HomeMy WebLinkAboutFile Documents.434 E Main St.0090-2023-BRES (6) HealthSa f e NSPECTIO NS HealthSafe Inspections Inc 390 Apple Drive Basalt CO 81621 970-920-2100 Jim Baker CDPHE Asbestos Building Inspector#13437 Ben Baker CDPHE Asbestos Building Inspector#25863 ASBESTOS REPORT DATE 01/19/2023 CLIENT Karen Jordan c/o McNamara&Associates Construction, LLC PO Box 6568 Snowmass Village, CO 81615 PROPERTY ADDRESS of INSPECTION Galena Lofts #203, 434 East Main Street,Aspen, Colorado 81611 41. 'l• ) 5. u• 1101V% A r s 'ems 4c, - ,nr r _ RECEIVED 1 07/17/2023 ASPEN BUILDING DEPARTMENT CLIENT BACKGROUND & PLANS The Client, Karen Jordan, is planning a renovation-remodel-demolition of the interior closets and bathroom water closet, which will have impacts of disturbance, detachment, deconstruction, demolition, and disposal(5D) of drywall building materials, of which some are suspect asbestos containing materials (ACM). Prior to 5D, Karen is required to have an asbestos inspection by a State of Colorado CDPHE certified asbestos inspector who will collect bulk samples of the suspect ACM and have those samples analyzed at a certified laboratory for asbestos content. Karen hired HealthSafe Inspections, Inc. (hereinafter, HealthSafe) via McNamara and Associates Construction, LLC to perform a limited asbestos inspection for the areas slated for impacts of 5D. VISUAL INSPECTION & LABORATORY FINDINGS An inspection was conducted by Ben Baker of HealthSafe on Wednesday, January 04, 2023, with Karen Jordan and Mike McNamara present during the initial survey, inspection and sample collecting.All suspect ACM were identified by homogenous materials and sampled randomly respective to the scope of those materials slated for 5D. The suspect ACM collected and analyzed by EPA 600 Method PLM analysis are the following: 1. Skip Trowel Surfacing Texture, a homogeneous trowel-applied surfacing material/texture [samples 1-3: ST 1,2,3], collected randomly from the coat closet north wall, water closet NE corner, and bedroom closet west wall, respectively, using the AHERA random sampling grid# 15. This surfacing material/texture is friable and located on the ceilings and walls of the condo interior. The estimated impact area of 5D is more than 10 sf,but less than 1,000 sf(±350 sf), requiring a minimum of at least three surfacing/texture material samples. The PLM analytical estimated results: NONE DETECTED. 2. Drywall System Joint Compound: a homogeneous miscellaneous seam taping compound requiring at least two samples [samples 4-5: JC-1,2], collected from the coat closet NW corner and bedroom closet NW corner, respectively. This material is friable and applied to the condo interior drywall system. The PLM analytical estimated results: NONE DETECTED. 3. Drywall System, a homogeneous taped and joint compounded drywall system (classified as a miscellaneous material as a complete integral system) [samples 6- 7: J-1,2], collected from the coat closet NW corner and bedroom closet NW corner, respectively. These composite layered taped and joint compounded drywall materials are friable and located on the ceilings and walls of the condo interior with a skip trowel applied surfacing material/texture. The estimated impact area of 5D is more than 10 sf,but less than 1,000 sf(±350 sf), requiring a minimum of at least two composite core samples of all layers. The PLM analytical estimated results: NONE DETECTED. RECEIVED 2 07/17/2023 ASPEN BUILDING DEPARTMENT A total of 7 suspect homogeneous ACM bulk samples were collected, and 7 samples were analyzed. The bulk samples were analyzed by EPA 600 PLM analytical methods by a NVLAP accredited laboratory in accordance with Colorado State Regulation 8 for the presence of asbestos mineral fibers. There is NO asbestos in all 7 samples. See supporting Hayes Microbial Consulting, Inc. data report#23000401_2. HEALTHSAFE CONCLUSIONS • There is NO asbestos in any of the suspect building materials slated for 5D in this condo remodel. NO asbestos abatement will be required for any of the building materials.All building waste and debris can be disposed of in any landfill which accepts normal, non-hazardous building waste. Sincerely Submitted, Ben Baker wommum. RECEIVED 3 07/17/2023 ASPEN BUILDING DEPARTMENT COLORADO & FEDERAL ASBESTOS REGULATIONS SUMMARY Regulation No. 8 Part B—Asbestos of the Colorado Department of Public Health and Environment(CDPHE),Air Quality Control Commission requires a State-certified Asbestos Building Inspector to inspect and collect bulk samples of all suspect asbestos containing materials (ACM) or suspect asbestos containing building materials (ACBM) prior to their disturbance, removal or demolition and disposal. The suspect materials shall be analyzed by a NVLAP accredited laboratory by polarized light microscopy(PLM) using EPA 600 analytical method.A material which is estimated to contain more than 1% asbestos is classified as ACM/ACBM and regulated by the State and Federal governments.Any friable (able to crush or reduce to powder by finger pressure) asbestos with trace amounts of asbestos fibers or less than 1%must be point-counted using EPA 400 analytical method to prove that it is indeed less than 1%; if not, it must be classified as ACM/ACBM and shall be treated as a State and Federal regulated material.Any friable asbestos containing material (greater than 1% asbestos concentration) or ACM/ACBM that could be rendered friable during its removal or demolition and disposal shall require an asbestos abatement by a certified asbestos abatement contractor to remove and dispose of the material(s). A Colorado State (CDPHE) issued asbestos abatement permit is required for the following trigger levels of ACM/ACBM: 1. Residential buildings of four or fewer units--if more than 32 square feet of any surface coverage (e.g., gypsum wallboard or drywall and associated applied surfacing materials/textures, acoustic sprays,joint compounds,plaster, etc.), 50 feet of asbestos covered or asbestos insulated pipe or any material which would fill a 55-gallon drum is going to be disturbed, removed or disposed of, an asbestos abatement permit is required. 2. Residential complexes with more than four residential units, public access areas to a residential building, commercial and retail buildings, public and civic buildings, industrial buildings--if more than 160 square feet of surfacing materials, 260 linear feet or more than 35 cubic feet(NESHAP) or 55-gallon drum(CDPHE) of suspect ACM/ACBM is going to be disturbed, removed or disposed of, an asbestos abatement permit is required under NESHAP and by the CDPHE. See note below on OSHA. The regulations require an absolute minimum of 3 samples (EPA suggests 9)per homogenous suspect surfacing and TSI materials and an absolute minimum of 2 samples of homogenous miscellaneous materials or any number of"samples sufficient to determine whether a material is ACM" (Reg8.IV.D.3). More samples are required based on surface area or volume. These are minimums; the asbestos building inspector has the field responsibility to determine homogenous materials and the number of samples to collect per material; more than the minimum number of samples may be necessary at the discretion of the inspector.An assessment of friability and functional space conditions of the materials are also the inspector's field responsibilities. RECEIVED 4 07/17/2023 ASPEN BUILDING DEPARTMENT OSHA compliance is required for all employers and employees no matter the quantity of asbestos present with strict regulations regarding 10 sf or more of TSI or friable surfacing materials, and therefore it does not matter what the quantity or State trigger levels are: all suspect ACM/ACBM shall be inspected and tested for asbestos prior to their disturbance, removal and disposal for worker protection and safety. See EPA 40 CFR 763.121 Worker Protection Rule, OSHA 29 CFR 1910.134 Respirator Protection Standard, OSHA 29 CFR 1910.1001 General Industry Standard and OSHA 29 CFR 1926.1101 Construction Standard regulations when dealing with asbestos hazards. Note: County or City regulations may be more stringent. RECEIVED 5 07/17/2023 ASPEN BUILDING DEPARTMENT 4 H AY E S MICROBIAL CONSULTING #23000401 Analysis Report prepared for We would like to thank you for trusting Hayes Microbial for your analytical needs! We received 7 samples by FedEx in good condition for this project on January 5th, 2023. HealthSafe The results in this analysis pertain only to this job, collected on the stated date, and should not be used Inspections in the interpretation of any other job. Information supplied by the customer can affect the validity of results. These results apply only to the samples as received. This report may not be duplicated,except in full,without the written consent of Hayes Microbial Consulting, LLC. 390 Apple Drive Basalt, CO 81621 All information provided to Hayes Microbial is confidential information relating to our customers and their Phone: (970) 920-2100 clients. We will not disclose,copy,or distribute any information verbally or written,except to those designated by the customer(s). We take confidentiality very seriously. No changes to the distribution list will be made without the express consent of the customer. This laboratory bears no responsibility for sample collection activities, analytical method limitations,or Karen Jordan your use of the test results. Interpretation and use of test results are your responsibility. Any reference to Galena Lofts #203 health effects or interpretation of mold levels is strictly the opinion of Hayes Microbial. In no event, shall 434 E. Main St. Hayes Microbial or any of its employees be liable for lost profits or any special, incidental or Aspen, CO 81 61 1 consequential damages arising out of the use of these test results. Collected: January 4, 2023 4-41 Received: January 5, 2023 g *-4-- Reported: January 16, 2023 Steve Hayes,BSMT(ASCP) Laboratory Director Hayes Microbial Consulting,LLC. Jo-cop sr,TFS �w ,� ` J Labo, td g_. Y° �„ DPH J � Zo o, �Y� r FZ1. ,..: ConofPobl[DePartmen[ PRot- Zta,�ae Ir RECEIVED EPA Laboratory ID: VA01419 Lab ID: #188863 DPH License: #PH-0198 07/17/2023 Hayes Microbial Consulting,LLC. 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com Page: 1 of 3 ASPEN BUILDING DEPARTMENT Ben Baker #23000401 HealthSafe Inspections Karen Jordan 390 Apple Drive Galena Lofts #203 Basalt,Co 81621 434 E. Main St. Asbestos PLM Bulk (970) 920-2100 Aspen,CO 81611 EPA 600/R-93,M-4/82-020 # Sample Material Description Non-Asbestos Fibers Asbestos Fibers 1 ST-1 Texture/White None Detected 2 ST-2 Texture/White None Detected 3 ST-3 Texture/White None Detected 4 JC-1 Joint Compound/White None Detected 5 JC-2 Joint Compound/White None Detected 6 J-1 Joint Compound/White None Detected Drywall/White 5%Cellulose Fibers None Detected 7 J-2 Joint Compound/White None Detected Drywall/White 5%Cellulose Fibers None Detected Collected:Jan 4,2023 Received: Jan 5,2023 Reported: Jan 16,2023 RECEIVED 0 H AY E S Project Analyst: Date: Reviewed By: ale//17/2 0 2 3 Angie LlatasCampos, ! ,4 01 - 16-2023 Brian Keith, 01 - 16-2023 MICROBIAL CONSULTING 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804)562-3435 contact@hayesmicrobial.com BUILDING T 2,4 33T Ben Baker #23000401 HealthSafe Inspections Karen Jordan 390 Apple Drive Galena Lofts #203 Basalt,CO 81621 434 E. Main st. Asbestos Analysis Information (970) 920-2100 Aspen,CO 81611 y Analysis Details All samples were received in acceptable condition unless otherwise noted on the report.This report must not be used by the client to claim product certification, approval,or endorsement by AIHA,NIST,NVLAP,NY ELAP,or any agency.The results relate only to the items tested. Hayes Microbial Consulting reserves the right to dispose of all samples after a period of 60 days in compliance with state and federal guidelines. PLM Analysis All Polarized Light Microscopy(PLM) results include an inherent uncertainty of measurement associated with estimating percentages by PLM. Materials with interfering matrix,low asbestos content,or small fiber size may require additional analysis via TEM Analysis. TEM Analysis Analysis by TEM is capable of providing positive identification of asbestos type(s) and semi-quantitation of asbestos content. Definitions 'None Detected'-Below the detected reporting limit of 1%unless point counting is performed,then the detected reporting limit is .25%. New York ELAP Per NY ELAP198.6(NOB),TEM is the only reliable method to declare an NOB material as Non-Asbestos Containing. Any NY ELAP samples that are subcontracted to another laboratory will display the name and ELAP Lab Identification number in the report page heading of those samples.The original report provided to Hayes Microbial Consulting is available upon request. RECEIVED H AY E S 07/17/2023 MICROBIAL CONSULTING 3005 East Boundary Terrace,Suite F. Midlothian,VA.23112 (804) 562-3435 contact@hayesmicrobial.com ASPal 3 of 3 BUILDING DEPARTMENT SHIP: FEDEX ENV PO ASBESTOS • HealthSafe Inspections DATE: 01-05-2023 _ -.. _: _ _ 390 Apple Drive 111111 11 Ill MICROBIAL CONSULTING Basalt, CO 81621 8176 1598 8558 1111111111111101IIIIIIIIIIIIIIIIIIIIII 23e00401 Job Number: Job Name: I(are,i Jor,,,„ Collector: (3en 13cii;of Lr t ic,“4 Lo f tj #2-03 Mobile: 970.E/g-/i83' Email: healthsafeinspections@gmail Li 3 y t niq' Note:(,,N Sfi Date Collected: oe �-l�C' 1�1 � /�Sa�ir, (� ?!Gl( •CC;i.i,,,,.bglSer' Imw?5�°,,f.co,>7 Analysis Type Analysis Methods • • Turnaround Times • PLM Bulk EPA 600 3 Hour Same Day 1 Day 2 Day 3 Day I 5 Day Point Count 400 Point,1000 Point 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day Vermiculite CARB 435 3 Hour Same Day 1 Day 2 Day 3 Day 5 Day TEM Air EPA AHERA,NIOSH 7402 - Same Day 1 Day 2 Day 3 Day 5 Day Bulk Chatfield - Same Day 1 Day 2 Day 3 Day 5 Day • Wipe ASTM D6480-05 • - - Same Day 1 Day 2 Day 3•Day 5 Day Microvac ASTM D5755-09 Same Day 1 Day 2 Day 3 Day 5 Day PCM Air NIOSH 7400 I - Same Day 1 Day I 2 Day 3 Day I 5 Day #1a Group Number Sample Name Analysis Type Turnaround Volume!Area 1 Stop (+) 1 1 - / Pi._ 5 /)c 2 a T -2 3 ST- 3 4 T(_/ I 5 JC- .2 6 _ T- / 7 j- - v 8 • 10 11 12 13 14 15 16 17 ii .ECEI'' Released by: e .+ Date:6vom Received By: Date: Hayes Microbial Consulting.LLC. 3005 East Boundary Terrace,Suite F.Midlothian.VA.23112 (SO4)562-3435 contact@hayesmicrohial.com Form 20.R2fv Ft i728, tp23 Chain of Custody ASPEN BUILDING DEPARTMENT �a.1cj•�• w .(1�wv• ,�.1•.ve• y' �►�1��6•�••• r :fiA.1.1. `v 4-",;;//1•. *•.i1►1.;•*f••7•-,►►��.��� , w:;�♦��1;:00) r ••'�►��.�?,t .•i♦illlllll�%i•. •it►i►//1/1/1/////%i•, :'i•i►►►11111111/1 I. :�i�i'j►111111111%1• :Dili►►�111111111i1i, :'i'i�►.1111111j�11i• .��i'i►►►11111111i16, .�i'il►.IIIIIIi1Pn, .'.'ii'i►►►11111111i1i,, : .i►►1►/i:�. •lell 11i1.$;..•�4III�1. 11110).;`y►t11Q11111In.i10►►H1111Ir.•.`�hI NH111I...`I►,410,lllr.,,�yl►IN1111r,•. IN�1 ,0 i►001,1 r 1 il:•/s •4 JI t/Gnu��11 ►1.11 11/bn,tilt IN►1111/ S'n.��y111►►HIN111✓1/4^n����IIII►IiP1111/11G'n���h4►41�'11j11/1.'r\\�2��1i►•Ii1��1�11%I%i'�'����i1i►�1'���/i/1%/%����\��yI1/�h11•11r�1%�/��%���22��11►/1��. ..�:�•JrI/1^\\�11,��//111/1111II//^ti`��1,�111111�111 III/ \\.�.II�I•III�II I///1 Z y�1t Hlt /��.'1 \ `�!I,IhN1�r(r/.//.��. yl Nh.�li.,.//^1�.���1 •N. r:, / I I / ,l/r,,l/^\,• I I_�� • 1=-:'4, !/ ,'4.14•JA,r1:/// ••.�, 3:,:,.(/:!1,,t,1 ,,.1;1/1:;111/11N�;:':,,•'id..;p!r //I%Ni���,.,y11�p 1/!/\�I�4:.'11'. 'f,/,' 11l Alf,�!its•1.1.Q�'��.111/n����;���,;.;,j!yr,0IIIN\I4�':�§ •::r: Iin\ 't'�'.:i':.t�.:•1j11n\i•R';t.;{:d,./111n1►•��•;�':•1k.•a� 1✓I \I'���;1,;�::,:.' /I11�\�.`�,�:�;.',q�.�j11j1�`I���•�;.,.,':;:,1111In`.1•�,a,t;:;:'://llj�\Il��,;fs'.�;:•/liI^\I\���\��. S.11^\i►\\\d�;r;.;: 1IIli/�.\►►�\V',:nS:•/II11:•'-`�►IN\�,�::Yr: /I/11�\II\►\',yNo,: /II/1�\I�N\.!;,..:: //��.�\�N\,;:•:rr II/it!`a`\\�\,•,:,'r� ///r.::::��►►\►\•,r,'N: Ill < +�.��\��•.. v4-.1.i..-vs,_-:4V.=-‘-t.!%,,-•:"*,_-:",::=A',:;:;•-)*.''...;.-:. iI��`�gi i lift �UtlillI�Jii�U�IVUfiUIIUIlitligt t a '' I' Ui tAgl-44tlel�11�U11U�i171111IUIfiI�EUt} rlJt.-41.1�Jf z-IJUIIUII k.:' , :_:• . „-,�-.\ V• 1 1I.I•V/V IV VIV.V IVI �1 y �M 1 •V1-.V.V V.V.V•V.V.V• .V V V.V. `.� �.. y:=-f ==1.• =-�;.�'v „ .vvv..0Lr ../vv v ,�� v .vv.,,vv\•,'vv G' ice:-z�`=_ — (C . :, . ••�O�9ii_i •~V - z. =c;_= ) OF'COS (Cc ::?:` \... �..."- ♦_ .�� � %:_ram . 1876 r";;�:.<�... •= •�� v Colorado Department (<<�` i= -•: --A* eila .• :-mac.. . =:K....falt.-.1.7 of Public Health ea'r :: „ ') and Environment .. == =__ _ ; ASBESTOS ____==__ . CERTIFICATION* `e ='_ _:<�Cck . Cam.: .44:•.0.1,,-.. \�\"•.: (-C'fir.Vi;:-i.i. ?'7, This certifies that ,1 =• yam:= (icy Benjamin L Baker (`c ��,���= `» (�' ;mac :; >; Certification No.. 25863 t« . s� j �� . t-1 . i--� <cc<c<>::-�= has met the requirements of 25-7-507, C.R.S. and Air ualit Control & »»Y.' -=_� r?a Commission Regulation No. 8, Part B, and is hereby certified by the « '"..... •.•sue :=__ -0) "==: '%=.. -:•.� state of Colorado in the following discipline: c / :: �� (« =' -� Building Inspector* g 0,,t= __ ':5. Issued: August 31 2022 °' '%%;�. )) Expires: September 25, 2023 c.:-....tizt...**.-_-_- (« '-s• �. `CtiSi 3J) I;i''i%1j iii.. •••♦ - - _ i��� (Cc� .:_:�,�per. •. �;,,,., This certificate is valid only with the possession of a •• �=��=::� •.;r0275,.:? 1) current Division-approved training course certification •'' ems:`• V ;cot...;':• - in the discipline specified above. '':J»>3-, `� `'• ;: Autho ize APCD Representative Cc �/'Z�ioil tea c« "==' •, •:�==- i. SEAL s '. V�� -•' I'��I'.^I'�^I'..I'�I'� ^I►I� I'.I'.I". I'./'�/� 111'� �S� ..;,;: ,����i���;�+�1�,}t��u���n��r�lln�j�inlxn}Ir�Ir11r�� an +ar�Gn�ar�_ln►IAIra11fi11raNrON.� _� 1�tiIr�1.1 _- �. < :t �1h - . '7 r� c `;>::�\ ✓11IG'rr+��\ ✓�I//,•;;.v�N�✓/1// \\C/i11�1/,'rr..�N�/l/11/,"",: \\�,1/1II ,'+,.t?rr,:, 11wY✓/i/G;sSv: �I'.�� l�l;;;.'t,�\I\\�l'I:..ri�. .. r_- ►\.i I I/s,i'J:.'h„\\ .ry''I✓ P'.'r 1;\\►\.*Ilirir,;1:A';;\\\\.1 iet,,.,•'ii.�A1,11\Ilj 11,dir:�, y\ \\ Irl/,,�r.i.5 kti ir,,k.f....,.,. \4/r✓, •. \\ \ !r ���. ► Vlrrl '' .�\\\V/rr✓i't1'ir.,�•,, \\/ r 'r..•. \\Nlrr.,,�r/111,�..,�\\Vi/ 1..1'r..,\►\ lr�{�ri111•. o,\Wi�,,,,h.r. �\\\V/rri,,,i�11/rYi�'�':\\�Ir/i.;.��J\.����.�cN404,,,,, ..1,e,...�0.l ,4,,,1/'111..,1.. \Vr/,,•,;.,Po N1�1`` \\i4•4 j1.$01��� \y.„-4i'/P,v,,,1\�,\A. ,,il//1./,1„ilk,l y/i,,,1 04,4i1`,„ ,,,,,Gr,'1„,,, ,,i,,,.\\\\V/,,,b,„41,-;- •♦•�--111�\��Y�/�//111/�Pj1���III����V�/�//111/0/11�/111►����lti��j//ll�{/V/�/11�j1�\�y�'id/IIII./'.�N11���\\v/i///1.1111 i�11�11��"�•,/'///111/.'•'�1,111\� �:v�/PI11/��/i�N11`\\��`••,�d/t1�/1�1111'�111\\\:V°/OIIii11?�%�:, ;�• i/►I1i►;,:f'./i�i�1////1/1111►i '�••rAi'1�1/►11//111►1��• ':i�j/1•1►///1/►�\�\i filoi�/1•►►///e;f •;���j�If1/il,�1�\i•r•./Aot%1►1111/11�11�►� g ji�/1'1►/1/+/10 4figt�/P1•///�1�0 11:i j/e;r9 '.-si:•/►/►1r—:��1��$4:ti►�)• :dj11Q/1►l.fi• :L�1��/►/►/►/��1. .��1/�/►/►/►/Ii• 0�.�:e...1�1•b '.�./1/►1►/►11 • ..�111/►/►1►1.i' ..�//1/./►1 ..4.tj/�/11►1.• T •ee•.. ,�, ,, ,4, /� •• n °•''ASP se• L BUILDING DEPARTMENT (,';-..e,•-_,-:,:?..:-7-',1 ti.>"4• ;.••,,ef• • ii a r.�'� ♦ rf :�- .♦.'.i.\,. i ifi iti tt ,'1Jriir•r:, l�•.1$°""''"441ry4.; (14$$.;4,. 4/4.'• ",,��41../u�%) y 'r40A' ►�iiiwikq : 101 1►►'�AriJi��„'4, isg ►w—". ?.41*g: fA6 :, t. ..,24 �Q�\�—��-/ ih.� ♦,o., .%% A`i.'`'.V j!' N. /A As'/••'',NP:►.. k.''.%��A.1._''',•.z' err. -.9'„a:. `' 4 . %\H.-..!A.z' •.i' ij .0 ,r,s,r,1'.!I �!A.444.1,,.,1..,.. •;: leo4. /-•..•.. y' „�04'. ::,O. :.;. .��+':'!SI.I:.•a...... 4 :.,N',4:11; e.....:.-h.,i 1''"':.;.•r v G.. 1 .V,,.j1.!p .y�,�,•.E£r,'. 1 •b•d..1,,1. .• .�.•.rr,•. \ •4li.'p��•r�.i��:. .'!tr•. ..4•.ly.p, .��'.,. ,.y.., An a.•• ..h�l�}I�An .y;.0•:.r•• •,.dl,tn a'v: ..,,dbl• .1D ,,�,.,.:!r• d •1�...v.Rr «A1• ..•Qs. ,. .)),}I. ..�..�r•. .•:�..,..i. eN .1�. rr.i115ryi •tI0 � l. Q.: ` Pip• ,(,;A;• 1,1, , ;0'�;. i`',o,t 1,1; ;0,1,1, ,;1�'.., ,Ic,.W7.7Y1- ,1.t,I I.0. ,st„o, , , ,t,1 0,..,.7,$I , ,.:1•,1.'. .I,o . . ,0.1.0,1,...A(}rt.tt. ,S•• •1),l ' . rye' 8 \ ' ''..q,.:.i e.;i!."A...,z.z.1F''..g;/t,•. et 11:0;;;V 'gip, r ° Q r I h 1 O wJ 9_1!II < , , ff\ ::,(,.. ...,...„„,::„. .• ,_, •,, CA (S .377:': :4:•.• it 9 .„..i:-l""":".: :,),:.rig ,I% 1r, d O N •a r ..�; \ o 3,>� icrs ce-+ `r' ' ,:•••`=`1 M...Ocl, o f • ✓ .t :/: . %:124-.''13) al mo � ,._ q =0* , Fes• :4 .. 1.1si7 . a N.aa °' Ln en C!Z -F., � p..l •E Sr a •\!; =" 4.4 E—i >l :: 17-0 ( Cm) Up r.• 70. '- 4 1 :.,Y1' G UN A ?i� O � � 4 5 . _ ,.,, g ,. to t : ''' n' .! :.1.......,,,773-:;&...-ai--11.7..:•„7 --... \‘‘...."..,,,\v";44.7\\....L:224'11,,,,,,„...z._11 --- 4 -' n::..1C) ,..4„:16a..41 C vIc..) 7.) -'' 0...,P;,.•-it- ..k,,,; '.. PfEr.'a-i i<1.:.; 4) N C(1.0, :;;`I/fin.\ o a) �". .''� E = � ;1 a..(0-....c.,K.,..,_....:.....;, -.3 '^, U N N `, y .s , -a. U N Ncn y . 'i ta•v 1.♦♦•♦ ? N S" CI ("4 d •••-' .? V , vry x R 1.10 1 -- -1 W y \,`•7 if (I� • 1 .,t 1 11 :tsl 1 1 t 1.1 1Ya1...................................... ..................` t 1"11t. hS..t1 ........................ �S L01.1:4 . . 'yy . .T I �� / .•• � .I.` e `- 'S` � w `'xJ. '. ,G ffixJ.G " .Ce�J •� !S YOy9. '� y�17 •y. aI 1) � °AID � � �. , x � ' ' • 1 ,.Nr 1!;fin y%: i+ 1 rI\ .I I,:I....11' .r:• . '11.•1•'441' .1 .1.• '.11,11i••1; ..`• ..1'N i*OOP y, 1.1i .I• ••1.• •�11 •• ' .•. .I �. .. �.i.;/ .�'� � .i'1 ♦. .�� 1i. ✓• I_Yisi 11 --���.... .11 1'r•r...f�. �1.• '1 . 1 •• .�:.. .f. ¢. .P T�i.l % Id1�jY111r1. ''1•{ 0 ..•'%t; �jl�°.1.11 '1�•\. e• /'�:..,i�Il,i. �:' � .:.I;•�Vf1,•Ir•. �'\. •e /'�%.•�j�1:rt�,��1 •,. � ''�'.I.yl.V�p \.•00);4. ��1+/•":,''o.. .1 C I� (11.,A:%it C 1 .. t• :/, ,40- . emu..• . : ;� ,1 &,. Z I . \ r /............................................/ ` {%I Lc..���-• ;�_•t..1. 0,►_-, V .�%V/r.,..A... • %.rIL►. EE'F •/ r1•. \ '_ BUILDING DEPARTMENT