shotcrete facing. An estimate of the on-site soils was made by two Rock Solid Professional Engineers withspecialties in Geotechnical Engineering. A sloped configuration in accordance withOSHA Regulations 29CFR 1926 Subpart P Appendix B was selected for stability of thesoil on site. The on-site soil is estimated to be classified as Type B soil as defined in 1926Subpart P Appendix A. A 1:1 slope is allowed for Type B soils. If the soils on site arenot cohesive enough to allow this configuration, the Rock Solid Professional Engineer onsite will direct the excavation and stabilization team to modify the slope stabilizationarea. The Rock Solid engineers are comfortable with this situation and will be on site to monitor slope stability. Trees to be removed, per plan sheet L2.00, are shown in red on the plan set dated 10/23/19. Shoring walls are outside the drip lines of all trees that will remain. Signature, stamp, and date added. Corrected Link errors 01/22/2020 Page: 5 Date: 10/12/2019 4:22:08 PM File Name: 931 Gibson_Civil_20190830_Report.pdf NRCS web soil survey indicates soil Type 108-Uracca is HSG type B. Please revise. Page: 6 Date: 10/22/2019 8:27:57 AM File Name: 931 Gibson_Civil_20190830_Report.pdf Street may have capacity, but spread needs to be verified as per 8/8 email. Please include a section of calculations and exhibits that demonstrate the flooding spread of each storm event meets requirements of Table 4.1 of the URMP for a Collector street. Page: 6 Date: 10/21/2019 12:59:40 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Describe changes to land use, topography, ground cover, drainage patterns, and receiving systems, or if no change. No change to off-site drainage patterns, as described in Section 2.3, is noted. Page: 6 Date: 10/22/2019 8:27:44 AM File Name: 931 Gibson_Civil_20190830_Report.pdf The addition of curb and gutter affects the offsite drainage that currently drains onto property. This must be examined within the drainage report to ensure roadway meets standards. Page: 11 Date: 10/22/2019 8:30:03 AM File Name: 931 Gibson_Civil_20190830_Report.pdf Please touch on why a drywell it being utilized as it is a last resort BMP per the URMP. 1.Introduction This report was prepared to meet the requirements of a City of Aspen Engineering Department Grading and Drainage Report for a Major Design. The report was prepared for a single family housing project at 931 Gibson Avenue, Aspen,Colorado,81611 (the “Site”).Facilities providing water quality capture volume and retention have been designed in this report and the associated plan. 2.General Site Description 2.1 Existing Condition The property was address as 931 Gibson Avenue, Aspen. Based on the topographical improvement survey, the lot area is approximately 15,497 square feet. The Site is located on the east side of Aspen (see Figure 1). The NRCS describes the hydrologic soil group as “Type A”(See Appendix A). The lot is currently occupied by a single family apartment. NRCS web soil survey indicates soil Type 108-Uracca is HSG type B. Please revise. constructed. ntrolling triggers when determining the ea. Based on these two triggers, Woody pture volume (“WQCV”) and detention he southwest. Drainage basins are delin- The basins are described in the following described. e capacity to convey the 100-year event. 1, below, describes the impervious area, , basin slope, runoff coefficients for the s for the minor (10-yr) and major (100- eet C200 (Appendix C, C200), they are were evaluated for the Site using a time age patterns. onal) )Tc (min)Intensity (5yr) (in/hr) Intensity (10yr) (in/hr) Intensity (100yr) (in/hr) PEAK FLOW 5YR (CFS) PEAK FLOW 10YR (CFS) PEAK FLOW 100YR (CFS) 78 10.8778 2.3243 2.7964 4.4669 0.050 0.149 0.556 0.050 0.149 0.556 onal) )Tc (min)Intensity (5yr) (in/hr) Intensity (10yr) (in/hr) Intensity (100yr) (in/hr) PEAK FLOW 5YR (CFS) PEAK FLOW 10YR (CFS) PEAK FLOW 100YR (CFS) Street may have capacity, but spread needs to be verified as per 8/8 email. Please include a section of calculations and exhibits that demonstrate the flooding spread of each storm event meets requirements of Table 4.1 of the URMP for a Collector street. single family home will be constructed. or/Minor the “URMP”) has two controlling triggers when determining the n and exterior disturbed area. Based on these two triggers, Woody mined that water quality capture volume (“WQCV”) and detention rea that slopes at 4.4% to the southwest. Drainage basins are delin- pendix C, C200 & C201). The basins are described in the following V treatment BMPs are also described. s that the street has adequate capacity to convey the 100-year event. Describe changes to land use, topography, ground cover, drainage patterns, and receiving systems, or if no change. No change to off-site drainage patterns, as described in Section 2.3, is noted. capture volume (“WQCV”) and detention o the southwest. Drainage basins are delin- 1). The basins are described in the following also described. uate capacity to convey the 100-year event. le 1, below, describes the impervious area, gth, basin slope, runoff coefficients for the rates for the minor (10-yr) and major (100- Sheet C200 (Appendix C, C200), they are nts were evaluated for the Site using a time ainage patterns. Tc (Regional) (min)Tc (min)Intensity (5yr) (in/hr) Intensity (10yr) (in/hr) Intensity (100yr) (in/hr) PEAK FLOW 5YR (CFS) PEAK FLOW 10YR (CFS) PEAK FLOW 100YR (CFS) 10.8778 10.8778 2.3243 2.7964 4.4669 0.050 0.149 0.556 0.050 0.149 0.556 Tc (Regional) (min)Tc (min)Intensity (5yr) (in/hr) Intensity (10yr) (in/hr) Intensity (100yr) (in/hr) PEAK FLOW 5YR (CFS) PEAK FLOW 10YR (CFS) PEAK FLOW 100YR (CFS) 10.2667 5.0000 3.2911 3.9596 6.3251 0.108 0.134 0.230 10.8778 10.8778 2.3243 2.7964 4.4669 0.020 0.061 0.227 10.8778 10.8778 2.3243 2.7964 4.4669 0.016 0.035 0.114 10.0444 5.0000 3.2911 3.9596 6.3251 0.033 0.040 0.067 10.0500 5.0000 3.2911 3.9596 6.3251 0.040 0.049 0.082 10.0667 5.0000 3.2911 3.9596 6.3251 0.021 0.026 0.044 10.0667 5.0000 3.2911 3.9596 6.3251 0.000 0.001 0.001 The addition of curb and gutter affects the offsite drainage that currently drains onto property. This must be examined within the drainage report to ensure roadway meets standards. n is 5 minutes. The resulting 100-year flowrate is 0.003 m and foundation drywell. w well on the west side of the historical structure. The pervious for calculation purposes. Based on a flow path n is 5 minutes. The resulting 100-year flowrate is 0.004 m and foundation drywell. outing le to provide WQCV. n the design process. water requirements early in the process. mwater quality treatment. s utilized to increase the time stromwater is in contact dscape buffer is used in the driveway and a portion of Please touch on why a drywell it being utilized as it is a last resort BMP per the URMP. We revised this statement to state type B. A spread analysis was completed. The requirements for a local street are met. A spread analysis was completed. The requirements for a local street are met. The section has been updated. A section was added that states: "A drywell is being utilized because this is an HPC project. During HPC approvals, the use of a drywell was approved to reduce the visual impact to the historical structure." 01/22/2020 Page: 12 Date: 10/22/2019 8:30:25 AM File Name: 931 Gibson_Civil_20190830_Report.pdf Make this conclusion using the estimated peak runoff, in gpm. How do you know the 208.91 gpm is sufficient? Page: 14 Date: 10/22/2019 8:35:14 AM File Name: 931 Gibson_Civil_20190830_Report.pdf Please include a drain time calculation to ensure drywell drains within the required 24 hrs. Page: 15 Date: 10/12/2019 7:36:23 PM File Name: 931 Gibson_Civil_20190830_Report.pdf For dry well, iclude a description of access for maintenance operations, maintenance schedule, and contact information for party responsible for maintenance. Page: 52 Date: 10/12/2019 5:41:56 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Revise to 0.08 for HSG B. Page: 55 Date: 10/12/2019 7:00:54 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Where do these areas come from? Is the 50% clogging factor accounted for? [is this what the 2x safety factor is from the report?] mal and designed with public safely in mind. DS Inlet Grates. Trench Drain 1 (“TD1”) is a 26 ft These inlets collect runoff from basin PR:1.0 which Each of the three inlets provide 68.19 gpm for a to- afety of 2 applied, the two inlets provide a capacity es an additional 213.24 gpm (106.62 gpm with a three inlets and slot drain in total have a capacity of y the tributary runoff. Make this conclusion using the estimated peak runoff, in gpm. How do you know the 208.91 gpm is sufficient? ix, the total retention volume is 654.55 cf. Therefore, the 6’ diameter drywell has capacity 00-year event. s Buffer ntrance sidewalk leading from the sidewalk in the ROW to the historic element. This side- ded WQCV by a grass buffer to the west. No detention is provided as the total discharge Basins 1.0 and 1.1 totals of 0.342 cfs versus the historical discharge was 0.556 cfs. ration and Maintenance o types of BMPs used on the property: grass buffers and a drywell. An operation and task and schedule list is provided for each of the BMPs below. Please include a drain time calculation to ensure drywell drains within the required 24 hrs. valuate the drain-down time of the dry well to ensure the maximum time of 24 hours exceeded. If drain-down times are exceeding the maximum, drain the dry well via d clean out the percolation area (the percolation barrel may be jetted to remove sedi- mulated in perforations). Consider drilling additional perforations in the barrel. If slo rsists, the system may need to be replaced. For dry well, iclude a description of access for maintenance operations, maintenance schedule, and contact information for party responsible for maintenance. US RUNOFF COEF. 5YR RUNOFF COEF. 10YR RUNOFF COEF. 100YR FLOW PATH LENGTH (FT) FLOW PATH SLOPE (FT/FT) Tc (Computed) (min) Tc ( 0.06 0.15 0.35 158.00 0.0443 14.44 1 ---- Revise to 0.08 for HSG B. TION *FORMULA USED: FLOOR)Q = 448.2 x Cd x A x √2gh 9.10 A (SQUARE FEET) 3.00 h (FEET) 68.19 Where do these areas come from? Is the 50% clogging factor accounted for? [is this what the 2x safety factor is from the report?] We revised this to 0.08 The section states that the tributary runoff is 103.22 gpm. The section states that the three inlets and the trench drain provide a total capacity of 208.91 gpm with a factor of safety applied. Therefore, there is adequate capacity. We have provided a drain time calculation which demonstrates that the drywell will drain within 24 hours.. The requested information has been added. The 9.1 square inch grate area comes from the grate information found on C500 for the 6" round grate. We analyzed the inlets with 3" of head. This results in a flow cacity of 68.19 gpm. Our 2x factor of safety is the same thing as a 50% clogging factor. Divided 68.19 gpm by 2 results in a grate capacity of 34.1 gpm. 01/22/2020 Page: 56 Date: 10/12/2019 7:01:04 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Where do these areas come from? Is the 50% clogging factor accounted for? [is this what the 2x safety factor is from the report?] Page: 57 Date: 10/12/2019 7:23:58 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Provide calculations for the total 100-year, runoff volume. Page: 58 Date: 10/12/2019 7:31:44 PM File Name: 931 Gibson_Civil_20190830_Report.pdf Per URMP requirements, use most conservative percolation rate from test, which is 2 in/min. OOR)Q = 448.2 x Cd x A x √2gh 156.00 A (SQUARE FEET) 0.10 h (FEET) 213.42 Where do these areas come from? Is the 50% clogging factor accounted for? [is this what the 2x safety factor is from the report?] 0.255 in **Based on 76% 132.30 cf Imperviousness. 1.50 198.45 cf 1.23 in 0.00 cf 1.00 613.67 cf 6 ft 7.04 ft 2 ft 28.26 cf/ft 95.68 sf Provide calculations for the total 100-year, runoff volume. 5 in/min 8E-04 ft/s 13.67 cf 51.14 square feet required 0.785 square inches 65 Per URMP requirements, use most conservative percolation rate from test, which is 2 in/min. The calculation is provided in the appendix. The calculation was changed to 2 in/min. The open grate area of the trench drain is shown on C500. The open area is 0.47". The length of the trench drain is approximately 27.5 ft long. The grate area then is 27.6 ft X 12in/ft X 0.47"=156 sq. in. Yes, the FS=2x is the same as a 50% clogging factor. 01/22/2020