File Name: 40.Engineering Round 1 Comments.20201216.pdf It is not clear why the retaining
wall is needed to preserve the
trees it appears the trees could
be preserved with grading. More
information is needed before a
retaining wall can be permitted in
the City ROW. The City standard
is does not permit retaining walls
in the ROW.
40.Engineering Round 1 Comments.20201216.pdf (3)
Page: 1
File Name: 40.Engineering Round 1 Comments.20201216.pdf Per the URMP all drywells
should be accessible by a pump
truck for maintenance. It is not
clear what site constraints result
in the inability to place the
drywell in an accessible location.
Please elaborate on why no
other accessible site is feasible
and why the resulting location
was chosen, or if an accessible
spot is feasible relocate the
drywell to that location.
Page: 1
File Name: 40.Engineering Round 1 Comments.20201216.pdf The note was not removed from
C4. A new survey was not
submitted that clarifies the gas
and communications line plans.
Please address.
Page: C4 - DEMOLITION PLAN
File Name: 90.Civil Plans.202012123.pdf Remove this note. The location
and removal extents of the gas
and communication lines need to
be determined prior to building
permit issuance.
The response to comments state
the lines were located and the
survey updated, but this
information is not provided in the
permit resubmittal.
90.Civil Plans.202012123.pdf (2)
Page: C13 - GRADING AND DRAINAGE
File Name: 90.Civil Plans.202012123.pdf Please elaborate on why the
retaining wall is needed in the
ROW to preserve the trees. It is
not clear and appears the
existing grade could be kept in
the proposed condition with
proper grading. Retaining walls
are not permitted in the ROW,
and a reason for a variance from
the standard is not clear.
215 S. Monarch Suite G-102 Aspen, Colorado 81611
P 970.544.4856 Email joseph@S2architects.com
4. Show the existing water service line tap location. Call out tap abandonment and removal on the utilities
sheet. Call out new tap location a minimum of 18” from the existing tap.
Response: Existing tap/separation shown. See sheet C8
5. Call out separation distance from the transformer to the hydrant. Ensure Holy Cross clearance distances are
met.
Response: Dimension added and vault rotated to C8
6. The proposed drywell is not accessible for maintenance. How will the drywell be maintained?
Response: Drywell to be maintained by manual access/sediment to be removed by hand. Note added to C10
7. Call this out as a raised steel retaining wall to preserve 2 trees. Typically retaining walls are not permitted in
the ROW. Verify in the response to comments that the retaining wall is needed to preserve the existing trees.
Response: Note has been added to C13. Ex. Contours are between 7840 and 7841 so the walls will be set at
7840.5. See comment responses from Parks and LS.2.2
8. No drywell is shown in the garage on the plans.
It is not clear why the retaining wall is needed to preserve the trees it appears the trees could be preserved withgrading. More information is needed before a retaining wall can be permitted in the City ROW. The Citystandard is does not permit retaining walls in the ROW.
215 S. Monarch Suite G-102 Aspen, Colorado 81611
P 970.544.4856 Email joseph@S2architects.com
Response: Information added to survey, also see C4
2. Per sheet LS 3.0 the driveway is snowmelted. Call out snowmelt in the ROW to be placed on a separate zone
and will require a Permanent Encroachment License prior to CO.
Response: Note has been added and encroachment license is being applied for. See sheet C8
3. Show curb stop location at the property line.
Response: Curb stop has been moved to property line. See sheet C8
4. Show the existing water service line tap location. Call out tap abandonment and removal on the utilities
sheet. Call out new tap location a minimum of 18” from the existing tap.
Response: Existing tap/separation shown. See sheet C8
5. Call out separation distance from the transformer to the hydrant. Ensure Holy Cross clearance distances are
met.
Response: Dimension added and vault rotated to C8
6. The proposed drywell is not accessible for maintenance. How will the drywell be maintained?
Response: Drywell to be maintained by manual access/sediment to be removed by hand. Note added to C10
7. Call this out as a raised steel retaining wall to preserve 2 trees. Typically retaining walls are not permitted in
the ROW. Verify in the response to comments that the retaining wall is needed to preserve the existing trees.
Response: Note has been added to C13. Ex. Contours are between 7840 and 7841 so the walls will be set at
7840.5. See comment responses from Parks and LS.2.2
8. No drywell is shown in the garage on the plans.
Per the URMP all drywells should be accessible by a pump truck formaintenance. It is not clear what site constraints result in the inability to placethe drywell in an accessible location. Please elaborate on why no otheraccessible site is feasible and why the resulting location was chosen, or if anaccessible spot is feasible relocate the drywell to that location.
December 16, 2020
Project: Chatfield View Residence
Permit Comments Round 1: Hailey Guglielmo – Engineering Review
Engineering Review Comments / Response
1. The location and removal extents of the gas and communication lines need to be determined prior to
building permit issuance
Response: Information added to survey, also see C4
2. Per sheet LS 3.0 the driveway is snowmelted. Call out snowmelt in the ROW to be placed on a separate zone
and will require a Permanent Encroachment License prior to CO.
Response: Note has been added and encroachment license is being applied for. See sheet C8
3. Show curb stop location at the property line.
Response: Curb stop has been moved to property line. See sheet C8
4. Show the existing water service line tap location. Call out tap abandonment and removal on the utilities
sheet. Call out new tap location a minimum of 18” from the existing tap.
Response: Existing tap/separation shown. See sheet C8
5. Call out separation distance from the transformer to the hydrant. Ensure Holy Cross clearance distances are
met.
Response: Dimension added and vault rotated to C8
The note was not removed from C4. A new survey was notsubmitted that clarifies the gas and communications line plans.Please address.
Remove this note. The locationand removal extents of the gasand communication lines needto be determined prior tobuilding permit issuance.
The response to commentsstate the lines were located andthe survey updated, but thisinformation is not provided inthe permit resubmittal.
Please elaborate on why theretaining wall is needed in theROW to preserve the trees. It is
not clear and appears the
existing grade could be kept inthe proposed condition withproper grading. Retaining wallsare not permitted in the ROW,and a reason for a variancefrom the standard is not clear.
Drywell placed at low point of site to
most effectively capture runoff.
Drywell could be moved to eastern
portion of lot, but wouldn't be
practical. Drywell would have to be
at least 10 feet deeper and would
require shoring.