HomeMy WebLinkAboutSurvey and Site Plan 10148150_FCD_REV0_11.30.20SITE PHOTO
PROJECT: 5G NR 1SR, LTE 3C
SITE NAME: ASPEN HIGHLANDS
at&t
r
US I D / SITE ID: 113891 /COL04136
FA NUMBER: 10148150
Sft�wwoo) PACE NUMBER: MRUTH039693/MRUTH039696
t&t
4393 RIVERBOAT ROAD, SUITE 400
TAYLORSVILLE, UT 84123
_ SITE ADDRESS. 75 PROSPECTOR ROAD
ASPEN, CO 81611
WEST OCEAN AIR DRIVE
10590 SUITE 300
SAN DIECO, CA 92130
z
RFDS ID: 3532122 VERSION 2.0
FULLERTON
ENGINEERING • DESIGN
ROAD, SUITE
IIOSCHAUUMBUFRG,,IILLIINOIS60173500
SITE INFORMATION
SITE LOCATION MAP
PROJECT DESCRIPTION
SHEET INDEX
TEL:847-908-8400
w .FullertonEngineeringxom
SITE NAME: ASPEN HIGHLANDS
USID: 113891
THE PROJECT CONSISTS OF THE INSTALLATION AND OPERATION
OF ANTENNAS AND ASSOCIATED EQUIPMENT CABINETS FOR
AT&T'S WIRELESS TELECOMMUNICATIONS NETWORK.
SHEET
UMBER
SHEET TITLE
PACE #: MRUTH039693/MRUTH039696
TOWER WORK
REMOVE 3 ANTENNAS AND (3) RRH UNITS
T-1
TITLE SHEET
GN-1
GENERAL NOTES
COUNTY: PITKIN
LATITUDE (NAD 83): 39• 10' 53.77008"
t
REMOVE 3 DC-2 RAYCAP UNITS
REMOVE 2 EXISTING DC TRUNKS AND (1) EXISTING FIBER TRUNK
INSTALL 3 NEW ANTENNAS
39.1816028•
N{arovRC
INSTALL 6 NEW RRH UNITS
C-1
SITE PLAN
LONGITUDE (NAD 83): —106' 51' 25.13016"
—106.8569806•
GROUND ELEVATION AMSL : 8,404'
( )
JURISDICTION: PITKIN COUNTY
OCCUPANCY USE: R-1, ACCESSORY USE
AspenHlphlands
Aspen Highlands SW ResoA
Lmjgmg r.mpwnr.h caxa
Strafe Outerwear
� Q
[Highlandsl
Cw�rIN aw.
� _ Aspen Valley Ski
Four MomIaLn Sports QSnawboard Ob
- Aspen Hi hlands slwl" 9' ' """
11
S" HghtandsA:ehou,
INSTALL 2 NEW UNISTRUTS
INSTALL 2 NEW DC-9 RAYCAP
INSTALL 6 NEW TW TRUNKS AND (2) NEW FIBER TRUNKS
INSTALL 6 NEW IN—DIPLEXERS
11
GROUND WORK
REMOVE EXISTING POWER PLANT AND EXISTING BATTERY RACK
REMOVE (22) EXISTING 155AH BATTERIES (5) STRINGS
INSTALL NEW NETSURE 721 POWER PLANT
INSTALL NEW BATTERY RACK
INSTALL 20) NEW 155AH BATTERIES CONFIGURED IN (5) STRINGS
INSTALL 5 STRINGS IN NEW BATTERY RACK
C-1A
ENLARGED ROOF PLAN
C-2
EQUIPMENT LAYOUT
C-3
SITE ELEVATIONS
0
11/30/20
FINAL
A
7/14/20
90% REVIEW
C-4
ANTENNA LAYOUTS
REV.
DATE
REVISION DESCRIPTION
CONSTRUCTION TYPE: III —A
INSTALL 1 NEW FSM4 W/(1) ASIA, (1) AMIA AND (3) ABIA CARDS
C-5
ANTENNA AND CABLE SCHEDULE
I HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
PROPERTY OWNER: ROBERT STUMPUS
ADDRESS: 77 ROS UMPU RD.
ASPEN, CO 81611
Vii
„<:
INSTALL 8 NEW —48V RECTIFIERS AND (5) NEW CONVERTERS
INSTALL 6 NEW VERTIV POWER EXTENDERS
INSTALL 1 NEW 25A DC CIRCUIT BREAKERS FOR NEW 5GNR FSM4
C-6
SPECIFICATIONS AND DETAILS
U'
CONTRACTOR SHALL FURNISH ALL MATERIAL WITH THE
E-1
SYSTEM SCHEMATIC DIAGRAM
E-2
SYSTEM SCHEMATIC DIAGRAM
EXCEPTION OF AT&T SUPPLIED MATERIAL.
ALL MATERIAL SHALL BE INSTALLED BY THE CONTRACTOR
NO Llr
\�Q`'--BED. F/ljs
; = 42914 D ;
CODE COMPLIANCE
G-1
GROUNDING DETAILS°
ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN
ACCORDANCE WITH THE CURRENT EDITIONS OF THE FOLLOWING
CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES.
BUILDING CODE: 2015 INTERNATIONAL BUILDING CODE
ELECTRICAL CODE: 2020 NATIONAL ELECTRICAL CODE
THE FACILITY IS UNMANNED AND NOT FOR HUMAN HABITATION. A
TECHNICIAN WILL VISIT THE SITE AS REQUIRED FOR ROUTINE
FS�CNALEN
LEGAL DESCRIPTION
PROJECT INFORMATION:
MAINTENANCE. THE PROJECT WILL NOT RESULT IN ANY SIGNIFICANT
DISTURBANCE OR EFFECT ON DRAINAGE, NO SANITARY SEWER
SERVICE, POTABLE WATER, OR TRASH DISPOSAL IS REQUIRED AND NO
113891 /COL04136
COMMERCIAL SIGNAGE IS INSTALLED.
ASPEN HIGHLANDS
PROJECT TEAM
DRIVING DIRECTIONS
DO NOT SCALE DRAWINGS
APPROVALS
75 PROSPECTOR ROAD
ASPEN, CO 81611
PROJECT MANAGER: ENGINEER:
RAY TAYLOR FULLERTON ENGINEERING OONSULTAMS, LC
161 INVERNESS DRIVE WEST, 1100 E. WOODFIELD ROAD
2ND FLOOR SUITE 500
ENGLEWOOD, CO 80112 SCHAUMBURG, ILLINOIS 60173
EMAIL: rt199w0ott.com CONTACT: VENERA TAKO
PHONE: (847) 908-8527
EMAIL: VfAKOOFULLERTONENGINEERING.COM
SITE ACQUISITION: CONSTRUCTION MANAGER:
I-70 W APPROX. 2.75 HOURS TO GLENWOOD SPRINGS; TURN S ON
HWY 82 THROUGH GLENWOOD SPRINGS, CARBONDALE, ETC. TO
MAROON CREEK ROUNDABOUT JUST W OF ASPEN PROPER; BEAR
RIGHT (SOUTH) ON MAROON CREEK ROAD UPHILL PAST HIGH
SCHOOL INTO HIGHLANDS VILLAGE; LEFT (EAST) ON PROSPECTOR
ROAD; SITE IS RITITE IS DOWN CLUB ON NORTH END A A—H
VILLAGE MALL. ARE IS DOWN IN THE LOADING AREA. WALK DOWN IN
THE LOADING AREA, GO TO THE LEFT AND ALL THE WAY TO THE
BACK THERE IS A DOOR. GO THROUGH AND JUST TO THE LEFT WILL
SUBCONTRACTOR SHALL VERIFY ALL PLANS & EXISTING DIMENSIONS
& CONDITIONS ON THE JOB SITE & SHALL IMMEDIATELY NOTIFY THE
ENGINEER IN WRITING OF ANY DISCREPANCIES BEFORE PROCEEDING
WITH THE WORK OR BE RESPONSIBLE FOR SAME
THE FOLLOWING PARTIES HEREBY APPROVE AND ACCEPT THESE
DOCUMENTS AND AUTHORIZE THE SUBCONTRACTOR TO PROCEED
WITH THE CONSTRUCTION DESCRIBED HEREIN. ALL DOCUMENTS ARE
SUBJECT TO REVIEW BY THE LOCAL BUILDING DEPARTMENT AND
MAY IMPOSE CHANGES OR MODIFICATIONS
AT&T QUALITY MANAGER: DATE:
AT&T PM: DATE:
SHEET TITLE:
TITLE SHEET
MD7 AT&T
BE A METAL DOOR WITH LOCK 2075 OR 0317. SITE IS JUST BELOW
CONTACT: HAILEE PERUCCI CONTACT: RICHARD MARTINEZ
PHONE: (858) 799-7886 PHONE: (385) 347-9079
EMAIL: HPERUCCI®MD7.COM EMAIL: rx33560att.com
RF ENGINEER: ROOFTOP MOUNT ANALYSIS DATED
CONTACT: ROEL SIGUE E723/20
PHONE: (703) 599-6115 COMPLETED BY MORRISON HERSHFIELD
EMAIL: rs067vOatt>com CONTACT: G. LANCE COOKE, P.E.
HONE: (770) 379-8500
MAIL: atlanta®morrisonhershfield.com
THIS DOOR ON THE RIGHT. CHECK IN WITH HOTEL SO THEY KNOW
YOUR THERE
is
NOTE: DRAWING SCALES ARE FOR 24"x36" SHEETS UNLESS OTHERWISE NOTED
AT&T RF: DATE:
AT&T OPS: DATE:
AT&T SAQ: DATE:
PROPERTY OWNER: DATE:
SHEET NUMBER*
T-
2020.0098-004 S
GENERAL:
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR FOLLOWING ALL LAWS, REGULATIONS, AND
RULES SET FORTH BY FEDERAL, STATE, AND LOCAL AUTHORITIES WITH JURISDICTION OVER
THE PROJECT. THIS RESPONSIBILITY IS IN EFFECT REGARDLESS OF WHETHER THE LAW,
ORDINANCE, REGULATION OR RULE IS MENTIONED IN THESE SPECIFICATIONS.
2. ALL WORK SHALL BE COMPLETED AS INDICATED ON THE DRAWINGS, PROJECT
SPECIFICATIONS, AND THE CONSTRUCTION CONTRACT DOCUMENTS.
3. THE CONTRACTOR SHALL HAVE AND MAINTAIN A VALID CONTRACTOR'S LICENSE FOR THE
LOCATION IN WHICH THE WORK IS TO BE PERFORMED. FOR JURISDICTIONS THAT LICENSE
INDIVIDUAL TRADES, THE TRADESMAN OR SUBCONTRACTOR PERFORMING THOSE TRADES
SHALL BE LICENSED.
4. FOLLOW ALL APPLICABLE RULES AND REGULATIONS OF THE OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION (OSHA) AND STATE LAW AS DEFINED IN THE FEDERAL
OCCUPATIONAL SAFETY AND HEALTH ACT.
5. PRIOR TO THE SUBMISSION OF THE BID, THE CONTRACTOR SHALL VISIT THE JOB SITE,
VERIFY ALL DIMENSIONS AND BECOME FAMILIAR WITH THE FIELD CONDITIONS. ANY
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE PROJECT MANAGER.
6. DRAWING PLANS SHALL NOT BE SCALED.
7. THE CONTRACTOR SHALL NOT PROCEED WITH ANY WORK NOT CLEARLY IDENTIFIED ON THE
DRAWINGS WITHOUT THE PRIOR WRITTEN APPROVAL OF THE PROJECT MANAGER.
8. THE CONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH
MANUFACTURER RECOMMENDATIONS UNLESS SPECIFICALLY OTHERWISE NOTED.
9. ALL MEANS AND METHODS OF CONSTRUCTION DEALING WITH TOWER CONSTRUCTION AND
SAFETY, STEEL ERECTION, EXCAVATIONS, TRENCHING, SCAFFOLDING, FORMWORK, ELECTRICAL,
AND WORK IN CONFINED SPACES ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR.
10. WHEN THE CONTRACTOR ACTIVITIES IMPEDE OR OBSTRUCT TRAFFIC FLOW, CONTRACTOR
SHALL PROVIDE TRAFFIC CONTROL DEVICES, SIGNS, AND FLAGMEN IN ACCORDANCE WITH
APPLICABLE FEDERAL, STATE, DOT AND LOCAL REQUIREMENTS.
11. THE CONTRACTOR SHALL COORDINATE SITE ACCESS AND SECURITY WITH THE PROPERTY
OWNER AND THE PROJECT MANAGER PRIOR TO CONSTRUCTION.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH UTILITIES.
13. THE CONTRACTOR SHALL CALL THE LOCAL PUBLIC UTILITY LOCATING PROVIDER (811) A
MINIMUM OF THREE BUSINESS DAYS PRIOR TO EXCAVATING IN THE PUBLIC RIGHT OF WAY.
14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING PRIVATE UTILITIES.
15. THE CONTRACTOR SHALL PROVIDE ANY TEMPORARY UTILITIES OR FACILITIES IT DEEMS
NECESSARY TO COMPLETE THE WORK. THIS INCLUDES, BUT IS NOT LIMITED TO WATER,
SEWER, POWER, TELEPHONE, HEAT, LIGHTING OR SECURITY.
16. WHEN EXCAVATING IN THE AREA OF EXISTING UTILITIES, THE CONTRACTOR SHALL USE
REASONABLE CARE IN PROTECTING SUCH UTILITIES. CONTRACTOR SHALL NOTIFY THE
PROJECT MANAGER IMMEDIATELY OF ANY CONFLICTS BETWEEN EXISTING UTILITIES AND
PROPOSED CONSTRUCTION.
17. DAMAGE TO PUBLIC OR PRIVATE UTILITIES SHALL BE REPORTED TO THE PROJECT MANAGER
AND THE OWNER OF THE UTILITY IMMEDIATELY. ANY DAMAGE RESULTING FROM
CONTRACTORS NEGLIGENCE OR FAILURE TO ACT WITH DUE REGARD SHALL BE REPAIRED AT
CONTRACTORS EXPENSE.
18. UNLESS OTHERWISE NOTED ON THE PLANS, CONTRACTOR SHALL ASSUME ALL SURFACE
FEATURES SUCH AS BUT NOT LIMITED TO BUILDINGS, PAVEMENTS, LANDSCAPING FEATURES,
PLANTS, ETC. ARE TO BE SAVED AND PROTECTED FROM DAMAGE. CONTRACTOR SHALL MAKE
NECESSARY PROVISIONS TO PROTECT EXISTING SITE CONDITIONS AND UPON COMPLETION OF
WORK REPAIR BACK TO ORIGINAL CONDITIONS ANY DAMAGE THAT OCCURRED DURING
CONSTRUCTION.
19. KEEP THE CONSTRUCTION SITE CLEAN, HAZARD FREE, AND DISPOSE OF ALL DIRT, DEBRIS,
RUBBISH AND REMOVE EQUIPMENT NOT SPECIFIED AS REMAINING ON THE PROPERTY. LEAVE
PREMISES IN CLEAN CONDITION AND SHALL BE SUBJECT TO APPROVAL BY THE PROPERTY
OWNER AND THE PROJECT MANAGER.
20. THE CONTRACTOR SHALL PROVIDE ON -SITE TRASH RECEPTACLES FOR COLLECTION OF
NON -TOXIC DEBRIS. ALL TRASH SHALL BE COLLECTED ON A DAILY BASIS.
21. ALL TOXIC AND ENVIRONMENTALLY HAZARDOUS SUBSTANCES SHALL BE USED AND DISPOSED
OF IN ACCORDANCE WITH MANUFACTURER SPECIFICATIONS. UNDER NO CIRCUMSTANCES
SHALL RINSING OR DUMPING OF THESE SUBSTANCES OCCUR ON -SITE.
22. UNLESS NOTED OTHERWISE, CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND
PAYING FOR ALL PERMITS NECESSARY FOR CONSTRUCTION.
23. THE PROJECT MANAGER MAY RETAIN THE SERVICES OF A TESTING LABORATORY TO
PERFORM QUALITY ASSURANCE TESTING ON VARIOUS PORTIONS OF THE CONTRACTORS
WORK. WHEN REQUESTED, THE CONTRACTOR SHALL INFORM THE TESTING LABORATORY AND
ASSIST THEM IN COMPLETING TESTS.
24. THE CONTRACTOR SHALL MAINTAIN AND SUPPLY THE PROJECT MANAGER WITH AS -BUILT
PLANS UPON COMPLETION OF THE PROJECT.
ELECTRIC:
1. THE CONTRACTOR SHALL PERFORM WORK IN ACCORDANCE WITH ALL GOVERNING STATE,
COUNTY AND LOCAL CODES AND OSHA REQUIREMENTS.
2. THE ENTIRE ELECTRICAL INSTALLATION SHALL BE GROUNDED AS REQUIRED BY ALL
APPLICABLE CODES.
3. THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, INSURANCE, EQUIPMENT,
INSTALLATION, CONSTRUCTION TOOLS AND TRANSPORTATION FOR A COMPLETE AND
PROPERLY OPERATIVE SYSTEM ENERGIZED THROUGHOUT AND AS INDICATED ON DRAWINGS.
4. THE CONTRACTOR SHALL OBTAIN ALL PERMITS, PAY PERMIT AND INSPECTION FEES, AND BE
RESPONSIBLE FOR SCHEDULING INSPECTIONS WITH THE AUTHORITY HAVING JURISDICTION.
5. MATERIALS SHALL BE MANUFACTURED IN ACCORDANCE WITH APPLICABLE STANDARDS
ESTABLISHED BY ANSI, IEEE, NEMA AND NFPA.
6. ALL MATERIALS SHALL BE U.L. LISTED.
7. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND IN PERFECT CONDITION WHEN
INSTALLED AND SHALL BE OF THE BEST GRADE AND OF THE SAME MANUFACTURER
THROUGHOUT FOR EACH CLASS OR GROUP OF EQUIPMENT.
8. MATERIALS SHALL MEET WITH APPROVAL OF THE AUTHORITY HAVING JURISDICTION.
9. THE CONTRACTOR SHALL PERFORM ALL VERIFICATION OBSERVATIONS TEST, AND EXAMINATION
WORK PRIOR TO THE ORDERING OF THE ELECTRICAL EQUIPMENT AND STARTING
CONSTRUCTION. CONTRACTOR SHALL ISSUE A WRITTEN NOTICE OF ALL FINDINGS TO THE
PROJECT MANAGER LISTING ALL MALFUNCTIONS, FAULTY EQUIPMENT AND DISCREPANCIES.
10. THE CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY FOR CONNECTION OF THE
TEMPORARY AND PERMANENT POWER TO THE SITE. THE TEMPORARY POWER AND ALL
HOOKUP COSTS TO BE PAID BY CONTRACTOR.
11. UPON COMPLETION OF WORK, CONDUCT CONTINUITY, SHORT CIRCUIT, AND FALL OF
POTENTIAL GROUND TESTS FOR APPROVAL. SUBMIT TEST REPORTS TO THE PROJECT
MANAGER.
12. ALL BROCHURES, OPERATING MANUALS, CATALOGS, SHOP DRAWINGS, ETC. SHALL BE
TURNED OVER TO THE PROJECT MANAGER AT JOB COMPLETION.
13. POST -INSTALLATION, ANY WORK, MATERIAL OR EQUIPMENT FOUND TO BE FAULTY SHALL BE
CORRECTED AT ONCE, UPON WRITTEN NOTIFICATION, AT THE EXPENSE OF THE CONTRACTOR.
14. PROVIDE THE PROJECT MANAGER WITH ONE SET OF COMPLETE ELECTRICAL "AS -INSTALLED"
DRAWINGS AT THE COMPLETION OF THE JOB, SHOWING ACTUAL DIMENSIONS, ROUTINGS AND
CIRCUITS.
15. ALL ELECTRICAL EQUIPMENT SHALL BE LABELED WITH PERMANENT ENGRAVED PLASTIC
LABELS NOTING USE FUNCTION.
16. EACH CONDUCTOR OF EVERY SYSTEM SHALL BE PERMANENTLY TAGGED IN EACH PANEL
BOARD, PULL BOX, J-BOX, SWITCH BOX, ETC.
17. ALL CONDUIT INSTALLED SHALL BE SURFACE MOUNTED OR DIRECT BURIAL UNLESS
OTHERWISE NOTED.
18. ALL CONDUIT SHALL HAVE A PULL WIRE OR ROPE.
19. ALL CONDUCTORS SHALL BE COPPER.
20. ALL CIRCUIT BREAKERS, FUSES AND ELECTRICAL EQUIPMENT SHALL HAVE AN INTERRUPTING
SHORT CIRCUIT CURRENT TO WHICH THEY MAY BE SUBJECTED, AND A MINIMUM OF 10,000
A.I.C.
21. PATCH, REPAIR AND PAINT ANY AREA THAT HAS BEEN DAMAGED IN THE COURSE OF THE
ELECTRICAL WORK.
22. PENETRATIONS IN FIRE RATED WALLS SHALL BE FIRE STOPPED TO MATCH ORIGINAL RATING.
23. BX OR ROMEX CABLE IS NOT PERMITTED.
24. ALL ELECTRICAL/FIBER ENCLOSURES, JUNCTION BOXES, CONDUIT KNOCKOUTS, RACEWAYS,
ETC. SHALL BE RODENT -PROOF.
25. CLEAN PREMISES OF ALL DEBRIS RESULTING FROM WORK AND LEAVE WORK IN A
COMPLETE AND UNDAMAGED CONDITION.
at&t
h0
4393 RIVERBOAT ROAD, SUITE 400
TAYLORSVILLE, UT 84123
sk
10590 WEST OCEAN AIR DRIVE
SUITE 300
SAN DIEGO, CA 92130
FULLERTON
1 100 E. WOODFIELD ROAD, SUITE 500
SCHAUMBURG, ILLINOIS 60173
TEL:847-908-8400
w .FullertonEngineeringxom
0 11/30/20 FINAL
A 7/14/20 90% REVIEW
REV. DATE REVISION DESCRIPTION
HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
PROJECT INFORMATION:
113891 /COL04136
ASPEN HIGHLANDS
75 PROSPECTOR ROAD
ASPEN, CO 81611
SHEET TITLE:
GENERAL NOTES
SHEET NUMBER:
GN-1
2020.0098 004,6
GENERAL ABBREVIATIONS
NOTES:
AFF ABOVE FINISHED FLOOR
AGL ABOVE GRADE LEVEL
1. SITE PLAN INFORMATION CONTAINED HEREIN IS TAKEN FROM
DOCUMENTS PROVIDED BY THE CLIENT AND PUBLICLY
/����
AMSL ABOVE MEAN SEA LEVEL
AAPPROXIMATE
AVAILABLE ONLINE SOURCES, INCLUDING THE COUNTY GIS
p
ATS AUTOMATIC TRANSFER SWITCH
WEB SITE. THIS IS NOT INTENDED TO BE A SUBSTITUTE FOR
j
AWG AMERICAN WIRE GAUGE
A FULL BOUNDARY SURVEY, AND NEITHER WARRANTY NOR
BLDG BUILDING
GUARANTEE IS GIVEN BY THE ENGINEER NOR FULLERTON
4393 RIVERBOAT ROAD, SUITE 400
CL CENTERLINE
ENGINEERING AS TO THE ACCURACY NOR THE
f'J
_
TAYLORSVILLE, UT 84123
CLR CLEAR
COMPLETENESS OF THE PROVIDED INFORMATION.
COL COLUMN
CONC CONCRETE
2. THERE IS NOTHING BLOCKING THE LINE OF SITE FOR THE
CND CONDUIT
ANTENNAS WITHIN 30FT
DWG DRAWING
FT FOOT(FEET)
EGB EQUIPMENT GROUND BAR
ELEC ELECTRICAL
Q !/
EMT ELECTRICAL METALLIC TUBING
�P
ELEV ELEVATION
%
10590 WEST OCEAN AIR DRIVE
EQUIP MENT//
(E)92130
SAN DI GO, CA0
EXQTERNG
UNDATION
FND F
i
GA GAUGE
LPG
'� EXISTING
GALV GALVANIZED
i PARKING
FULLERTON
GPS GLOBAL POSITIONING SYSTEM
j
AREA
EXISTING
GND GROUND
LP LIQUID PROPANE
BUILDINGG
ENGINEERING • DESIGN
MAX MAXIMUM
MFR MANUFACTURER
f/
=
1100 E. WOODFIELD ROAD, SUITE 500
MGB MASTER GROUND BAR
/
SCHAUMBURG, ILLINOIS 60173
MIN MINIMUM
TEL: 847-908-8400
MTS MANUAL TRANSFER SWITCH
www.FullertonEngineering.com
N.T.S. NOT TO SCALE
j
O.C. ON CENTER
OE/OT OVERHEAD ELECTRIC/TELCO
EXISTING
PPC POWER PROTECTION CABINET
BUILDINGG
PL PROPERTY LINE
%
RGS RIGID GALVANIZED STEEL
IN INCH(ES)
G
INT INTERIOR
_
LB(S), # SQUARE
SF SQUAREARE FOOT
STL STEEL
EXISTING
TYP TYPICAL
UE/UT UNDERGROUND ELECTRIC/TELCO
UNO UNLESS NOTED OTHERWISE
\
BUILDING
P�
0
FINAL
VIF VERIFY IN FIELD
W
O� _
_
\�,
XFMR TRANSFORMER
O
�G
\
Q P
P \ O�
—
2
EXISTING —
BUILDING
/
A
7/14/ 0
7/14/20
90% REVIEW
TELECOM ABBREVIATIONS
REV.
DATE
REVISION DESCRIPTION
BTS BASE TRANSMISSION STATION
FIE FACILITY INTERFACE FRAME
HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME UNDER MY DIRECT
GSM GLOBAL SYSTEM FOR MOBILE
SUPERVISION AND CONTROL, AND TO THE BEST
CO
COMMUNICATION
LTE LONG TERM EVOLUTION
NEW AND EXISTING AT&T EQUIPMENT
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
WITHIN EXISTING 20'-6"X11'-0"
MCPA MULTI —CARRIER POWER AMPLIFIER
EQUIPMENT ENCLOSURE
-
RBS RADIO BASED STATION
PET REMOTE ELECTRIC TILT
SEE C-2 FOR EQUIPMENT LAYOUT
RRH REMOTE RADIO HEAD
RRU REMOTE RADIO UNIT
TMA TOWER MOUNTED AMPLIFIER
NEW AND EXISTING AT&T ANTENNAS AND T
UMTS UNIVERSAL MOBILE
EQUIPMENT ON EXISTING BUILDING
TELECOMMUNICATION SYSTEM
SEE C-1A FOR ENLARGED ROOF PLAN
SEE C-4 FOR ANTENNA LAYOUT
SYMBOLS
Q REVISION
0 WORK POINT
I-o-) UTILITY POLE
® BRICK
\
G
PROJECT INFORMATION:
EXISTING BUILDING ,
G
COMPRESSED STONE
113891 /COL04136
CONCRETE
O G
ASPEN HIGHLANDS
EARTH
O
75 PROSPECTOR ROAD
GRAVEL
ASPEN, CO 81611
CENTERLINE
�
------- PROPERTY LINE
G'
---------- LEASE LINE
— — — — — — EASEMENT LINE
FENCE
/
SHEET TITLE:
CHAINLINK
�
❑ ❑ WOOD
O O WROUGHT IRON
\
SITE PLAN
E ELECTRIC
OE —OE— OVERHEAD
SHEET NUMBER:
UPUE UNDERGROUND
F F FIBER
OFOE OVERHEAD
up —Up— UNDERGROUND
T T TELEPHONE
•
1
Oj Oj OVERHEAD
UA UX UNDERGROUND
[SITE PLAN
SCALE: 1"
= 500'-0"
DC DC DCPOWER
2020.0098.0043
PHOTO
2) EXISTING 3/4" DC POWER TRUNKS
1) EXISTING 3/8" FIBER TRUNKS TO BE REMOVED
TOUTED ON EXISTING UPPORTS
APPROX. LENGTH = 90'-0")
6) NEW 3/4" DC POWER TRUNKS
2) NEW 3/8" FIBER TRUNKS
'OUTED ON EXISTING SUPPORTS
APPROX. LENGTH = 90'-0")
Sk �-
a t & t
4393 RIVERBOAT ROAD, SUITE 400
TAYLORSVILLE, UT 84123
06
10590 WEST OCEAN AIR DRIVE
SUITE 300
SAN DIEGO, CA 92130
FULLERTON
ENGI N EERI N G• DESIGN
1 100 E. WOODFIELD ROAD, SUITE 500
SCHAUMBURG, ILLINOIS 60173
TEL:847-908-8400
W .FullertonEngineeringxom
0 11/30/20 FINAL
A 7/14/20 90% REVIEW
REV. DATE REVISION DESCRIPTION
I HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
PROJECT INFORMATION:
113891 /COL04136
ASPEN HIGHLANDS
75 PROSPECTOR ROAD
ASPEN, CO 81611
SHEET TITLE:
ENLARGED ROOF PLAN
SHEET NUMBER:
•
C 1A
ENLARGED ROOF PLAN
SCALE: 3/32" = 1'-0" 1 1
2020.0098.0043
EXISTING FIBER BOX
kamoo
EXISTING CIENA
at&t
�'•
(6) EXISTING
"
,.
■
DIPLEXERS UNITS/
-
lop
_
EXISTING AC PANEL
EXISTING 5-TON A/C
4393 RIVERBOAT ROAD, SUITE 400
1
I CONDENSING UNIT ON
TAYLORSVILLE, UT 84123
Y
WALL STAND (TYP.)
EXISTING DISCONNECT
EXISTING AT&T
SWITCH
26'-3" X 10'-11"
EQUIPMENT SHELTER
•
I
EXISTING CABLE PORT-1UMTS
XISTING EXISTING
LTE �
RACK
----- EXISTING HYDROGEN
--� SENSOR
10590 WEST OCEAN AIR DRIVE
CABINET
RACK .
SUITE 300
it
SAN DIEGO, CA 92130
EXISTING POWER PLANT
TO BE REMOVED
FULLERTON
+ ■ -*
EXISTING SMOKE
DETECTOR �� I
ENGINEERING•DESIGN
_
(20) 155AH BATTERIES
1100 E. WOODFIELD ROAD, SUITE 500
5 STRINGS TO BE
j ( )
SCHAUMBURG, ILLINOIS 60173
REMOVED
TEL: 847-908-8400
-
w .FullertonEngineering.tom
EXISTING ACCESS
DOOR
EXISTING
EXISTING
EXISTING BATTERY RACK
TO BE REMOVED
•
AIR AIR
M
HANDLER
HANDLER
i
UNIT UNIT
EXISTING TEMP
CONTROL
�oQ
0 fl Q �ae�o
0
11/30/20
FINAL
A
7/14/20
90% REVIEW
EQUIPMENT RACK PHOTOS - EXISTING SCALE: N.T.S.
EQUIPMENT LAYOUT - EXISTING
SCALE: 1/2" = 1'-0"
2
REV.
DATE
REVISION DESCRIPTION
I HEREBY CERTIFY THAT THESE DRAWINGS WERE
—
EXISTING FIBER BOX
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
(6) EXISTING
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
DIPLEXERS UNITS
EXISTING CIENA
- EXISTING LTE RACK W/
THE REQUIREMENTS OF ALL APPLICABLE CODES.
EXISTING AC PANEL
(1) NEW FSM4
(1) ASIA
.
(1) AMIA
�+
11771
(3) ABIA
rr t
I
EXISTING 5—TON A/C
EXISTING DISCONNECT
I CONDENSING UNIT ON
\�]
SWITCH
j�
j WALL STAND (TYP.)
'
'•. — , �
w�� y
-�•••
EXISTING CABLE PORT
EXISTING
UMTS
I
XISTING EXISTING M 6"
LTE RACK
I
I EXISTING AT&T
----- J
ISHELTER
CABINET
RACK.
EQUIPMENT
r
r
NEW EMERSON NETSURE 721
PROJECT INFORMATION:
LI
DC POWER PLANT W/
NEW I
EXISTING SMOKE
(8) NEW RECTIFIERS
FSM4
• `+
DETECTOR
(5) NEW CONVERTERS
113891 /COL04136
T` LOCATION _ rao I
__
-J
(6) VERTIV POWER EXTENDERS
ASPEN HIGHLANDS
(1) NEW 25A DC BREAKERS
75 PROSPECTOR ROAD
ASPEN, CO 81611
EXISTING ACCESS
(20) NEW 155AH BATTERIES
ol
DOOR
EXISTING
EXISTING o
(5) STRINGS OF BATTERIES
SHEETTITLE
Of
AIR AIR M - -I IN NEW RACK
HANDLER
HANDLER
UNIT
UNIT
EQUIPMENT LAYOUT
EXISTING TEMP
SHEET NUMBER:
�oQ
I
Q 0 0 �oe0°e
CONTROL
EXISTING HYDROGEN SENSOR
`
r %
V L
EQUIPMENT RACK -NEW SCALE: N.T.S.
3
EQUIPMENT LAYOUT - NEW SCALE: 1/2" = 1'-0"
4
2020.0098.0043
(3) EXISTING AT&T ANTENNAS
(3) EXISTING ANTENNAS
1 PER SECTOR)
(TYP. 1 PER SECTORS)
(3) EXISTING RAYCAP DC-2 UNITS
����
(TYP.
(3) EXISTING RRH UNITS
(TYP. 1 PER SECTOR)
r T/EXISTING AT&T ANTENNAS
ELEV. = 64'-6"t AGL
(TYP. 1 PER SECTOR)
(3) EXISTING DC-2 RAYCAP UNITS
(3) EXISTING TMA UNITS
(TYP. 1 PER SECTORS)
(TYP. 1 PER SECTOR)
TO REMAIN
4393 RIVERBOAT ROAD, SUITE 400
TO BE REMOVED
TAYLORSVILLE, UT 84123
0 OF EXISTING AT&T ANTENNAS
"
-
POWER TRUNKS
(1) EXISTING 3/4" FIBER
(1) EXISTING 3/8" FIBER TRUNKS
ELEV. = 62'-6" AGL
ROUTED THROUGH EXISTING BUILDING TO BE REMOVED
T EXISTING BUILDING
(APPROX. LENGTH = 90'-0")
14
ELEV. = 58'-9" f AGL ---- --- --
EXISTING BUILDING
��
��
Fp-pl
10590 WEST OCEAN AIR DRIVE
SUITE 300
ummmummi
SAN DIEGO, CA 92130
E
ME
p
FULLERTON
_��
ENGINEERING•DESIGN
—
1100 E. WOODFIELD ROAD, SUITE 500
'MIDI
ILL
SCHAUMBURG, ILLINOIS 60173
TELrtonli847 gineer0
www.FullertonEngineering.com
T GRADE
ELEV. — 0'—O"t AGL
0
11/30/20
FINAL
UT N - EXISTING
SCALE: N.T.S.
A
7/14/20
90% REVIEW
NOTES:
REV.
DATE
REVISION DESCRIPTION
1. CALCULATIONS FOR THE STRUCTURE AND ANTENNA
MOUNTS WERE PREPARED BY OTHERS AND THOSE
PREPARED CBYRTME ORAU DER EMY RDIRIECT WERE
CALCULATIONS CERTIFY THE CAPACITY OF THE
STRUCTURE TO SUPPORT THE NEW EQUIPMENT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
2. CABLES NOT SHOWN FOR CLARITY
(3) NEW ANTENNAS
(TYP. 1 PER SECTOR)
(3) EXISTING AT&T ANTENNAS
(6) NEW RRH UNITS
(TYP. 1 PER SECTORS)
(TYP. 2 PER SECTOR)
(3) EXISTING RAYCAP DC-2 UNITS
(2) NEW DC-9 RAYCAP UNITS
(TYP. 1 PER SECTOR)
T/EXISTING AT&T ANTENNAS
ELEV. = 64'-6"t AGL
(ALPHA AND GAMMA SECTOR)
(6) NEW DIPLEXERS
(3) EXISTING TMA UNITS
(TYP. 1 PER SECTORS)
(6) NEW 8—AWG DC POWER TRUNKS
(2) NEW 3/8" FIBER TRUNKS
(TYP. 2 PER SECTOR)
ROUTED THROUGH EXISTING BUILDING
(2) NEW UNISTRUTS
(APPROX. LENGTH = 90'-0")
OF EXISTING AT&T ANTENNAS_______________
ELEV. = 62'-6" AGL
T EXISTING BUILDING
Z
ELEV. - 58 —9 f AGL
--`
PROJECT INFORMATION:
EXISTING BUILDING
M
TM
113891 /COL04136
ASPEN HIGHLANDS
�m
��
��
75 PROSPECTOR ROAD
ASPEN, CO 81611
ID ME I��
��'I
��
I�''
��'I
:ME:
SHEET TITLE:
Ll
FLL
SITE ELEVATIONS
T GRADE
—
SHEET NUMBER:
ELEV. = 0'—O" t AGL
C-3
SOUTHEAST ELEVATION -NEW
SCALE: N.T.S.
2
2020.0098.0043
4000*
S"amm'"o-ol,
at&t
4393 RIVERBOAT ROAD, SUITE 400
TAYLORSVILLE, UT 84123
64
10590 WEST OCEAN AIR DRIVE
SUITE 300
SAN DIEGO, CA 92130
(3) EXISTING AT&T ANTENNAS
TO REMAIN
TYP. 1 PER
(SECTOR)�a
0
h
co
o co
J ° O
o
o
(3) EXISTING AT&T ANTENNAS
(TYP. 1 PER SECTOR)
2 �)a
0
�
`b
o \
J ° O O
N
Q
FULLERTON
ENGI N EERI N G• DESIGN
1 100 E. WOODFIELD ROAD, SUITE 500
SCHAUMBURG, ILLINOIS 60173
TEL: 847-908-8400
www.FullertonEngineering.com
(3) EXISTING AT&T RRH UNITS
(6) NEW AT&T RRH UNITS
TO BE REMOVED
ON NEW UNISTRUT
(TYP. 1 PER SECTOR)
(3) EXISTING AT&T ANTENNAS
(TYP. 2 PER SECTOR)
(3) NEW AT&T ANTENNAS
(2) EXISTING DC-2 RAYCAP UNITS
TO BE REMOVED
TO BE REMOVED
(TYP. 1 PER SECTOR)
(TYP. 1 PER SECTOR)
(TYP. 1 PER SECTOR)
EXISTING CHIMNEY (TYP.)
(6) NEW DIPLEXERS
(TYP. 2 PER SECTOR)
0
11/30/20
FINAL
A
7/14/20
90% REVIEW
EXISTING OTHER CARRIER
EXISTING OTHER CARRIER
REV.
DATE
REVISION DESCRIPTION
ANTENNAS (TYP.)
ANTENNAS (TYP.)
�00 P
VjE 2
P05' �9MTS
Aps O 8S0/
0' 5O 85
pW5 2
QOS'
(2) NEW DC-9 RAYCAP UNIT
SMOUNTED INSIDE EXISTING CHIMNEY
(ALPHA AND GAMMA SECTOR)
�9�TS
Aps O 8S0/
EXISTING CHIMNEY
HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
a5ol
�S T
EPOS 1 OS �00
2 q�
j UM�S
905 1
A9lyS >00
OS ?
n
PROJECT INFORMATION:
113891 /COL04136
ASPEN HIGHLANDS
75 PROSPECTOR ROAD
ASPEN, CO 81611
SHEET TITLE:
ANTENNA LAYOUT
SHEET NUMBER:
C4
ANTENNA LAYOUT - EXISTING SCALE: 3/8" = V-0"
1
ANTENNA LAYOUT - NEW SCALE: 3/8" = 1'-0"
2
2020.0098.0043
ANTENNA AND TRANSMISSION CABLE REQUIREMENTS (VERIFY WITH CURRENT RFDS)
TECHNOLOGY
ANTENNA MODEL
RAID CENTER
TMA/RRH MODEL
FEEDER
�� ��
SECTOR
ADDITIONAL EQUIPMENT
LENGTH
(})�
EXIST.
I FINAL
EXISTING
FINAL
EXIST.
FINAL
EXIST.
FINAL
4393 RIVERBOAT ROAD, SUITE 400
Al
UMTS
850/1900
UMTS
850/1900
POWERWAVE
P65-15—XLH—RR
POWERWAVE
P65-15—XLH—RR
62'-6"
62'-6"
(1) TT19-08BPIII-001 (TOWER)
(1) TT19-08BP111-001 (TOWER)
(2) CM1007—DBPXBC-003
(DIPLEXER UNIT)
112'
TAYLORSVILLE, UT 84123
(1) B14/12/29 TRIBAND RRH AHLBBA
LTE
QUINTEL
CCI
(1) RRH2X40-07L—AT (ROOFTOP)
(ROOFTOP)
(1) DC9-48-60-24—PC16—EV
A2
700LTE TAWS
700/AWS/
QS46512-2
TPA-65R—BU4DA—K
62'-6"
62'-6"
(1) B66A RRH4X45-4R (ROOFTOP)
(1) RRH 4T4R B5 160W AHCA (ROOFTOP)
(RAYCAP UNIT)
112'
14
5G 850
(1) B66A RRH4X45-4R (ROOFTOP)
A3
—
—
—
—
—
—
—
—
—
10590 WEST OCEAN AIR DRIVE
SUITE 300
SAN DIEGO, CA 92130
A4
—
—
—
—
—
—
—
—
—
—
FU L L E RTON
Bl
UMTS
850/1900
UMTS
850/1900
POWERWAVE
P65-15—XLH—RR
POWERWAVE
P65-15—XLH—RR
62'-6"
62'-6"
(1) TT19-08BPI I I-001 (TOWER)
(1) TT19-08BP111-001 (TOWER)
(2) CM1007—DBPXBC-003
(DIPLEXER UNIT)
172'
ENGI N EERI N G• DESIGN
1 100 E. WOODFIELD ROAD, SUITE 500
LTE
(1) B14/12/29 TRIBAND RRH AHLBBA
82
LTE
AWS/
75G
QUINTEL
CCI
62'-6"
62'-6"
(1) RRH2X40-07L—AT (ROOFTOP)
(ROOFTOP)
(2) DBC0056F1V51—V (DIPLEXER UNIT)
172'
SCHAUMBURG, ILLINOIS 60173
700/AWS
SG 850
QS46512-2
TPA-65R—BU4DA—K
(1) B66A RRH4X45-4R (ROOFTOP)
(1) RRH 4T4R B5 16OW AHCA (ROOFTOP)
TEL:847-908-8400
(1) B66A RRH4X45-4R (ROOFTOP)
w .FullertonEngineeringxom
B3
—
—
—
—
—
—
—
—
—
—
B4
—
—
—
—
—
—
—
—
—
—
Cl
UMTS
850/1900
UMTS
850/1900
POWERWAVE
P65-15—XLH—RR
POWERWAVE
P65-15—XLH—RR
62'-6"
62'-6"
(1) TT19-08BP111-001 (TOWER)
TT19-08BP111-001 (TOWER)
(2) CM1007—DBPXBC-003
(DIPLEXER UNIT)
73'
(1) B14/12/29 TRIBAND RRH AHLBBA
LTE
QUINTEL
CCI
(1) RRH2X40-07L—AT (ROOFTOP)
(ROOFTOP)
(1) DC9-48-60-24—PC16—EV
0
vso/2o
FINAL
C2
700/AWS
75G AWS/
OS46512-2
TPA-65R—BU4DA—K
62'-6"
62'-6"
(1) B66A RRH4X45-4R (ROOFTOP)
(1) RRH 4T4R B5 160W AHCA (ROOFTOP)
(RAYCAP UNIT)
172
850
(1) B66A RRH4X45-4R (ROOFTOP)
A
7/14/20
90% REVIEW
C3
—
—
—
—
—
—
—
—
(2) DBC0056F1V51—V (DIPLEXER UNIT)
172'
REV.
DATE
REVISION DESCRIPTION
I HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
C4
-
-
-
-
-
-
-
-
-
-
CONTROL,TO E T
OFPMYVIKNOW KNOWLEDGE BELEFDCOMP YWITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
CABLE LENGTH TABLE
DISTANCE & CABLE
DISTANCE AND
TOTAL
SECTOR
TYPE
CABLE TYPE
CABLE
u-
=
LENGTH
ALPHA
97'
8—AWG 2
15'
12—AWG 2
112'
OL
I
o
BETA
157'
8—AWG 2
15'
12—AWG 2
172'
GAMMA
157'
8—AWG 2
15'
12—AWG 2
172'
CABLE COUNT
QUANTITY
CABLE TYPE
6
CONDUCTOR (3PR)
8—AWG DC CABLE
2
36 FIBER (18 PAIR)
10MM FIBER
6
7/8" COAX CABLES
COAX CABLE
SECTOR
DISTANCE
CABLE TYPE
ALPHA
112'
7/8" COAX
BETA
172'
7/8" COAX
GAMMA
172'
7/8" COAX
PROJECT INFORMATION:
113891 /COL04136
ASPEN HIGHLANDS
75 PROSPECTOR ROAD
ASPEN, CO 81611
SHEET TITLE:
ANTENNA AND
CABLE SCHEDULE
SHEET NUMBER:
C-5
ANTENNA SCHEDULE AND CABLE SCHEDULE
SCALE: N.T.S.
2020.0098.0043
�,...� at&t
CO.
Boa
4393 RIVERBOAT ROAD, SUITE 400
a
�
N
h
w�
M
�
TAYLORSVILLE, UT 84123
a
M
20.7" o
00 a3
^
10590 WEST OCEAN AIR DRIVE
t
9y.
SUITE 300
4)�
SAN DIEGO, CA 92130
1
� 14.09"
FULLERTON
ENGINEERING•DESIGN
:00—
�8.0"3.2" N
I�
o
NN N
c6
1100 E.WOOFIEL ROAD, SUITE 50014.09"
N
SAUMBUG, ILLIN 0173
77.6.
\-
12.7" 14.09"
8.0"
TEL: 847 -908-8400
w .FullertonEngineeringxom
6�0
� X
PLAN VIEW SIDE VIEW FRONT VIEW
PLAN VIEW
SIDE VIEW FRONT VIEW
PLAN VIEW
SIDE VIEW FRONT VIEW
CCI — TPA65R—BU4D
MULTI —BAND TWELVE ANTENNA
NSN — AIRSCALE RRH 4T4R B5 160W AHCA NOKIA — AHLBBA—TRIBAND
RRH B14/12/29
KAELUS
— DBC0056F1 V51-1
DIPLEXER
CAPACITY, PERFORMANCE, RADIO— INTERGRATED PASSIVE SUPPORTS 3 LOW BANDS IN 1 RRH
FREQUENCY RANGE 4 LOW x 698-896 MHz
8 HIGH x 1695-2400 MHz
INTERMODULATION (PIM) FREQUENCY RANGE
FREQUENCY RANGE 698-746 MHz
ANTENNA 52.6 Lbs
(3) RETS 15 Lbs
B12: DL 729-744 MHz, UL 699-714 MHz
FREQUENCY RANGE DL 869-894 MHz B14: DL 758-768 MHz, UL 788-798 MHz
824-894 MHz
BRACKET 16. Lbs
UL 824-849 MHz
TOTAL WEIGHT 35.3 Lbs
B29: DL 718-728 MHz
UNIT WEIGHT
7.05 Lbs
0
11/30/20
FINAL
TOTAL WEIGHT 83.7 Lbs
WEIGHT 94.8 Lbs
ANTENNA SPEC (NEW OR SIMILAR) SCALE: N T S
1
RRH SPEC (NEW OR SIMILAR)
SCALE N.T.s.
2
DIPLEXER SPEC (NEW OR SIMILAR)SCAEE: N.T.S.
3
A
7/14/20
90%REVIEW
NOTE:
REV.
DATE
REVISION DESCRIPTION
11 - ---- T
II
PROVIDE SILICONE SEALANT
AROUND PERIMETER OF ALL
NEW SCREW PENETRATIONS
HEREBY CERTIFY THAT THESE DRAWINGS wERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
____
oq
N N
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
N �a
r
7.2" 11.8"
NEW GOFV3 UNISTRUT
(TYP
PLAN VIEW SIDE VIEW FRONT VIEW
0 o
ALCATEL—LUCENT B66A RRH4x45-4R
Io Lo
WITH (4) TRANSMIT RF PATHS
12 3"
FREQUENCY RANGE
DOWNLOAD 2100-2180 MHz
UPLOAD 1710-1780 MHz
NEW AT&T RRH UNIT
UNIT WITH SOLAR SHIELD 56.8 Lbs
MR.)
PROJECT INFORMATION:
loo
"123-
113891 /COL04136
RRH SPEC (EXISTING) SCALE N T S
5
ASPEN HIGHLANDS
9.65' 15.92"
EXISTING 2X4 WOOD
75 PROSPECTOR ROAD
14.57-
STUD @ 16" O.C.
I I
a u
n
ASPEN, CO 81611
of `° ao
PLAN VIEW SIDE VIEW FRONT VIEW
NEW SIMPSON SDS25312
SHEET TITLE:
SCREWS ® EACH EXISTING
POWERWAVE — P65-15—XLH—RR
PLAN VIEW SIDE VIEW FRONT VIEW
STUD
SPECIFICATIONS
DUAL BROADBAND ANTENNA
AND DETAILS
FREQUENCY RANGE 698-894 MHz
RAYCAP — DC9-48-60-24—PC16—EV
EXISTING WOOD SIDING
SHEET NUMBER*
1710-2170 MHz
OVERVOLTAGE PROTECTION AND FIBER DISTRIBUTION/CABLE
ANTENNA 42 Lbs
MANAGEMENT JUNCTION BOX
WITH BRACKET 50 Lbs
r1 �'1
WEIGHT 34.9 Lbs
IV_ 6
I
ANTENNA SPEC (EXISTING) SCALE: N.T.S.
4
RAYCAP SPEC (NEW OR SIMILAR) SCALE: N.T.S.
6
RRH MOUNTING DETAIL SCALE: LT. s.Pi
2020.0098.0043
(1) EXISTING CONDUIT
(8) NEW EMERSON 2
RECTIFIERS (NEQ.16551
(5) NEW C48/24-150
(NEQ. 15929)
NOTES:
1. DC POWER WIRING SHALL BE COLOR CODED AT EACH END FOR
IDENTIFYING +24V AND —48V CONDUCTORS. RED MARKINGS SHALL
IDENTIFY +24V AND BLUE MARKINGS SHALL IDENTIFY —48V. REFER
TO ATT-002-290-701.
2. NON—LTE DC POWER WIRING SIZE 14 AWG TO 10 AWG SHALL BE
TELCOFLEX III. DC POWER WIRING 8 AWG AND LARGER SHALL BE
TELCOFLEX IV.
3. LTE POWER WIRING SHALL BE IN ACCORDANCE WITH
ATT-002-290-531.
4. DC ELECTRICAL LOAD DEMAND FOR PROPOSED ADDITIONS WERE
INCLUDED IN PRIOR AC LOAD CALCULATION.
RRH
(TYP.)
(1) ALARM CABLE AND (1) SET OF
DC POWER CABLES
(2—#10 THHN/THWN/VW-1 TYPE TC—ER)
FROM DC9 TO RRH
(TYP.)
RAYCAP FIBER AND DISTRIBUTION UNIT
W/ INTEGRATED SURGE PROTECTOR
MODEL #DC6-48-60-0-8F
TA SECTOR
\MMA SECTOR
at&t
4393 RIVERBOAT ROAD, SUITE 400
TAYLORSVILLE, UT 84123
64
10590 WEST OCEAN AIR DRIVE
SUITE 300
SAN DIEGO, CA 92130
FULLERTON
ENGI N EERI N G• DESIGN
1 100 E. WOODFIELD ROAD, SUITE 500
SCHAUMBURG, ILLINOIS 60173
TEL:847-908-8400
w .FullertonEngineeringxom
0 11/30/20 FINAL
A 7/14/20 90% REVIEW
REV. DATE REVISION DESCRIPTION
I HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
PROJECT INFORMATION:
113891 /COL04136
ASPEN HIGHLANDS
75 PROSPECTOR ROAD
ASPEN, CO 81611
SHEET TITLE:
SYSTEM SCHEMATIC
DIAGRAM
SHEET NUMBER:
E-1
SYSTEM SCHEMATIC DIAGRAM
SCALE: N.T.S. 1
2020.0098.0043
EXISTING CONDUIT WITH
(3) 3/0 AWG (W.F.)
EXISTING SERVICE
GROUND
TO EXISTING
SOURCE
ISTING 200A METER
EXISTING CONDUIT WITH
(3) 3/0 AWG & (1) #6 AWG GND
(V. I. F. )
DISCONNECT
SWITCH
EXISTING CONDUIT WITH
(3) 3/0 AWG & (1) #6 AWG GND
(V.I.F.)
EXISTING PANEL A
200A, 120/240 V
1 P/3W, DISTRIBUTION
PANEL
S"umm, ' ww" 1,
at&t
4393 RIVERBOAT ROAD, SUITE 400
TAYLORSVILLE, UT 84123
lw
10590 WEST OCEAN AIR DRIVE
SUITE 300
SAN DIEGO, CA 92130
FULLERTON
ENGI N EERI N G• DESIGN
1 100 E. WOODFIELD ROAD, SUITE 500
SCHAUMBURG, ILLINOIS 60173
TEL:847-908-8400
w .FullertonEngineeringxom
0 11/30/20 FINAL
A 7/14/20 90% REVIEW
REV. DATE REVISION DESCRIPTION
I HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
PROJECT INFORMATION:
113891 /COL04136
ASPEN HIGHLANDS
75 PROSPECTOR ROAD
ASPEN, CO 81611
SHEET TITLE:
SYSTEM SCHEMATIC
DIAGRAM
SHEET NUMBER:
E-2
2020.0098.0043
:Qwwwl , ww" 1, at&t
4393 RIVERBOAT ROAD, SUITE 400
TAYLORSVILLE, UT 84123
64
10590 WEST OCEAN AIR DRIVE
SUITE 300
SAN DIEGO, CA 92130
FULLERTON
ENGI N EERI N G• DESIGN
ANTENNA PIPE
MOUNT
1 100 E. WOODFIELD ROAD, SUITE 500
SCHAUMBURG, ILLINOIS 60173
TEL:847-908-8400
NEW ANTENNA
NOTE: MINIMUM OF
S/S NUT
(TYP.)
w .FullertonEngineeringxom
3 THREADS TO BE
VISIBLE (TYP.)
S/S SPLIT WASHER
GROUNDING NOTES:
NEW RRU
(TYp)
NEW #2 AWG
--- _
__— _
2 HOLE, LONG
BARREL TINNED
SOLID COPPER
LUG (TYP.)
(�')
S/S FLAT WASHER
(TYp.)
1.
METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY
CONTINUOUS WITH LISTED BONDING FITTINGS OR BY BONDING ACROSS THE
DISCONTINUITY WITH #6 AWG COPPER WIRE AND UL APPROVED GROUNDING
__--- ,
TYPE CONDUIT CLAMPS PER NEC AND AT&T ND-00071.
NEW JUMPERPCABLE(S)
' '
EXISTING GROUND BAR
2.
CONNECTIONS TO THE GROUND BAR SHALL NOT BE DOUBLED UP OR STACKED.
BACK TO BACK CONNECTIONS ON OPPOSITE SIDES OF THE GROUND BUSS ARE
NEW DC AND FIBER
JUMPER CABLES
(E) SECTOR
GROUND BAR
EXISTING INSULATOR
S/S FLAT WASHER
(TYp,)
3.
PERMITTED.
METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT
0
11/30/20
FINAL
A
7/14/20
90% REVIEW
EXISTING RAYCAP
SQUID
(E) GND
AND MOUNTING BRACKET
S/S BOLT
(T,p)
GROUND CONDUCTOR. STRANDED COPPER CONDUCTORS WITH GREEN
INSULATION, SIZED IN ACCORDANCE WITH NEC, SHALL BE FURNISHED AND
INSTALLED WITH POWER CIRCUITS TO BTS EQUIPMENT.
REV.
DATE
REVISION DESCRIPTION
HEREBY CERTIFY THAT THESE DRAWINGS WERE
PREPARED BY ME OR UNDER MY DIRECT
SUPERVISION AND CONTROL, AND TO THE BEST
OF MY KNOWLEDGE AND BELIEF COMPLY WITH
THE REQUIREMENTS OF ALL APPLICABLE CODES.
EXISTING
GROUND WIRE
4. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE
USED FOR GROUNDING CONNECTIONS.
5. USE OF 90' BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE
AVOIDED WHEN 45' BENDS CAN BE ADEQUATELY SUPPORTED. IN ALL CASES,
EXISTING FIBER/DC
NOTES:
BENDS SHALL BE MADE WITH A MINIMUM BEND RADIUS OF 8 INCHES.
CABLE WITH INTERNAL
"DRAIN WIRE" TO
EQUIPMENT
(E) COLLECTOR
GROUND BAR
1. ALL HARDWARE 18-8 STAINLESS STEEL INCLUDING SPLIT WASHERS.
2. COAT WIRE END WITH ANTI —OXIDATION COMPOUND PRIOR TO INSERTION
INTO LUG BARREL AND CRIMPING.
3. APPLY ANTI —OXIDATION COMPOUND BETWEEN ALL LUGS AND BUSS BARS
6.
MISCELLANEOUS ELECTRICAL AND NON —ELECTRICAL METAL BOXES, FRAMES AND
SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN ACCORDANCE WITH
NEC.
It
PRIOR TO MATING AND BOLTING.
7.
GROUND ALL RF EQUIPMENT INCLUDING BUT NOT LIMITED TO COAX,
DIPLEXERS, SURGE ARRESTORS, TMA'S, ANTENNAS, AND ANTENNA MAST PER
LEGEND
NEC AND AT&T ND-00071.
EXOTHERMIC CONNECTION
O
MECHANICAL CONNECTION
A
GREEN STRANDED INSULATED COPPER GND WIRE — — —
(SUNLIGHT RESISTANT)
PROJECT INFORMATION:
113891 /COL04136
ASPEN HIGHLANDS
75 PROSPECTOR ROAD
ASPEN, CO 81611
SHEET TITLE'
GROUNDING DETAILS
SHEET NUMBER:
G-1
GROUNDING SCHEMATIC SCALE: N.T.S.
1
LUG DETAIL SCALE N.T.S.
2
GROUNDING NOTES SCALE: N.T.S.
3
2020.0098.0043