HomeMy WebLinkAbout233 W Bleeker.Response.20220112 300 SO SPRING ST | 202 | ASPEN, CO 81611 970.925.2855 | BENDONADAMS.COM January 11, 2022 Sarah Yoon and Natalie Feinberg Lopez Historic Preservation Commission c/o Aspen City Hall 130 South Galena Street, 3rd Floor Aspen, CO 81611 Re: 233 West Bleeker Street Referral Comment Response Dear Sarah, HPC and City Referral Departments, Thank you for the referral comments received January 6, 2022. We have reviewed the comments and have provided responses below. Items for building permit review will be addressed at that time. Please reach out with any questions. Building Department 1. Fire sprinkler required because the gross area exceeds 5,000 sq. ft. 2. Lightwells at the patio will require guards per City of Aspen policy. 3. Snow stops will be required at all roof pitches that shed onto potentially occupied areas per R910 as amended by the City of Aspen. Response – These items are mainly for building permit submittal. The plan will be amended to show lightwells with guards around the interior patio courtyard as opposed to grates, or landscaping will be proposed to create a buffer between the lightwell and the walking surface. Considering the location of the lightwells interior to the property and not visible from the streets, we request that this be addressed at Final Design as part of the landscape plan. Parks Department 1. See attached mark up comments. Response - We met with Parks very early in the design process to discuss tree protection areas and tree removals. We excavated around root systems for Parks review in Fall 2021 to confirm drip line areas as well. Page 2 of 5 233 West Bleeker Street – 10/1/2021 Engineering Department Land Use Comments 1. Sidewalk is not required at this property per the Sidewalk Deferred Zones defined in the Engineering Standards, however Engineering supports the installation of a sidewalk in the ROW as proposed in this land use application. Response – Noted. A sidewalk will be removed from the landscape plan for review at Final Design. 2. ADA compliant ramps need to be installed at the corner of Bleeker and 2nd St with the proposed sidewalk. Confirm layout and grading is achievable. Final grading can be determined at building permit. Response – Noted. The landscape plan will be updated for review at Final Design. Updated civil drawings are attached. 3. What is the proposed stormwater treatments approach? The drainage design needs to be clearly communicated on these plans. Confirm detention is not required for this property. Response – Updated civil drawings are attached. 4. What transformer serves the property and does the existing transformer have capacity for the increased use? Will this property require a new transformer? Work with the City Electric Department to determine available capacity. A Load Calc Form will be required at time of building permit. Response – Brandon Architects discussed using the existing transformer with Ron Christianson early in the design process. It was indicated that there is existing capacity so an onsite transformer is not proposed at this time. 5. Is the transformer in the SE corner a proposed transformer? Does this property connect to this transformer? Are adequate easements provided for this transformer? What size is this transformer? It appears that parking is proposed within the easement, this is not permitted in the easement so access to the transformer is maintained at all times. If this is a new transformer it needs to be replaced fully within the property boundary rather than bridging the property line. Response – The 10’ x 10’ utility easement is not for a transformer; therefore the surface parking space is permitted to be located as shown. 6. A telephone pedestal is shown in the transformer easement, this is not permitted in easement. Please revise. Page 3 of 5 233 West Bleeker Street – 10/1/2021 Response – A transformer easement is not proposed, see notes above. A bollard may be required by Comcast or Lumen, and will be shown for review at Final Design if required. 7. Access is only permitted off the alley per the Engineering Standards. Remove the access to the historic garage as shown on L.1.00 Response – The attached civil drawings removed the proposed double track. The intention was not to provide access to the carriage house (which is a separate dwelling unit with parking off the alley), but to convey the original use of the historic accessory building as a utilitarian carriage house. Note: Building Permit Comments – to be addressed at the time of building permit submittal. Zoning 1. Please provide a zoning summary sheet. Response – updated zoning sheet is attached. 2. Please provide sections. Response – please see attached. 3. Floor Area: a. We encourage the applicant to provide more than 2 SF of unbuilt floor area. b. Please show existing and proposed grade on the subgrade wall calculations. c. Please reach out to work through deck area calculations. d. Provide sections for the attic. e. Please provide proposed floor area summaries unit by unit. Response – please see attached. 4. Setbacks: a. Show the separation between the dwelling units as a setback on all applicable sheets. b. Please update L.1.00 and A-0.0 to accurately reflect the setbacks. c. Dimension all projections into the setback. d. Please provide details to show that the pool and deck to the east of the pool comply with the setback regulations. e. A variance needs to be requested for the stairs from the screen porch. f. Provide details for planters and built-in grill. Response – Please see attached. The steps to the screened in porch are less than 30” above grade. Landscape details will be developed and provide at Final Design Review. 5. Height: a. Without a height over topography sheet, proposed height measurements cannot be reviewed. b. The chimney on the addition is on a roof with a pitch of 12:12 and goes above the ridgeline Page 4 of 5 233 West Bleeker Street – 10/1/2021 of the structure. Please lower the height of the chimney or show that the height of the chimney is necessary to meet building code. Please note that currently the chimneys on the historic resource meet this code; the top of the reconstructed chimneys is below the ridgeline of the addition. If the ridgeline of the addition is lowered, the height of the chimneys will need to be examined. Response – Please see attached. The chimney height has been lowered to the same height as the ridge. As per IRC requirements, the hood extends above the ridge. 6. Demolition: Provide demolition calculations. It appears that demolition is going to be triggered. All non-conformities that are proposed to be maintained need to be reviewed. Response – All existing historic setback non-conformities are requested to be reviewed by HPC for variances. 7. Site Coverage: provide an existing and proposed site coverage diagram. The coverage should be measured as the gross area of the building where it meets the ground; there are no exemptions for staircases and the like. Response – Please see attached email from Sarah Yoon regarding site coverage calculation. 8. Where will mechanical equipment be placed? Response – Mechanical will be placed in the subgrade basement. Air conditioning units are shown on the plans in the east setback and meet setback allowances for height and placement. 9. Parking: please dimension the required third parking space. Response – Please see attached sheet A0.0. Dimensions of the surface parking space are 8.5’ x 18’ and open to the sky. Thank you for reviewing this application. Please reach out if you need additional information to complete your review. Sincerely, Sara Adams, AICP Exhibits A – HP Conceptual Review Criteria and FAR Bonus B – Demolition and Temporary Relocation C – Setback Variance for Existing Historic Condition D – Pre application summary E – Agreement to Pay F – Land Use application G – HOA form H – Authorization to represent Page 5 of 5 233 West Bleeker Street – 10/1/2021 I – Proof of ownership J – Vicinity Map K – Mailing List L – Streetscape context images M - Drawing set: M. 1 Stamped survey M.2 Civil/drainage drawing set M.3 Existing and proposed drawings and renderings N – Referral comments response N.1 Updated drawing set N.2 Updated civil/drainage set N.3 Email from Ron Christianson re: transformer capacity N.4 Email from Planner of the Day re: site coverage DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: SHEET LIST CODE INFORMATIONSITE INFORMATIONPROJECT STATISTICSDEFERRED SUBMITTALSPROJECT DESCRIPTION VICINITY MAP SPECIAL INSPECTIONS SHORING & EXCAVATION AGENCIES & SERVICES PROJECT DIRECTORY 1 3 24 57 68 911 10 BR A N D O N ARCHITECT STRUCTURAL ENGINEER INTERIOR DESIGNER ENERGY CONSULTANT BRANDON ARCHITECTS, INC. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 P: 714.454.4040 WWW.BRANDONARCHITECTS.COM OWNER CIVIL ENGINEER LANDSCAPE DESIGNER MEP CONSULTANT GENERAL CONTRACTOR GEOTECHNICAL ENGINEER SURVEYOR AR C H I T E C T S , I N C . BRANDON ARCHITECTS HISTORIC PRESERVATION 01.10.22 TITLE SHEET KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 T-1.0 KAO RESIDENCE 233 W. BLEEKER ST., ASPEN, CO, 81611 TBD RYAN McDANIEL, AIA LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 STEEPLECHASE 0124 TOTTERDOWN ROAD ASPEN, CO 81611 T: 970.920.4079 KUMAR & ASSOCIATES, INC. 5020 COUNTY ROAD 154 GLENWOOD SPRINGS, CO 81601 P: 970.945.7988 ASPEN SURVEY 210 S. GALENA ST., #22 ASPEN, CO 81611 P: 970.925.3816 CONNECT ONE DESIGN SARA TIE 435 N 8TH ST. CARBONDALE, CO 81623 T: 970.355.5457 TBD DB STRUCTURAL DESIGN LTD. 1229 SAGE CT. RIFLE, CO 81650 T: 801.529.6481 YARNELL CONSULTING & CIVIL DESIGN, LLC P.O. BOX 3901 EAGLE, CO 81631 T: 970.323.7008 TBD TBD MAIN HOUSE LIVING BASEMENT LIVING 3865 SF FIRST FLOOR LIVING 2505 SF SECOND FLOOR LIVING 1470 SF 7840 SF GARAGE 2-CAR GARAGE 494 SF 494 SF GRAND TOTAL 8334 SF LEGAL DESCRIPTION: LOT INFORMATION: ZONED: R-6 SINGLE-UNIT RESIDENTIAL SITE AREA:9,000 S.F. BUILDABLE AREA: 5,950 S.F. TOTAL ALLOWABLE FAR = 4,080 SF + 500 BONUS = 4,580 SF TOTAL PROPOSED FAR = 4,578 SF TOTAL ALLOWABLE LOT COVERAGE = 40% TOTAL PROPOSED LOT COVERAGE = 38.41% EXISTING BUILDING INFORMATION: EXISTING SINGLE FAMILY TO BE RENOVATED BACK TO HISTORICAL FOOTPRINT EXISTING MAIN HOUSE S.F. = 4,893 EXISTING CARRIAGE HOUSE S.F. = 988 ZONING INFORMATION: R6 ZONE DISTRICT REQUIRED SETBACKS: FRONT SETBACK (NORTH): 10 FT. REAR SETBACK (SOUTH): 10 FT. LIVING, 5 FT. GARAGE SIDE SETBACK (EAST): 10 FT. SIDE SETBACK (WEST): 10 FT. DISTANCE BET. BUILDINGS:10 FT. PROPOSED SETBACKS: FRONT SETBACK (NORTH): 15 FT. REAR SETBACK (SOUTH): 0 FT. EXISTING HISTORIC CONDITION (BARN); 5 FT. 1 IN. NEW GARAGE SIDE SETBACK (EAST): 10 FT. SIDE SETBACK (WEST): 8 FT 2 3/8 IN. EXISTING HISTORIC CONDITION BARN AND HOUSE DISTANCE BET. BUILDINGS:10 FT. APN: 273512440001 LOTS A, B AND C, BLOCK 51 CITY AND TOWNSITE OF ASPEN CODES:CITY OF ASPEN MUNICIPAL CODE 2015 IBC, 2015 IRC, 2015 IECC, 2015 IPC, 2015 IMC, 2015 IFC, 2015 IEBC, 2015 INTERNATIONAL SWIMMING POOL AND SPA CODE, 2015 INTERNATIONAL SOLAR ENERGY PROVISIONS, 2020 NEC OCCUPANT LOAD 2 UNITS OCCUPANCY CLASSIFICATION R-3/U OCCUPANCY SEPARATION (GARAGE)1-HR. TYPE OF CONSTRUCTION VB -SPRINKLERED DIG ALERT:1.800.922.1987 ELECTRICAL UTILITY COMPANY:X.XXX.XXXX GAS UTILITY COMPANY:X.XXX.XXXX CITY WATER & SEWER:1.970.920.5030 TELEPHONE COMPANY:X.XXX.XXXX CITY OF ASPEN PUBLIC WORKS DEPT.:1.970.920.5080 CITY OF ASPEN PLANNING DEPT.: GENERAL INFOMATION:1.970.429.2764 CITY OF ASPEN BUILDING DEPT.: GENERAL:1.970.920.5090 PERMITS:1.970.920.5090 INSPECTIONS:1.970.920.5065 CITY OF ASPEN HISTORIC PRESERVATION: GENERAL:1.970.920.5144 ASPEN FIRE DEPARTMENT:1.970.925.5532 1.REF. STRUCTURAL DRAWINGS FOR SPECIAL INSPECTIONS BY ENGINEER OF RECORD 1. LANDSCAPE PLAN; BBQ; FIRE PIT; ACCESSORY STRUCTURES, MASONRY OR CONCRETE WALLS/FENCES; RETAINING WALLS OVER 4 FT. HIGH FROM THE BOTTOM OF THE FOUNDATION TO THE TOP OF WALL; UNDER SEPERATE REVIEWS AND PERMITS. 2. POOLS, SPAS, WALLS, FENCES, PATIO COVERS AND OTHER FREESTANDING STRUCTURES REQUIRE SEPARATE REVIEWS AND PERMITS. 3. SUBMIT SOUND ATTENUATION DESIGN FOR HVAC EQUIPMENT PER ARI STD. 275. SOUND LEVEL NOT TO EXCEED 50dBA (55dBA WITH TIMER, 65dBA WITH TIMER AND NEIGHBORS CONSENT). LOCATION OF MEASUREMENT TO BE AT ADJACENT PROPERTY PATIO OR OPENING. 4. FIRE SPRINKLERS REQUIRED, CONSTRACTOR TO SUBMIT FIRE SPRINKLER DRAWINGS FOR ARCHITECT'S APPROVAL PRIOR TO SUBMITTING TO CITY. OBTAIN FIRE SPRINKLER PERMIT PRIOR TO CALLING FOR ROOF SHEATHING INSPECTION. 5. ELEVATOR NOTE: DEFERRED SUBMITTALS TO BE REVIEWED BY PROJECT ARCHITECT OR ENGINEER OF RECORD AND CERTIFIED PRIOR TO SUBMITTAL TO LOCAL AGENCY FOR REVIEW. THE SUBJECT PROPERTY IS LOCATED IN ASPEN, CO. THE LOT IS APPROXIMATELY 90' WIDE BY 100' DEEP, IT IS ZONED R-6 AND DESIGNATED AS A LOCAL HISTORIC LANDMARK. THE PROPERTY INCLUDES AN EXISTING SINGLE-FAMILY RESIDENCE TO BE RENOVATED BACK TO THE HISTORICAL DESIGN. THE CLIENT PROPOSES A TWO-STORY ADDITION CONNECTED TO THE HISTORIC 2-STORY STRUCTURE BY A ONE-STORY GLASS CONNECTOR. THE PROPOSED DESIGN INCLUDES A 2-CAR GARAGE AND BASEMENT. THE PROJECT WILL BE A MODERN DESIGN WITH DETAILS THAT COMPLEMENT THE VICTORIAN DESIGN OF THE HISTORICAL STRUCTURE. THE ADDITION WILL CONSIST OF AMPLE INDOOR/OUTDOOR LIVING SPACES INTEGRATED WITH A MODERN 'OPEN' LIVING PLAN MAXIMIZING THE FUNCTIONALITY OF THE MAIN LIVING FLOOR AND RELATIONSHIP TO THE HISTORIC STRUCTURE. THE EXTERIOR ON THE ADDITION WILL BE PRIMARILY VERTICAL SIDING AND METAL PANEL WITH A METAL STANDING SEAM ROOF. THE DESIGN CONSISTS OF A GREAT ROOM, OFFICE, MASTER BEDROOM WITH EN-SUITE, 4 BEDROOMS, 9 BATHROOMS, GUEST CASITA, ELEVATOR AND MECHANICAL CLOSETS. T-1.0 TITLE SHEET T-1.1 ARCHITECTURAL GENERAL NOTES T-1.2 ZONING SUMMARY SUR TOPOGRAPHIC SURVEY C1 SITE PLAN C2 OVERALL GRADING PLAN C3 OVERALL UTILITY PLAN C4.1 DETAILED GRADING & UTILITY PLAN C4.2 DETAILED GRADING & UTILITY PLAN C4.3 DETAILED GRADING & UTILITY PLAN C4.4 DETAILED GRADING & UTILITY PLAN L.1.00 LANDSCAPE PLANTING PLAN LIGHT.1.00 SCHEMATIC LIGHTING PLAN LIGHT.1.1 LIGHTING CUTSHEETS D-0.0 EXISTING SITE PLAN D-0.1 ROOF DEMOLITION CALCULATIONS D-0.2 WALL DEMOLITION CALCULATIONS D-1.0 EXISTING FIRST FLOOR DEMOLITION PLAN D-1.1 EXISTING SECOND LEVEL DEMOLITION PLAN D-1.2 EXISTING LOWER LEVEL DEMOLITION PLAN D-2.0 EXISTING ROOF DEMOLITION PLAN D-3.0 EXTERIOR ELEVATION DEMOLITION D-3.1 EXTERIOR ELEVATION DEMOLITION D-3.2 EXTERIOR ELEVATION DEMOLITION A-0.0 ARCHITECTURAL SITE PLAN A-0.1 SITE COVERAGE A-0.2 SETBACKS & ALLOWED PROJECTIONS A-0.3 BASEMENT LEVEL AREA CALCULATIONS A-0.4 FIRST LEVEL AREA CALCULATIONS A-0.5 SECOND LEVEL AREA CALCULATIONS A-0.6 CARRIAGE HOUSE AREA CALCULATIONS A-2.0 FIRST LEVEL FLOOR PLAN A-2.1 SECOND LEVEL FLOOR PLAN A-2.2 BASEMENT LEVEL FLOOR PLAN A-2.3 FIRST LEVEL DIMENSION PLAN A-2.4 SECOND LEVEL DIMENSION PLAN A-2.5 BASEMENT LEVEL DIMENSION PLAN A-3.0 ROOF PLAN A-3.1 ROOF PLAN - HEIGHT OVER TOPOGRAPHY A-4.0 EXTERIOR ELEVATIONS A-4.1 EXTERIOR ELEVATIONS A-5.0 BUILDING SECTIONS A-5.1 BUILDING SECTIONS A-8.0 REALISTIC PERSPECTIVE VIEW A-8.1 REALISTIC PERSPECTIVE VIEW A-8.2 REALISTIC PERSPECTIVE VIEW MAIN STREET R O A R I N G F O R K R I V E R W BLEEKER STREET BENDON ADAMS SARA ADAMS 300 S. SPRING ST. SUITE 202 ASPEN, CO 81611 P: 970.925.2855 DECK AREA <varies>568 SF GRAND TOTAL 568 SF TOTAL GARAGE TOTAL LIVING OVERALL FAR FIRST FLOOR F.F.2964 SF SECOND FLOOR F.F.1470 SF 4435 SF + BASEMENT 154 SF -GARAGE 494 SF GRAND TOTAL 4,578 SF NO. REVISION DATE CARRIAGE HOUSE FIRST FLOOR LIVING 460 SF GRAND TOTAL 460 SF HEIGHT 3 -LEVELS FLOOR AREA REF. 7/T-1.0 FIRE SPRINKLERS REQUIRED458 SF 458 SF 3856 SF 2505 SF 7646 SF POOL DECK 436.72 SF EXTERIOR STAIR 16.95 SF BACK DECK 74.48 SF MASTER BALCONY 83.51 SF GRAND TOTAL 611.66 SF 2999 SF CARRIAGE HOUSE 458 SF TOTAL 4918 SF 3680 SF 1461 SF 8140 SF 1461 SF DEFINITIONS: (AS USED IN THESE SPECIFICATIONS) OWNER SHALL MEAN: LOT D, LLC. "CUSTOM" -C/O JOHN KAO ARCHITECT SHALL MEAN: BRANDON ARCHITECTS, INC., RYAN MCDANIEL CONTRACTOR SHALL MEAN:LICENSED GENERAL CONTRACTOR HIRED TO PERFORM THE WORK UNDER THIS CONTRACT SPECIFICATIONS SHALL MEAN:WRITTEN SPECIFICATIONS IN THE PLANS OR THE "PROJECT MANUAL" (IF PROVIDED FOR THIS PROJECT) CONTRACT DOCUMENTS SHALL MEAN: WORKING DRAWINGS APPROVED FOR BUILDING PERMIT, PLUS ANY CHANGE ORDERS OR ADDENDA TO SAME. ARCHITECTURAL GENERAL NOTES: 1. CODES/GENERAL PROVISIONS: ALL WORK, CONSTRUCTION AND MATERIALS SHALL COMPLY WITH ALL PROVISIONS OF THE APPLICABLE BUILDING CODES AND WITH OTHER RULES, REGULATIONS AND ORDINANCES GOVERNING THE PLACE OF CONSTRUCTION. IT IS THE RESPONSIBILITY OF THE CONTRACTOR, SUB-CONTRACTORS, AND ANYONE SUPPLYING LABOR AND/OR MATERIAL TO BRING TO THE ATTENTION OF THE ARCHITECT (VERBALLY AND IN WRITING) ANY KNOWN DISCREPANCIES OR CONFLICT BETWEEN THE REQUIREMENTS OF THESE CODES AND THE CONTRACT DOCUMENTS (DRAWINGS). THE APPLICABLE CODES SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO THOSE AS LISTED IN "CODE REVIEW" BOX. (T-1.0) ALL WORK SHALL BE PERFORMED SO AS TO COMPLY WITH ALL LEGAL AND INDUSTRY REQUIREMENTS AND STANDARDS INCLUDING THE FOLLOWING: -BUILDING CODES AS ADOPTED BY THE STATE OF COLORADO AND CITY OF ASPEN AND ALL APPLICABLE RELATED SPECIALTY CODES. -THE CITY OF ASPEN MUNICIPAL CODE INCLUDING ANY WORK TIME RESTRICTION AND ANY AMENDMENT TO 2015 INTERNATIONAL BUILDING CODES. -THE MANUFACTURER'S REQUIREMENTS OF RECOMMENDATIONS FOR ANY INCORPORATED PRODUCTS. 2. FEES: CONTRACTOR AND HIS SUB-CONTRACTORS SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES, CONSTRUCTION TAXES AND FEES REQUIRED BY CITY, COUNTY AND STATE LAWS EXCEPT THE GENERAL BUILDING PLAN CHECK FEE AND REQUIRED REFUNDABLE DEPOSITS WHICH WILL BE PAID BY THE OWNER. CONTRACTOR SHALL ARRANGE FOR ALL METER INSTALLATIONS AND PAY ALL FEES FOR SAID METERS. CONTRACTOR SHALL PROVIDE TEMPORARY TOILET FACILITIES AND EROSION CONTROL MEASURES AS REQUIRED BY STATE AND LOCAL BUILDING CODE. 3. CONTRACTOR'S SURVEY: CONTRACTOR SHALL VISIT THE JOB SITE AND BE RESPONSIBLE FOR HAVING COMPLETE KNOWLEDGE OF EXISTING CONDITIONS. CONTRACTOR SHALL VERIFY EXISTING CONDITIONS WITH THOSE SHOWN ON THE DRAWINGS AND SHALL VERIFY GRADES, CONDITIONS AND DIMENSIONS PRIOR TO COMMENCING DEMOLITION AND CONSTRUCTION. CONTRACTOR SHALL NOTIFY THE ARCHITECT IMMEDIATELY VERBALLY AND IN WRITING OF DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND THOSE DEPICTED IN THE CONTRACT DOCUMENTS. CONTRACTOR SHALL NOTIFY ARCHITECT IMMEDIATELY VERBALLY AND IN WRITING OF ANY DISCREPANCIES FOUND WITHIN THE DRAWINGS AND SPECIFICATIONS. 4. COORDINATION OF CONSTRUCTION: CONTRACTOR IS SOLELY RESPONSIBLE FOR THE ACCURACY OF DETAILS; FOR CONFIRMING AND COORDINATING ALL QUANTITIES AND DIMENSIONS; FOR SELECTING FABRICATION PROCESSES; FOR TECHNIQUES OF ASSEMBLY AND PERFORMANCE OF ALL WORK IN A SAFE AND SATISFACTORY MANNER. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL WORK INCLUDING THAT OF THE SUB-CONTRACTORS. CONTRACTOR SHALL PROVIDE SUPERVISION OF THE JOB DURING ALL PHASES OF CONSTRUCTION ACTIVITIES. A COMPETENT SUPERINTENDENT SHALL BE SELECTED BY THE CONTRACTOR AND SHALL BE IN CHARGE OF THE JOB UNTIL ITS COMPLETION. CONTRACTOR AGREES TO BIND EVERY SUB-CONTRACTOR BY THE TERMS OF THE CONTRACT AS FAR AS SUCH TERMS ARE APPLICABLE TO THE SUB-CONTRACTOR'S WORK. 5. CLEAN-UP: ALL SUBCONTRACTORS SHALL BE RESPONSIBLE FOR THE DAILY REMOVAL OF ALL DEBRIS ACCUMULATED AS A RESULT OF THEIR OPERATIONS. ALL SCRAP DEBRIS AND OTHER EXCESS MATERIAL SHALL BE LAWFULLY REMOVED FROM THE SITE, UNLESS OTHERWISE DIRECTED BY THE CONTRACTOR. 6. TESTS AND PERMITS: CONTRACTOR SHALL ARRANGE FOR, AND SECURE REQUIRED TESTS, PERMITS AND INSPECTIONS, AND SHALL BEAR COSTS FOR SAME. 7. GUARANTEES: CONTRACTOR SHALL GUARANTEE ALL WORK, MATERIALS AND PRODUCTS FOR ONE YEAR AFTER THE DATE OF ACCEPTANCE OF THE WORK AND CONTRACTOR SHALL REPAIR OR REPLACE, OR CAUSE TO BE REPAIRED OR REPLACED ANY OR ALL SUCH WORK TOGETHER WITH ANY OTHER WORK WHICH MAY BE DISPLACED IN DOING SO, THAT MAY PROVE DEFECTIVE WITHIN ONE YEAR, WITHOUT ADDITIONAL EXPENSE; ORDINARY WEAR AND TEAR, UNUSUAL ABUSE OR NEGLECT IS EXCEPTED. EXCEPTIONS TO ONE YEAR GUARANTEE ARE SPECIFIED IN OTHER SECTIONS OF THE PROJECT MANUAL OR DRAWINGS. STATE LAW, OR MANUFACTURER'S GUARANTEE SHALL GOVERN IF LENGTH AND TYPES OF GUARANTEES ARE MORE STRICT OR FOR LONGER PERIODS. IT IS UNDERSTOOD BY CONTRACTOR THAT IT IS HIS RESPONSIBILITY TO PROVIDE MATERIALS AND CONSTRUCTION WHICH WILL YIELD A REASONABLE VALUE OVER A PERIOD OF TIME WHICH MAY EXCEED THE SPECIFIED GUARANTEE AND WARRANTY PERIODS. CONTRACTOR SHALL BE RESPONSIBLE FOR A WEATHER TIGHT BUILDING, FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP. EACH SUB-CONTRACTOR SHALL PROVIDE A WRITTEN GUARANTEE STATING THAT WORK EXECUTED BY HIM IS FREE AND WILL REMAIN FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR ONE YEAR FROM DATE OF ACCEPTANCE OF HIS WORK BY OWNER, AND THAT REPAIR AND REPLACEMENT OF SUCH DEFECTIVE WORK AND ALL OTHER WORK DAMAGED AS A RESULT THEREBY WILL BE EXECUTED IN A TIMELY MANNER AT THE CONVENIENCE OF THE OWNER AND WITHOUT COST TO OWNER. 8. WAIVER OF LIENS: CONTRACTOR SHALL PROVIDE CERTIFIED RELEASE OF LIENS BY ALL SUBCONTRACTORS AND SUPPLIERS, OR ANYONE PROVIDING MATERIALS AND/OR LABOR AS THEY BECOME AVAILABLE. 9. ROLL OF ARCHITECT DURING CONSTRUCTION: THE ARCHITECT WILL NOT ACT AS THE OWNER'S REPRESENTATIVE DURING CONSTRUCTION. ARCHITECT WILL ADVISE AND CONSULT WITH OWNER. ARCHITECT WILL OBSERVE CONSTRUCTION PER HIS/HER AGREEMENT WITH OWNER AND RENDER INTERPRETATIONS NECESSARY FOR THE PROPER EXECUTION OR PROGRESS OF THE WORK IN ACCORDANCE WITH THE INTENT OF THE PLANS AND SPECIFICATIONS. ARCHITECT WILL NOT BE RESPONSIBLE OR HAVE CONTROL OR CHARGE OVER THE ACTS OR OMISSIONS, CONSTRUCTION MEANS, METHODS, TECHNIQUES,SEQUENCES OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND PROGRAMS, OF THE CONTRACTOR, SUB-CONTRACTORS, OR ANY OF THEIR AGENTS OR EMPLOYEES, OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK. ANY VERBAL INSTRUCTION OR AUTHORIZATION THAT IS CONFIRMED BY LETTER, MEETING NOTE, MEMORANDA, OR THE LIKE, (WITH A COPY SENT TO THE OWNER, OR THE OWNER'S REPRESENTATIVE) & THERE IS NO EXCEPTION TAKEN WITHIN (10) CALENDAR DAYS, SHALL BE DEEMED EQUIVALENT TO RECEIPT OF WRITTEN INSTRUCTION, APPROVAL AND AUTHORIZATION FROM THE OWNER. 10. A.I.A. GENERAL CONDITIONS: THE CURRENT GENERAL CONDITIONS OF THE CONTRACT FOR CONSTRUCTION PUBLISHED BY THE AMERICAN INSTITUTE OF ARCHITECTS SHALL APPLY AS THOUGH IT WERE PART OF THESE DOCUMENTS UNLESS SPECIFICALLY MODIFIED IN THE OWNER/CONTRACTOR AGREEMENT. A COPY OF SAID GENERAL CONDITIONS MAY BE OBTAINED FROM THE ARCHITECT UPON REQUEST. THE NOTES CONTAINED IN THESE "GENERAL NOTES" ON THIS SHEET ARE INTENDED TO SUMMARIZE AND COMPLIMENT THE A.I.A. GENERAL CONDITIONS. THE A.I.A. GENERAL CONDITIONS SHALL TAKE PRECEDENCE OVER THESE NOTES SHOULD A CONFLICT IN WORDING OCCUR. 11. EXTRAS: OWNER MAY ORDER EXTRA WORK OR MAKE CHANGES BY ALTERING, ADDING TO OR DEDUCTING FROM THE WORK, THE CONTRACT SUM BEING ADJUSTED TO THE MUTUAL SATISFACTION OF THE OWNER AND CONTRACTOR. BEFORE ANY CHANGES ARE BEGUN, THE ADDED OR DEDUCTED SUM SHALL BE PRESENTED TO OWNER IN WRITING FOR APPROVAL. 12. SUBSTITUTIONS: SUBSTITUTIONS OF MATERIALS OR METHODS PROPOSED BY THE CONTRACTOR OR HIS SUB-CONTRACTORS CONTRARY TO DRAWINGS AND SPECIFICATIONS SHALL BE SUBMITTED TO ARCHITECT IN WRITING FOR APPROVAL OR DENIAL. IF MORE THAN ONE MANUFACTURER IS SPECIFIED IN THE PLANS OR SPECIFICATIONS, IT SHALL BE THE CONTRACTOR'S OPTION TO SELECT THE ONE WHICH HE MAY DESIRE. IF MORE THAN ONE FINISH OR STYLE IS AVAILABLE IN THE ITEM SPECIFIED, CONTRACTOR SHALL BE OBLIGATED TO NOTIFY ARCHITECT VERBALLY AND IN WRITING OF THIS FACT FOR ARCHITECT'S AND OWNER'S DECISION. WHERE THE TERM "OR EQUAL" IS USED IN DRAWINGS OR SPECS IT SHALL BE UNDERSTOOD THAT THE REFERENCE IS MADE SUBJECT TO THE RULING AND JUDGMENT OF THE ARCHITECT AND SHALL BE SUBMITTED TO THE ARCHITECT FOR REVIEW AND APPROVAL. ACTUAL SAMPLES OF THE SUBSTITUTIONS SHALL ALSO BE SUBMITTED TO THE ARCHITECT FOR REVIEW AND APPROVAL. 13. INSURANCE: CONTRACTOR SHALL CARRY GENERAL LIABILITY INSURANCE WITH BROAD FORM PROPERTY DAMAGE ENDORSEMENT AND CONTINGENT LIABILITY ENDORSEMENT. OWNER AND ARCHITECT SHALL BE LISTED AS ADDITIONAL INSURERS UNDER THE POLICY WITH WAIVER OF SUBROGATION. CONTRACTOR SHALL FURNISH OWNER WITH A CERTIFICATE OF INSURANCE WITH A 30 DAY NOTICE OF CANCELLATION. OWNER SHALL OBTAIN A BUILDER'S RISK POLICY WITH ARCHITECT NAMED AS AN ADDITIONAL INSURED WITH WAIVER OF SUBROGATION. 14. SCOPE OF DRAWINGS AND SPECIFICATIONS: THESE DRAWINGS AND SPECIFICATIONS SHALL BE INTENDED TO SHOW AND DESCRIBE DETAILS FOR A CONSTRUCTIBLE BUILDING. PARTS AND DETAILS NOT FULLY SHOWN OR DESCRIBED SHALL BE DETAILED AND EXECUTED ACCORDING TO STANDARD FIRST CLASS PRACTICE AND IN SIMILAR MANNER AND SPIRIT OF THE DETAILS WHICH ARE SHOWN ON THE DRAWINGS AND/OR DESCRIBED IN THE PROJECT MANUAL. IF CONTRACTOR OR SUB-CONTRACTOR FINDS ANY DETAILS WHICH, IN HIS OPINION, ARE UNSOUND, UNSAFE, OR NOT WATERPROOF, IT IS HIS DUTY TO NOTIFY ARCHITECT IN WRITING OF THIS FACT. IF WORK IS PERFORMED AS DETAILED, IT WILL BE ASSUMED THAT THERE ARE NO OBJECTIONS TO THE DETAIL. ACCURACY OF ALL DIMENSIONS SHALL BE CHECKED. NO EXTRA COMPENSATION WILL BE ALLOWED FOR DIFFERENCE BETWEEN ACTUAL DIMENSIONS AND THOSE INDICATED ON THE DRAWINGS. IN USING THESE PLAN FOR BIDDING OR CONSTRUCTION PURPOSES, ALL CONTRACTORS ARE REQUIRED TO REVIEW AND TREAT THEM AS A WHOLE IN ORDER TO IDENTIFY ALL REQUIREMENTS THAT DIRECTLY OR INDIRECTLY AFFECT THEIR PORTION OF THE WORK, EVEN REQUIREMENTS LOCATED IN SECTIONS DESIGNATED AS APPLICABLE TO OTHER TRADES. IN CASE OF CONFLICTS, THE AFFECTED CONTRACTOR IS REQUIRED TO EITHER OBTAIN DIRECTION FROM AN APPROPRIATE REPRESENTATIVE OF THE OWNER, OR OTHERWISE TO APPLY THE MORE STRINGENT STANDARD. THESE PLANS ARE INTENDED TO SET FORTH THE REQUIREMENTS FOR CONSTRUCTION IN ONLY AN INDUSTRY-STANDARD LEVEL OF QUALITY AND DETAIL, AND THEY ARE INTENDED TO BE SUPPLEMENTED BY APPROPRIATE REQUESTS FOR CLARIFICATION AND INFORMATION. ERRORS AND OMISSIONS ARE TO BE EXPECTED AND ANTICIPATED, AND ALL CONTRACTORS ARE REQUIRED TO CAREFULLY REVIEW THESE PLANS FOR ERRORS AND OMISSIONS AND TO BRING THESE ERRORS AND OMISSIONS TO THE ATTENTION OF A APPROPRIATE OWNER & ARCHITECT IN WRITING IN A TIMELY MANNER; AND ANY CONTRACTOR WHO FAILS TO DO SO BEFORE BIDDING OR OTHERWISE PROCEEDING ASSUMES THE RISK OF ANY CONSEQUENCES. SCALED DIMENSIONS SHOULD BE CONSIDERED ONLY APPROXIMATE; AND IN ANY DIMENSIONS BEFORE PROCEEDING WITH ANY AFFECTED PROCUREMENT, FABRICATION OR CONSTRUCTION. SCHEMATIC PLANS ARE INTENDED ONLY TO DEMONSTRATE THE RELATIONSHIP AMONG COMPONENT PARTS, AND NOT TO DEPICT SPECIFIC LOCATIONS (E.G. SCHEMATIC ELECTRICAL PLANS). 15. DIMENSIONS ON DRAWINGS: FIGURED DIMENSIONS SHALL BE FOLLOWED IN PREFERENCE TO SCALE, AND DETAIL DRAWINGS IN PREFERENCE TO SMALL SCALE DRAWINGS. SUB-CONTRACTOR AND CONTRACTOR SHALL CHECK ACCURACY OF ALL DIMENSIONS IN THE FIELD PRIOR TO ANY WORK BEING CONSTRUCTED OR MATERIALS OR PRODUCTS FABRICATED OR ORDERED. SPECIFICATIONS AND WRITTEN NOTES AND SCHEDULES ON DRAWINGS SHALL BE FOLLOWED IN PREFERENCE TO INFORMATION FURNISHED IN THE FORM OF LINE DRAWINGS. DETAILED DRAWINGS FURNISHED DURING CONSTRUCTION OR APPROVED BY CONTRACTOR OR ARCHITECT ARE TO BE CONSIDERED EXPLANATORY AND NOT AS CHANGES TO DRAWINGS AND SPECIFICATIONS. NOTES, FIGURES AND DETAILS ON SAID DRAWINGS SHALL BE FOLLOWED AND EXECUTED AS IF PART OF THESE DOCUMENTS. DRAWINGS ARE NOT TO BE SCALED UNLESS PERMITTED BY THE ARCHITECT. DIMENSIONS SHALL GOVERN. ALL EXTERIOR DIMENSIONS ARE BASED ON NOMINAL SIZES OF MEMBERS AND ARE GIVEN TO THE OUTER FACE OF SUCH MEMBERS, UNLESS OTHERWISE NOTED ON DRAWINGS. INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE UNLESS OTHERWISE NOTED ON DRAWINGS. WHERE DIMENSION IS LABELED "CLEAR" IT IS TAKEN FROM THE FACE OF FINISH TO FACE OF FINISH OF EACH MATERIAL. PLUS OR MINUS (+/-) DIMENSIONS SHALL NOT VARY BY MORE THAN 2" WITHOUT APPROVAL BY ARCHITECT. WALL ANGLES ARE EITHER 90° OR 45° UNLESS NOTED OTHERWISE. 16. SUBMITTALS, MEETING NOTES, BULLETINS, AND MEMOS: SUBMITTALS WILL BE REVIEWED BY THE ARCHITECT, IF AT ALL, ONLY PURSUANT TO THE INDUSTRY-STANDARD PROTOCOL SET FORTH IN AIA DOCUMENT A201-2017; AND IN NO EVENT WILL THE SUBMITTAL REVIEW PROCESS RELIEVE OR LESSEN THE SUBMITTING CONTRACTOR'S RESPONSIBILITY FOR AN INAPPROPRIATE SUBMITTAL. ARCHITECT, FROM TIME TO TIME, WILL ISSUE CONSTRUCTION NOTES OR MEMOS REGARDING CONSTRUCTION ISSUES THAT HAVE ARISEN SINCE THE DRAWINGS AND SPECIFICATIONS WERE COMPLETED. CONTRACTOR SHALL REVIEW THESE WRITTEN DOCUMENTS AND INCORPORATE THEM INTO THE PROJECT. ANY QUESTIONS OR OBJECTIONS AS TO THE INTENT OF THE WRITTEN DOCUMENT ITEMS WILL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT FOR DISCUSSION AND OR CLARIFICATION. ANY ITEM THAT RESULTS IN A CHANGE TO THE COST OR TIMING OF THE PROJECT SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE OWNER & ARCHITECT PRIOR TO EXECUTING. CONTRACTOR SHALL SUBMIT FABRICATION SHOP DRAWINGS TO THE ARCHITECT FOR APPROVAL PRIOR TO ORDERING AND/OR FABRICATION. CONTRACTOR SHALL SUBMIT MANUFACTURER'S CUTS FOR ALL FIXTURES AND EQUIPMENT CALLED FOR ON THE CONSTRUCTION DOCUMENTS TO ARCHITECT INCLUDING BUT NOT LIMITED TO LIGHT FIXTURES, HARDWARE, PLUMBING FIXTURES, KITCHEN EQUIPMENT, ETC. BY SUBMITTING SHOP DRAWINGS AND PRODUCT DATA, THE CONTRACTOR REPRESENTS THAT HE/SHE HAS VERIFIED FIELD CONDITIONS, DIMENSIONS AND RELATED CONSTRUCTION AND HAS COORDINATED THE SUBMISSION CONSTRUCTION WITH THE REQUIREMENTS OF ALL OTHER RELATED WORK IN THE CONSTRUCTION DOCUMENTS. ALL SHOP DRAWINGS AND CUTS MARKED "REVIEWED" BY ARCHITECT, ARE FOR VERIFICATION OF ADHERENCE TO THE DESIGN INTENT ONLY. THE CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR ALL MEANS AND METHODS AND ERRORS AND OMISSIONS ON THEIR DRAWINGS. CONTRACTOR TO SUBMIT A COMPLETE SHOP DRAWINGS AND OR SUBMITTAL FOR APPROVAL BEFORE COMMENCING FABRICATION AND/OR INSTALLATION OF ALL APPLICABLE ITEMS. ALL SHOP DRAWINGS DIMENSIONS SHALL BE FIELD VERIFIED, REVIEWED AND APPROVED BY CONTRACTOR BEFORE SUBMITTAL. SHOP DRAWINGS WHICH ARE INCOMPLETE OR LACKING SUFFICIENT INFORMATION WILL BE RETURNED WITHOUT REVIEW. SUBMIT SAMPLES FOR INITIAL SELECTION PURPOSES OF ACTUAL VENEERS SHOWING A FULL RANGE OR GRAIN VARIATION, FINISH AND PATTERNS PROPOSED. SUBMIT SAMPLES AS REQUIRED UNTIL APPROVED BY ARCHITECT. SAMPLES SHALL BE 12" X 12" MIN., ONE UNIT OF EACH TYPE AND FINISH. 17. ERRORS AND OMISSIONS: ERRORS OR OMISSIONS WHICH APPEAR ON THE DRAWINGS, IN SPECIFICATIONS OR OTHER CONTRACT DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT BY THE CONTRACTOR AND TO THE CONTRACTOR BY THE SUB-CONTRACTOR IN WRITING. IN EVENT OF FAILURE OF SUB-CONTRACTOR TO GIVE SUCH WRITTEN NOTIFICATION BEFORE CONSTRUCTION OR FABRICATIONS OF THE WORK, HE WILL BE HELD RESPONSIBLE FOR THE RESULTS OF ANY SUCH ERRORS OR OMISSIONS AND THE COSTS OF RECTIFYING SAME. HOWEVER, DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY AND WORK CALLED FOR ON ONE AND NOT THE OTHER SHALL BE PROVIDED AS THOUGH FULLY SET FORTH IN BOTH. 18. BARRICADES: CONTRACTOR SHALL ERECT AND PROPERLY MAINTAIN AT ALL TIMES AS REQUIRED BY CONDITIONS AND PROGRESS OF THE WORK, ALL NECESSARY PROTECTIVE BARRICADES, FENCES AND OTHER SAFEGUARDS FOR THE PROTECTION OF THE WORKERS AND THE PUBLIC. THESE BARRICADES SHALL BE CONSTRUCTED AND BE LOCATED AS SHALL BE DETERMINED BY LOCAL AUTHORITIES AND CODES. 19. TEMPORARY BRACING: AT ALL TIMES DURING CONSTRUCTION ACTIVITIES OR ERECTION OF PROJECT OR ITS COMPONENT PARTS, PRIOR TO COMPLETION OF THE STRUCTURAL FRAME OR REPLACEMENT AND PERMANENT CONNECTION OF COMPONENT MEMBERS TO THE STRUCTURAL FRAME, SUB-CONTRACTORS SHALL PROVIDE, INSTALL AND MAINTAIN PROPERLY DESIGNED AND CONSTRUCTED TEMPORARY BRACING OF ADEQUATE STRENGTH TO PREVENT DISLOCATION, DISTORTION, CRACKING, FALLING OFF, OR ANY OTHER DAMAGE TO WORK OR ANY OF ITS COMPONENT PARTS DUE TO FORESEEABLE NORMAL AS WELL AS NOT FORESEEABLE EXCESSIVE WIND AND EARTHQUAKE FORCES WITHOUT ADDITIONAL COST TO OWNER. CONTRACTOR AND HIS SUBCONTRACTORS SHALL, AT THEIR EXPENSE, REPLACE OR REPAIR, AS DIRECTED, DAMAGED PORTIONS OF THEIR WORK OR COMPONENT PARTS. 20. TOXIC SUBSTANCES REMOVAL: PRIOR TO ANY WORK BEING PERFORMED, WHENEVER THERE ARE EXISTING STRUCTURES TO BE REMOVED OR ALTERED, CONTRACTOR SHALL BE RESPONSIBLE FOR THE LOCATION AND REMOVAL OF ANY TOXIC MATERIALS OR SUBSTANCES AS REQUIRED BY THE STATE OF COLORADO INCLUDING BUT NOT LIMITED TO ASBESTOS, LEAD PAINTS, MOLD, ETC. REMOVAL AND DISPOSAL SHALL FOLLOW STATE MANDATED METHODS, PROCEDURES, DOCUMENTATION AND APPLICATION REQUIREMENTS. 21. NO CHANGES ARE TO BE MADE ON THESE PLANS WITHOUT THE KNOWLEDGE OR CONSENT OF THE ARCHITECT/ ENGINEER WHOSE SIGNATURE APPEARS HERON. 22. NO FRAMING OF ANY TYPE TO BE CONCEALED PRIOR TO INSPECTION BY GOVERNING AGENCIES. 23. REFERENCES TO ANY DETAIL OR DRAWINGS IS FOR CONVENIENCE ONLY AND DOES NOT LIMIT THE APPLICATION OF SUCH DETAIL OR DRAWINGS. 24. USE 2X6 MINIMUM STUDS FOR PLUMBING WALLS 25. MAINTENANCE INFORMATION: THE BUILDER SHALL PROVIDE TO THE BUILDING OWNER AT OCCUPANCY MAINTENANCE INFORMATION FOR ALL FEATURES, MATERIALS, COMPONENTS, AND MANUFACTURED INFORMATION FOR ALL FEATURES, MATERIALS, AND COMPONENTS AND MANUFACTURED DEVICES THAT REQUIRE ROUTINE MAINTENANCE FOR EFFICIENT OPERATION. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY STATED AND INCORPORATED ON A READILY ACCESSIBLE LABEL. THE LABEL MAY BE LIMITED TO IDENTIFYING, BY TITLE AND/OR PUBLICATION NUMBER, THE OPERATION AND MAINTENANCE MANUAL FOR THAT PARTICULAR MODEL AND TYPE OF FEATURE, MATERIAL, COMPONENT, OR MANUFACTURED DEVICE. 26. GENERAL CONTRACTOR, CONTRACTORS, SUB-CONTRACTORS AND BUILDERS TO COORDINATE ALL ENGINEERING AND MECHANICAL DRAWINGS WITH ARCHITECTURAL DRAWINGS BEFORE PROCEEDING WITH WORK. IF DISCREPANCIES ARE APPARENTLY OBSERVED OR INFORMATION APPARENTLY IS THOUGHT TO BE MISSING, NOTIFY ARCHITECT WITHIN 24 HOURS WITH SKETCH, DRAWING, PDF, PHOTOCOPIES WITH LEGIBLE HANDWRITTEN NOTES AND/OR WRITING (FAX, EMAIL OR CORRESPONDENCE). IF CONFLICT WITH EXISTING CONDITIONS, PROVIDE DOCUMENTATION (PHOTOS, SKETCHES, DWGS) OF EXISTING CONDITIONS AND SUGGEST PROPOSAL(S) FOR SOLUTION (SKETCH, DRAWING, AND/OR WRITING). IN CASE OF ANY DISCREPANCIES, THE ARCHITECT IS THE SOLE INTERPRETER OF THE CONTRACT DOCUMENTS. 27. CONTRACTOR SHALL NOTIFY ARCHITECT FOR CLARIFICATION PRIOR TO BIDDING OF ANY DISCREPANCIES BETWEEN ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. BID SHALL BE BASED ON THE MOST STRINGENT REQUIREMENT. 28. CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ARCHITECT OF ANY UNEXPECTED OR UNKNOWN FIELD CONDITIONS, ERRORS, OMISSIONS, OR DISCREPANCIES IN THE DRAWINGS, PROJECT MANUAL, OR CONTRACT DOCUMENTS PRIOR TO PROCEEDING WITH THE WORK OR SHOP FABRICATIONS. 29. CONTRACTOR SHALL PREPARE AND MAINTAIN ALL CONSTRUCTION, AND SURROUNDING AREAS, FREE OF DEBRIS OR HAZARDOUS MATERIALS AT ALL TIMES. CONTRACTOR SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT DUST FROM RISING. 30. CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR AND/OR THE REPLACEMENT OF ANY ITEMS DAMAGED DURING CONSTRUCTION OR CLEAN-UP. ANY DAMAGE TO EXISTING STRUCTURES DURING THE CONSTRUCTION OR THE NEW WORK SHALL BE REPAIRED TO EQUIVALENT OR BETTER THAN ORIGINAL CONDITION AT CONTRACTOR'S EXPENSE. 31. ALL OSHA REGULATIONS FOR CONSTRUCTION AREAS SHALL BE STRICTLY FOLLOWED. CONTRACTOR SHALL PROVIDE PROPER SAFEGUARDS DURING ALL PHASES OF CONSTRUCTION. 32. CONTRACTOR TO REMOVE, RELOCATE OR RE-ROUTE, AS NECESSARY, ELECTRICAL, TELEPHONE, WATER, SEWER, GAS OR ANY OTHER UTILITY LINES ENCOUNTERED AND SHALL COORDINATE THIS WORK WILL ALL LOCAL UTILITY COMPANIES. 33. CONTRACTOR SHALL PROVIDE TEMPORARY WEATHER PROTECTION FOR PORTIONS OF THE WORK THAT BECOME EXPOSED TO WEATHER AND SHALL BE RESPONSIBLE FOR DAMAGE CAUSED BY INSUFFICIENT PROTECTION. 34. CONTRACTOR TO OBTAIN WRITTEN APPROVAL FROM OWNER AND ARCHITECT PRIOR TO ANY CHANGES OR DEVIATION FROM CONTRACT DOCUMENTS. 35. CONTRACTOR SHALL SUBMIT IN WRITING ALL PROPOSALS FOR ADDITIONAL WORK TO THE OWNER FOR REVIEW AND APPROVAL. NO WORK IS TO PROCEED UNTIL AN AUTHORIZATION TO PROCEED; SIGNED BY THE ARCHITECT & OWNER'S REPRESENTATIVE IS RETURNED TO THE GENERAL CONTRACTOR. 36. CONTRACTOR SHALL BE AWARE THAT SPECIFIC FIRE-RATED SEPARATION WITHIN THE BUILDING'S CONSTRUCTION IS REQUIRED BY CODE. THE USE OF SPECIFIC MATERIALS AND COMBINATION OF MATERIALS WITHIN FIRE RATED ASSEMBLIES, AS CALLED FOR ON THE DRAWINGS AND SPECIFICATIONS, ARE FOR THE PURPOSE OF ACHIEVING THOSE REQUIRED FIRE SEPARATIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THAT ANY CHANGE IN MATERIAL THAT IS REQUESTED BY OR MADE BY THE CONTRACTOR AND/OR ITS SUBCONTRACTORS, FROM THOSE MATERIALS DRAWN OR SPECIFIED,DOES NOT IN ANY WAY AFFECT OR LESSEN THE REQUIRED CONSTRUCTION ASSEMBLY INTEGRITY. SPECIFIC SEQUENCES OR METHODS OF ACHIEVING FIRE RATED ASSEMBLIES REQUIRED BY A "U.L. NO." LISTING SHALL BE FOLLOWED WITHOUT DEVIATION, UNLESS OTHERWISE NOTED OR DETAILED. 69. CONTRACTOR TO FURNISH AND INSTALL ALL BLOCKING REQUIRED FOR WALL MOUNTED OR BRACED FIXTURES, MILLWORK, SHELVES, TOILET FIXTURES, AND ACCESSORIES OR 'BY OTHER' ITEMS DESCRIBED IN INTERIOR DESIGN AND ARCHITECTURAL DRAWINGS. BLOCKING SHALL BE CONSTRUCTED TO SUPPORT THE IMPOSED LOAD. 37. ALL MANUFACTURED ARTICLES, MATERIALS AND EQUIPMENT SHALL BE SUPPLIED, INSTALLED, CONNECTED, ERECTED, USED, CLEANED AND CONDITIONED AS DIRECTED BY THE MANUFACTURERS AND REQUIRED BY CODE. 38. PRIOR TO CONSTRUCTION, CONTRACTOR TO VERIFY/COORDINATE UTILITY REQUIREMENTS FOR ALL OWNER/VENDOR FURNISHED EQUIPMENT, FIXTURES OR APPLIANCES. 39. CONTRACTOR SHALL PROVIDE ALL NECESSARY FASTENERS, SUPPORTS, SHIMMING, FLASH PATCHING, ETC. FOR THE PROPER INSTALLATION OF SUCH ITEMS AS DIRECTED BY THE MANUFACTURERS. 40. UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL GIVE TO THE OWNER A COMPLETE SET OF AS-BUILT CIVIL, LANDSCAPE, ARCHITECTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND FIRE PROTECTION DRAWINGS ALONG WITH THE WRITTEN GUARANTIES, OPERATION AND MAINTENANCE MANUALS OF ALL EQUIPMENT AND FINISHES INSTALLED. THE CONTRACTOR SHALL MAINTAIN A CURRENT SET OF AS-BUILT DRAWINGS AND SPECIFICATIONS. INFORMATION SHALL BE RECORDED BY CONTRACTOR AS CONSTRUCTION PROGRESSES AND REVIEWED FOR COMPLETENESS AT EACH REQUISITION REQUEST. 41. CONTRACTOR IS RESPONSIBLE TO THOROUGHLY VACUUM CLEAN ALL CARPETED AREAS, CLEAN ALL FLOORING, MILLWORK, LIGHT FIXTURES, GLASS, ETC. AND UNCOVER AND VACUUM OUT ALL MECHANICAL UNITES AFTER THE WORK IS COMPLETED AND MAINTAIN CLEAN CONDITIONS THROUGH THE TENANT'S MOVE-IN. WATERPROOFING AND DAMPPROOFING NOTES: R406.1 CONCRETE AND MASONRY FOUNDATION DAMPPROOFING EXCEPT WHERE REQUIRED BY SECTION R406.2 TO BE WATERPROOFED, FOUNDATION WALLS THAT RETAIN EARTH AND ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE DAMPPROOFED FROM THE HIGHER OF (A) THE TOP OF THE FOOTING OR (B) 6 INCHES (152 MM) BELOW THE TOP OF THE BASEMENT FLOOR, TO THE FINISHED GRADE.MASONRY WALLS SHALL HAVE NOT LESS THAN 3/8-INCH (9.5 MM) PORTLAND CEMENT PARGING APPLIED TO THE EXTERIOR OF THE WALL. THE PARGING SHALL BE DAMPPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING: 1. BITUMINOUS COATING. 2. THREE POUNDS PER SQUARE YARD (1.63 KG/M2) OF ACRYLIC MODIFIED CEMENT. 3. ONE-EIGHTH-INCH (3.2 MM) COAT OF SURFACE-BONDING CEMENT COMPLYING WITH ASTM C887. 4. ANY MATERIAL PERMITTED FOR WATERPROOFING IN SECTION R406.2. 5. OTHER APPROVED METHODS OR MATERIALS. EXCEPTION:PARGING OF UNIT MASONRY WALLS IS NOT REQUIRED WHERE A MATERIAL IS APPROVED FOR DIRECT APPLICATION TO THE MASONRY.CONCRETE WALLS SHALL BE DAMPPROOFED BY APPLYING ANY ONE OF THE LISTED DAMPPROOFING MATERIALS OR ANY ONE OF THE WATERPROOFING MATERIALS LISTED IN SECTION R406.2 TO THE EXTERIOR OF THE WALL. R406.2 CONCRETE AND MASONRY FOUNDATION WATERPROOFING IN AREAS WHERE A HIGH WATER TABLE OR OTHER SEVERE SOIL-WATER CONDITIONS ARE KNOWN TO EXIST, EXTERIOR FOUNDATION WALLS THAT RETAIN EARTH AND ENCLOSE INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE WATERPROOFED FROM THE HIGHER OF (A) THE TOP OF THE FOOTING OR (B) 6 INCHES (152 MM) BELOW THE TOP OF THE BASEMENT FLOOR, TO THE FINISHED GRADE. WALLS SHALL BE WATERPROOFED IN ACCORDANCE WITH ONE OF THE FOLLOWING: 1. TWO-PLY HOT-MOPPED FELTS. 2. FIFTY-FIVE-POUND (25 KG) ROLL ROOFING. 3. SIX-MIL (0.15 MM) POLYVINYL CHLORIDE. 4. SIX-MIL (0.15 MM) POLYETHYLENE. 5. FORTY-MIL (1 MM) POLYMER-MODIFIED ASPHALT. 6. SIXTY-MIL (1.5 MM) FLEXIBLE POLYMER CEMENT. 7. ONE-EIGHTH-INCH (3 MM) CEMENT-BASED, FIBER-REINFORCED, WATERPROOF COATING. 8. SIXTY-MIL (1.5 MM) SOLVENT-FREE LIQUID-APPLIED SYNTHETIC RUBBER. ALL JOINTS IN MEMBRANE WATERPROOFING SHALL BE LAPPED AND SEALED WITH AN ADHESIVE COMPATIBLE WITH THE MEMBRANE. EXCEPTION: ORGANIC-SOLVENT-BASED PRODUCTS SUCH AS HYDROCARBONS, CHLORINATED HYDROCARBONS, KETONES AND ESTERS SHALL NOT BE USED FOR ICF WALLS WITH EXPANDED POLYSTYRENE FORM MATERIAL. USE OF PLASTIC ROOFING CEMENTS, ACRYLIC COATINGS, LATEX COATINGS, MORTARS AND PARGINGS TO SEAL ICF WALLS IS PERMITTED. COLD-SETTING ASPHALT OR HOT ASPHALT SHALL CONFORM TO TYPE C OF ASTM D449. HOT ASPHALT SHALL BE APPLIED AT A TEMPERATURE OF LESS THAN 200°F (93°C). DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. -CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. ROUGH FRAMING: ALL EXTERIOR WALLS TO BE FRAMED W/. 2X6 STUD MIN. U.N.O. USE 2X6 MINIMUM STUDS FOR PLUMBING WALLS SECOND AND THIRD FLOOR PLYWOOD TO BE 1-1/8" ENTIRE EXTERIOR TO BE SHEATHED WITH 1/2" PLYWOOD DOORS AND WINDOWS WILL TYPICALLY BE RECESSED FROM EXTERIOR WALL PLANE. VERIFY ALL ROUGH OPENING DIMENSIONS WITH DOOR AND WINDOW MFGR. ROUGH OPENING MAY NEED TO BE OVERSIZED TO ACCOUNT FOR ADDITIONAL FRAMING. SEE SHT. AD-2.0 FOR TYP. RECESSED CONDITIONS. DUCTS PENETRATION: DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A MINIMUM NO. 26 GAGE (0.48 MM) SHEET STEEL OR OTHER APPROVED MATERIAL AND SHALL NOT HAVE OPENINGS INTO THE GARAGE (R302.5.2) STAIRWAY ILLUMINATION: 1.INTERIOR STAIRWAYS SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT SOURCE TO ILLUMINATE THE LANDINGS AND TREADS. THE LIGHT SOURCE SHALL BE CAPABLE OF ILLUMINATING TREADS AND LANDINGS TO LEVELS OF NOT LESS THAN 1 FOOT-CANDLE (11 LUX) AS MEASURED AT THE CENTER OF TREADS AND LANDINGS. THERE SHALL BE A WALL SWITCH AT EACH FLOOR LEVEL TO CONTROL THE LIGHT SOURCE WHERE THE STAIRWAY HAS SIX OR MORE RISERS. (R303.7) EXCEPTION:A SWITCH IS NOT REQUIRED WHERE REMOTE, CENTRAL OR AUTOMATIC CONTROL OF LIGHTING IS PROVIDED. 2.EXTERIOR STAIRWAYS SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT SOURCE LOCATED AT THE TOP LANDING OF THE STAIRWAY. EXTERIOR STAIRWAYS PROVIDING ACCESS TO A BASEMENT FROM THE OUTDOOR GRADE LEVEL SHALL BE PROVIDED WITH AN ARTIFICIAL LIGHT SOURCE LOCATED AT THE BOTTOM LANDING OF THE STAIRWAY. (R303.8) GARAGE FLOOR: GARAGE FLOOR SURFACES SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIAL.THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN VEHICLE ENTRY DOORWAY. (R309.1) PLUMBING: 1. ALL FIXTURES AND FITTINGS SHALL COMPLY WITH THE MAX FLOW RATE SET BY SET BY EPA AND INTERNATIONAL PLUMBING CODES. G.C. TO VERIFY PRIOR TO PURCHASE AND INSTALL OF ANY FIXTURE AND FITTING 2. MAX. TEMP. OF 120° TO BE APPROVED BY THE USE OF PRESSURE BALANCE OR THERMOSTATIC MIXING VALVES TYP. IN COMPLIANCE W/. ASSE 1016/ASME A112.1016/CSA B125.16 @ SHOWERS & TUBS. (IPC 412.3) 3. MAX. TEMP. OF 110° TO BE APPROVED BY THE USE OF PRESSURE BALANCE OR THERMOSTATIC MIXING VALVES TYP. IN COMPLIANCE W/. ASSE 1070/ASME A112.1070/CSA B125.70 @ BIDETS. (IPC 408.3) 4. SUPPORT ALL WALL-HUNG FIXTURES WITH METAL SUPPORTING MEMBERS TO PREVENT ANY STRAIN TRANSMISSION TO THE CONNECTIONS. FRAMING AFFIXED SUPPORTS FOR OFF-THE-FLOOR WATER CLOSETS WITH CONCEALED TANKS SHALL COMPLY WITH ASME A112.6.2. SECURE FLUSH TANK AND SIMILAR APPURTENANCES WITH APPROVED NON-CORROSIVE SCREW OR BOLTS. (IRC P2702) 5. THE NET AREA OF THE SHOWER ENCLOSURE SHALL BE 1,024 SQ. INCHES (7.1 SQ. FT.) OR MORE IN THE CLEAR FLOOR AREA, AND SHALL ALSO BE CAPABLE OF ENCOMPASSING A 30-INCH DIAMETER CIRCLE. (IRC 92708 & IPC 421) 6. THE WATER HEATER BURNER AND BURNER-IGNITION DEVICE TO BE AT LEAST 18-INCHES ABOVE THE FLOOR, IF LOCATED IN A GARAGE AND IN ADJACENT SPACES THAT OPEN TO THE GARAGE. FOR WATER HEATER IN THE GARAGE OR OTHER AREAS SUBJECT TO MECHANICAL DAMAGE PROVIDE A PROTECTIVE BARRIER OR ELEVATE THE APPLIANCE TO BE OUT OF THE NORMAL PATH OF THE VEHICLE. (IRC P2801) 7. ANCHOR OR STRAP THE WATER HEATER(S) TO RESIST HORIZ. DISPLACEMENT DUE TO THE EARTHQUAKE. STRAPPING SHOULD BE AT THE UPPER AND LOWER ONE THIRD (1/3) POINTS OF THE APPLIANCE HEIGHT. MAINTAIN A MIN. 4-INCHES ABOVE THE CONTROLS WITH STRAPPING AT LOWER POINT. (IRC P92801.8) MATERIALS & FINISHES: 1. WALLS COVERINGS AND FLOOR OF SHOWERS AND BATHTUBS WITH A SHOWER HEAD SHALL BE OF CEMENT PLASTER, TILE, OR APPROVED EQUAL NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 72-INCHES ABOVE THE FLOOR. PROVIDE CEMENT BOARD, CEMENT PLASTER BACKING, OR TILE BACKBOARD FOR TILE FINISH. (IRC R307.2) 2. INSTALL MIN. 5/8" TYPE 'X' MOISTURE & MOLD RESISTANT GYPSUM WALL BOARD IN ALL BATHROOMS AND KITCHENS. FIREPLACES: 1. FACTORY-BUILT FIREPLACES, CHIMNEYS AND ALL OF THEIR COMPONENTS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1004.1) 2. DECORATIVE SHROUDS SHALL NOT BE INSTALLED AT THE TERMINATION OF FACTORY-BUILT CHIMNEYS EXCEPT WHERE SUCH SHROUDS ARE LISTED AND LABELED FOR USE WITH THE SPECIFIC FACTORY- BUILT CHIMNEY SYSTEM AND ARE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1005.2 & IMC 805.7) 3. HORIZONTAL OPENINGS ARE NOT ALLOWED, FOR EXHAUST VENTS, IN WALLS CLOSER THAN 3 FEET TO A PROPERTY LINE. (TABLES R302.1(1)&(2)). HORIZONTAL VENT CAPS SHALL BE 2 FEET CLEAR FROM PROPERTY LINES. 4. EXHAUST OPENINGS SHALL NOT BE DIRECTED ONTO WALKWAYS. (R303.5.2) 5. SOLID FUEL BURNING FIREPLACES (IF PERMISSIBLE): A. PROVIDE A PERMANENTLY ANCHORED GASEOUS FUEL BURNING PAN TO THE FIREBOX OF A SOLID FUEL BURNING FIREPLACE. B. SOLID FUEL BURNING FIREPLACE MUST COMPLY WITH THE CALIFORNIA ENERGY STANDARDS MANDATORY MEASURES. C. CHIMNEY SHALL EXTEND AT LEAST 2 FT. HIGHER THAN ANY PORTION OF THE BUILDING WITHIN 10 FT., BUT SHALL NOT BE LESS THAN 3 FT. ABOVE THE HIGHEST POINT WHERE THE CHIMNEY PASSES THROUGH THE ROOF. (CRC R1003.9) D. LIQUID FUELED FIREPLACES ARE NOT ALLOWED FOR INTERIOR USE. POOL: 1. PROVIDE AN ALARM FOR DOORS AND WINDOWS WITH SILL HEIGHTS LESS THAN 60-INCHES ABV.F.F. OF THE DWELLING THAT FORMS A PART OF THE POOL ENCLOSURE. THE ALARM SHALL BE LISTED AS A WATER HAZARD ENTRANCE ALARM IN ACCORDANCE WITH UL 2017. THE DEACTIVATION SWITCH SHALL BE AT LEAST 60" ABOVE THE FLOOR IF THE RESIDENCE IS NOT REQUIRED TO BE ACCESSIBLE. (CBC 3109 & ISPSC 305.4) 2. SUCTION ENTRAPMENT AVOIDANCE FOR POOL AND SPA SHALL BE PROVIDED IN ACCORDANCE WITH APSP-7 PER ISPSC SECTION 310. 3. PROVIDE POWER SAFETY COVER IN COMPLIANCE WITH ASTM F1346 FOR POOL & SPA (ISPSC 305). 4. POOL ENCLOSURE FENCE SHALL BE 60-INCHES MIN. ABV. FS/NG MEASURED ON THE SIDE THAT FACES AWAY FROM SWIMMING POOL W/. MAX VERTICAL CLEARANCE OF 2-INCHES BETWEEN FS/NG AND BOTTOM OF THE FENCE/BARRIER MEASURED ON THE SIDE OF FENCE THAT FACES AWAY FROM SWIMMING POOL. OPENING, GAP, AND VOID IN ENCLOSURE FENCE OR GATE SHALL NOT ALLOW THE PASSAGE OF 4-INCHES DIAMETER SPHERE OR LARGER. OUTSIDE SURFACE (FACING AWAY FROM SWIMMING POOL) OF THE POOL ENCLOSURE INCLUDING THE GATE TO BE FREE OF PROTRUSIONS, CAVITIES, OR OTHER PHYSICAL CHARACTERISTICS THAT WOULD SERVE AS HANDHOLDS OR FOOTHOLDS WHICH COULD ENABLE A CHILD FIVE YEARS OLD OR YOUNGER TO CLIMB OVER. (ISPSC 305) WOOD OR WOODBASED PRODUCTS NOTE: WOOD OR WOODBASE PRODUCT SHALL BE OF A NATURAL DURABLE OR PRESERVATIVE-TREADED WOOD IN ACCORDANCE WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND END USE IN THE FOLLOWING LOCATIONS: 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION. 2. WOOD FRAMING MEMBERS THAT REST ON CONCRETE OR MASONRY EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8 INCHES (203 MM) FROM THE EXPOSED GROUND. 3. SILLS AND SLEEPERS ON A CONCRETE OR MASONRY SLAB THAT IS IN DIRECT CONTACT WITH THE GROUND UNLESS SEPARATED FROM SUCH SLAB BY AN IMPERVIOUS MOISTURE BARRIER. 4. THE ENDS OF WOOD GIRDERS ENTERING EXTERIOR MASONRY OR CONCRETE WALLS HAVING CLEARANCES OF LESS THAN 1/2 INCH (12.7 MM) ON TOPS, SIDES AND ENDS. 5. WOOD SIDING, SHEATHING AND WALL FRAMING ON THE EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE WEATHER. 6. WOOD STRUCTURAL MEMBERS SUPPORTING MOISTURE-PERMEABLE FLOORS OR ROOFS THAT ARE EXPOSED TO THE WEATHER, SUCH AS CONCRETE OR MASONRY SLABS, UNLESS SEPARATED FROM SUCH FLOORS OR ROOFS BY AN IMPERVIOUS MOISTURE BARRIER. 7. WOOD FURRING STRIPS OR OTHER WOOD FRAMING MEMBERS ATTACHED DIRECTLY TO THE INTERIOR OF EXTERIOR MASONRY WALLS OR CONCRETE WALLS BELOW GRADE EXCEPT WHERE AN APPROVED VAPOR RETARDER IS APPLIED BETWEEN THE WALL AND THE FURRING STRIPS OR FRAMING MEMBERS. WASHER & DRYER NOTE: AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , GAS, WATER SUPPLY & DRAINAGE AS REQUIRED -THE CLOTHES DRYERS VENT SHALL BE OF A RIGID METALLIC MATERIAL AND HAVE A BACKDRAFT DAMPER (IMC 504) AND DUCT LENGTH, CONNECTION AND TRANSITION SHALL BE PER SECTION 504.9.4 OF IMC. DRYER VENT TERMINATION MUST BE AT LEAST 3-FEET FROM PROPERTY LINE (NOT TO DISCHARGE ONTO A PUBLIC WALKWAY). (IMC 504.1.1) IF DRYER LOCATED IN A CLOSET PROVIDE A MIN. 100 SQ.IN. OPENING IN THE CLOSET DOOR. (IMC 504.7) *HERS VERIFICATION REQUIRED-REFERENCE T-24.1 &AND .ANGLE @ AT C.L. CENTERLINE ∅DIAMETER, ROUND .PERPENDICULAR # POUND OR NUMBER A.B.ANCHOR BOLT ABV. ABOVE A/C.AIR CONDITIONING A.C.ASPHALT CONCRETE ACOUS ACOUSTICAL A.D.AREA DRAIN ADH. ADHESIVE ADJ. ADJUSTABLE, ADJACENT AL.ALUMINUM ALT.ALTERNATE ANOD.ANODIZED A.P.ACCESS PANEL APPX. APPROXIMATE APPV'D. APPROVED ARCH.ARCHITECTURAL,ARCHITECT ASB. ASBESTOS ASSY. ASSEMBLY AUTO.AUTOMATIC B. BATHROOM BD. BOARD BEL. BELOW BET. BETWEEN BIT. BITUMINOUS BLDG.BUILDING BLK. BLOCK BLK'G.BLOCKING BM. BEAM B.O.BY OWNER, BY OTHERS BOT. BOTTOM BR. BEDROOM B.W. BACK OF WALL, BOTTOM OF WALL CAB. CABINET C.B.CATCH BASIN CEM.CEMENT C.G.CORNER GUARD CHAN.CHANNEL CHG.CHANGE C.I. CAST IRON C.J. CONTROL / CONSTRUCT./CEILING JOINT CLG. CEILING CLKG. CAULKING CLR. CLEAR, CLEARANCE CNTR.COUNTER CONC.CONCRETE COND.CONDITION CONST. CONSTRUCT, CONSTRUCTION CORR.CORRIDOR, CORROSIVE CTSK. COUNTER SINK, COUNTERSUNK CTR. CENTER DBL. DOUBLE DECO.DECORATIVE DEPT. DEPARTMENT DET. DETAIL D.F.DRINKING FOUNTAIN, DOUGLAS FIR DIA.DIAMETER DIAG. DIAGONAL DIM. DIMENSION DN. DOWN DR. DOOR D.S.DOWNSPOUT D.S.P. DRY STANDPIPE DWG. DRAWING(S) E. EXISTING, EAST, ENTRY, EACH E.J. EXPANSION JOINT ELEC. ELECTRIC, ELECTRICAL ELEV. ELEVATOR EMER.EMERGENCY ENCL. ENCLOSED, ENCLOSURE E.P.ELECTRICAL PANEL, END POINT EQ. EQUAL EQV. EQUIVALENT EQUIP.EQUIPMENT E.W. EACH WAY EXH. EXHAUST EXPO.EXPOSED EXT. EXTERIOR E.G.EXISTING GRADE F.FIXED F.A. FIRE ALARM FAC. FACTORY F.C.O. FLOOR CLEAN OUT F.D.FLOOR DRAIN FDN. FOUNDATION F.E. FIRE EXTINGUISHER F.E.C. FIRE EXTINGUISHER CABINET F.G.FINISH GRADE FIXT.FIXTURE F.J. FLOOR JOIST F.L. FLOW LINE FLASH. FLASHING FLR. FLOOR FLUOR. FLUORESCENT F.O.C. FACE OF CONCRETE/CURB F.O.F. FACE OF FINISH F.O.S. FACE OF STUD / STRUCTURE / SHEATHING F.O.M.FACE OF MASONRY FP. FIREPLACE F.S. FLOOR SINK, FINISH SURFACE FT.FOOT, FEET FTG. FOOTING FURR.FURRING FUT. FUTURE F.V. FIELD VERIFY GA. GAUGE GALV. GALVANIZED G.B.GRAB BAR, GRADE BEAM G.C.GENERAL CONTRACTOR GEN.GENERAL G.F.I.GROUND FAULT INTERRUPT G.I. GALVANIZED IRON G.L.B. GLU-LAM BEAM GND.GROUND GR. GRADE GYP. GYPSUM G.P.GRADE PLANE IBC INTERNATIONAL BUILDING CODE IRC INTERNATIONAL RESIDENTIAL CODE H./HT. HIGH, HEIGHT H.B.HOSE BIBB H.C.HOLLOW CORE HD. HARD, HEAD HDR.HEADER HDWD.HARDWOOD HDWR.HARDWARE H.M. HOLLOW METAL HORIZ. HORIZONTAL HR. HOUR HVAC HEATING VENTILATING AIR CONDITIONING I.D. INTERIOR DESIGNER, INSIDE DIAMETER/DIMENSION IN.INCH INSUL.INSULATION INT.INTERIOR INV.INVERT/INVERTED JAN. JANITOR JT.JOINT JST.JOIST KIT. KITCHEN L.LOW, LINEN L.A. LANDSCAPED AREA LAB. LABORATORY LAM. LAMINATED LAV. LAVATORY LBS. POUNDS LFA.LOAD FROM ABOVE L.H. LEFT HAND LKR. LOCKER LT.LIGHT LUM. LUMINOUS, LUMENS MAINT. MAINTENANCE MAS.MASONRY MAT. MATERIAL MAX.MAXIMUM M.B.METAL BOLT M.C. MEDICINE CABINET MECH.MECHANICAL MEMB.MEMBRANE MTL. METAL MFGR.MANUFACTURER M.H. MANHOLE MIN. MINIMUM MIR. MIRROR MISC. MISCELLANEOUS M.O. MASONRY OPENING MT. MOUNTED MUL. MULLION N. NEW, NORTH NAT. NATURAL N.I.C.NOT IN CONTRACT, CONTACT N.G.NATURAL GRADE NO. NUMBER NOM.NOMINAL N.T.S. NOT TO SCALE O/.OVER O.A.OVERALL OBS. OBSCURE O.C.ON CENTER O.D.OUTSIDE DIAMETER, DIMENSION O.F.D. OVERFLOW DRAIN OFF. OFFICE OPNG.OPENING OPP. OPPOSITE PERIM. PERIMETER PL.PROPERTY LINE, PLATE P.LAM. PLASTIC LAMINATE PLAS. PLASTER PLUMB. PLUMBING PLYWD. PLYWOOD PNT. PAINT(ED) P.O.C. POINT OF CONTACT, CONNECTION PR. PAIR PROJ. PROJECTION PSL. PARALLEL STRAND LAMINATE PT. POINT R.A.RETURN AIR RAD. RADIUS R.D.ROOF DRAIN R.D.L. ROOF DRAIN LEADER RECPT. RECEPTACLE RECT. RECTANGLE, RECTANGULAR REF. REFERENCE REFR.REFRIGERATOR REG.REGULAR, REGISTER REINF. REINFORCE(D), REINFORCEMENT REQ'D. REQUIRED RESIL.RESILIENT RET. RETAIN(ING), RETURN RM. ROOM R.O.ROUGH OPENING R.R.ROOF RAFTER RWD. REDWOOD S. SOUTH S.A.SUPPLY AIR S.C.SOLID CORE S.C.D. SEAT COVER DISPENSER SCHED. SCHEDULE S.D.SUBDRAIN, SOAP DISPENSER SEC. SECTION SEL. SELECT(ED) SH. SHELF SHT. SHEET SHT'G.SHEATHING SIM.SIMILAR SIMP. SIMPSON S.J. SOFFIT JOIST S.S.STAINLESS STEEL S.SK.SERVICE SINK STA. STATION STD. STANDARD STL.STEEL STOR.STORAGE STRUCT. STRUCTURE, STRUCTURAL SUSP. SUSPEND(ED) SYM.SYMMETRICAL SYS. SYSTEM T.TREAD, TRASH T.C.TOP OF CURB T.CL. TIME CLOCK TEL.TELEPHONE TEMP.TEMPERED TER. TERRAZZO T & G TONGUE & GROOVE THK. THICK, THICKNESS T.P. TOP OF PAVING T.PL. TOP OF PLATE T.O.S. TOP OF STRUCTURE, SHEATHING, SLAB TRANS. TRANSFORMER T.S. TOP OF STEP T.W.TOP OF WALL TYP. TYPICAL U. UNDER U.B.C. UNIFORMBUILDING CODE U.G.UNDERGROUND U.L. UNDERWRITER'S LABORATORY UNF. UNFINISHED U.N.O.UNLESS NOTED OTHERWISE UR. URINAL V./VERT. VERTICAL VENT. VENTILATION, VENTILATING VER. VERIFY V.T.R. VENT THROUGH ROOF W. WEST, WIDTH, WASHER W/.WITH WD.WOOD W.H. WATER HEATER W.C.WATER CLOSET W.I. WROUGHT IRON WP.WATERPROOF(ING) W.W.M. WELDED WIRE MESH DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 ARCHITECTURAL GENERAL NOTES KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 T-1.1 TBD RYAN McDANIEL, AIA NO. REVISION DATE ABBREVIATIONS3 GENERAL NOTES2 CONTRACT DOCUMENT NOTES1 ZONING ALLOWANCE & PROJECT SUMMARY 233 W. BLEEKER ST. PROPOSED DEVELOPMENT SINGLE FAMILY & CARRIAGE HOUSE |HISTORICAL RENOVATION AND ADDITION PARCEL #273512440001 ZONE DISTRICT R-6 SETBACKS EXISTING ALLOWED (PRINCIPAL) ALLOWED (CARRIAGE HOUSE) PROPOSED (PRINCIPAL) PROPOSED (CARRAIGE HOUSE)REFERENCE FRONT 15 FT 10 FT 10 FT 15 FT 15 FT 26.710.040 REAR 0 FT EXISTING HISTORIC CONDITION 10 FT 10 FT 5 FT 1 IN 0 FT 26.710.040 COMBINED FRONT/REAR N/A N/A N/A N/A N/A 26.710.040 SIDE (EAST)10 FT 10 FT 10 FT 10 FT 53 FT 9 5/8 IN 26.710.040 SIDE (WEST)8 FT 2 3/8 IN E. HISTORIC CONDITION 10 FT 10 FT 8 FT 2 3/8 IN 8 FT 2 3/8 IN 26.710.040 COMBINED SIDE N/A N/A N/A N/A N/A 26.710.040 DISTANCE BETWEEN BUILDINGS 0 FT 10 FT 10 FT 10 FT 10 FT 26.710.040 CORNER LOT YES 26.710.040 SUPPLEMENTAL BREAKDOWN INFO EXISTING REQUIRED PROPOSED REFERENCE NET LEASABLE/COMM SQ FT 0 NOT REQ'D FOR R-6 N/A 26.575.020.I. OPEN SPACE %0 NOT REQ'D FOR R-6 N/A 26.710.040 SITE COVERAGE 40%40%38.41%26.710.040 ON-SITE PARKING 0 3 3 26.515.040 SITE COVERAGE EXISTING PROPOSED REFERENCE GROSS LOT AREA (SQ FT)9,000 9,000 A-0.1 AREA OF BUILDING FOOTPRINT (SQFT)3,609 3,457 A-0.1 SITE COVERAGE %40%38.41%26.710.040 TRANSFEREABLE DEVELPOMENT RIGHT (TDR) RECEIVED TDR CERTIFICATE NO SENT TDR CERTIFICATE NO TRANSFERRED TDR CERTIFICATE NO LAND VALUE SUMMARY ACTUAL VALUE REFERENCE LAND 4,559,000 PITKIN COUNTY ASSESSOR IMPROVEMENTS 3,727,100.00 PITKIN COUNTY ASSESSOR TOTAL 8,286,100 PITKIN COUNTY ASSESSOR NET LOT AREA 233 W. BLEEKER ST. ZONE DISTRICT REQUIREMENTS REFERENCE MIN. GROSS LOT AREA (PER R-6)3,000 SF (HISTORIC LANDMARK PROPERTIES)26.710.040 MIN. NET LOT AREA (PER R-6)3,000 SF (HISTORIC LANDMARK PROPERTIES)26.710.040 LOT SIZE PER SURVEY 9,000 SF REFERENCE REDUCTIONS FOR AREA WITH SLOPES 0%-20% (100% OF PARCEL AREA TO BE INCLUDED IN NET LOT AREA)9,000 SF SURVEY 26.575.020-1 REDUCTIONS FOR AREA WITH SLOPES 20%-30% (50% OF PARCEL AREA TO BE INCLUDED IN NET LOT AREA)0 SF SURVEY 26.575.020-1 REDUCTIONS FOR AREA WITH SLOPES GREATER THAN 30% (0% OF PARCEL AREA TO BE INCLUED IN NET LOT AREA)0 SF SURVEY 26.575.020-1 TOTAL AREA REDUCTIONS 9,000 SF - 0 SF - 0 SF = 9,000 SF NET LOT AREA 9,000 SF ALLOWABLE FLOOR AREA 233 W. BLEEKER ST. ALLOWABLE FLOOR AREA REFERENCE PER R-6: FOR NET LOT AREA BETWEEN 9,000 - 15,000: 4,080 SF OF FLOOR AREA + 6 SF OF FLOOR AREA FOR EACH ADDITIONAL 100 SF IN NET LOT AREA UP TO A MAX. 4,440 SF OF FLOOR AREA 26.710.040 ALLOWABLE FLOOR AREA ADJUSTED PER UNIQUE APPROVALS 26.710.040 UNIQUE APPROVALS REFERENCE POTENTIAL FOR 500 SF ADDITIONAL FAR TO BE GRANTED BY HPC 26.415.110.F VARIANCES REFERENCE EXEMPTIONS REFERENCE GARAGE EXEMPTION FIRST 250 SF EXEMPT NEXT 251-500 SF EXEMPT FOR SECOND DWELLING UNIT (CARRIAGE HOUSE) 26.575.020.D.7 A-0.4 DECK EXEMPTION 612 SF EXEMPT (ALLOWABLE FLOOR AREA 4,080 SF X 15%) 26.575.020.D.4 A-0.4 FLOOR AREA SUMMARY EXISTING GROSS (SF)EXISTING FLOOR AREA (SF) PROPOSED GROSS (SF)PROPOSED FLOOR AREA (SF) REFERENCE BASEMENT LEVEL 763 45 3680 154 A-0.3 FIRST LEVEL 2861 2861 2505 2505 A-0.4 GARAGE (LOCATED ON FIRST LEVEL)0 0 494 0 A-0.4 SECOND LEVEL 1269 1269 1461 1461 A-0.5 DECK AREA 410 0 612 0 A-0.4 CARRIAGE HOUSE 988 988 458 458 A-0.6 TOTAL 6291 5163 9210 4578 A-0.4 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 ZONING SUMMARY KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 T-1.2 TBD RYAN McDANIEL, AIA NO. REVISION DATE SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 SITE PLAN C1 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 OVERALL GRADING PLAN C2 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 OVERALL UTILITY PLAN C3 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.1 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.2 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.3 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.4 4 1 2 3 1 1 5 SYMBOL DESCRIPTION PATIO/DECKING CONCRETE OR CONCRETE-SET PAVERS (TYPE 1) CONCRETE OR CONCRETE-SET PAVERS (TYPE 2) DECORATIVE PEBBLE STABILIZED DECOMPOSED GRANITE 1 2 3 4 5 REFERENCE NOTES SCHEDULE SCHEMATIC SITE PLAN L.1.00 0'5'10' SCALE: 1"=5' NOR T H THIS SHEET CONTAINS LINES, SYMBOLS, ETC THAT ARE IN A COLOR OTHER THAN BLACK AND IS INTENDED TO BE VIEWED AND PRINTED IN COLOR VS B L A C K A N D W H I T E ISSUE & REVISION DATES Plot Date: 01/10/22 Project #: 463 Drawn By:DK Checked By:ST HPC CONCEPT SET 09/27/2021 HPC CONCEPT SET 01/07/2022 23 3 W B L E E K E R AS P E N , C O 81 6 2 1 0,0,0 LA N D S C A P E A R C H I T E C T U R E ▪ L A N D P L A N N I N G 35 0 M A R K E T S T R E E T | S U I T E 3 0 7 | B A S A L T | C O | 8 1 6 2 1 WW W . C O N N E C T O N E D E S I G N . C O M | 9 7 0 . 3 5 5 . 5 4 5 7 PROPERTY LINE PROPERTY LINE PR O P E R T Y L I N E HISTORIC SETBACK DRIVEWAY PR O P E R T Y L I N E FR O N T Y A R D S E T B A C K GA R A G E S E T B A C K SIDE YARD SETBACK PORCH POOL DECK FRONT PORCH HISTORIC SIDE PORCH EXISTING TREES TO REMAIN (TYP). 3' WIDE CONCRETE FRONT WALK SPRINKLER STRIP (TYP) PROPERTY LINE PARKING DECK PLANTED JOINT WALKWAY FREE STANDING GRILL COURTYARD FENCE (MAX 4' 6" HEIGHT) REAR YARD FENCE (MAX 6' HEIGHT) COURTYARD LAWN (TYP) LA W N ( T Y P ) MIXED PERENNIAL AND LOW SHRUB PLANTING IN FRONT OF HISTORIC STRUCTURE (TYP) MIXED PERENNIAL AND LOW SHRUB PLANTING IN FRONT OF HISTORIC STRUCTURE (TYP) MIXED PERENNIAL AND SHRUB PLANTING SIDE YARD FENCE (MAX 6' HEIGHT)PLANTER SCREEN PLANTING BETWEEN POOL AND FENCE POOL IN SETBACK (POOL TO BE MAX 30" ABOVE AND 30" BELOW FINISHED GRADE)REAR FENCE (MAX 6' HEIGHT) RAISED COURTYARD PLANTERS (TYP) N 2ND ST. W B L E E K E R S T AL L E Y HISTORIC STRUCTURE HISTORIC STRUCTURE ADDITION ADDITION STEPPERS FROM SIDE YARD GATE TO SIDEWALK BARN STRUCTURE SETBACK SIDE YARD SETBACK RE A R Y A R D S E T B A C K SIDE YARD SETBACK HI S T O R I C S E T B A C K SYMBOL MANUFACTURER/MODEL/DESCRIPTION QTY BEGA 33 054 5 BEGA 84 218 2 BEGA 22 230 5 LIGHTING SCHEDULE SCHEMATIC LIGHTING PLAN L.1.00 0'5'10' SCALE: 1"=5' NOR T H THIS SHEET CONTAINS LINES, SYMBOLS, ETC THAT ARE IN A COLOR OTHER THAN BLACK AND IS INTENDED TO BE VIEWED AND PRINTED IN COLOR VS B L A C K A N D W H I T E ISSUE & REVISION DATES Plot Date: 01/10/22 Project #: 463 Drawn By:DK Checked By:ST HPC CONCEPT SET 09/27/2021 HPC CONCEPT SET 01/07/2022 23 3 W B L E E K E R AS P E N , C O 81 6 2 1 0,0,0 LA N D S C A P E A R C H I T E C T U R E ▪ L A N D P L A N N I N G 35 0 M A R K E T S T R E E T | S U I T E 3 0 7 | B A S A L T | C O | 8 1 6 2 1 WW W . C O N N E C T O N E D E S I G N . C O M | 9 7 0 . 3 5 5 . 5 4 5 7 PROPERTY LINE PROPERTY LINE PR O P E R T Y L I N E HISTORIC SETBACK DRIVEWAY PR O P E R T Y L I N E FR O N T Y A R D S E T B A C K GA R A G E S E T B A C K SIDE YARD SETBACK PORCH POOL DECK FRONT PORCH HISTORIC SIDE PORCH PROPERTY LINE PARKING DECK COURTYARD N 2ND ST. W B L E E K E R S T AL L E Y HISTORIC STRUCTURE HISTORIC STRUCTURE ADDITION ADDITION BARN STRUCTURE SETBACK SIDE YARD SETBACK RE A R Y A R D S E T B A C K SIDE YARD SETBACK HI S T O R I C S E T B A C K BEGA 33 054 BEGA 33 054 BEGA 22 230 BEGA 22 230 BEGA 84 218 BEGA 84 218 BEGA 84 218 LIGHTING CUTSHEETS LIGHT.1.1 T HIS SHEET CONTAINS LINES, SYMBOLS, ETC THAT ARE IN A COLOR OTHER THAN BLACK AND IS INTENDED TO BE VIEWED AND PRINTED IN COLOR VS B L A C K A N D W H I T E ISSUE & REVISION DATES Plot Date: 01/10/22 Project #: 463 Drawn By:DK Checked By:ST HPC CONCEPT SET 09/27/2021 HPC CONCEPT SET 01/07/2022 23 3 W B L E E K E R AS P E N , C O 81 6 2 1 0,0,0 LA N D S C A P E A R C H I T E C T U R E ▪ L A N D P L A N N I N G 35 0 M A R K E T S T R E E T | S U I T E 3 0 7 | B A S A L T | C O | 8 1 6 2 1 WW W . C O N N E C T O N E D E S I G N . C O M | 9 7 0 . 3 5 5 . 5 4 5 7 BEDROOM BEDROOM BEDROOM BATH FAMILY ROOM ATRIUM DINING ROOM KITCHEN LIVING ROOM ENTRY BATH W.C. STAIR STAIR DIRTY KITCHEN LIVING ROOM MECH BATH BEDROOM STAIR D-3.01 D-3.0 2 D-3.1 2 D-3.1 1 D-3.2 1 2 FOOTPRINT OF HISTORICAL CARRIAGE HOUSE REMOVE NON-HISTORIC ADDITION FOOTPRINT OF HISTORICAL HOUSE REMOVE NON- HISTORIC GATE REMOVE NON- HISTORIC ADDITION REMOVE NON-HISTORIC ADDITION REMOVE NON-HISTORIC SITE WALL REMOVE NON- HISTORIC DOOR AND STAIRCASE REMOVE NON-HISTORIC FENESTRATIONS 1 1 1 1 N 75o 09'11" W 90.00' S 75o 09'11" E 90.00' N 1 4 o 50 ' 4 9 " E 1 0 0 . 0 0 ' N 75o 09'11" W 30.00' N 1 4 o 50 ' 4 9 " E 1 0 0 . 0 0 ' S 1 4 o 50 ' 4 9 " W 1 0 0 . 0 0 ' S 75o 09'11" E 30.00' S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " EXISTING SIDEYARD SETBACK 10' - 0" ROOM TAGROOM NAME ? 1 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG PROPERTY LINE TAG90 00' 00"20.00'N E LIMITS OF DEMOLITION -PORTION OF CURRENT STRUCTURE THAT WAS ADDED TO HISTORICAL BUILDING AND TO BE DEMOLISHED TREE TO REMAIN -EXISTING TREE TO BE PROTECTED IN PLACE. REF. SURVEY LIMITS OF HISTORICAL STRUCTURE -PORTION OF CURRENT STRUCTURE THAT IS A PART OF THE HISTORICAL FOOTPRINT AND TO REMAIN IN PLACE TREE TO BE REMOVED -EXISTING TREE TO BE REMOVED. REF. SURVEY EXISTING WALL TO REMAIN -GC TO PATCH AND REPAIR AS NECESSARY EXISTING WALL TO BE DEMOLISHED -GC TO REMOVE WALL AND PREP AREA FOR NEW CONSTRUCTION DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. -CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. GENERAL HISTORICAL RESTORATION NOTES: ALL EXTERIOR FENESTRATIONS WITHIN IN HISTORICAL FOOTPRINT TO BE EITHER REMOVED OR REPLACED TO MATCH ORIGINAL SANBORN MAP AND DESIGN EXTERIOR WALLS ADJACENT TO EXISTING ADDITION TO BE REFINISHED TO MATCH ORIGINAL SANBORN MAP AND DESIGN. GENERAL DEMOLITION NOTES: VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ARCHITECT IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST. MATERIAL HAVING SALVAGE VALUE SHALL BECOME THE PROPERTY OF THE OWNER ALL OTHER MATERIAL AND DEBRIS ACCUMULATED AS A RESULT OF DEMOLITION SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES BY THE CONTRACTOR AND DISPOSED OF IN A LEGAL AND PROPER MANNER. FURNISH, INSTALL, AND MAINTAIN IN SAFE CONDITIONS AT ALL TIMES TEMPORARY PROTECTION REQUIRED TO ENSURE SAFETY FOR PERSONS AND PROPERTY DURING DEMOLITION AND REMOVAL WORK. REMOVE EXISTING ELECTRICAL OUTLETS AND WIRING AS REQUIRED IN WALLS, FLOORS AND FURNISHINGS TO BE DEMOLISHED. ALL WALLS, DOORS, WINDOWS, FURNISHINGS AND EQUIOMENT DENOTED WITH DASHED LINES ARE TO BE REMOVED. REFER TO PROPOSED PLAN LAYOUT FOR CLARIFICATIONS. ALL ELECTRICAL, PLUMBING, AND MECHANICAL WORK (DEMOLITION AND NEW) IS TO BE PERFORMED BY LICENSED, COMPETENT CONTRACTORS. REFER TO STRUCTURAL DRAWINGS FOR ALL STRUCTURAL DEMOLITION LOCATIONS AND DETAILS. EXISTING ITEMS TO REMAIN SHALL BE PROTECTED DURING DEMOLITION AND NEW CONSTRUCTION. DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXISTING SITE PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-0.0 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 1/8" = 1'-0"1 EXISTING SITE PLAN DEMOLITION GENERAL NOTESA ANNOTATION LEGENDB KEYNOTESC 1 PROPERTY LINE NO. REVISION DATE A 43.19 SF B 42.93 SF C 280.85 SF D 457.38 SF E 25.41 SF F 1125.18 SF G 321.91 SF H 31.64 SF I 7.81 SF J 116.60 SF K 28.74 SF L 647.79 SF M 88.08 SF N 122.59 SF O 511.18 SF P 68.18 SF ROOF DEMO LEGEND EXISTING ROOF TO REMAIN ROOF TO BE REMOVED A 26.40 SF E 26.19 SF G 227.17 SF H 283.97 SF J 16.32 SF L 588.42 SF S 152.83 SF U 39.35 SF W 8.05 SF Z 64.53 SF AA 29.81 SF BB 483.01 SF EE 44.04 SF GG 122.59 SF HH 287.13 SF KK 35.83 SF B 26.40 SF C 72.23 SF D 72.23 SF F 26.19 SF I 287.99 SF K 16.32 SF M 56.72 SF N 161.36 SF O 107.92 SF P 329.06 SF Q 53.44 SF R 129.97 SF T 260.83 SF Y 66.21 SF CC 39.97 SF DD 144.65 SF FF 44.04 SF II 237.56 SF JJ 35.83 SF X 221.8 SF V 31.64 SF DEMOLITION CALCULATIONS - RATIO METHOD 233 W. BLEEKER STREET ROOF DEMOLITION ROOF LABEL INDIVIDUAL ROOF AREA IN PLAN (SF)ROOF SLOPE ADJUSTMENT FACTOR ACTUAL AREA OF ROOF USED FOR DEMO CALC (SF) AREA OF ROOF TO BE REMOVED (SF) A 43.19 12:12 1.414 61.07 61.07 B 42.93 12:12 1.414 60.70 60.70 C 280.85 5:12 1.086 305.00 305.00 D 457.38 10:12 1.315 601.45 - E 25.41 12:12 1.414 35.93 35.93 F 1125.18 12:12 1.414 1591.00 - G 321.91 12:12 1.414 455.18 455.18 H 31.64 0:12 1 31.64 31.64 I 7.81 3:12 1.034 8.08 8.08 J 116.6 6:12 1.118 130.36 130.36 K 28.74 3:12 1.034 29.72 29.72 L 647.79 3:12 1.034 669.81 669.81 M 88.08 0:12 1 88.08 88.08 N 112.59 0:12 1 112.59 112.59 O 511.18 3:12 1.034 528.56 528.56 P 68.18 6:12 1.118 76.23 76.23 ROOF SURFACE TOTAL (SF)3909.46 4785.41 ROOF SURFACE AREA TO BE REMOVED (SF)2592.95 DEMOLITION TOTALS ROOF + WALL AREA USED FOR DEMO CALC. (SF) 4,785.41 + 3,990.08 8775.49 SURFACE AREA TO BE REMOVED (SF)2,592.95 + 1,925.41 4518.36 TOTAL 51.49% Notes: Actural area of roof to be removed is calculated by multiplying the plan area by an adjustment facot, in lieu of depicting each roof segment as a flat plane. The adjustment factor is determined by a ratio of the roof slope. DEMOLITION CALCULATIONS - FLAT PLANE METHOD 233 W. BLEEKER STREET ROOF DEMOLITION ROOF LABEL INDIVIDUAL ROOF AREA (SF) AS FLAT PLANE AREA OF ROOF TO BE REMOVED (SF) A 26.4 26.4 B 26.4 26.4 C 72.23 - D 72.23 - E 26.19 26.19 F 26.19 26.19 G 227.17 227.17 H 283.97 - I 287.99 - J 16.32 16.32 K 16.32 16.32 L 588.42 - M 56.72 - N 161.36 - O 107.92 107.92 P 329.06 - Q 53.44 - R 129.97 - S 152.83 152.83 T 260.83 260.83 U 39.35 39.35 V 31.64 31.64 W 8.05 8.05 X 221.8 - Y 66.21 66.21 Z 64.56 64.56 AA 29.81 29.81 BB 483.01 483.01 CC 39.97 39.97 DD 144.65 144.65 EE 44.04 44.04 FF 44.04 44.04 GG 122.59 122.59 HH 287.13 287.13 II 237.56 237.56 JJ 35.83 35.83 KK 35.83 35.83 ROOF SURFACE TOTAL (SF)4858.03 ROOF SURFACE AREA TO BE REMOVED (SF)2600.84 DEMOLITION TOTALS ROOF + WALL AREA USED FOR DEMO CALC. (SF) 4,858.03 + 3,990.08 8848.11 SURFACE AREA TO BE REMOVED (SF)2,600.84 + 1,925.41 4526.25 TOTAL 51.15% DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 ROOF DEMOLITION CALCULATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-0.1 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1" = 10'-0"1 ROOF DEMO (RATIO METHOD) 1" = 10'-0"2 ROOF DEMO (FLAT PLANE METHOD) PROPERTY LINE SETBACK LINE A D H E I G J N O P Q R U AA BB CC DD V T S PROPERTY LINE SETBACK LINE A C B F K J L P M R S AA BB CC DD G E D C A V U A B A T S R P N S J J L M K I AA BB CC DD F H P OQ EXPOSED WALL LEGEND EXISTING WALL TO REMAIN WALL AREA TO BE REMOVED AREA REDUCED FOR FENESTRATION 420.80 SF 46.22 SF 306.33 SF 87.56 SF 45.31 SF 223.76 SF 121.39 SF 56.68 SF 323.75 SF 21.84 SF 37.66 SF 369.73 SF 12.14 SF 5.06 SF 112.85 SF 59.38 SF 151.90 SF 167 SF 151.81 SF 113.40 SF 34.28 SF 225.55 SF 46.02 SF 209.88 SF 34.23 SF 45.72 SF 126.02 SF 176.59 SF 303.63 SF 172.38 SF 77.31 SF 295.26 SF 21.76 SF 169.54 SF 250.06 SF STAIR DEMOLITION CALCULATIONS 233 W. BLEEKER STREET WALL DEMOLITION WALL LABEL INDIVIDUAL WALL AREA (SF) AREA REDUCED FOR FENESTRATION (SF) AREA OF WALL TO BE REMOVED (SF) A 726.83 157.14 358.8 B 46.22 8.36 37.86 C 21.84 -- D 323.75 66.02 257.73 E 56.68 9.38 47.30 F 121.39 39.95 81.44 G 223.76 115.39 108.37 H 167 79.44 87.56 I 151.9 81.54 70.36 J 520.24 65.73 150.51 K 59.38 18.67 40.71 L 5.06 -- M 12.14 -- N 126.02 39.03 86.99 O 45.72 8.03 - P 244.11 37.25 34.23 Q 46.02 8.03 - R 225.55 37.17 - S 147.68 12.93 23.28 T 115.81 9.42 - U 45.31 8.03 - V 87.56 21.5 - AA 480.22 25.26 176.59 BB 249.69 40.87 172.38 CC 486.56 40.41 191.30 DD 250.06 66.87 - WALL SURFACE AREA TOTAL (SF)4986.5 AREA REDUCED FOR FENESTRATION (SF)996.42 AREA USED FOR DEMO CALCULATION (SF) 3990.08 WALL SURFACE AREA TO BE REMOVED (SF)1925.41 DEMOLITION TOTALS ROOF + WALL AREA USED FOR DEMO CALCULATION (SF)4,785.41 + 3,990.08 8775.4882 SURFACE AREA TO BE REMOVED (SF) 2,592.95 + 1,925.41 4518.36 TOTAL 51.49% DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 WALL DEMOLITION CALCULATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-0.2 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1" = 10'-0"1 FIRST LEVEL FLOOR PLAN - WALL DEMOLITION 1" = 10'-0"2 SECOND LEVEL FLOOR PLAN - WALL DEMOLITION 3' - 5" KITCHEN DINING ROOM LIVING ROOM BATH BEDROOM BEDROOM BATH BEDROOM FAMILY ROOM DIRTY KITCHEN STAIR STAIR BATH LIVING ROOM MECH BATH BEDROOM STAIR D-3.01 D-3.0 2 D-3.1 2 D-3.1 1 D-3.2 1 2 1 1 1 1 REMOVE NON-HISTORIC PATIO REMOVE NON-HISTORIC DOOR REMOVE INTERIOR WALLS AND STAIRCASE WALL TO BE REFINSHED TO MATCH HISTORICAL EXTERIOR REMOVE NON- HISTORIC BAY WINDOW S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " EXISTING SIDEYARD SETBACK 10' - 0" ROOM TAGROOM NAME ? 1 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG PROPERTY LINE TAG90 00' 00"20.00'N E LIMITS OF DEMOLITION -PORTION OF CURRENT STRUCTURE THAT WAS ADDED TO HISTORICAL BUILDING AND TO BE DEMOLISHED TREE TO REMAIN -EXISTING TREE TO BE PROTECTED IN PLACE. REF. SURVEY LIMITS OF HISTORICAL STRUCTURE -PORTION OF CURRENT STRUCTURE THAT IS A PART OF THE HISTORICAL FOOTPRINT AND TO REMAIN IN PLACE TREE TO BE REMOVED -EXISTING TREE TO BE REMOVED. REF. SURVEY EXISTING WALL TO REMAIN -GC TO PATCH AND REPAIR AS NECESSARY EXISTING WALL TO BE DEMOLISHED -GC TO REMOVE WALL AND PREP AREA FOR NEW CONSTRUCTION DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. -CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. GENERAL HISTORICAL RESTORATION NOTES: ALL EXTERIOR FENESTRATIONS WITHIN IN HISTORICAL FOOTPRINT TO BE EITHER REMOVED OR REPLACED TO MATCH ORIGINAL SANBORN MAP AND DESIGN EXTERIOR WALLS ADJACENT TO EXISTING ADDITION TO BE REFINISHED TO MATCH ORIGINAL SANBORN MAP AND DESIGN. GENERAL DEMOLITION NOTES: VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ARCHITECT IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST. MATERIAL HAVING SALVAGE VALUE SHALL BECOME THE PROPERTY OF THE OWNER ALL OTHER MATERIAL AND DEBRIS ACCUMULATED AS A RESULT OF DEMOLITION SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES BY THE CONTRACTOR AND DISPOSED OF IN A LEGAL AND PROPER MANNER. FURNISH, INSTALL, AND MAINTAIN IN SAFE CONDITIONS AT ALL TIMES TEMPORARY PROTECTION REQUIRED TO ENSURE SAFETY FOR PERSONS AND PROPERTY DURING DEMOLITION AND REMOVAL WORK. REMOVE EXISTING ELECTRICAL OUTLETS AND WIRING AS REQUIRED IN WALLS, FLOORS AND FURNISHINGS TO BE DEMOLISHED. ALL WALLS, DOORS, WINDOWS, FURNISHINGS AND EQUIOMENT DENOTED WITH DASHED LINES ARE TO BE REMOVED. REFER TO PROPOSED PLAN LAYOUT FOR CLARIFICATIONS. ALL ELECTRICAL, PLUMBING, AND MECHANICAL WORK (DEMOLITION AND NEW) IS TO BE PERFORMED BY LICENSED, COMPETENT CONTRACTORS. REFER TO STRUCTURAL DRAWINGS FOR ALL STRUCTURAL DEMOLITION LOCATIONS AND DETAILS. EXISTING ITEMS TO REMAIN SHALL BE PROTECTED DURING DEMOLITION AND NEW CONSTRUCTION. DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXISTING FIRST FLOOR DEMOLITION PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-1.0 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 FIRST LEVEL FLOOR PLAN - DEMOLITION DEMOLITION GENERAL NOTESA ANNOTATION LEGENDB KEYNOTESC 1 PROPERTY LINE NO. REVISION DATE BEDROOM CLOSET BEDROOM CLOSET BATHROOM CLOSET DEN CLOSET BEDROOM STORAGE BALCONY STAIR OPEN TO BELOW BEDROOM BALCONY D-3.01 D-3.0 2 D-3.1 2 D-3.1 1 D-3.2 1 2 REMOVE NON-HISTORIC PATIO REMOVE NON-HISTORIC ADDITION AND BALCONY 1 1 1 1 S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " EXISTING SIDEYARD SETBACK 10' - 0" ROOM TAGROOM NAME ? 1 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG PROPERTY LINE TAG90 00' 00"20.00'N E LIMITS OF DEMOLITION -PORTION OF CURRENT STRUCTURE THAT WAS ADDED TO HISTORICAL BUILDING AND TO BE DEMOLISHED TREE TO REMAIN -EXISTING TREE TO BE PROTECTED IN PLACE. REF. SURVEY LIMITS OF HISTORICAL STRUCTURE -PORTION OF CURRENT STRUCTURE THAT IS A PART OF THE HISTORICAL FOOTPRINT AND TO REMAIN IN PLACE TREE TO BE REMOVED -EXISTING TREE TO BE REMOVED. REF. SURVEY EXISTING WALL TO REMAIN -GC TO PATCH AND REPAIR AS NECESSARY EXISTING WALL TO BE DEMOLISHED -GC TO REMOVE WALL AND PREP AREA FOR NEW CONSTRUCTION DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. -CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. GENERAL HISTORICAL RESTORATION NOTES: ALL EXTERIOR FENESTRATIONS WITHIN IN HISTORICAL FOOTPRINT TO BE EITHER REMOVED OR REPLACED TO MATCH ORIGINAL SANBORN MAP AND DESIGN EXTERIOR WALLS ADJACENT TO EXISTING ADDITION TO BE REFINISHED TO MATCH ORIGINAL SANBORN MAP AND DESIGN. GENERAL DEMOLITION NOTES: VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ARCHITECT IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST. MATERIAL HAVING SALVAGE VALUE SHALL BECOME THE PROPERTY OF THE OWNER ALL OTHER MATERIAL AND DEBRIS ACCUMULATED AS A RESULT OF DEMOLITION SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES BY THE CONTRACTOR AND DISPOSED OF IN A LEGAL AND PROPER MANNER. FURNISH, INSTALL, AND MAINTAIN IN SAFE CONDITIONS AT ALL TIMES TEMPORARY PROTECTION REQUIRED TO ENSURE SAFETY FOR PERSONS AND PROPERTY DURING DEMOLITION AND REMOVAL WORK. REMOVE EXISTING ELECTRICAL OUTLETS AND WIRING AS REQUIRED IN WALLS, FLOORS AND FURNISHINGS TO BE DEMOLISHED. ALL WALLS, DOORS, WINDOWS, FURNISHINGS AND EQUIOMENT DENOTED WITH DASHED LINES ARE TO BE REMOVED. REFER TO PROPOSED PLAN LAYOUT FOR CLARIFICATIONS. ALL ELECTRICAL, PLUMBING, AND MECHANICAL WORK (DEMOLITION AND NEW) IS TO BE PERFORMED BY LICENSED, COMPETENT CONTRACTORS. REFER TO STRUCTURAL DRAWINGS FOR ALL STRUCTURAL DEMOLITION LOCATIONS AND DETAILS. EXISTING ITEMS TO REMAIN SHALL BE PROTECTED DURING DEMOLITION AND NEW CONSTRUCTION. DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXISTING SECOND LEVEL DEMOLITION PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-1.1 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 SECOND LEVEL FLOOR PLAN - DEMOLITION DEMOLITION GENERAL NOTESA ANNOTATION LEGENDB KEYNOTESC 1 PROPERTY LINE NO. REVISION DATE 1 11 1 S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " EXISTING SIDEYARD SETBACK 10' - 0" ROOM TAGROOM NAME ? 1 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG PROPERTY LINE TAG90 00' 00"20.00'N E LIMITS OF DEMOLITION -PORTION OF CURRENT STRUCTURE THAT WAS ADDED TO HISTORICAL BUILDING AND TO BE DEMOLISHED TREE TO REMAIN -EXISTING TREE TO BE PROTECTED IN PLACE. REF. SURVEY LIMITS OF HISTORICAL STRUCTURE -PORTION OF CURRENT STRUCTURE THAT IS A PART OF THE HISTORICAL FOOTPRINT AND TO REMAIN IN PLACE TREE TO BE REMOVED -EXISTING TREE TO BE REMOVED. REF. SURVEY EXISTING WALL TO REMAIN -GC TO PATCH AND REPAIR AS NECESSARY EXISTING WALL TO BE DEMOLISHED -GC TO REMOVE WALL AND PREP AREA FOR NEW CONSTRUCTION DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. -CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. GENERAL HISTORICAL RESTORATION NOTES: ALL EXTERIOR FENESTRATIONS WITHIN IN HISTORICAL FOOTPRINT TO BE EITHER REMOVED OR REPLACED TO MATCH ORIGINAL SANBORN MAP AND DESIGN EXTERIOR WALLS ADJACENT TO EXISTING ADDITION TO BE REFINISHED TO MATCH ORIGINAL SANBORN MAP AND DESIGN. GENERAL DEMOLITION NOTES: VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING ANY WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ARCHITECT IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST. MATERIAL HAVING SALVAGE VALUE SHALL BECOME THE PROPERTY OF THE OWNER ALL OTHER MATERIAL AND DEBRIS ACCUMULATED AS A RESULT OF DEMOLITION SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE PREMISES BY THE CONTRACTOR AND DISPOSED OF IN A LEGAL AND PROPER MANNER. FURNISH, INSTALL, AND MAINTAIN IN SAFE CONDITIONS AT ALL TIMES TEMPORARY PROTECTION REQUIRED TO ENSURE SAFETY FOR PERSONS AND PROPERTY DURING DEMOLITION AND REMOVAL WORK. REMOVE EXISTING ELECTRICAL OUTLETS AND WIRING AS REQUIRED IN WALLS, FLOORS AND FURNISHINGS TO BE DEMOLISHED. ALL WALLS, DOORS, WINDOWS, FURNISHINGS AND EQUIOMENT DENOTED WITH DASHED LINES ARE TO BE REMOVED. REFER TO PROPOSED PLAN LAYOUT FOR CLARIFICATIONS. ALL ELECTRICAL, PLUMBING, AND MECHANICAL WORK (DEMOLITION AND NEW) IS TO BE PERFORMED BY LICENSED, COMPETENT CONTRACTORS. REFER TO STRUCTURAL DRAWINGS FOR ALL STRUCTURAL DEMOLITION LOCATIONS AND DETAILS. EXISTING ITEMS TO REMAIN SHALL BE PROTECTED DURING DEMOLITION AND NEW CONSTRUCTION. DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXISTING LOWER LEVEL DEMOLITION PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-1.2 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 BASEMENT LEVEL FLOOR PLAN - DEMOLITION DEMOLITION GENERAL NOTESA ANNOTATION LEGENDB KEYNOTESC 1 PROPERTY LINE NO. REVISION DATE D-3.01 D-3.0 2 D-3.1 2 D-3.1 1 D-3.2 1 2 REMOVE NON-HISTORIC ADDITION DECK REMOVE NON-HISTORIC ADDITION AND COVERED WALKWAY REMOVE NON-HISTORIC DECK AND ADDITION REMOVE NON-HISTORIC DORMER REMOVE NON-HISTORIC DORMER REMOVE NON-HISTORIC DORMER 12 : 1 2 12 : 1 2 12 : 1 2 12 : 1 2 12 : 1 2 12 : 1 2 12:1212:12 5:12 5:12 10 : 1 2 10 : 1 2 10 : 1 2 10 : 1 2 12:1212:12 12 : 1 2 12 : 1 2 12:1212:12 12:12 6: 1 2 6: 1 2 12 : 1 2 3:12 3:12 3: 1 2 3: 1 2 3: 1 2 3: 1 2 6:126:12 12:1212:12 12:1212:12 DIMENSION NOTE: ALL DIMS. ARE TO FACE OF STUD (F.O.S.) OR FACE OF SHT'G. (F.O.S.) TYP. U.N.O. EAVE DIMS. ARE FROM FACE OF SHT'G. TO FACE OF FINISH FASCIA ENLOSED ATTIC AND ENCLOSED RAFTER SPACES VENTING NOTES: 1. ENCLOSED ATTIC AND ENCLOSED RAFTER SPACES SHALL HAVE CROSS VENTILATION BY VENTILATION OPENING PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW UNLESS THEY MEET THE REQUIREMENT OF SECTION R806.5 FOR UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES. VENTILATION OPENING SHALL HAVE THE LEAST DIMENSION OF 1/16”MIN. AND 1/4”MAX OTHERWISE THE OPENING SHALL HAVE THE CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE CLOTH, PERFORATED VINYL OR SIMILAR MATERIAL WITH OPENINGS HAVE A LEAST DIMENSION OF 1/16”MIN. AND 1/4”MAX. OPENING IN ROOF FRAMING MEMBERS SHALL BE PER THE REQUIREMENT OF SECTION R802.7. REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO THE OUTSIDE AIR AND SHALL BE PROTECTED TO PREVENT THE ENTRY OF BIRDS, RODENTS, SNAKES AND OTHER SIMILAR CREATURES. (R806.1) 2. THE MINIMUM NET FREE VENTILATING AREA SHOULD BE 1/150 OF THE AREA OF THE VENTED SPACE, EXCEPT FOR THE PROJECT LOCATED IN CLIMATE ZONE 14 OR 16 WITH A CLASS I OR II VAPOR RETARDER AT THE WARM-IN-WINTER SIDE OF THE CEILING AND WHERE MIN. 40% AND MAX 50% OF THE REQUIRED VENTILATION PROVIDED IN THE UPPER PORTION OF THE ATTIC OR RAFTER SPACE PER SECTION R806.2 THEN THE MINIMUM NET FREE VENTILATING AREA CAN BE 1/300 OF THE VENTED SPACE. (R802.2) 3. PROVIDE 1”SPACE BETWEEN THE INSULATION AND THE ROOF SHEATHING WHERE EAVE OR CORNICE VENTS PROVIDE BLOCKING, BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW OF AIR. (R806.3) 4. INSTALL VENTILATOR PER MANUFACTURER INSTRUCTION. INSTALL VENTILATOR IN ROOF PER SECTION R903 AND VENTILATOR IN WALL ASSEMBLIES PER SECTION R703.1. 5. FOR THE ATTIC WITH VERTICAL HEIGHT GREATER THAN OR EQUAL TO 30”(VERTICAL HEIGHT MEASURED FROM THE TOP OF CEILING JOIST TO THE BOTTOM OF THE ROOF RAFTERS) WITHIN 30S.F. MIN. PROVIDE THE OPENING WITH ROUGH-FRAMED OPENING OF NOT LESS THAN 22”X30”WHICH SHOULD BE LOCATED IN HALLWAY OR OTHER LOCATION WITH READY ACCESS. IF THE ACCESS LOCATED IN THE WALL THEN THE WIDTH SHOULD BE 22”AND HEIGHT SHOULD BE 30”MIN. IF LOCATED IN CEILING THEN THE MIN. UNOBSTRUCTED HEADROOM IN THE ATTIC SHOULD BE 30”FROM THE BOTTOM OF CEILING JOIST AT SOME POINT. ROOF DRAINAGE: IF THE PROJECT LOCATED IN THE AREA WITH EXPANSIVE OR COLLAPSIBLE SOILS, WATER RUNOFF FROM ROOFS OF ALL DWELLINGS SHALL BE DISCHARGED TO THE GROUND SURFACE NOT LESS THAN 5 FEET FROM FOUNDATION WALLS OR TO AN APPROVED DRAINAGE SYSTEM. (R801.3) -REF.CIVIL DWGS FOR STORM WATER MANAGMENT AND SYSTEM. WEATHER PROTECTION: 1. ROOF DECKS SHALL BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN ACCORDANCE WITH THE CHAPTER 9 OF THE CURRENT IRC. ROOF ASSEMBLIES SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE CHAPTER 9 OF IRC AND THE APPROVED MANUFACTURER’S INSTRUCTIONS SUCH THAT THE ROOF ASSEMBLY SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. (R903.1) 2. PROVIDE AND INSTALL FLASHING TO PREVENT ENTRY OF MOISTURE TO WALL AND ROOF ASSEMBLIES THRU THE JOINTS IN COPINGS, PERMEABLE MATERIAL, AND AT INTERSECTION WITH PARAPET WALLS AND OTHER PENETRATION THRU ROOF. (R903.2) 3. FLASHINGS SHALL BE INSTALLED AT WALL AND ROOF INTERSECTIONS, WHEREVER THERE IS A CHANGE IN ROOF SLOPE OR DIRECTION AND AROUND ROOF OPENINGS. A FLASHING SHALL BE INSTALLED TO DIVERT THE WATER AWAY FROM WHERE THE EAVE OF A SLOPED ROOF INTERSECTS A VERTICAL SIDEWALL. WHERE FLASHING IS OF METAL, THE METAL SHALL BE CORROSION RESISTANT WITH A THICKNESS OF NOT LESS THAN 0.019 INCH (0.5 MM) (NO. 26 GALVANIZED SHEET). (R903.2.1) 4. A CRICKET OR SADDLE SHALL BE INSTALLED ON THE RIDGE SIDE OF ANY CHIMNEY OR PENETRATION MORE THAN 30 INCHES (762 MM) WIDE AS MEASURED PERPENDICULAR TO THE SLOPE. CRICKET OR SADDLE COVERINGS SHALL BE SHEET METAL OR OF THE SAME MATERIAL AS THE ROOF COVERING. EXCEPT FOR UNIT SKYLIGHTS INSTALLED IN ACCORDANCE WITH HYPERLINK "HTTPS://CODES.ICCSAFE.ORG/LOOKUP/CRC2019P1_PT03_CH03_SECR308.6" SECTION R308.6 AND FLASHED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS SHALL BE PERMITTED TO BE INSTALLED WITHOUT A CRICKET OR SADDLE. (R903.2) 5. PARAPET WALLS SHALL BE PROPERLY COPED WITH NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A WIDTH NOT LESS THAN THE THICKNESS OF THE PARAPET WALL. (R903.3) 6. UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE ROOF. IF WATER CAN BE ENTRAPPED WITHIN THE ROOF AREA THEN SECONDARY EMERGENCY OVERFLOW ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED PER SECTION R903.4.1. (R903.4) 7. SNOW STOPS REQUIRED AT ALL ROOF PITCHES THAT SHED ONTO POTENTIALLY OCCUPIED AREAS PER R901 AS AMENDED BY CITY OF ASPEN MISC. NOTES: 1. INSTALL ROOF PER ROOFING MFG'R. SPECS & INSTALLATION GUIDELINE 2. ARCH. TO APPV. SIZE, COLOR & PROFILE OF EAVE & RAKE COMPONENTS. G.C. TO PROVIDE MOCK-UPS. 3. UNVENTED ENCLOSED RAFTER ASSEMBLY: NO INTERIOR CLASS I VAPOR RETARDER SHALL BE INSTALLED ON THE CEILING SIDE (ATTIC FLOOR) OF THE UNVENTED ATTIC ASSEMBLY OR ON THE CEILING SIDE OF THE UNVENTED ENCLOSED ROOF FRAMING ASSEMBLY. 4. REF. WOOD OR WOODBASE PRODUCT NOTES ON FLOOR PLANS DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXISTING ROOF DEMOLITION PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-2.0 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 ARCHITECTURAL ROOF PLAN - DEMOLITION DEMOLITION GENERAL NOTESA KEYNOTESB NO. REVISION DATE FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' SECOND FLOOR F.F. 7904.91' ROOF PLATE 7911.75' ROOF PLATE 7911.75' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' SECOND FLOOR PLATE 7903.83' MAIN RIDGE 7919.33' MAIN RIDGE 7919.33' REMOVE NON- HISTORIC ADDITION REMOVE NON- HISTORIC BALCONY REMOVE NON-HISTORIC FENESTRATIONS REMOVE NON-HISTORIC COVERED WALKWAY REMOVE NON-HISTORIC FENESTRATIONS REMOVE NON-HISTORIC ADDITION REMOVE NON-HISTORIC FENESTRATION REMOVE NON- HISTORIC STAIRCASE REMOVE NON-HISTORIC ADDITION REMOVE NON-HISTORIC DORMER FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' SECOND FLOOR F.F. 7904.91' ROOF PLATE 7911.75' ROOF PLATE 7911.75' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' SECOND FLOOR PLATE 7903.83' MAIN RIDGE 7919.33' MAIN RIDGE 7919.33' REMOVE NON- HISTORIC ADDITION REMOVE NON- HISTORIC FENESTRATION REPLACE NON-HISTORIC FENESTRATION TO MATCH HISTORICAL DESIGN REMOVE NON-HISTORIC DORMER REMOVE NON-HISTORIC PORCH DETAILS AND RESTORE REMOVE NON-HISTORIC ADDITION AND FENESTRATIONS REMOVE NON-HISTORIC DOOR AND LIGHTING DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXTERIOR ELEVATION DEMOLITION KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-3.0 TBD RYAN McDANIEL, AIA 1/4" = 1'-0"1 EAST ELEVATION - DEMOLITION 1/4" = 1'-0"2 NORTH ELEVATION - DEMOLITION NO. REVISION DATE CARRIAGE HOUSE F.F. 7893.50' CARRIAGE HOUSE F.F. 7893.50' REMOVE NON-HISTORIC ADDITION AND BALCONYREMOVE NON-HISTORIC DORMER CARRIAGE HOUSE ROOF PLATE 7904.50' CARRIAGE HOUSE ROOF PLATE 7904.50' FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' SECOND FLOOR F.F. 7904.91' ROOF PLATE 7911.75' ROOF PLATE 7911.75' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' SECOND FLOOR PLATE 7903.83' MAIN RIDGE 7919.33' MAIN RIDGE 7919.33' REMOVE NON-HISTORIC FENESTRATIONS REMOVE NON-HISTORIC COVERED WALKWAY REPLACE NON-HISTORIC FENESTRATIONS TO MATCH HISTORICAL DESIGN REMOVE NON-HISTORIC STAIRCASE REMOVE NON-HISTORIC ADDITION REPLACE NON-HISTORIC FENESTRATIONS TO MATCH HISTORICAL DESIGN REMOVE NON-HISTORIC DORMER REMOVE ENTIRE DORMER AND RESTORE REMOVE NON-HISTORIC PORCH DETAILS AND RESTORE REPLACE NON-HISTORIC FENESTRATION TO MATCH HISTORICAL DESIGN REPLACE NON-HISTORIC FENESTRATION TO MATCH HISTORICAL DESIGN DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXTERIOR ELEVATION DEMOLITION KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-3.1 TBD RYAN McDANIEL, AIA 1/4" = 1'-0"2 SOUTH ELEVATION - DEMOLITION 1/4" = 1'-0"1 WEST ELEVATION - DEMOLITION NO. REVISION DATE FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' SECOND FLOOR F.F. 7904.91' ROOF PLATE 7911.75' ROOF PLATE 7911.75' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' SECOND FLOOR PLATE 7903.83' MAIN RIDGE 7919.33' MAIN RIDGE 7919.33' REMOVE NON-HISTORIC ADDITION REMOVE NON-HISTORIC COVERED WALKWAY REMOVE NON-HISTORIC FENESTRATIONS REMOVE NON-HISTORIC ADDITION CARRIAGE HOUSE F.F. 7893.50' CARRIAGE HOUSE F.F. 7893.50' REMOVE NON-HISTORIC COVERED WALKWAY REMOVE NON-HISTORIC DOOR REMOVE NON-HISTORIC ADDITION CARRIAGE HOUSE ROOF PLATE 7904.50' CARRIAGE HOUSE ROOF PLATE 7904.50' DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXTERIOR ELEVATION DEMOLITION KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 D-3.2 TBD RYAN McDANIEL, AIA 1/4" = 1'-0"1 BACK OF HOUSE ELEVATION - DEMOLITION 1/4" = 1'-0"2 FRONT OF CARRIAGE HOUSE ELEVATION - DEMOLITION NO. REVISION DATE DN DN DN DN UP UP DN DN DN DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. -CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. GENERAL NOTE: SEE SHEET A-3.0 FOR ROOF PLAN INFORMATION NOT SHOWN ON THIS SHEET (INCLUDING EAVE DETAILS AND PROJECTION DISTANCES). LANDSCAPE NOTES: 1. ENCROACHMENT PERMIT REQ'D. FOR ANY WORK PROPOSED IN THE PUBLIC R.O.W. 2. IF APPLICABLE, REF. PRELIMINARY LANDSCAPE PLANS, FOR ALL HARDSCAPE & PLANTING AREAS WITH RESPECTIVE HEIGHTS AND MATERIALS. LIGHTING NOTES: 1. ALL OUTDOOR LIGHTING MUST COMPLY WITH THE CITY OF ASPEN LIGHTING CODE SECTION 26.575.150. S.Y.S.B. (REQUIRED) 10' - 0" 1 1 1 1 2 3 3 4 2 OFFICE FOYER KITCHEN GREAT ROOM HALLWAY STAIR #2 ELEV. MUD ROOM 2-CAR GARAGE CARRIAGE HOUSE BATH #6 W.C. DIRTY KITCHEN BATH #7PWDR. SPOOL (UNDER SEP. PERMIT) CLR. 20 ' - 1 7 / 8 " CLR. 21' - 10 5/8" W. BLEEKER ST. N. 2 N D S T . ALLEY LIGHT WELL LIGHT WELL N 75° 09' 11" W 90.00' S 75° 09' 11" E 90.00' N 1 4 ° 5 0 ' 4 9 " E 1 0 0 . 0 0 ' S 1 4 ° 5 0 ' 4 9 " W 1 0 0 . 0 0 ' 7894.83' T.O.S. 7894.83' T.O.S. 7893.50' T.O.S. DRIVEWAY PATIO POOL DECK PORCH PORCH PORCH DECK FIREPIT 5678 EM GM I C X 8 8 8 9 10 1112 13 13 13 14 14 15 10 1010 10 15 ' - 0 1 / 2 " 32 ' - 0 1 / 2 " 25 ' - 8 " 11' - 7 3/8" S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" 11' - 7 3/8" 8' - 2 3/8" R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " R. Y . S . B . 10 ' - 0 " S.Y.S.B. (PROPOSED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " CARPORT YARD 30 ' - 6 1 / 2 " 37 ' - 6 1 / 2 " 18' - 9 3/8" 26 ' - 9 1 / 4 " 44 ' - 1 3 / 8 " 56' - 9 3/4" 5' - 0 1 / 2 " S.Y.S.B. (REQUIRED & PROPOSED) 10' - 0" 11' - 0 1/2" 16' - 5 7/8" SP O O L C L R . 26 ' - 6 1 / 2 " PO O L C O V E R D E C K 5' - 0 " SPOOL CLR. 7' - 0" FRONT YARD (PER LANDSCAPE DWGS.) 16 16 17 TYP OF 3 F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " 10 ' - 0 " 10' SETBACK BETWEEN BUILDINGS 10' - 0" S.Y.S.B. (REQUIRED) 10' - 0" PARKING SPACE ( MIN. 8'-6" X 18'-0") 8' - 6" PA R K I N G S P A C E ( M I N . 8 ' - 6 " X 1 8 ' - 0 " ) 18 ' - 0 " 7894.83' T.W. 7894.83' T.W. ADDITIONAL SETBACK 20 ' - 6 " SE T B A C K F R O M H I S T O R I C R E S O U R C E 15 ' - 6 " 7893.50' 10' SETBACK BETWEEN BUILDINGS 10 ' - 0 " 53' - 9 5/8" ROOM TAGROOM NAME ? 1 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG PROPERTY LINE TAG90 00' 00"20.00'N E FIREPIT -AS SELECTED TO BE LISTED AND APPROVED, VERIFY W/. OWNER –PROVIDE POWER AND GAS AS REQUIRED –INSTALL AND MAINTAIN CLEARANCES PER MFGR. AND SECTION 308 OF IFC RECESSED MAIN SERVICE PANEL -400 AMP MAX. (MAINTAIN 36" CLEAR FROM FACE OF PANEL TO ANY OBSTRUCTION) –GC TO COORDINATE W/. UTILITY COMPANY A/C CONDENSER / HEAT PUMP -TO BE IN COMPLIANCE OF SECTION 1403.1 & 1404.1 OF IRC AS SELECTED, VERIFY W/. OWNER -SIZE PER HVAC CONSULTANT –PROVIDE POWER AND SOUND DAMPENING PAD AS REQ’D. –INSTALL AND MAINTAIN REQUIRED CLEARANCES PER MFGR. INSTRUCTION & LISTING AND LABELING (IRC M1307.1) DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 ARCHITECTURAL SITE PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-0.0 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 1/8" = 1'-0"1 ARCHITECTURAL SITE PLAN SITE PLAN NOTESA ANNOTATION LEGENDB KEYNOTESC 1 PROPERTY LINE 2 REAR YARD SETBACK 3 SIDE YARD SETBACK 4 FRONT YARD SETBACK 5 (E.) TELEPHONE BOX LOCATION - (REF. SURVEY & CIVIL DWGS.) 6 (E.) CABLE TV JUNCTION BOX 7 (E.) POWER POLE - PROTECT IN PLACE 8 (E.) STREET SIGN - PROTECT IN PLACE 9 (E.) STREET LIGHT (REF. SURVEY & CIVIL DWGS.) 10 (E.) STREET TREE TO REMAIN - PROTECT IN PLACE 11 (E.) GAS METER LOCATION - (REF. SURVEY & CIVIL DWGS.) 12 (E.) NEIGHBORS' ELECTRIC METER - (REF. SURVEY & CIVIL DWGS.) 13 (E.) ROLLED-CURB - (REF. CIVIL & SURVEY DWGS.) 14 (E.) SIDEWALK - PROTECT IN PLACE 15 (E.) CURB STOP - REF. SURVEY 16 LIGHTWELL PROTECTION RAILING - PER IBC AND CITY OF ASPEN ERMERGENCY ESCAPE AND RESCUE OPENING REQUIREMENTS 17 A/C. CONDENSER UNIT - SIZE TBD - PROVIDE POWER AND SOUND DAMPENING PAD AS REQ'D. (SOUND ATTENUATION REQ'D. PER SECTION 10.26.045 N.B.M.C. UNDER SEPARATE PERMIT & PLAN CHECK) NO. REVISION DATE PROPERTY LINE GROSS LOT SIZE 9,000 SF NET LOT SIZE 9,000 SF BUILDING FOOTPRINT 2,998.93 SF COVERAGE 38.41% BUILDING FOOTPRINT 457.95 SF PROPERTY LINE GROSS LOT SIZE 9,000 SF NET LOT SIZE 9,000 SF BUILDING FOOTPRINT 2,889.41 SF COVERAGE 40.0% BUILDING FOOTPRINT 719.52 SF DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 SITE COVERAGE KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-0.1 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1/8" = 1'-0"2 PROPOSED SITE COVERAGE 1/8" = 1'-0"1 EXISTING SITE COVERAGE 30 " M A X 2' - 6 " 30 " M A X 2' - 6 " S.Y.S.B. (REQUIRED & PROPOSED) 10' - 0" PL POOL DECK SPOOL BASEMENT MASTER BALCONY W. BLEEKER ST. N. 2 N D S T . LANDSCAPE PAVERS ON GRADE HARDSCAPE PAVERS ON GRADE 1 A-0.2 4' - 7 " PROPOSED EGRESS WINDOW WELL PER IRC R310.2 (16.09 SF) PROPOSED EGRESS WINDOW WELL PER IRC R310.2 (9.00 SF)3' - 0" 3' - 0 " FRONT PORCH REQ'D SPOOL SPOOL <30" ABOVE / BELOW FINISHED GRADE PER 26.575.020.E.5.M DECK <30" ABOVE / BELOW FINISHED GRADE PER 26.575.020.E.5.M S.Y.S.B. (REQUIRED) 10' - 0" I C X S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " S.Y.S.B. (PROPOSED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " S.Y.S.B. (REQUIRED & PROPOSED) 10' - 0" SIDEWALK 5' - 0" SIDEWALK 5' - 0" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " S.Y.S.B. (REQUIRED) 10' - 0" PARKING SPACE ( MIN. 8'-6" X 18'-0") 8' - 6" PA R K I N G S P A C E ( M I N . 8 ' - 6 " X 1 8 ' - 0 " ) 18 ' - 0 " ADDITIONAL SETBACK 20 ' - 6 " SE T B A C K F R O M H I S T O R I C R E S O U R C E 15 ' - 6 " SETBACK BETWEEN BUILDINGS 10 ' - 0 " EXISTING 8' - 2 3/8" 7' - 9 7/8"4 1/2" PROPOSED RETAINING WALL AND LANDSCAPING NOT TO EXCEED 30" ABOVE FINISHED GRADE PER 26.575.020.E.5.K PROPOSED PROPERTY WALL NOT TO EXCEED 30" ABOVE FINISHED GRADE PER 26.575.020.E.5.K PROPOSED WOOD FENCE AND POOL SCREEN NOT TO EXCEED 30" ABOVE FINISHED GRADE PER 26.575.020.E.5.K AND 26.575.020.E.5.M PROPOSED LANDSCAPING PAVERS ON GRADE PROPOSED MECHCANICAL EQUIPMENT NOT TO EXCEED 30" ABOVE FINISHED GRADE AND SCREENED PER 26.575.020.E.5.N 3 3/4" 6" 3 1 / 4 " PROPOSED DRIVEWAY < 30" ABOVE FINISHED GRADE PER 26.575.020.E.5.Q PROPOSED ROOF EAVE <18" PROJECTION PER 26.575.020.E.5.G EXISTING ROOF EAVE <18" PROJECTION PER 26.575.020.E.5.G EXISTING ROOF EAVE <18" PROJECTION PER 26.575.020.E.5.G EXISTING ROOF EAVE <18" PROJECTION PER 26.575.020.E.5.G FRONT PORCH REQ'D EXISTING UNDERGROUND UTILITIES 1' - 3 7 / 8 " 5' - 0 " EX I S T I N G H I S T O R I C PR O J E C T I O N 1"STAIRCASE DESIGNED TO HISTORIC CONDITION AND PROJECTION DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 SETBACKS & ALLOWED PROJECTIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-0.2 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1/4" = 1'-0"1 SPOOL & POOL DECK SECTION PROJECT NORTHTRUE NORTH 1/8" = 1'-0"2 SETBACKS AND ALLOWABLE PROJECTIONS SITE PLAN UP 1 2 3 4 5 67 8 9 10 11 12 35' - 8 3/8"26' - 11 1/2" 4' - 1 0 " 71 ' - 1 1 1 / 4 " 17 ' - 1 1 1 / 4 " 7' - 0 5 / 8 " 4' - 7 3 / 4 " 10 ' - 0 " 4' - 1 " 10 ' - 5 3 / 8 " 12 ' - 1 1 1 / 4 " 3' - 0 " 8' - 10 1/8"10' - 8 3/8"22' - 11 7/8" 3' - 0" 25' - 9 3/8" 3' - 0" 3' - 0 " 13 14 15 1617 6' - 7 3/8" 5' - 7 3/4" 18 1 SUBGRADE CALCULATIONS LEGEND WALL BELOW GRADE EXPOSED WALL EXISTING GRADE A=428.38 SF A=58 SF 12 ' - 0 " 2 12 ' - 0 " 3 A=320.86 SF A=2.64 SF 4 A=854.51 SF A=8.74 SF 12 ' - 0 " 11 ' - 5 5 / 8 " 6 3 / 8 " 12 ' - 0 " A=271.53 SF A=4.35 SF 5 12 ' - 0 " 6 3 / 8 " 11 ' - 5 5 / 8 " 35' - 8 3/8"4' - 10"26' - 11 1/2"71' - 11 1/4"22' - 11 7/8" 10 A=27 SF A=128.25 SF 12 ' - 0 " 12' - 11 1/4" 3' - 0" 3' - 0 " 9' - 0 " 11 3' - 0 " 9' - 0 " A=27 SF 3' - 0" 12 ' - 0 " 25' - 9 3/8" A=282.38 SF 12 11 ' - 5 5 / 8 " 6 3 / 8 " 17' - 11 1/4" A=9.51 SF A=205.74 SF 13 A=67.75 SF 12 ' - 0 " 5' - 7 3/4" 14 A=84.63 SF 12 ' - 0 " 7' - 0 5/8" 15 A=79.38 SF 12 ' - 0 " 6' - 7 3/8" 16 4' - 7 3/4" 12 ' - 0 " A=55.75 SF 17 A=79.38 SF 12 ' - 0 " 6' - 7 3/8" 18 A=120 SF 12 ' - 0 " 10' - 0" 8 A=5.54 SF A= 119.84 SF 11 ' - 5 5 / 8 " 6 3 / 8 " 10' - 5 3/8" 9 A=108.01 SF A=4.69 SF 11 ' - 5 5 / 8 " 6 3 / 8 " 8' - 10 1/8" 6 A=27.57 SF A= 21.43 SF 11 ' - 5 5 / 8 " 6 3 / 8 " 3' - 0 " 9' - 0 " 7 3' - 0 " 9' - 0 " A=31.08 SF 3' - 0"3' - 0" A= 97.3 SF 10' - 8 3/8" 11 ' - 5 5 / 8 " 6 3 / 8 " 4' - 1" 1 2 3 4 5 6 7 8 763.10 SF INTERIOR SPACE 33' - 11 3/4" 30 ' - 0 3 / 8 " 12' - 0 1/2"5' - 0 1/4"16' - 11" 6' - 3 1 / 8 " 12 ' - 6 " 11 ' - 3 1 / 4 " FLOOR AREA CALCULATIONS PROPOSED BASEMENT LEVEL EXPOSED WALL CALCULATIONS BASEMENT LEVEL WALL LABEL TOTAL WALL AREA (SF)EXPOSED WALL AREA (SF) 1 428.38 0 2 58 0 3 323.5 2.64 4 863.25 8.74 5 275.88 4.35 6 49 27.57 7 128.38 31.08 8 125.38 5.54 9 112.7 4.69 10 155.25 27 11 309.38 27 12 215.25 9.51 13 67.75 0 14 84.63 0 15 79.38 0 16 55.75 0 17 79.38 0 18 120 0 OVERALL TOTAL WALL AREA (SF)3531.24 EXPOSED WALL AREA (SF)148.12 % OF EXPOSED WALL (SF) (EXPOSED / TOTAL) 4.19% PROPOSED BASEMENT FLOOR AREA CALCULATIONS BASEMENT LEVEL GROSS AREA (SF)3,680 BASEMENT COUNTABLE FLOOR AREA (SF)154.35 (3,680 X 4.19%) TOTAL PROPOSED FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)154.35 FIRST LEVEL FLOOR AREA (SF)2504.65 SECOND LEVEL FLOOR AREA (SF)1461.50 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)457.95 OVERALL TOTAL AREA (SF)4578.45 1 2 3 4 5 6 7 8 BASEMENT F.F. 7884.53' 33' - 11 3/4"30' - 0 3/8"16' - 11" 6' - 3 1/8" 5' - 0 1/4"12' - 6"12' - 0 1/2"11' - 3 1/4" A=287.80 SF A=254.36 SF A=142.38 SF A=53.03 SF A=101.99 SF A=96.46 SF A=42.53 SF A=105.88 SF 9' - 0 " FIRST FLOOR PLATE 7893.53' LOWEST EXISTING GRADE 7893.53' 6 3 / 8 " 8' - 5 5 / 8 " A=18.01SF A=15.92 SF A=8.97 SF A=3.32 SF A=6.38 SF A=5.97 SF A=2.66 SF A=6.63 SF FLOOR AREA CALCULATIONS EXISTING BASEMENT LEVEL EXPOSED WALL CALCULATIONS BASEMENT LEVEL WALL LABEL TOTAL WALL AREA (SF)EXPOSED WALL AREA (SF) 1 305.81 18.01 2 270.28 15.92 3 151.35 8.97 4 56.35 3.32 5 45.19 2.66 6 112.51 6.63 7 108.37 6.38 8 102.43 5.97 OVERALL TOTAL WALL AREA (SF)1152.29 EXPOSED WALL AREA (SF)67.86 % OF EXPOSED WALL (SF) (EXPOSED / TOTAL) 5.89% EXISTING BASEMENT FLOOR AREA CALCULATIONS BASEMENT LEVEL GROSS AREA (SF)763 BASEMENT COUNTABLE FLOOR AREA (SF)44.94 (763 X 5.89%) TOTAL EXISTING FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)44.94 FIRST LEVEL FLOOR AREA (SF)2860.76 SECOND LEVEL FLOOR AREA (SF)1269.46 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)987.86 OVERALL TOTAL AREA (SF)5163.02 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 BASEMENT LEVEL AREA CALCULATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-0.3 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1" = 10'-0"4 PROPOSED BASEMENT LEVEL AREA PLAN 1/16" = 1'-0"3 PROPOSED BASEMENT LEVEL AREA CALCULATION 1" = 10'-0"2 EXISTING BASEMENT LEVEL AREA PLAN 3,679.75 SF INTERIOR SPACE 1/16" = 1'-0"1 EXISTING BASEMENT LEVEL AREA CALCULATION DN DN DN UP _ UP _ 494.28 SF GARAGE SPACE 2,504.65 SF INTERIOR SPACE 71.47 SF FRONT PORCH (EXEMPT) 436.72 SF POOL DECK 74.48 SF BACK DECK 16.95 SF EXT. STAIR 27.38 SF HISTORICAL STAIR (EXEMPT) 40.81 SF ON-GRADE STAIR (EXEMPT) 2860.76 SF INTERIOR SPACE 110.19 SF FIRST FLOOR DECK 71.47 SF FRONT PORCH (EXEMPT) FLOOR AREA CALCULATIONS PROPOSED FIRST LEVEL FLOOR AREA CALCULATIONS FIRST LEVEL GROSS AREA (SF)2504.65 GARAGE GROSS FLOOR AREA (SF)494.28 GARAGE FLOOR AREA (SF)0 (494.28 - 500 = 0 /2) FIRST LEVEL COUNTABLE FLOOR AREA (SF) 2504.65 GARAGE COUNTABLE FLOOR AREA (SF)0 TOTAL FIRST LEVEL COUNTABLE FLOOR AREA (SF)2504.65 PROPOSED DECK/PORCH FLOOR AREA CALCULATIONS FRONT PORCH FLOOR AREA (SF)71.47 EXEMPT PER 26.575.020.D.5 HISTORICAL PORCH STAIRCASE (SF)27.38 EXEMPT PER 26.575.020.D.5 PORCH 40.81 EXEMPT PER 26.575.020.D.6 POOL DECK 436.72 EXTERIOR STAIR 16.95 BACK DECK 74.48 SECOND FLOOR BALCONY 83.51 EXEMPT DECK FLOOR AREA (SF)612 (4,080 ALLOWABLE X 15%) DECK/PORCH COUNTABLE FLOOR AREA (SF)0 (436.72 + 16.95 + 74.48 + 83.51 - 612) TOTAL PROPOSED FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)154.35 FIRST LEVEL FLOOR AREA (SF)2504.65 SECOND LEVEL FLOOR AREA (SF)1461.50 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)457.95 OVERALL TOTAL AREA (SF)4578.45 FLOOR AREA CALCULATIONS EXISTING FIRST LEVEL FLOOR AREA CALCULATIONS FIRST LEVEL GROSS AREA (SF)2860.76 GARAGE GROSS FLOOR AREA (SF)0 GARAGE FLOOR AREA (SF)0 NO EXISTING GARAGE FIRST LEVEL COUNTABLE FLOOR AREA (SF) 2860.76 GARAGE COUNTABLE FLOOR AREA (SF)0 TOTAL FIRST LEVEL COUNTABLE FLOOR AREA (SF)2860.76 EXISTING DECK/PORCH FLOOR AREA CALCULATIONS FRONT PORCH FLOOR AREA (SF)71.47 EXEMPT PER 26.575.020.D.5 FIRST FLOOR DECK 110.19 SECOND FLOOR DECK 39.9 EXEMPT DECK FLOOR AREA (SF)612 (4,080 ALLOWABLE X 15%) DECK/PORCH COUNTABLE FLOOR AREA (SF)0 (110.19 + 39.90 - 612) TOTAL EXISTING FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)44.94 FIRST LEVEL FLOOR AREA (SF)2860.76 SECOND LEVEL FLOOR AREA (SF)1269.46 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)987.86 OVERALL TOTAL AREA (SF)5163.02 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 FIRST LEVEL AREA CALCULATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-0.4 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1" = 10'-0"2 PROPOSED FIRST LEVEL AREA PLAN 1" = 10'-0"1 EXISTING FIRST LEVEL AREA PLAN DN DN _ _ 83.51 SF MASTER BALCONY 753.55 SF INTERIOR SPACE 707.95 SF INTERIOR SPACE 1269.46 SF INTERIOR SPACE 39.90 SF SECOND FLOOR DECK FLOOR AREA CALCULATIONS PROPOSED SECOND LEVEL FLOOR AREA CALCULATIONS SECOND LEVEL GROSS AREA (SF)1461.5 SECOND LEVEL COUNTABLE FLOOR AREA (SF) 1461.5 TOTAL PROPOSED FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)154.35 FIRST LEVEL FLOOR AREA (SF)2504.65 SECOND LEVEL FLOOR AREA (SF)1461.50 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)457.95 OVERALL TOTAL AREA (SF)4578.45 FLOOR AREA CALCULATIONS EXISTING SECOND LEVEL FLOOR AREA CALCULATIONS SECOND LEVEL GROSS AREA (SF)1269.46 SECOND LEVEL COUNTABLE FLOOR AREA (SF) 1269.46 TOTAL EXISTING FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)44.94 FIRST LEVEL FLOOR AREA (SF)2860.76 SECOND LEVEL FLOOR AREA (SF)1269.46 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)987.86 OVERALL TOTAL AREA (SF)5163.02 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 SECOND LEVEL AREA CALCULATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-0.5 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1" = 10'-0"2 PROPOSED SECOND LEVEL AREA PLAN 1" = 10'-0"1 EXISTING SECOND LEVEL AREA PLAN _ _ DN DN DN DN UP UP 457.95 SF INTERIOR SPACE FLOOR AREA CALCULATIONS PROPOSED CARRIAGE HOUSE FLOOR AREA CALCULATIONS FIRST LEVEL GROSS AREA (SF)457.95 SECOND LEVEL GROSS AREA (SF)0 NO PROPOSED SECOND LEVEL CARRIAGE HOUSE COUNTABLE FLOOR AREA 457.95 TOTAL PROPOSED FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)154.35 FIRST LEVEL FLOOR AREA (SF)2504.65 SECOND LEVEL FLOOR AREA (SF)1461.50 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)457.95 OVERALL TOTAL AREA (SF)4578.45 719.52 SF INTERIOR SPACE 268.34 SF INTERIOR SPACE 259.83 SF SECOND FLOOR DECK FLOOR AREA CALCULATIONS EXISTING CARRIAGE HOUSE FLOOR AREA CALCULATIONS FIRST LEVEL GROSS AREA (SF)719.52 SECOND LEVEL GROSS AREA (SF)268.34 SECOND FLOOR DECK (SF)259.83 EXEMPT CARRIAGE HOUSE COUNTABLE FLOOR AREA 987.86 TOTAL EXISTING FLOOR AREA CALCULATIONS BASEMENT LEVEL FLOOR AREA (SF)44.94 FIRST LEVEL FLOOR AREA (SF)2860.76 SECOND LEVEL FLOOR AREA (SF)1269.46 DECK/PORCH FLOOR AREA (SF)0.00 CARRIAGE HOUSE FLOOR AREA (SF)987.86 OVERALL TOTAL AREA (SF)5163.02 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 CARRIAGE HOUSE AREA CALCULATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-0.6 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1" = 10'-0"3 PROPOSED CARRIAGE HOUSE FIRST LEVEL AREA PLAN 1" = 10'-0"2 EXISTING CARRIAGE HOUSE FIRST LEVEL AREA PLAN 1" = 10'-0"1 EXISTING CARRIAGE HOUSE SECOND LEVEL AREA PLAN D W _ FRZ._ TRDW FAU DN DN DN DN UP _ UP _ DN DN DN ROOM TAGROOM NAME 1 A-5.0 1 1 ? 1 1 A-4.0 1 1 1 1 ELEVATION / SECTION INDICATOR AD-1.0 1 CALL-OUT TAG 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG FIRE RATED CEILING ASS'Y -REF. DTLS. 7/AD-1.0 1-HR RATED INT CONDITION -REF. DTLS. 7/AD-1.0 1-HR RATED EXT CONDITION -REF. DTLS. 7/AD-1.0 STRUCTURAL STEEL COLUMN PER STRUCT., REF. STRUTC. DWGS, -PAINT AND SEAL AS REQUIRED –ARCH. TO APPV. COLOR FOR EXPOSED STEEL COLUMNS STRUCTURAL WOOD POST/COLUMN COLUMN -PER STRUCT., REF. STRUTC. DWGS, - PAINT, STAIN AND SEAL AS REQUIRED –ARCH. TO APPV. PAINT COLOR FOR EXPOSED WOOD POST/COLUMN, IF TO BE STAINED PROVIDE STAINED SAMPLE FOR ARCH, APPROVAL DOORS -AS SPECIFIED, SEE WINDOW SCHEDULE AND GENERAL NOTES ON SHEET A-7.0 - SHGC & U-FCTOR PER IECC & PLANS – SEE SHEET AD-2.0 FOR JAMB, HEAD AND THRESHOLD DETAILS, PROVIDE FLASHING AND WATERPROOFING AT DOOR OPENING PER THE DOOR MFGR. INSTRUCTION AND/OR FLASHING MFGR. INSTRUCTION PER SECTIONS R609.1 & R703.4 OF IRC WINDOW -AS SPECIFIED, SEE WINDOW SCHEDULE AND GENERAL NOTES ON SHEET A-7.0 -SHGC & U-FCTOR PER IECC & PLANS – SEE SHEET AD-2.0 FOR JAMB, HEAD AND SILL DETAILS, PROVIDE FLASHING AND WATERPROOFING AT WINDOW OPENING PER THE WINDOW MFGR. INSTRUCTION AND/OR FLASHING MFGR. INSTRUCTION PER SECTIONS R609.1 & R703.4 OF IRC REFRIGERATOR (REF) / FREEZER (FRZ) -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER AND WATER SUPPLY AS REQUIRED BUILT-IN APPLIANCE / DISHWASHER (DW) / TRASH COMPACTOR (TR)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , WATER SUPPLY & DRAINAGE PIPE AS REQUIRED CASEWORK, TALL CABINET -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER CASEWORK, BASE CABINET W/. COUNTERTOP -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER CASEWORK, UPPER CABINET/SHELVES -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER BUILT-IN CLOSET -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER ELEVATOR -PRIVATE RESIDENCE ELEVATOR IN COMPLIANCE W/. ASME A17.1/CSA B44 AS SELECTED PER PLANS, VERIFY W/. OWNER –PROVIDE POWER AS REQ'D. (CRC 321.1) RECESSED MAIN SERVICE PANEL -400 AMP MAX. (MAINTAIN 36" CLEAR FROM FACE OF PANEL TO ANY OBSTRUCTION) –GC TO COORDINATE W/. UTILITY COMPANY KITCHEN RANGE W/. EXHAUST HOOD -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – PROVIDE POWER AND GAS AS REQUIRED -30”MIN. VERTICAL CLEARANCE TO ANY COMBUSTIBLE MATERIAL ABV. COOKING TOP –EXHAUST HOOD TO HAVE EXHAUST RATE OF MIN. 100 CFM AND VENT TO OUTDOOR , HOOD DUCTS TO BE OF METAL WITH SMOOTH INTERIOR FINISH PER SECTION 505 OF IMC KITCHEN/BAR SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –SINK TO COMPLY W/. REQUIREMENT OF SECTION 422 OF IPC AND HAVE A MAX FLOW RATE OF 2.2 GPM @ 60 PSI PER SECTION 604.4 OF IPC –TRAP AND VENT FOR ISLAND SINK AND SIMILAR EQUIPMENT SHALL BE PER SECTION 916 OF IPC VANITY SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – LAVATORY TO HAVE 21”MIN. CLEAR SPACE IN FRONT OF IT.(IRC 307.1) W/. MAXIMUM FLOW RATE OF 2.2 GPM @ 60 PSI AND MIN. FLOW RATE OF 0.8 GPM @ 8 PSI PER SECTION 604.3 IPC WASHER (W) / DRYER (D) / STACKED (W/D)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , GAS, WATER SUPPLY & DRAINAGE AS REQUIRED -THE CLOTHES DRYERS VENT SHALL BE OF A RIGID METALLIC MATERIAL AND HAVE A BACKDRAFT DAMPER (IMC 504) DUCT LENGTH, CONNECTION AND TRANSITION SHALL BE PER SECTION 504.9.4 OF IMC. SEE WASHER & DRYER NOTES, REF. T-1.1. TOILET -WATER CLOSET SHALL BE IN COMPLIANCE OF SECTION 401 OF IPC AND HAS MAX EFFECTIVE FLUSH RATE OF 1.6 GAL. PER FLUSH (IPC 604.3). WATER CLOSETS CLR. TO BE 21”IN FRONT AND 15”FROM ITS CENTER TO ANY SIDE WALL OR OBSTRUCTION. (IPC 405.3.1 & IRC R307) FIREPLACE -FACTORY-BUILT DIRECT VENT GAS FIREPLACE W/. SEALED COMBUSTION - FACTORY-BUILT FIREPLACES, CHIMNEYS AND ALL OF THEIR COMPONENTS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1004.1) A/C CONDENSER / HEAT PUMP -TO BE IN COMPLIANCE OF SECTION 1403.1 & 1404.1 OF IRC AS SELECTED, VERIFY W/. OWNER -SIZE PER HVAC CONSULTANT –PROVIDE POWER AND SOUND DAMPENING PAD AS REQ’D. –INSTALL AND MAINTAIN REQUIRED CLEARANCES PER MFGR. INSTRUCTION LISTING AND LABELING (IRC M1307.1) FAU -PROVIDE GAS S.O., POWER, AND VENTING AS REQ'D. BY MFG'R. –INSTALL PER MFGR. INSTRUCTION ROOF/DECK DRAIN -PER CHAPTER 11 OF IPC -SECTOPM 1106 OF IPC –ROOF DRAIN SHALL HAVE DOMED STRAINER –REF. DETAIL 11/AD-1.0 OVERFLOW OR EMERGENCY DRAIN -PER CHAPTER 11 OF IPC -COPPER OR EQ., INSTALL PER MFGR. INSTRUC., SLOPED TOWARD IN-WALL DRAIN INLETS –SLOPE AND SIZE PER SECTION 1108 OF IPC –REF. DTL. 11/AD-1.0 A-4.1 A-4.0 A-4.12A-4.0 1 1 2 R. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " S.Y.S.B. (REQUIRED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " S.Y.S.B. (REQUIRED) 10' - 0" OFFICE FOYER KITCHEN GREAT ROOM HALLWAY STAIR #2 ELEV. MUD ROOM 2-CAR GARAGE CARRIAGE HOUSE W.C. BATH #6 DIRTY KITCHEN PWDR.BATH #7 SPOOL (UNDER SEP. PERMIT) STAIR #1 CLR. 20 ' - 1 7 / 8 " CLR. 21' - 10 5/8" LIGHT WELL 3'-0" x 3'-0" ENTRY PORCH PORCH PORCH 85 89 2 91 3 B 5 4 92 118 88 12 11 14 97 98 13 6 8 910 49 48 1 47 12 13 D 11 7 FAUX GARAGE DOOR TO MATCH HISTORIC DESIGN (NOT OPERABLE) 1 2 1313 4 1 4 1 3 5 4 7 6 8 9 10 A 2 SHWR. SHWR. C 6.1 6"6" FAUX MANDOOR TO MATCH HISTORIC DESIGN (NOT OPERABLE)LIGHT WELL 3'-0" x 3'-0" ATTIC ACCESS HATCH (2'-6" x 2'-6" MIN.) ATTIC ACCESS HATCH (2'-6" x 2'-6" MIN.) 5 5 5.5 F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " 15 ' - 0 " S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" S.Y.S.B. (EXISTING HISTORIC) 10' - 0" R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " A-4.03 A-4.1 4 A-4.1 3 PARKING SPACE ( MIN. 8'-6" X 18'-0") 8' - 6" PA R K I N G S P A C E ( M I N . 8 ' - 6 " X 1 8 ' - 0 " ) 18 ' - 0 " S.Y.S.B. (PROPOSED) 10' - 0" 0 FT. SETBACK -EXSITING HISTORIC CONDITION (BARN) 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 10' SETBACK BETWEEN BUILDINGS 10' - 0" 10' SETBACK BETWEEN BUILDINGS 10 ' - 0 " DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 FIRST LEVEL FLOOR PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-2.0 TBD RYAN McDANIEL, AIA 1 PROPERTY LINE 2 FRONT YARD SETBACK 3 SIDE YARD SETBACK 4 REAR YARD SETBACK 5 OUTLINE OF ATTIC SPACE ABV. PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 FIRST LEVEL FLOOR PLAN ANNOTATION LEGENDA KEYNOTESB NO. REVISION DATE DN DN _ _ D W _ FRZ._ TRDW FAU A-4.1 A-4.0 A-4.12A-4.0 1 1 2 F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " R. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " S.Y.S.B. (REQUIRED) 10' - 0" S.Y.S.B. (PROPOSED) 10' - 0" 1 2 3 1 3 1 4 4 1 12 : 1 2 12 : 1 2 6:12 6:12 BEDROOM #2 W/D. BEROOM #3 BATH #2 BATH #3 SHWR. SHWR. 12:12 12:12 6:12 12 : 1 2 12 : 1 2 12:1212:12 12 : 1 2 12:1212 : 1 2 12:12 12:12 6: 1 2 6: 1 2 12 : 1 2 12:12 12:12 12:12 CLR. 2' - 2 7/8" STAIR #1 R @ 0' -6 23/32"18 R @ 0' -6 23/32"18 MA. BATH MASTER BEDROOM W.C.W.I.C. W.I.C. ELEV. STAIR #2 130 34 107 94 96 115 114 113 122 MA. SHWR. SEAT F H J 7980 39 47 49 25 26 63 60 62 55 46 47 44 MASTER BALCONY 6: 1 2 3:123:12 HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. ATTIC SPACE 266 SF ATTIC SPACE 74 SF 5 5 SEE SHEET A-2.0 FOR ATTIC ACCESS HATCH SEE SHEET A-2.0 FOR ATTIC ACCESS HATCH F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " S.Y.S.B. (REQUIRED) 10' - 0" (EXISTING HISTORIC) 8' - 2 3/8" R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " 30 ' - 6 " 0 FT. SETBACK -EXSITING HISTORIC CONDITION (BARN) 6 15 ' - 0 " A-4.03 A-4.1 4 A-4.1 3 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 10' SETBACK BETWEEN BUILDINGS 10' - 0" 10' SETBACK BETWEEN BUILDINGS 10 ' - 0 " ROOM TAGROOM NAME 1 A-5.0 1 1 ? 1 1 A-4.0 1 1 1 1 ELEVATION / SECTION INDICATOR AD-1.0 1 CALL-OUT TAG 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG FIRE RATED CEILING ASS'Y -REF. DTLS. 7/AD-1.0 1-HR RATED INT CONDITION -REF. DTLS. 7/AD-1.0 1-HR RATED EXT CONDITION -REF. DTLS. 7/AD-1.0 STRUCTURAL STEEL COLUMN PER STRUCT., REF. STRUTC. DWGS, -PAINT AND SEAL AS REQUIRED –ARCH. TO APPV. COLOR FOR EXPOSED STEEL COLUMNS STRUCTURAL WOOD POST/COLUMN COLUMN -PER STRUCT., REF. STRUTC. DWGS, - PAINT, STAIN AND SEAL AS REQUIRED –ARCH. TO APPV. PAINT COLOR FOR EXPOSED WOOD POST/COLUMN, IF TO BE STAINED PROVIDE STAINED SAMPLE FOR ARCH, APPROVAL DOORS -AS SPECIFIED, SEE WINDOW SCHEDULE AND GENERAL NOTES ON SHEET A-7.0 - SHGC & U-FCTOR PER IECC & PLANS – SEE SHEET AD-2.0 FOR JAMB, HEAD AND THRESHOLD DETAILS, PROVIDE FLASHING AND WATERPROOFING AT DOOR OPENING PER THE DOOR MFGR. INSTRUCTION AND/OR FLASHING MFGR. INSTRUCTION PER SECTIONS R609.1 & R703.4 OF IRC WINDOW -AS SPECIFIED, SEE WINDOW SCHEDULE AND GENERAL NOTES ON SHEET A-7.0 -SHGC & U-FCTOR PER IECC & PLANS – SEE SHEET AD-2.0 FOR JAMB, HEAD AND SILL DETAILS, PROVIDE FLASHING AND WATERPROOFING AT WINDOW OPENING PER THE WINDOW MFGR. INSTRUCTION AND/OR FLASHING MFGR. INSTRUCTION PER SECTIONS R609.1 & R703.4 OF IRC REFRIGERATOR (REF) / FREEZER (FRZ) -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER AND WATER SUPPLY AS REQUIRED BUILT-IN APPLIANCE / DISHWASHER (DW) / TRASH COMPACTOR (TR)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , WATER SUPPLY & DRAINAGE PIPE AS REQUIRED CASEWORK, TALL CABINET -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER CASEWORK, BASE CABINET W/. COUNTERTOP -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER CASEWORK, UPPER CABINET/SHELVES -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER BUILT-IN CLOSET -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER ELEVATOR -PRIVATE RESIDENCE ELEVATOR IN COMPLIANCE W/. ASME A17.1/CSA B44 AS SELECTED PER PLANS, VERIFY W/. OWNER –PROVIDE POWER AS REQ'D. (CRC 321.1) RECESSED MAIN SERVICE PANEL -400 AMP MAX. (MAINTAIN 36" CLEAR FROM FACE OF PANEL TO ANY OBSTRUCTION) –GC TO COORDINATE W/. UTILITY COMPANY KITCHEN RANGE W/. EXHAUST HOOD -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – PROVIDE POWER AND GAS AS REQUIRED -30”MIN. VERTICAL CLEARANCE TO ANY COMBUSTIBLE MATERIAL ABV. COOKING TOP –EXHAUST HOOD TO HAVE EXHAUST RATE OF MIN. 100 CFM AND VENT TO OUTDOOR , HOOD DUCTS TO BE OF METAL WITH SMOOTH INTERIOR FINISH PER SECTION 505 OF IMC KITCHEN/BAR SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –SINK TO COMPLY W/. REQUIREMENT OF SECTION 422 OF IPC AND HAVE A MAX FLOW RATE OF 2.2 GPM @ 60 PSI PER SECTION 604.4 OF IPC –TRAP AND VENT FOR ISLAND SINK AND SIMILAR EQUIPMENT SHALL BE PER SECTION 916 OF IPC VANITY SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – LAVATORY TO HAVE 21”MIN. CLEAR SPACE IN FRONT OF IT.(IRC 307.1) W/. MAXIMUM FLOW RATE OF 2.2 GPM @ 60 PSI AND MIN. FLOW RATE OF 0.8 GPM @ 8 PSI PER SECTION 604.3 IPC WASHER (W) / DRYER (D) / STACKED (W/D)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , GAS, WATER SUPPLY & DRAINAGE AS REQUIRED -THE CLOTHES DRYERS VENT SHALL BE OF A RIGID METALLIC MATERIAL AND HAVE A BACKDRAFT DAMPER (IMC 504) DUCT LENGTH, CONNECTION AND TRANSITION SHALL BE PER SECTION 504.9.4 OF IMC. SEE WASHER & DRYER NOTES, REF. T-1.1. TOILET -WATER CLOSET SHALL BE IN COMPLIANCE OF SECTION 401 OF IPC AND HAS MAX EFFECTIVE FLUSH RATE OF 1.6 GAL. PER FLUSH (IPC 604.3). WATER CLOSETS CLR. TO BE 21”IN FRONT AND 15”FROM ITS CENTER TO ANY SIDE WALL OR OBSTRUCTION. (IPC 405.3.1 & IRC R307) FIREPLACE -FACTORY-BUILT DIRECT VENT GAS FIREPLACE W/. SEALED COMBUSTION - FACTORY-BUILT FIREPLACES, CHIMNEYS AND ALL OF THEIR COMPONENTS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1004.1) A/C CONDENSER / HEAT PUMP -TO BE IN COMPLIANCE OF SECTION 1403.1 & 1404.1 OF IRC AS SELECTED, VERIFY W/. OWNER -SIZE PER HVAC CONSULTANT –PROVIDE POWER AND SOUND DAMPENING PAD AS REQ’D. –INSTALL AND MAINTAIN REQUIRED CLEARANCES PER MFGR. INSTRUCTION LISTING AND LABELING (IRC M1307.1) FAU -PROVIDE GAS S.O., POWER, AND VENTING AS REQ'D. BY MFG'R. –INSTALL PER MFGR. INSTRUCTION ROOF/DECK DRAIN -PER CHAPTER 11 OF IPC -SECTOPM 1106 OF IPC –ROOF DRAIN SHALL HAVE DOMED STRAINER –REF. DETAIL 11/AD-1.0 OVERFLOW OR EMERGENCY DRAIN -PER CHAPTER 11 OF IPC -COPPER OR EQ., INSTALL PER MFGR. INSTRUC., SLOPED TOWARD IN-WALL DRAIN INLETS –SLOPE AND SIZE PER SECTION 1108 OF IPC –REF. DTL. 11/AD-1.0 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 SECOND LEVEL FLOOR PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-2.1 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 SECOND LEVEL FLOOR PLAN 1 PROPERTY LINE 2 FRONT YARD SETBACK 3 REAR YARD SETBACK 4 SIDE YARD SETBACK 5 BASE CABINET & COUNTER - BUILT-IN, FINISH AS SEL. 6 OUTLINE OF EXISTING HISTORIC FOOTPRINT BELOW 1 PROPERTY LINE 2 FRONT YARD SETBACK 3 REAR YARD SETBACK 4 SIDE YARD SETBACK 5 BASE CABINET & COUNTER - BUILT-IN, FINISH AS SEL. 6 OUTLINE OF EXISTING HISTORIC FOOTPRINT BELOW ANNOTATION LEGENDA KEYNOTESB NO. REVISION DATE _ _ UP UP D W _ FRZ._ TRDW FAU LAUNDRY WINE ROOM LOUNGE GYM ELEV. MECH. BEDROOM #4 BATH #4 BUNK ROOM BATH #5 W.I.C. PWDR. MECH. GAME ROOM MEDIA ROOM STAIRS #2 STAIRS #1 BAR 75 76 74 E 101 81 67 72 124 74 90 71 70 73 SAUNA BATH #8 LIGHT WELL 3'-0" x 3'-0" LIGHT WELL 3'-0" x 3'-0" SHWR. SHWR. SHWR. R @ 0' -6 29/32"21 R @ 0' -7 1/4"18 1 11 1 2 2 3 4 4 S.Y.S.B. (REQUIRED) 10' - 0" S.Y.S.B. (REQUIRED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " R. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " 2' - 8" SETBACK BETWEEN BUILDINGS 10' - 0" SETBACK BETWEEN BUILDINGS 10 ' - 0 " 2' - 8" S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " S.Y.S.B. (PROPOSED) 10' - 0" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " 16 ' - 1 0 7 / 8 " 10' - 1 1/2" 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 0 FT. SETBACK -EXSITING HISTORIC CONDITION (BARN) 3' - 0" 3' - 0 " 3' - 0" 3' - 0 " DU M B B E L L R A C K ROOM TAGROOM NAME 1 A-5.0 1 1 ? 1 1 A-4.0 1 1 1 1 ELEVATION / SECTION INDICATOR AD-1.0 1 CALL-OUT TAG 10.00'SPOT ELEVATION KEYNOTE TAG REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG FIRE RATED CEILING ASS'Y -REF. DTLS. 7/AD-1.0 1-HR RATED INT CONDITION -REF. DTLS. 7/AD-1.0 1-HR RATED EXT CONDITION -REF. DTLS. 7/AD-1.0 STRUCTURAL STEEL COLUMN PER STRUCT., REF. STRUTC. DWGS, -PAINT AND SEAL AS REQUIRED –ARCH. TO APPV. COLOR FOR EXPOSED STEEL COLUMNS STRUCTURAL WOOD POST/COLUMN COLUMN -PER STRUCT., REF. STRUTC. DWGS, - PAINT, STAIN AND SEAL AS REQUIRED –ARCH. TO APPV. PAINT COLOR FOR EXPOSED WOOD POST/COLUMN, IF TO BE STAINED PROVIDE STAINED SAMPLE FOR ARCH, APPROVAL DOORS -AS SPECIFIED, SEE WINDOW SCHEDULE AND GENERAL NOTES ON SHEET A-7.0 - SHGC & U-FCTOR PER IECC & PLANS – SEE SHEET AD-2.0 FOR JAMB, HEAD AND THRESHOLD DETAILS, PROVIDE FLASHING AND WATERPROOFING AT DOOR OPENING PER THE DOOR MFGR. INSTRUCTION AND/OR FLASHING MFGR. INSTRUCTION PER SECTIONS R609.1 & R703.4 OF IRC WINDOW -AS SPECIFIED, SEE WINDOW SCHEDULE AND GENERAL NOTES ON SHEET A-7.0 -SHGC & U-FCTOR PER IECC & PLANS – SEE SHEET AD-2.0 FOR JAMB, HEAD AND SILL DETAILS, PROVIDE FLASHING AND WATERPROOFING AT WINDOW OPENING PER THE WINDOW MFGR. INSTRUCTION AND/OR FLASHING MFGR. INSTRUCTION PER SECTIONS R609.1 & R703.4 OF IRC REFRIGERATOR (REF) / FREEZER (FRZ) -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER AND WATER SUPPLY AS REQUIRED BUILT-IN APPLIANCE / DISHWASHER (DW) / TRASH COMPACTOR (TR)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , WATER SUPPLY & DRAINAGE PIPE AS REQUIRED CASEWORK, TALL CABINET -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER CASEWORK, BASE CABINET W/. COUNTERTOP -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER CASEWORK, UPPER CABINET/SHELVES -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER BUILT-IN CLOSET -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER ELEVATOR -PRIVATE RESIDENCE ELEVATOR IN COMPLIANCE W/. ASME A17.1/CSA B44 AS SELECTED PER PLANS, VERIFY W/. OWNER –PROVIDE POWER AS REQ'D. (CRC 321.1) RECESSED MAIN SERVICE PANEL -400 AMP MAX. (MAINTAIN 36" CLEAR FROM FACE OF PANEL TO ANY OBSTRUCTION) –GC TO COORDINATE W/. UTILITY COMPANY KITCHEN RANGE W/. EXHAUST HOOD -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – PROVIDE POWER AND GAS AS REQUIRED -30”MIN. VERTICAL CLEARANCE TO ANY COMBUSTIBLE MATERIAL ABV. COOKING TOP –EXHAUST HOOD TO HAVE EXHAUST RATE OF MIN. 100 CFM AND VENT TO OUTDOOR , HOOD DUCTS TO BE OF METAL WITH SMOOTH INTERIOR FINISH PER SECTION 505 OF IMC KITCHEN/BAR SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –SINK TO COMPLY W/. REQUIREMENT OF SECTION 422 OF IPC AND HAVE A MAX FLOW RATE OF 2.2 GPM @ 60 PSI PER SECTION 604.4 OF IPC –TRAP AND VENT FOR ISLAND SINK AND SIMILAR EQUIPMENT SHALL BE PER SECTION 916 OF IPC VANITY SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – LAVATORY TO HAVE 21”MIN. CLEAR SPACE IN FRONT OF IT.(IRC 307.1) W/. MAXIMUM FLOW RATE OF 2.2 GPM @ 60 PSI AND MIN. FLOW RATE OF 0.8 GPM @ 8 PSI PER SECTION 604.3 IPC WASHER (W) / DRYER (D) / STACKED (W/D)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , GAS, WATER SUPPLY & DRAINAGE AS REQUIRED -THE CLOTHES DRYERS VENT SHALL BE OF A RIGID METALLIC MATERIAL AND HAVE A BACKDRAFT DAMPER (IMC 504) DUCT LENGTH, CONNECTION AND TRANSITION SHALL BE PER SECTION 504.9.4 OF IMC. SEE WASHER & DRYER NOTES, REF. T-1.1. TOILET -WATER CLOSET SHALL BE IN COMPLIANCE OF SECTION 401 OF IPC AND HAS MAX EFFECTIVE FLUSH RATE OF 1.6 GAL. PER FLUSH (IPC 604.3). WATER CLOSETS CLR. TO BE 21”IN FRONT AND 15”FROM ITS CENTER TO ANY SIDE WALL OR OBSTRUCTION. (IPC 405.3.1 & IRC R307) FIREPLACE -FACTORY-BUILT DIRECT VENT GAS FIREPLACE W/. SEALED COMBUSTION - FACTORY-BUILT FIREPLACES, CHIMNEYS AND ALL OF THEIR COMPONENTS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1004.1) A/C CONDENSER / HEAT PUMP -TO BE IN COMPLIANCE OF SECTION 1403.1 & 1404.1 OF IRC AS SELECTED, VERIFY W/. OWNER -SIZE PER HVAC CONSULTANT –PROVIDE POWER AND SOUND DAMPENING PAD AS REQ’D. –INSTALL AND MAINTAIN REQUIRED CLEARANCES PER MFGR. INSTRUCTION LISTING AND LABELING (IRC M1307.1) FAU -PROVIDE GAS S.O., POWER, AND VENTING AS REQ'D. BY MFG'R. –INSTALL PER MFGR. INSTRUCTION ROOF/DECK DRAIN -PER CHAPTER 11 OF IPC -SECTOPM 1106 OF IPC –ROOF DRAIN SHALL HAVE DOMED STRAINER –REF. DETAIL 11/AD-1.0 OVERFLOW OR EMERGENCY DRAIN -PER CHAPTER 11 OF IPC -COPPER OR EQ., INSTALL PER MFGR. INSTRUC., SLOPED TOWARD IN-WALL DRAIN INLETS –SLOPE AND SIZE PER SECTION 1108 OF IPC –REF. DTL. 11/AD-1.0 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 BASEMENT LEVEL FLOOR PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-2.2 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 BASEMENT LEVEL FLOOR PLAN 1 PROPERTY LINE 2 SIDE YARD SETBACK 3 FRONT YARD SETBACK 4 REAR YARD SETBACK ANNOTATION LEGENDA KEYNOTESB NO. REVISION DATE D W _ FAU DN DN UP _ UP _ DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. - CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. ROUGH FRAMING: ALL EXTERIOR WALLS TO BE FRAMED W/. 2X6 STUD MIN. U.N.O. USE 2X6 MINIMUM STUDS FOR PLUMBING WALLS SECOND AND THIRD FLOOR PLYWOOD TO BE 1-1/8" ENTIRE EXTERIOR TO BE SHEATHED WITH 1/2" PLYWOOD DOORS AND WINDOWS WILL TYPICALLY BE RECESSED FROM EXTERIOR WALL PLANE. VERIFY ALL ROUGH OPENING DIMENSIONS WITH DOOR AND WINDOW MFGR. ROUGH OPENING MAY NEED TO BE OVERSIZED TO ACCOUNT FOR ADDITIONAL FRAMING. SEE SHT. AD-2.0 FOR TYP. RECESSED CONDITIONS. GARAGE FLOOR: GARAGE FLOOR SURFACES SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIAL.THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN VEHICLE ENTRY DOORWAY. (R309.1) PLUMBING: 1. SUPPORT ALL WALL-HUNG FIXTURES WITH METAL SUPPORTING MEMBERS TO PREVENT ANY STRAIN TRANSMISSION TO THE CONNECTIONS. FRAMING AFFIXED SUPPORTS FOR OFF-THE-FLOOR WATER CLOSETS WITH CONCEALED TANKS SHALL COMPLY WITH ASME A112.6.2. SECURE FLUSH TANK AND SIMILAR APPURTENANCES WITH APPROVED NON-CORROSIVE SCREW OR BOLTS. (IRC P2702) 2. THE NET AREA OF THE SHOWER ENCLOSURE SHALL BE 900 SQ. INCHES (6.25 SQ. FT.) OR MORE IN THE CLEAR FLOOR AREA, AND SHALL ALSO BE CAPABLE OF ENCOMPASSING A 30-INCH DIAMETER CIRCLE. (IPC 421.4) 3. THE WATER HEATER BURNER AND BURNER-IGNITION DEVICE TO BE AT LEAST 18-INCHES ABOVE THE FLOOR, IF LOCATED IN A GARAGE AND IN ADJACENT SPACES THAT OPEN TO THE GARAGE. FOR WATER HEATER IN THE GARAGE OR OTHER AREAS SUBJECT TO MECHANICAL DAMAGE PROVIDE A PROTECTIVE BARRIER OR ELEVATE THE APPLIANCE TO BE OUT OF THE NORMAL PATH OF THE VEHICLE. (IRC P2801) 4. ANCHOR OR STRAP THE WATER HEATER(S) TO RESIST HORIZ. DISPLACEMENT DUE TO THE EARTHQUAKE. STRAPPING SHOULD BE AT THE UPPER AND LOWER ONE THIRD (1/3) POINTS OF THE APPLIANCE HEIGHT. MAINTAIN A MIN. 4-INCHES ABOVE THE CONTROLS WITH STRAPPING AT LOWER POINT. (IRC P2801.8) WOOD OR WOODBASED PRODUCTS NOTE: WOOD OR WOODBASE PRODUCT SHALL BE OF A NATURAL DURABLE OR PRESERVATIVE-TREADED WOOD IN ACCORDANCE WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND END USE IN THE FOLLOWING LOCATIONS: 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION. 2. WOOD FRAMING MEMBERS THAT REST ON CONCRETE OR MASONRY EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8 INCHES (203 MM) FROM THE EXPOSED GROUND. 3. SILLS AND SLEEPERS ON A CONCRETE OR MASONRY SLAB THAT IS IN DIRECT CONTACT WITH THE GROUND UNLESS SEPARATED FROM SUCH SLAB BY AN IMPERVIOUS MOISTURE BARRIER. 4. THE ENDS OF WOOD GIRDERS ENTERING EXTERIOR MASONRY OR CONCRETE WALLS HAVING CLEARANCES OF LESS THAN 1/2 INCH (12.7 MM) ON TOPS, SIDES AND ENDS. 5. WOOD SIDING, SHEATHING AND WALL FRAMING ON THE EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE WEATHER. 6. WOOD STRUCTURAL MEMBERS SUPPORTING MOISTURE-PERMEABLE FLOORS OR ROOFS THAT ARE EXPOSED TO THE WEATHER, SUCH AS CONCRETE OR MASONRY SLABS, UNLESS SEPARATED FROM SUCH FLOORS OR ROOFS BY AN IMPERVIOUS MOISTURE BARRIER. 7. WOOD FURRING STRIPS OR OTHER WOOD FRAMING MEMBERS ATTACHED DIRECTLY TO THE INTERIOR OF EXTERIOR MASONRY WALLS OR CONCRETE WALLS BELOW GRADE EXCEPT WHERE AN APPROVED VAPOR RETARDER IS APPLIED BETWEEN THE WALL AND THE FURRING STRIPS OR FRAMING MEMBERS. ROOM TAGROOM NAME 1 1 1 1 10.00' SPOT ELEVATION REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG STRUCTURAL STEEL COLUMN PER STRUCT., REF. STRUTC. DWGS, -PAINT AND SEAL AS REQUIRED –ARCH. TO APPV. COLOR FOR EXPOSED STEEL COLUMNS STRUCTURAL WOOD POST/COLUMN COLUMN -PER STRUCT., REF. STRUTC. DWGS, -PAINT, STAIN AND SEAL AS REQUIRED –ARCH. TO APPV. PAINT COLOR FOR EXPOSED WOOD POST/COLUMN, IF TO BE STAINED PROVIDE STAINED SAMPLE FOR ARCH, APPROVAL KITCHEN RANGE W/. EXHAUST HOOD -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – PROVIDE POWER AND GAS AS REQUIRED -30”MIN. VERTICAL CLEARANCE TO ANY COMBUSTIBLE MATERIAL ABV. COOKING TOP –EXHAUST HOOD TO HAVE EXHAUST RATE OF MIN. 100 CFM AND VENT TO OUTDOOR , HOOD DUCTS TO BE OF METAL WITH SMOOTH INTERIOR FINISH PER SECTION 505 OF IMC KITCHEN/BAR SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –SINK TO COMPLY W/. REQUIREMENT OF SECTION 422 OF IPC AND HAVE A MAX FLOW RATE OF 2.2 GPM @ 60 PSI PER SECTION 604.4 OF IPC –TRAP AND VENT FOR ISLAND SINK AND SIMILAR EQUIPMENT SHALL BE PER SECTION 916 OF IPC VANITY SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – LAVATORY TO HAVE 21”MIN. CLEAR SPACE IN FRONT OF IT.(IRC 307.1) W/. MAXIMUM FLOW RATE OF 2.2 GPM @ 60 PSI AND MIN. FLOW RATE OF 0.8 GPM @ 8 PSI PER SECTION 604.3 IPC WASHER (W) / DRYER (D) / STACKED (W/D)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , GAS, WATER SUPPLY & DRAINAGE AS REQUIRED -THE CLOTHES DRYERS VENT SHALL BE OF A RIGID METALLIC MATERIAL AND HAVE A BACKDRAFT DAMPER (IMC 504) DUCT LENGTH, CONNECTION AND TRANSITION SHALL BE PER SECTION 504.9.4 OF IMC. SEE WASHER & DRYER NOTES, REF. T-1.1. TOILET -WATER CLOSET SHALL BE IN COMPLIANCE OF SECTION 401 OF IPC AND HAS MAX EFFECTIVE FLUSH RATE OF 1.6 GAL. PER FLUSH (IPC 604.3). WATER CLOSETS CLR. TO BE 21”IN FRONT AND 15”FROM ITS CENTER TO ANY SIDE WALL OR OBSTRUCTION. (IPC 405.3.1 & IRC R307) FIREPLACE -FACTORY-BUILT DIRECT VENT GAS FIREPLACE W/. SEALED COMBUSTION - FACTORY-BUILT FIREPLACES, CHIMNEYS AND ALL OF THEIR COMPONENTS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1004.1) A/C CONDENSER / HEAT PUMP -TO BE IN COMPLIANCE OF SECTION 1403.1 & 1404.1 OF IRC AS SELECTED, VERIFY W/. OWNER -SIZE PER HVAC CONSULTANT –PROVIDE POWER AND SOUND DAMPENING PAD AS REQ’D. –INSTALL AND MAINTAIN REQUIRED CLEARANCES PER MFGR. INSTRUCTION LISTING AND LABELING (IRC M1307.1) FAU -PROVIDE GAS S.O., POWER, AND VENTING AS REQ'D. BY MFG'R. –INSTALL PER MFGR. INSTRUCTION RECESSED MAIN SERVICE PANEL -400 AMP MAX. (MAINTAIN 36" CLEAR FROM FACE OF PANEL TO ANY OBSTRUCTION) –GC TO COORDINATE W/. UTILITY COMPANY ROOF/DECK DRAIN -PER CHAPTER 11 OF IPC -SECTOPM 1106 OF IPC –ROOF DRAIN SHALL HAVE DOMED STRAINER –REF. DETAIL 11/AD-1.0 OVERFLOW OR EMERGENCY DRAIN -PER CHAPTER 11 OF IPC -COPPER OR EQ., INSTALL PER MFGR. INSTRUC., SLOPED TOWARD IN-WALL DRAIN INLETS –SLOPE AND SIZE PER SECTION 1108 OF IPC –REF. DTL. 11/AD-1.0 2X4 STUD WALL 2X6 STUD WALL 2X8 STUD WALL 2X10 STUD WALL EXT. POCKET DOOR WALL - TYP. 2X6 EXT. FRMG. AND 2X4 INTERIOR FRAMING W/. DOUBLE TOP PLATE AND SINGLE SILL PLATE U.N.O., MIN. AIR SPACE/DOOR POCKET TO BE VERIFIED W/. DOOR MFGR. - STUDS MIN. SPACING PER STRUCT. AND EXT. FINISH MFGR. INSTRUCTION AND/OR LISTING –SEE EXT. WALL DETAILS AND STRUCT. DWGS CONCRETE WALL -12”REINFORCED CAST IN PLACE CONCRETE WALL TYP. U.N.O. PER STRUCT., REF. STRCUTC. DWGS. –FOR BASEMENT/RETAINING CONCRETE WALL PROVIDE WATERPROOFING OR DAMPPROOFING AND DRAINAGE AS REQUIRED PER SECTION R406.1 & R406.2, REF. SOILS REPORT,WATERPROOFING & DAMPROOFING NOTES ON SHEET T-1.1 –EXPOSED SURFACES TO HAVE TROWELED SMOOTH FINISH WITH A LIGHT GRAY COLOR, PROVIDE SAMPLE FOR ARCH. APPROVAL SLAB/FRAMING DEPRESSION -SEE STRUCT. DWGS. FOR THE RECESSION DETAILS -FOR RECESSION SPECIFIC TO EQUIPMENT OR ASSEMBLY VERIFY THE REQUIRED RECESSION W/. MFGR. OR FABRICATOR –SHOWER RECESSION TO BE VERIFIED W/. I.D. SEE SHEET AD-2.0 FOR THE TYPICAL DEPRESSION OF DOORS AND WINDOWS, VERIFY ALL DEPRESSIONS W/. MFGR. STUDS MIN. SPACING PER STRUCT. AND EXT. FINISH MFGR. INSTRUCTION AND/OR LISTING –SEE EXT. WALL DETAILS AND STRUCT. DWGS A-4.1 A-4.0 A-4.12A-4.0 1 1 2 F. Y . S . B . 10 ' - 0 " R. Y . S . B . 10 ' - 0 " R. Y . S . B . 5' - 0 " S.Y.S.B. 10' - 0" S.Y.S.B. 10' - 0" 8' - 2 3/8"65' - 2 7/8"16' - 6 7/8" 3' - 5"7' - 2"15' - 6 7/8"3' - 5 1/2"12' - 10 1/2"22' - 9" 2' - 1 1/2"3' - 8 1/8"1' - 11"7' - 3 3/4"1' - 11"3' - 8 1/8"2' - 1 1/2"1' - 8"1' - 9"3' - 8 1/4"3' - 5 3/4"8' - 0 3/4"7' - 6 1/8"1' - 9"1' - 8 5/8" 3' - 3 7/8"3' - 3 7/8" 22 ' - 6 " 5' - 6 " 7' - 4 " 9' - 8 1 / 8 " OFFICE FOYER KITCHEN GREAT ROOM HALLWAY STAIR #2 ELEV. MUD ROOM 2-CAR GARAGE CARRIAGE HOUSEBATH #6 W.C. DIRTY KITCHEN PWDR. BATH #7 6' - 1 1 " 58 ' - 2 1 / 4 " 15 ' - 0 1 / 2 " 10 ' - 7 1 / 2 " 3' - 4 1 / 4 " 2' - 1 0 1 / 8 " 4' - 4 7 / 8 " 4' - 0 " 4' - 4 7 / 8 " 5' - 3 " 4' - 0 " 7' - 5 1 / 2 " 2' - 5 3 / 4 " 9' - 4 1 / 2 " 11 ' - 1 0 1 / 4 " 16 ' - 8 3 / 8 " 12 ' - 9 3 / 4 " 16 ' - 9 7 / 8 " 48' - 8 3/8" 3' - 5"22' - 7 7/8"22' - 7 1/2" 1' - 8"1' - 9"4' - 4 1/4"9' - 1 3/4"9' - 1 3/4"3' - 6 1/2" 14' - 11 1/4"9' - 5" 24' - 4 3/4" 28' - 0 3/4" 4' - 11 5/8"2' - 1 1/8"4' - 3 7/8"16' - 8 1/8" 16 ' - 3 7 / 8 " 8' - 1 7 / 8 " 8' - 1 7 / 8 " 28' - 0 3/4" 7' - 0 3/4"21' - 0" 16 ' - 3 7 / 8 " 11 ' - 0 3 / 4 " 8' - 1 7 / 8 " 4' - 6 1 / 8 " 3' - 7 3 / 4 " 17 ' - 4 1 / 4 " 5' - 5 3 / 4 " 11 ' - 1 0 3 / 8 " 5' - 7 3 / 4 " 6' - 2 3 / 4 " 9' - 4 3 / 4 " 6' - 8 5 / 8 " 10 ' - 6 1 / 4 " 7' - 5 3 / 8 " 4' - 1 0 3 / 8 " 7 1 / 2 " 30 ' - 2 " 5' - 6" 22' - 11 7/8" 1' - 9 5/8" CLR. 9' - 0"1' - 4 5/8" CLR. 9' - 0"1' - 9 5/8" 30 ' - 7 1 / 2 " 64 ' - 3 " 5' - 1 1 / 2 " 24 ' - 9 " 9' - 3 1 / 2 " 30 ' - 2 1 / 2 " 16 ' - 0 3 / 4 " 8' - 8 1 / 8 " 6 5 / 8 " 8' - 8 " 7/ 8 " 4' - 8 5 / 8 " 4' - 3 1 / 4 " 2' - 8 " 18 ' - 6 5 / 8 " A-4.03 A-4.1 4 A-4.1 3 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 SETBACK BETWEEN BUILDINGS 10' - 0" DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 FIRST LEVEL DIMENSION PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-2.3 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 FIRST LEVEL DIMENSION PLAN NO. REVISION DATE SITE PLAN NOTESA KEYNOTESC DN DN _ _ D W _ FAU A-4.1 A-4.0 A-4.12A-4.0 1 1 2 BEDROOM #2 BATH #2 BEROOM #3 BATH #3 W/D. MA. BATH MASTER BEDROOM W.C. W.I.C. W.I.C. ELEV. STAIR #1 STAIR #2 HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. 12 : 1 2 12 : 1 2 6:12 6:12 3:123:12 6: 1 2 12:12 12:12 12:1212:12 6: 1 2 6:12 6: 1 2 12 : 1 2 12:12 12 : 1 2 12 : 1 2 12:12 12:12 12 : 1 2 12 : 1 2 12:12 12:12 6:12 19' - 4" 3' - 4"15' - 11 7/8" 5' - 9 1/4"2' - 5 1/2"7' - 9 1/4" 41 ' - 1 7 / 8 " 6' - 1 1 / 2 " 6' - 8 3 / 8 " 4' - 8 5 / 8 " 11 ' - 8 1 / 2 " 11 ' - 1 1 " 1' - 1 " 2' - 3 " 2' - 3 " 1' - 1 3 / 8 " 20' - 1 3/8" 13' - 7 1/8"3' - 11 3/4"2' - 6 1/2" 41 ' - 1 7 / 8 " 13 ' - 3 3 / 8 " 7' - 9 7 / 8 " 7' - 8 1 / 4 " 7' - 7 1 / 2 " 4' - 9 " 1' - 7 " 2' - 3 " 2' - 3 " 1' - 6 1 / 2 " 1' - 6 7 / 8 " 2' - 3 " 2' - 3 " 7' - 2 1 / 2 " 22' - 9" 6' - 3 5/8"10' - 1 3/4"6' - 3 5/8" 40 ' - 1 5 / 8 " 24 ' - 9 1 / 2 " 9' - 9 1 / 2 " 5' - 6 3 / 4 " 10 3 / 8 " 8' - 5 " 6 1 / 8 " 11 ' - 1 0 1 / 2 " 12 ' - 1 1 " 40 ' - 1 5 / 8 " 24 ' - 9 1 / 2 " 9' - 9 1 / 2 " 1 1 / 2 " 4' - 1 0 5 / 8 " 6 5 / 8 " 34 ' - 7 " 5' - 6 3 / 4 " 28' - 3 3/8" 6' - 2 1/2"10' - 8 1/8"11' - 4 3/4" A-4.03 A-4.1 4 A-4.1 3 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 S.Y.S.B. (REQUIRED) 10' - 0" S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " S.Y.S.B. (PROPOSED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " S.Y.S.B. (REQUIRED & PROPOSED) 10' - 0" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " S.Y.S.B. (REQUIRED) 10' - 0" 10' SETBACK BETWEEN BUILDINGS 10' - 0" 10' SETBACK BETWEEN BUILDINGS 10 ' - 0 " DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. - CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. ROUGH FRAMING: ALL EXTERIOR WALLS TO BE FRAMED W/. 2X6 STUD MIN. U.N.O. USE 2X6 MINIMUM STUDS FOR PLUMBING WALLS SECOND AND THIRD FLOOR PLYWOOD TO BE 1-1/8" ENTIRE EXTERIOR TO BE SHEATHED WITH 1/2" PLYWOOD DOORS AND WINDOWS WILL TYPICALLY BE RECESSED FROM EXTERIOR WALL PLANE. VERIFY ALL ROUGH OPENING DIMENSIONS WITH DOOR AND WINDOW MFGR. ROUGH OPENING MAY NEED TO BE OVERSIZED TO ACCOUNT FOR ADDITIONAL FRAMING. SEE SHT. AD-2.0 FOR TYP. RECESSED CONDITIONS. GARAGE FLOOR: GARAGE FLOOR SURFACES SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIAL.THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN VEHICLE ENTRY DOORWAY. (R309.1) PLUMBING: 1. SUPPORT ALL WALL-HUNG FIXTURES WITH METAL SUPPORTING MEMBERS TO PREVENT ANY STRAIN TRANSMISSION TO THE CONNECTIONS. FRAMING AFFIXED SUPPORTS FOR OFF-THE-FLOOR WATER CLOSETS WITH CONCEALED TANKS SHALL COMPLY WITH ASME A112.6.2. SECURE FLUSH TANK AND SIMILAR APPURTENANCES WITH APPROVED NON-CORROSIVE SCREW OR BOLTS. (IRC P2702) 2. THE NET AREA OF THE SHOWER ENCLOSURE SHALL BE 900 SQ. INCHES (6.25 SQ. FT.) OR MORE IN THE CLEAR FLOOR AREA, AND SHALL ALSO BE CAPABLE OF ENCOMPASSING A 30-INCH DIAMETER CIRCLE. (IPC 421.4) 3. THE WATER HEATER BURNER AND BURNER-IGNITION DEVICE TO BE AT LEAST 18-INCHES ABOVE THE FLOOR, IF LOCATED IN A GARAGE AND IN ADJACENT SPACES THAT OPEN TO THE GARAGE. FOR WATER HEATER IN THE GARAGE OR OTHER AREAS SUBJECT TO MECHANICAL DAMAGE PROVIDE A PROTECTIVE BARRIER OR ELEVATE THE APPLIANCE TO BE OUT OF THE NORMAL PATH OF THE VEHICLE. (IRC P2801) 4. ANCHOR OR STRAP THE WATER HEATER(S) TO RESIST HORIZ. DISPLACEMENT DUE TO THE EARTHQUAKE. STRAPPING SHOULD BE AT THE UPPER AND LOWER ONE THIRD (1/3) POINTS OF THE APPLIANCE HEIGHT. MAINTAIN A MIN. 4-INCHES ABOVE THE CONTROLS WITH STRAPPING AT LOWER POINT. (IRC P2801.8) WOOD OR WOODBASED PRODUCTS NOTE: WOOD OR WOODBASE PRODUCT SHALL BE OF A NATURAL DURABLE OR PRESERVATIVE-TREADED WOOD IN ACCORDANCE WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND END USE IN THE FOLLOWING LOCATIONS: 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION. 2. WOOD FRAMING MEMBERS THAT REST ON CONCRETE OR MASONRY EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8 INCHES (203 MM) FROM THE EXPOSED GROUND. 3. SILLS AND SLEEPERS ON A CONCRETE OR MASONRY SLAB THAT IS IN DIRECT CONTACT WITH THE GROUND UNLESS SEPARATED FROM SUCH SLAB BY AN IMPERVIOUS MOISTURE BARRIER. 4. THE ENDS OF WOOD GIRDERS ENTERING EXTERIOR MASONRY OR CONCRETE WALLS HAVING CLEARANCES OF LESS THAN 1/2 INCH (12.7 MM) ON TOPS, SIDES AND ENDS. 5. WOOD SIDING, SHEATHING AND WALL FRAMING ON THE EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE WEATHER. 6. WOOD STRUCTURAL MEMBERS SUPPORTING MOISTURE-PERMEABLE FLOORS OR ROOFS THAT ARE EXPOSED TO THE WEATHER, SUCH AS CONCRETE OR MASONRY SLABS, UNLESS SEPARATED FROM SUCH FLOORS OR ROOFS BY AN IMPERVIOUS MOISTURE BARRIER. 7. WOOD FURRING STRIPS OR OTHER WOOD FRAMING MEMBERS ATTACHED DIRECTLY TO THE INTERIOR OF EXTERIOR MASONRY WALLS OR CONCRETE WALLS BELOW GRADE EXCEPT WHERE AN APPROVED VAPOR RETARDER IS APPLIED BETWEEN THE WALL AND THE FURRING STRIPS OR FRAMING MEMBERS. ROOM TAGROOM NAME 1 1 1 1 10.00' SPOT ELEVATION REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG STRUCTURAL STEEL COLUMN PER STRUCT., REF. STRUTC. DWGS, -PAINT AND SEAL AS REQUIRED –ARCH. TO APPV. COLOR FOR EXPOSED STEEL COLUMNS STRUCTURAL WOOD POST/COLUMN COLUMN -PER STRUCT., REF. STRUTC. DWGS, -PAINT, STAIN AND SEAL AS REQUIRED –ARCH. TO APPV. PAINT COLOR FOR EXPOSED WOOD POST/COLUMN, IF TO BE STAINED PROVIDE STAINED SAMPLE FOR ARCH, APPROVAL KITCHEN RANGE W/. EXHAUST HOOD -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – PROVIDE POWER AND GAS AS REQUIRED -30”MIN. VERTICAL CLEARANCE TO ANY COMBUSTIBLE MATERIAL ABV. COOKING TOP –EXHAUST HOOD TO HAVE EXHAUST RATE OF MIN. 100 CFM AND VENT TO OUTDOOR , HOOD DUCTS TO BE OF METAL WITH SMOOTH INTERIOR FINISH PER SECTION 505 OF IMC KITCHEN/BAR SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –SINK TO COMPLY W/. REQUIREMENT OF SECTION 422 OF IPC AND HAVE A MAX FLOW RATE OF 2.2 GPM @ 60 PSI PER SECTION 604.4 OF IPC –TRAP AND VENT FOR ISLAND SINK AND SIMILAR EQUIPMENT SHALL BE PER SECTION 916 OF IPC VANITY SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – LAVATORY TO HAVE 21”MIN. CLEAR SPACE IN FRONT OF IT.(IRC 307.1) W/. MAXIMUM FLOW RATE OF 2.2 GPM @ 60 PSI AND MIN. FLOW RATE OF 0.8 GPM @ 8 PSI PER SECTION 604.3 IPC WASHER (W) / DRYER (D) / STACKED (W/D)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , GAS, WATER SUPPLY & DRAINAGE AS REQUIRED -THE CLOTHES DRYERS VENT SHALL BE OF A RIGID METALLIC MATERIAL AND HAVE A BACKDRAFT DAMPER (IMC 504) DUCT LENGTH, CONNECTION AND TRANSITION SHALL BE PER SECTION 504.9.4 OF IMC. SEE WASHER & DRYER NOTES, REF. T-1.1. TOILET -WATER CLOSET SHALL BE IN COMPLIANCE OF SECTION 401 OF IPC AND HAS MAX EFFECTIVE FLUSH RATE OF 1.6 GAL. PER FLUSH (IPC 604.3). WATER CLOSETS CLR. TO BE 21”IN FRONT AND 15”FROM ITS CENTER TO ANY SIDE WALL OR OBSTRUCTION. (IPC 405.3.1 & IRC R307) FIREPLACE -FACTORY-BUILT DIRECT VENT GAS FIREPLACE W/. SEALED COMBUSTION - FACTORY-BUILT FIREPLACES, CHIMNEYS AND ALL OF THEIR COMPONENTS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1004.1) A/C CONDENSER / HEAT PUMP -TO BE IN COMPLIANCE OF SECTION 1403.1 & 1404.1 OF IRC AS SELECTED, VERIFY W/. OWNER -SIZE PER HVAC CONSULTANT –PROVIDE POWER AND SOUND DAMPENING PAD AS REQ’D. –INSTALL AND MAINTAIN REQUIRED CLEARANCES PER MFGR. INSTRUCTION LISTING AND LABELING (IRC M1307.1) FAU -PROVIDE GAS S.O., POWER, AND VENTING AS REQ'D. BY MFG'R. –INSTALL PER MFGR. INSTRUCTION RECESSED MAIN SERVICE PANEL -400 AMP MAX. (MAINTAIN 36" CLEAR FROM FACE OF PANEL TO ANY OBSTRUCTION) –GC TO COORDINATE W/. UTILITY COMPANY ROOF/DECK DRAIN -PER CHAPTER 11 OF IPC -SECTOPM 1106 OF IPC –ROOF DRAIN SHALL HAVE DOMED STRAINER –REF. DETAIL 11/AD-1.0 OVERFLOW OR EMERGENCY DRAIN -PER CHAPTER 11 OF IPC -COPPER OR EQ., INSTALL PER MFGR. INSTRUC., SLOPED TOWARD IN-WALL DRAIN INLETS –SLOPE AND SIZE PER SECTION 1108 OF IPC –REF. DTL. 11/AD-1.0 2X4 STUD WALL 2X6 STUD WALL 2X8 STUD WALL 2X10 STUD WALL EXT. POCKET DOOR WALL - TYP. 2X6 EXT. FRMG. AND 2X4 INTERIOR FRAMING W/. DOUBLE TOP PLATE AND SINGLE SILL PLATE U.N.O., MIN. AIR SPACE/DOOR POCKET TO BE VERIFIED W/. DOOR MFGR. - STUDS MIN. SPACING PER STRUCT. AND EXT. FINISH MFGR. INSTRUCTION AND/OR LISTING –SEE EXT. WALL DETAILS AND STRUCT. DWGS CONCRETE WALL -12”REINFORCED CAST IN PLACE CONCRETE WALL TYP. U.N.O. PER STRUCT., REF. STRCUTC. DWGS. –FOR BASEMENT/RETAINING CONCRETE WALL PROVIDE WATERPROOFING OR DAMPPROOFING AND DRAINAGE AS REQUIRED PER SECTION R406.1 & R406.2, REF. SOILS REPORT,WATERPROOFING & DAMPROOFING NOTES ON SHEET T-1.1 –EXPOSED SURFACES TO HAVE TROWELED SMOOTH FINISH WITH A LIGHT GRAY COLOR, PROVIDE SAMPLE FOR ARCH. APPROVAL SLAB/FRAMING DEPRESSION -SEE STRUCT. DWGS. FOR THE RECESSION DETAILS -FOR RECESSION SPECIFIC TO EQUIPMENT OR ASSEMBLY VERIFY THE REQUIRED RECESSION W/. MFGR. OR FABRICATOR –SHOWER RECESSION TO BE VERIFIED W/. I.D. SEE SHEET AD-2.0 FOR THE TYPICAL DEPRESSION OF DOORS AND WINDOWS, VERIFY ALL DEPRESSIONS W/. MFGR. STUDS MIN. SPACING PER STRUCT. AND EXT. FINISH MFGR. INSTRUCTION AND/OR LISTING –SEE EXT. WALL DETAILS AND STRUCT. DWGS DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 SECOND LEVEL DIMENSION PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-2.4 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 SECOND LEVEL DIMENSION PLAN NO. REVISION DATE SITE PLAN NOTESA KEYNOTESC _ _ UP D W _ FAU 39 ' - 7 1 / 2 " 1' - 0 5 / 8 " 8' - 4 3 / 4 " 6' - 1 1 3 / 4 " 7' - 0 5 / 8 " 15 ' - 1 1 / 4 " 1' - 0 5 / 8 " 26' - 11 1/2" 15' - 7 7/8"1' - 0 5/8"24' - 10 1/4"1' - 0 5/8" 71 ' - 1 1 1 / 4 " 1' - 0 5 / 8 " 12 ' - 1 1 1 / 8 " 33 ' - 1 0 1 / 4 " 6' - 0 3 / 4 " 16 ' - 1 1 7 / 8 " 1' - 0 5 / 8 " 68' - 3 5/8" 1' - 0 5/8"5' - 7 3/4"15' - 0"4' - 1"1' - 0 5/8" 25' - 9 3/8" 1' - 0 5/8" LAUNDRY WINE ROOM LOUNGE BUNK ROOM ?PWDR. BATH #5 GYM SAUNA BATH #8 BEDROOM #4 BATH #4 W.I.C. ELEV. MECH. BATH #4 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 S.Y.S.B. (REQUIRED) 10' - 0" S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " S.Y.S.B. (PROPOSED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " S.Y.S.B. (REQUIRED) 10' - 0" 10' SETBACK BETWEEN BUILDINGS 10' SETBACK BETWEEN BUILDINGS DIMENSION NOTE: ALL DIMENSIONS ARE TO FACE OF SHEATHING (EXT. WALLS) OR FACE OF STRUCTURE (F.O.S.) TYP. U.N.O. ROUNDED TO THE NEAREST 1/8" AND INTERIOR PARTITIONS ARE DIMENSIONED FROM FACE OF STRUCTURE TO FACE OF STRUCTURE (F.O.S.) U.N.O. - CONTACT ARCHITECT IN WRITING FOR ANY CLARIFICATION OF NOTED DIMENSIONS, DO NOT SCALE PLANS. ROUGH FRAMING: ALL EXTERIOR WALLS TO BE FRAMED W/. 2X6 STUD MIN. U.N.O. USE 2X6 MINIMUM STUDS FOR PLUMBING WALLS SECOND AND THIRD FLOOR PLYWOOD TO BE 1-1/8" ENTIRE EXTERIOR TO BE SHEATHED WITH 1/2" PLYWOOD DOORS AND WINDOWS WILL TYPICALLY BE RECESSED FROM EXTERIOR WALL PLANE. VERIFY ALL ROUGH OPENING DIMENSIONS WITH DOOR AND WINDOW MFGR. ROUGH OPENING MAY NEED TO BE OVERSIZED TO ACCOUNT FOR ADDITIONAL FRAMING. SEE SHT. AD-2.0 FOR TYP. RECESSED CONDITIONS. GARAGE FLOOR: GARAGE FLOOR SURFACES SHALL BE OF APPROVED NONCOMBUSTIBLE MATERIAL.THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN VEHICLE ENTRY DOORWAY. (R309.1) PLUMBING: 1. SUPPORT ALL WALL-HUNG FIXTURES WITH METAL SUPPORTING MEMBERS TO PREVENT ANY STRAIN TRANSMISSION TO THE CONNECTIONS. FRAMING AFFIXED SUPPORTS FOR OFF-THE-FLOOR WATER CLOSETS WITH CONCEALED TANKS SHALL COMPLY WITH ASME A112.6.2. SECURE FLUSH TANK AND SIMILAR APPURTENANCES WITH APPROVED NON-CORROSIVE SCREW OR BOLTS. (IRC P2702) 2. THE NET AREA OF THE SHOWER ENCLOSURE SHALL BE 900 SQ. INCHES (6.25 SQ. FT.) OR MORE IN THE CLEAR FLOOR AREA, AND SHALL ALSO BE CAPABLE OF ENCOMPASSING A 30-INCH DIAMETER CIRCLE. (IPC 421.4) 3. THE WATER HEATER BURNER AND BURNER-IGNITION DEVICE TO BE AT LEAST 18-INCHES ABOVE THE FLOOR, IF LOCATED IN A GARAGE AND IN ADJACENT SPACES THAT OPEN TO THE GARAGE. FOR WATER HEATER IN THE GARAGE OR OTHER AREAS SUBJECT TO MECHANICAL DAMAGE PROVIDE A PROTECTIVE BARRIER OR ELEVATE THE APPLIANCE TO BE OUT OF THE NORMAL PATH OF THE VEHICLE. (IRC P2801) 4. ANCHOR OR STRAP THE WATER HEATER(S) TO RESIST HORIZ. DISPLACEMENT DUE TO THE EARTHQUAKE. STRAPPING SHOULD BE AT THE UPPER AND LOWER ONE THIRD (1/3) POINTS OF THE APPLIANCE HEIGHT. MAINTAIN A MIN. 4-INCHES ABOVE THE CONTROLS WITH STRAPPING AT LOWER POINT. (IRC P2801.8) WOOD OR WOODBASED PRODUCTS NOTE: WOOD OR WOODBASE PRODUCT SHALL BE OF A NATURAL DURABLE OR PRESERVATIVE-TREADED WOOD IN ACCORDANCE WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND END USE IN THE FOLLOWING LOCATIONS: 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION. 2. WOOD FRAMING MEMBERS THAT REST ON CONCRETE OR MASONRY EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8 INCHES (203 MM) FROM THE EXPOSED GROUND. 3. SILLS AND SLEEPERS ON A CONCRETE OR MASONRY SLAB THAT IS IN DIRECT CONTACT WITH THE GROUND UNLESS SEPARATED FROM SUCH SLAB BY AN IMPERVIOUS MOISTURE BARRIER. 4. THE ENDS OF WOOD GIRDERS ENTERING EXTERIOR MASONRY OR CONCRETE WALLS HAVING CLEARANCES OF LESS THAN 1/2 INCH (12.7 MM) ON TOPS, SIDES AND ENDS. 5. WOOD SIDING, SHEATHING AND WALL FRAMING ON THE EXTERIOR OF A BUILDING HAVING A CLEARANCE OF LESS THAN 6 INCHES (152 MM) FROM THE GROUND OR LESS THAN 2 INCHES (51 MM) MEASURED VERTICALLY FROM CONCRETE STEPS, PORCH SLABS, PATIO SLABS AND SIMILAR HORIZONTAL SURFACES EXPOSED TO THE WEATHER. 6. WOOD STRUCTURAL MEMBERS SUPPORTING MOISTURE-PERMEABLE FLOORS OR ROOFS THAT ARE EXPOSED TO THE WEATHER, SUCH AS CONCRETE OR MASONRY SLABS, UNLESS SEPARATED FROM SUCH FLOORS OR ROOFS BY AN IMPERVIOUS MOISTURE BARRIER. 7. WOOD FURRING STRIPS OR OTHER WOOD FRAMING MEMBERS ATTACHED DIRECTLY TO THE INTERIOR OF EXTERIOR MASONRY WALLS OR CONCRETE WALLS BELOW GRADE EXCEPT WHERE AN APPROVED VAPOR RETARDER IS APPLIED BETWEEN THE WALL AND THE FURRING STRIPS OR FRAMING MEMBERS. ROOM TAGROOM NAME 1 1 1 1 10.00' SPOT ELEVATION REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG STRUCTURAL STEEL COLUMN PER STRUCT., REF. STRUTC. DWGS, -PAINT AND SEAL AS REQUIRED –ARCH. TO APPV. COLOR FOR EXPOSED STEEL COLUMNS STRUCTURAL WOOD POST/COLUMN COLUMN -PER STRUCT., REF. STRUTC. DWGS, -PAINT, STAIN AND SEAL AS REQUIRED –ARCH. TO APPV. PAINT COLOR FOR EXPOSED WOOD POST/COLUMN, IF TO BE STAINED PROVIDE STAINED SAMPLE FOR ARCH, APPROVAL KITCHEN RANGE W/. EXHAUST HOOD -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – PROVIDE POWER AND GAS AS REQUIRED -30”MIN. VERTICAL CLEARANCE TO ANY COMBUSTIBLE MATERIAL ABV. COOKING TOP –EXHAUST HOOD TO HAVE EXHAUST RATE OF MIN. 100 CFM AND VENT TO OUTDOOR , HOOD DUCTS TO BE OF METAL WITH SMOOTH INTERIOR FINISH PER SECTION 505 OF IMC KITCHEN/BAR SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –SINK TO COMPLY W/. REQUIREMENT OF SECTION 422 OF IPC AND HAVE A MAX FLOW RATE OF 2.2 GPM @ 60 PSI PER SECTION 604.4 OF IPC –TRAP AND VENT FOR ISLAND SINK AND SIMILAR EQUIPMENT SHALL BE PER SECTION 916 OF IPC VANITY SINK -AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER – LAVATORY TO HAVE 21”MIN. CLEAR SPACE IN FRONT OF IT.(IRC 307.1) W/. MAXIMUM FLOW RATE OF 2.2 GPM @ 60 PSI AND MIN. FLOW RATE OF 0.8 GPM @ 8 PSI PER SECTION 604.3 IPC WASHER (W) / DRYER (D) / STACKED (W/D)-AS SELECTED PER I.D., VERIFY W/. I.D. & OWNER –PROVIDE POWER , GAS, WATER SUPPLY & DRAINAGE AS REQUIRED -THE CLOTHES DRYERS VENT SHALL BE OF A RIGID METALLIC MATERIAL AND HAVE A BACKDRAFT DAMPER (IMC 504) DUCT LENGTH, CONNECTION AND TRANSITION SHALL BE PER SECTION 504.9.4 OF IMC. SEE WASHER & DRYER NOTES, REF. T-1.1. TOILET -WATER CLOSET SHALL BE IN COMPLIANCE OF SECTION 401 OF IPC AND HAS MAX EFFECTIVE FLUSH RATE OF 1.6 GAL. PER FLUSH (IPC 604.3). WATER CLOSETS CLR. TO BE 21”IN FRONT AND 15”FROM ITS CENTER TO ANY SIDE WALL OR OBSTRUCTION. (IPC 405.3.1 & IRC R307) FIREPLACE -FACTORY-BUILT DIRECT VENT GAS FIREPLACE W/. SEALED COMBUSTION - FACTORY-BUILT FIREPLACES, CHIMNEYS AND ALL OF THEIR COMPONENTS SHALL BE LISTED AND INSTALLED IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. (IRC R1004.1) A/C CONDENSER / HEAT PUMP -TO BE IN COMPLIANCE OF SECTION 1403.1 & 1404.1 OF IRC AS SELECTED, VERIFY W/. OWNER -SIZE PER HVAC CONSULTANT –PROVIDE POWER AND SOUND DAMPENING PAD AS REQ’D. –INSTALL AND MAINTAIN REQUIRED CLEARANCES PER MFGR. INSTRUCTION LISTING AND LABELING (IRC M1307.1) FAU -PROVIDE GAS S.O., POWER, AND VENTING AS REQ'D. BY MFG'R. –INSTALL PER MFGR. INSTRUCTION RECESSED MAIN SERVICE PANEL -400 AMP MAX. (MAINTAIN 36" CLEAR FROM FACE OF PANEL TO ANY OBSTRUCTION) –GC TO COORDINATE W/. UTILITY COMPANY ROOF/DECK DRAIN -PER CHAPTER 11 OF IPC -SECTOPM 1106 OF IPC –ROOF DRAIN SHALL HAVE DOMED STRAINER –REF. DETAIL 11/AD-1.0 OVERFLOW OR EMERGENCY DRAIN -PER CHAPTER 11 OF IPC -COPPER OR EQ., INSTALL PER MFGR. INSTRUC., SLOPED TOWARD IN-WALL DRAIN INLETS –SLOPE AND SIZE PER SECTION 1108 OF IPC –REF. DTL. 11/AD-1.0 2X4 STUD WALL 2X6 STUD WALL 2X8 STUD WALL 2X10 STUD WALL EXT. POCKET DOOR WALL - TYP. 2X6 EXT. FRMG. AND 2X4 INTERIOR FRAMING W/. DOUBLE TOP PLATE AND SINGLE SILL PLATE U.N.O., MIN. AIR SPACE/DOOR POCKET TO BE VERIFIED W/. DOOR MFGR. - STUDS MIN. SPACING PER STRUCT. AND EXT. FINISH MFGR. INSTRUCTION AND/OR LISTING –SEE EXT. WALL DETAILS AND STRUCT. DWGS CONCRETE WALL -12”REINFORCED CAST IN PLACE CONCRETE WALL TYP. U.N.O. PER STRUCT., REF. STRCUTC. DWGS. –FOR BASEMENT/RETAINING CONCRETE WALL PROVIDE WATERPROOFING OR DAMPPROOFING AND DRAINAGE AS REQUIRED PER SECTION R406.1 & R406.2, REF. SOILS REPORT,WATERPROOFING & DAMPROOFING NOTES ON SHEET T-1.1 –EXPOSED SURFACES TO HAVE TROWELED SMOOTH FINISH WITH A LIGHT GRAY COLOR, PROVIDE SAMPLE FOR ARCH. APPROVAL SLAB/FRAMING DEPRESSION -SEE STRUCT. DWGS. FOR THE RECESSION DETAILS -FOR RECESSION SPECIFIC TO EQUIPMENT OR ASSEMBLY VERIFY THE REQUIRED RECESSION W/. MFGR. OR FABRICATOR –SHOWER RECESSION TO BE VERIFIED W/. I.D. SEE SHEET AD-2.0 FOR THE TYPICAL DEPRESSION OF DOORS AND WINDOWS, VERIFY ALL DEPRESSIONS W/. MFGR. STUDS MIN. SPACING PER STRUCT. AND EXT. FINISH MFGR. INSTRUCTION AND/OR LISTING –SEE EXT. WALL DETAILS AND STRUCT. DWGS DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 BASEMENT LEVEL DIMENSION PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-2.5 TBD RYAN McDANIEL, AIA PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 BASEMENT LEVEL DIMENSION PLAN NO. REVISION DATE SITE PLAN NOTESA KEYNOTESC A-4.1 A-4.0 A-4.12A-4.0 1 1 2 6:12 6: 1 2 12 : 1 2 12 : 1 2 6: 1 2 12:12 12:12 12:1212:12 12 : 1 2 12 : 1 2 4:12 4:1212:1212:12 12 : 1 2 12:12 12:1212:12 12 : 1 2 12 : 1 2 12:1212:12 6:12 6: 1 2 3:123:12 7:12 7:12 12:12 12:12 6:12 6:12 6:12 6:12 12 : 1 2 12 : 1 2 12 : 1 2 12 : 1 2 2% MIN. 2% MIN. 2% M I N . 2% M I N . HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. 12:12 1 2 3 1 3 1414 5 5 5 5 5 6 6 6 66 6 6 66 6 6 6 6 66 7 7 7 CHIMNEY TO BE WRAPPED IN ACM PANEL PARAPET WALL TO BE WRAPPED IN ACM PANEL PARAPET WALL TO BE WRAPPED IN ACM PANEL HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. 7919.57' 7919.57' 7921.27' 7914.60' 7917.50' 7917.45' 7921.70' 7921.92' 7922.34' 7922.34' 7922.41' 7906.65' 7916.91' 7916.91' 7916.91'7910.83' 7910.83' 7910.83' 7913.53'7913.53' 7917.50' 7903.52' 7903.52' A-4.03 A-4.1 4 A-4.1 3 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 S.Y.S.B. (REQUIRED) 10' - 0" S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " S.Y.S.B. (PROPOSED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " S.Y.S.B. (REQUIRED & PROPOSED) 10' - 0" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " S.Y.S.B. (REQUIRED) 10' - 0" 10' SETBACK BETWEEN BUILDINGS 10 ' - 0 " 10' SETBACK BETWEEN BUILDINGS 10' - 0" DIMENSION NOTE: ALL DIMS. ARE TO FACE OF STUD (F.O.S.) OR FACE OF SHT'G. (F.O.S.) TYP. U.N.O. EAVE DIMS. ARE FROM FACE OF SHT'G. TO FACE OF FINISH FASCIA ENLOSED ATTIC AND ENCLOSED RAFTER SPACES VENTING NOTES: 1. ENCLOSED ATTIC AND ENCLOSED RAFTER SPACES SHALL HAVE CROSS VENTILATION BY VENTILATION OPENING PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW UNLESS THEY MEET THE REQUIREMENT OF SECTION R806.5 FOR UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES. VENTILATION OPENING SHALL HAVE THE LEAST DIMENSION OF 1/16”MIN. AND 1/4”MAX OTHERWISE THE OPENING SHALL HAVE THE CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE CLOTH, PERFORATED VINYL OR SIMILAR MATERIAL WITH OPENINGS HAVE A LEAST DIMENSION OF 1/16”MIN. AND 1/4”MAX. OPENING IN ROOF FRAMING MEMBERS SHALL BE PER THE REQUIREMENT OF SECTION R802.7. REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO THE OUTSIDE AIR AND SHALL BE PROTECTED TO PREVENT THE ENTRY OF BIRDS, RODENTS, SNAKES AND OTHER SIMILAR CREATURES. (R806.1) 2. THE MINIMUM NET FREE VENTILATING AREA SHOULD BE 1/150 OF THE AREA OF THE VENTED SPACE, EXCEPT FOR THE PROJECT LOCATED IN CLIMATE ZONE 14 OR 16 WITH A CLASS I OR II VAPOR RETARDER AT THE WARM-IN-WINTER SIDE OF THE CEILING AND WHERE MIN. 40% AND MAX 50% OF THE REQUIRED VENTILATION PROVIDED IN THE UPPER PORTION OF THE ATTIC OR RAFTER SPACE PER SECTION R806.2 THEN THE MINIMUM NET FREE VENTILATING AREA CAN BE 1/300 OF THE VENTED SPACE. (R802.2) 3. PROVIDE 1”SPACE BETWEEN THE INSULATION AND THE ROOF SHEATHING WHERE EAVE OR CORNICE VENTS PROVIDE BLOCKING, BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW OF AIR. (R806.3) 4. INSTALL VENTILATOR PER MANUFACTURER INSTRUCTION. INSTALL VENTILATOR IN ROOF PER SECTION R903 AND VENTILATOR IN WALL ASSEMBLIES PER SECTION R703.1. 5. FOR THE ATTIC WITH VERTICAL HEIGHT GREATER THAN OR EQUAL TO 30”(VERTICAL HEIGHT MEASURED FROM THE TOP OF CEILING JOIST TO THE BOTTOM OF THE ROOF RAFTERS) WITHIN 30S.F. MIN. PROVIDE THE OPENING WITH ROUGH-FRAMED OPENING OF NOT LESS THAN 22”X30”WHICH SHOULD BE LOCATED IN HALLWAY OR OTHER LOCATION WITH READY ACCESS. IF THE ACCESS LOCATED IN THE WALL THEN THE WIDTH SHOULD BE 22”AND HEIGHT SHOULD BE 30”MIN. IF LOCATED IN CEILING THEN THE MIN. UNOBSTRUCTED HEADROOM IN THE ATTIC SHOULD BE 30”FROM THE BOTTOM OF CEILING JOIST AT SOME POINT. ROOF DRAINAGE: IF THE PROJECT LOCATED IN THE AREA WITH EXPANSIVE OR COLLAPSIBLE SOILS, WATER RUNOFF FROM ROOFS OF ALL DWELLINGS SHALL BE DISCHARGED TO THE GROUND SURFACE NOT LESS THAN 5 FEET FROM FOUNDATION WALLS OR TO AN APPROVED DRAINAGE SYSTEM. (R801.3) -REF.CIVIL DWGS FOR STORM WATER MANAGMENT AND SYSTEM. WEATHER PROTECTION: 1. ROOF DECKS SHALL BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN ACCORDANCE WITH THE CHAPTER 9 OF THE CURRENT IRC. ROOF ASSEMBLIES SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE CHAPTER 9 OF IRC AND THE APPROVED MANUFACTURER’S INSTRUCTIONS SUCH THAT THE ROOF ASSEMBLY SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. (R903.1) 2. PROVIDE AND INSTALL FLASHING TO PREVENT ENTRY OF MOISTURE TO WALL AND ROOF ASSEMBLIES THRU THE JOINTS IN COPINGS, PERMEABLE MATERIAL, AND AT INTERSECTION WITH PARAPET WALLS AND OTHER PENETRATION THRU ROOF. (R903.2) 3. FLASHINGS SHALL BE INSTALLED AT WALL AND ROOF INTERSECTIONS, WHEREVER THERE IS A CHANGE IN ROOF SLOPE OR DIRECTION AND AROUND ROOF OPENINGS. A FLASHING SHALL BE INSTALLED TO DIVERT THE WATER AWAY FROM WHERE THE EAVE OF A SLOPED ROOF INTERSECTS A VERTICAL SIDEWALL. WHERE FLASHING IS OF METAL, THE METAL SHALL BE CORROSION RESISTANT WITH A THICKNESS OF NOT LESS THAN 0.019 INCH (0.5 MM) (NO. 26 GALVANIZED SHEET). (R903.2.1) 4. A CRICKET OR SADDLE SHALL BE INSTALLED ON THE RIDGE SIDE OF ANY CHIMNEY OR PENETRATION MORE THAN 30 INCHES (762 MM) WIDE AS MEASURED PERPENDICULAR TO THE SLOPE. CRICKET OR SADDLE COVERINGS SHALL BE SHEET METAL OR OF THE SAME MATERIAL AS THE ROOF COVERING. EXCEPT FOR UNIT SKYLIGHTS INSTALLED IN ACCORDANCE WITH HYPERLINK "HTTPS://CODES.ICCSAFE.ORG/LOOKUP/CRC2019P1_PT03_CH03_SECR308.6" SECTION R308.6 AND FLASHED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS SHALL BE PERMITTED TO BE INSTALLED WITHOUT A CRICKET OR SADDLE. (R903.2) 5. PARAPET WALLS SHALL BE PROPERLY COPED WITH NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A WIDTH NOT LESS THAN THE THICKNESS OF THE PARAPET WALL. (R903.3) 6. UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE ROOF. IF WATER CAN BE ENTRAPPED WITHIN THE ROOF AREA THEN SECONDARY EMERGENCY OVERFLOW ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED PER SECTION R903.4.1. (R903.4) 7. SNOW STOPS REQUIRED AT ALL ROOF PITCHES THAT SHED ONTO POTENTIALLY OCCUPIED AREAS PER R901 AS AMENDED BY CITY OF ASPEN MISC. NOTES: 1. INSTALL ROOF PER ROOFING MFG'R. SPECS & INSTALLATION GUIDELINE 2. ARCH. TO APPV. SIZE, COLOR & PROFILE OF EAVE & RAKE COMPONENTS. G.C. TO PROVIDE MOCK-UPS. 3. UNVENTED ENCLOSED RAFTER ASSEMBLY: NO INTERIOR CLASS I VAPOR RETARDER SHALL BE INSTALLED ON THE CEILING SIDE (ATTIC FLOOR) OF THE UNVENTED ATTIC ASSEMBLY OR ON THE CEILING SIDE OF THE UNVENTED ENCLOSED ROOF FRAMING ASSEMBLY. 4. REF. WOOD OR WOODBASE PRODUCT NOTES ON FLOOR PLANS DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 ROOF PLAN KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-3.0 TBD RYAN McDANIEL, AIA 1 PROPERTY LINE 2 FRONT YARD SETBACK 3 REAR YARD SETBACK 4 SIDE YARD SETBACK 5 STANDING SEAM METAL ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 6 WOOD SHINGLE ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 7 FLAT COOL ROOF, CLASS 'A' - COLOR AS SELECTED - TPO MEMBRANE - REF. MAT. SCHEDULE SHT. A-4.0 PROJECT NORTHTRUE NORTH 3/16" = 1'-0"1 ARCHITECTURAL ROOF PLAN ROOF PLAN NOTESA KEYNOTESB NO. REVISION DATE 7896 7 8 9 5 7 8 9 4 7893 7 8 9 5 7 8 9 4 1 111 1 212 22 11 2 424 2 3 3 1 2 8 2 7 3 0 2 9 90.00 100.00 90.00 100.00 S 75°09'11" E N 14°50'49" E N 14°50'49" E N 75°09'11" W 39.5 1.01.4 1.2 13.6 1.5 12.5 19.3 12.1 3.4 STONE WALL W A L K FEATURE W A L K W A T E R F E A T U R E WM P A R C E L 1 W A L K BAY RO STONE WALL W A L KRO CONC GMEM BAY #5 R E B A R 0 .6 ' P O B 1 " I R O N P I P E A-4.1 A-4.0 A-4.12A-4.0 1 1 2 A-4.03 A-4.1 4 A-4.1 3 R. Y . S . B . 10 ' - 0 " 6:12 6: 1 2 12 : 1 2 12 : 1 2 6: 1 2 12:12 12:12 12:1212:12 12 : 1 2 12 : 1 2 4:12 4:1212:1212:12 12 : 1 2 12:12 12:1212:12 12 : 1 2 12 : 1 2 12:1212:12 6:12 6: 1 2 3:123:12 7:12 7:12 12:12 12:12 6:12 6:12 6:12 6:12 12 : 1 2 12 : 1 2 12 : 1 2 12 : 1 2 2% MIN. 2% MIN. 2% M I N . 2% M I N . HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. 12:12 1 2 3 1 3 1414 5 5 5 5 5 6 6 6 66 6 6 66 6 6 6 6 66 7 7 7 CHIMNEY TO BE WRAPPED IN ACM PANEL PARAPET WALL TO BE WRAPPED IN ACM PANEL PARAPET WALL TO BE WRAPPED IN ACM PANEL HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. PT.12 - 7916.91' PT.13 - 7916.91' 7893' (E.) NG 7894' (E.) NG 7893' (E.) NG 7893' (E.) NG 7893' (E.) NG 7893' (E.) NG 7893' (E.) NG 7893' (E.) NG7893' (E.) NG 1 A-5.1 1 A-5.1 1 A-5.0 1 A-5.0 PT.1 - 7911.50'PT.2 - 7914.42' PT.3 - 7909.85' 7893' (E.) NG PT.4 - 7912.08' PT.5 - 7916.68' 7893' (E.) NG PT.7 - 7910.82' PT.8 - 7907.60' PT.9 - 7914.34' PT.11 - 7917.66' 7893' (E.) NG PT.10 - 7914.34' 7893' (E.) NG PT.14 - 7907.80' 7893' (E.) NG PT.6 - 7912.08' S.Y.S.B. (REQUIRED) 10' - 0" S.Y.S.B. (EXISTING HISTORIC) 8' - 2 3/8" R. Y . S . B . ( R E Q U I R E D ) - G A R A G E 5' - 0 " S.Y.S.B. (PROPOSED) 10' - 0" F. Y . S . B . ( R E Q U I R E D ) 10 ' - 0 " S.Y.S.B. (REQUIRED & PROPOSED) 10' - 0" F. Y . S . B . ( E X I S T I N G H I S T O R I C ) 15 ' - 0 " R. Y . S . B . ( P R O P O S E D ) - G A R A G E 5' - 1 " S.Y.S.B. (REQUIRED) 10' - 0" DIMENSION NOTE: ALL DIMS. ARE TO FACE OF STUD (F.O.S.) OR FACE OF SHT'G. (F.O.S.) TYP. U.N.O. EAVE DIMS. ARE FROM FACE OF SHT'G. TO FACE OF FINISH FASCIA ENLOSED ATTIC AND ENCLOSED RAFTER SPACES VENTING NOTES: 1. ENCLOSED ATTIC AND ENCLOSED RAFTER SPACES SHALL HAVE CROSS VENTILATION BY VENTILATION OPENING PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW UNLESS THEY MEET THE REQUIREMENT OF SECTION R806.5 FOR UNVENTED ATTIC AND UNVENTED ENCLOSED RAFTER ASSEMBLIES. VENTILATION OPENING SHALL HAVE THE LEAST DIMENSION OF 1/16”MIN. AND 1/4”MAX OTHERWISE THE OPENING SHALL HAVE THE CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE CLOTH, PERFORATED VINYL OR SIMILAR MATERIAL WITH OPENINGS HAVE A LEAST DIMENSION OF 1/16”MIN. AND 1/4”MAX. OPENING IN ROOF FRAMING MEMBERS SHALL BE PER THE REQUIREMENT OF SECTION R802.7. REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO THE OUTSIDE AIR AND SHALL BE PROTECTED TO PREVENT THE ENTRY OF BIRDS, RODENTS, SNAKES AND OTHER SIMILAR CREATURES. (R806.1) 2. THE MINIMUM NET FREE VENTILATING AREA SHOULD BE 1/150 OF THE AREA OF THE VENTED SPACE, EXCEPT FOR THE PROJECT LOCATED IN CLIMATE ZONE 14 OR 16 WITH A CLASS I OR II VAPOR RETARDER AT THE WARM-IN-WINTER SIDE OF THE CEILING AND WHERE MIN. 40% AND MAX 50% OF THE REQUIRED VENTILATION PROVIDED IN THE UPPER PORTION OF THE ATTIC OR RAFTER SPACE PER SECTION R806.2 THEN THE MINIMUM NET FREE VENTILATING AREA CAN BE 1/300 OF THE VENTED SPACE. (R802.2) 3. PROVIDE 1”SPACE BETWEEN THE INSULATION AND THE ROOF SHEATHING WHERE EAVE OR CORNICE VENTS PROVIDE BLOCKING, BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW OF AIR. (R806.3) 4. INSTALL VENTILATOR PER MANUFACTURER INSTRUCTION. INSTALL VENTILATOR IN ROOF PER SECTION R903 AND VENTILATOR IN WALL ASSEMBLIES PER SECTION R703.1. 5. FOR THE ATTIC WITH VERTICAL HEIGHT GREATER THAN OR EQUAL TO 30”(VERTICAL HEIGHT MEASURED FROM THE TOP OF CEILING JOIST TO THE BOTTOM OF THE ROOF RAFTERS) WITHIN 30S.F. MIN. PROVIDE THE OPENING WITH ROUGH-FRAMED OPENING OF NOT LESS THAN 22”X30”WHICH SHOULD BE LOCATED IN HALLWAY OR OTHER LOCATION WITH READY ACCESS. IF THE ACCESS LOCATED IN THE WALL THEN THE WIDTH SHOULD BE 22”AND HEIGHT SHOULD BE 30”MIN. IF LOCATED IN CEILING THEN THE MIN. UNOBSTRUCTED HEADROOM IN THE ATTIC SHOULD BE 30”FROM THE BOTTOM OF CEILING JOIST AT SOME POINT. ROOF DRAINAGE: IF THE PROJECT LOCATED IN THE AREA WITH EXPANSIVE OR COLLAPSIBLE SOILS, WATER RUNOFF FROM ROOFS OF ALL DWELLINGS SHALL BE DISCHARGED TO THE GROUND SURFACE NOT LESS THAN 5 FEET FROM FOUNDATION WALLS OR TO AN APPROVED DRAINAGE SYSTEM. (R801.3) -REF.CIVIL DWGS FOR STORM WATER MANAGMENT AND SYSTEM. WEATHER PROTECTION: 1. ROOF DECKS SHALL BE COVERED WITH APPROVED ROOF COVERINGS SECURED TO THE BUILDING OR STRUCTURE IN ACCORDANCE WITH THE CHAPTER 9 OF THE CURRENT IRC. ROOF ASSEMBLIES SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH THE CHAPTER 9 OF IRC AND THE APPROVED MANUFACTURER’S INSTRUCTIONS SUCH THAT THE ROOF ASSEMBLY SHALL SERVE TO PROTECT THE BUILDING OR STRUCTURE. (R903.1) 2. PROVIDE AND INSTALL FLASHING TO PREVENT ENTRY OF MOISTURE TO WALL AND ROOF ASSEMBLIES THRU THE JOINTS IN COPINGS, PERMEABLE MATERIAL, AND AT INTERSECTION WITH PARAPET WALLS AND OTHER PENETRATION THRU ROOF. (R903.2) 3. FLASHINGS SHALL BE INSTALLED AT WALL AND ROOF INTERSECTIONS, WHEREVER THERE IS A CHANGE IN ROOF SLOPE OR DIRECTION AND AROUND ROOF OPENINGS. A FLASHING SHALL BE INSTALLED TO DIVERT THE WATER AWAY FROM WHERE THE EAVE OF A SLOPED ROOF INTERSECTS A VERTICAL SIDEWALL. WHERE FLASHING IS OF METAL, THE METAL SHALL BE CORROSION RESISTANT WITH A THICKNESS OF NOT LESS THAN 0.019 INCH (0.5 MM) (NO. 26 GALVANIZED SHEET). (R903.2.1) 4. A CRICKET OR SADDLE SHALL BE INSTALLED ON THE RIDGE SIDE OF ANY CHIMNEY OR PENETRATION MORE THAN 30 INCHES (762 MM) WIDE AS MEASURED PERPENDICULAR TO THE SLOPE. CRICKET OR SADDLE COVERINGS SHALL BE SHEET METAL OR OF THE SAME MATERIAL AS THE ROOF COVERING. EXCEPT FOR UNIT SKYLIGHTS INSTALLED IN ACCORDANCE WITH HYPERLINK "HTTPS://CODES.ICCSAFE.ORG/LOOKUP/CRC2019P1_PT03_CH03_SECR308.6" SECTION R308.6 AND FLASHED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS SHALL BE PERMITTED TO BE INSTALLED WITHOUT A CRICKET OR SADDLE. (R903.2) 5. PARAPET WALLS SHALL BE PROPERLY COPED WITH NONCOMBUSTIBLE, WEATHERPROOF MATERIALS OF A WIDTH NOT LESS THAN THE THICKNESS OF THE PARAPET WALL. (R903.3) 6. UNLESS ROOFS ARE SLOPED TO DRAIN OVER ROOF EDGES, ROOF DRAINS SHALL BE INSTALLED AT EACH LOW POINT OF THE ROOF. IF WATER CAN BE ENTRAPPED WITHIN THE ROOF AREA THEN SECONDARY EMERGENCY OVERFLOW ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED PER SECTION R903.4.1. (R903.4) 7. SNOW STOPS REQUIRED AT ALL ROOF PITCHES THAT SHED ONTO POTENTIALLY OCCUPIED AREAS PER R901 AS AMENDED BY CITY OF ASPEN MISC. NOTES: 1. INSTALL ROOF PER ROOFING MFG'R. SPECS & INSTALLATION GUIDELINE 2. ARCH. TO APPV. SIZE, COLOR & PROFILE OF EAVE & RAKE COMPONENTS. G.C. TO PROVIDE MOCK-UPS. 3. UNVENTED ENCLOSED RAFTER ASSEMBLY: NO INTERIOR CLASS I VAPOR RETARDER SHALL BE INSTALLED ON THE CEILING SIDE (ATTIC FLOOR) OF THE UNVENTED ATTIC ASSEMBLY OR ON THE CEILING SIDE OF THE UNVENTED ENCLOSED ROOF FRAMING ASSEMBLY. 4. REF. WOOD OR WOODBASE PRODUCT NOTES ON FLOOR PLANS DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 ROOF PLAN -HEIGHT OVER TOPOGRAPHY KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-3.1 TBD RYAN McDANIEL, AIA 3/16" = 1'-0"1 ROOF PLAN - HEIGHT OVER TOPOGRAPHY NO. REVISION DATE 1 PROPERTY LINE 2 FRONT YARD SETBACK 3 REAR YARD SETBACK 4 SIDE YARD SETBACK 5 STANDING SEAM METAL ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 6 WOOD SHINGLE ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 7 FLAT COOL ROOF, CLASS 'A' - COLOR AS SELECTED - TPO MEMBRANE - REF. MAT. SCHEDULE SHT. A-4.0 ROOF PLAN NOTESA KEYNOTESB ROOF HEIGHT OVER TOPOGRAPHY POINT ROOF ELEVATION NATURAL GRADE FINISHED GRADE HT. ABV. PT. 1 -7911.50'7893'7893.50'18.50' PT. 2 -7914.42'7893'7893.50'21.42' PT. 3 -7909.85'7893'7893.50'16.85' PT. 4 -7912.08'7893'7893.50'19.08' PT. 5 -7916.68'7893'7893.50'23.68' PT. 6 -7912.08'7893'7893.50'19.08' PT. 7 -7910.82'7893'7893.50'17.82' PT. 8 -7907.60'7894'7893.50'14.10' PT. 9 -7914.34'7893'7893.50'21.34' PT. 10 -7914.34'7893'7893.50'21.34' PT. 11 -7917.66'7893'7893.50'24.66' PT. 12 -7916.91'7893'7893.50'23.91' PT. 13 -7916.91'7893'7893.50'23.91' PT. 14 -7907.80'7893'7893.50'14.80' *BOLD GRADE POINTS INDICATE MOST RESTRICTIVE ELEVATION. FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' SECOND FLOOR F.F. 7904.91' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' SECOND FLOOR PLATE 7903.83' LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' 79 80 9 10 41 A 13 2526 1 3 1 1 1 2 12 :12 12 :12 12: 12 1/ 3 P O I N T F R O M E A V E T O R I D G E 18 ' - 1 1 1 / 2 " 1/ 3 P O I N T F R O M E A V E T O R I D G E 18 ' - 1 0 5 / 8 " 7921.92' 7919.57' 7924.91' 7922.34' 23 ' - 1 0 7 / 8 " 7906.65' 1/ 3 P O I N T F R O M E A V E T O R I D G E 20 ' - 9 3 / 4 " 7916.91' 3 2 4 5 6 7 6 8 HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. 2' - 6 " 1 A-5.0 25 ' - 0 " ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7.ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. 25 ' - 0 " WINDOWS & DOORS: AUTHORIZED DEALER (PRODUCTS LISTED BELOW) SUPPLIER:ASSOCIATED BUILDING SUPPLY ADDRESS:STONE MILL DESIGN CENTER 2915 RED HILL AVE., SUITE F104, COSTA MESA, CA 92626 CONTACT:JOE YOUNAN PHONE:949-872-3319 FAX:206-666-2150 EMAIL:JYOUNAN@ABSSOCAL.COM WEB:WWW.ASSOCIATEDBUILDINGSUPPLY.COM ALUMINUM CLAD WINDOWS & PATIO DOORS MANUFACTURER: JELD-WEN WINDOWS & DOORS PRODUCT:CUSTOM COLLECTION ADDRESS:3250 LAKEPORT BLVD. P.O. BOX 1329; KLAMATH FALLS, OREGON 97601 PHONE:541-885-7412 OR 800-535-3936 FAX:541-884-3331 WEB:WWW.JELD-WEN.COM MULTI SLIDE DOORS & STOREFRONT MANUFACTURER:WESTERN WINDOW SYSTEMS PRODUCT: SERIES 600 & STOREFRONT SYSTEMS ADDRESS: 5621 S. 25TH ST., PHOENIX, AZ 85040 PHONE: 877.268.1300 WEB: WWW.WESTERNWINDOWSYSTEMS.COM WOOD SIDING: MANUFACTURER: TBD COLOR: TBD APPLICATION: TBD CODE: TBD ROOFING: PRODUCT: TBD MFGR:TBD COLOR: TO BE APPROVED BY ARCH. & OWNER APPLICATION: TBD CODE:ICC # ESR-_____ WEIGHT: ???? LBS./S.F. GUTTERS: MATERIAL: METAL -COPPER/ALUM. PAINTED KYNAR SHAPE: HALF ROUND/SQUARE (5") (VERIFY W/. ARCH.) GARAGE DOORS: SUPPLIER:RANCH HOUSE DOORS WEB:WWW.RANCHHOUSEDOORS.COM STYLE: CUSTOM MATERIAL: CUSTOM BUILT, WOOD & GLASS WATERPROOF DECK MEMBRANE: MFGR:TUFFLEX POLYMERS ADDRESS:10880 POPLAR AVE., FONTANA, CA PHONE: 909.349.2016 WEB:WWW.TUFFLEXPOLYMERS.COM CODE:ICC # ESR-2505 FLASHING & WEATHERSTRIPPING PROVIDE MIN. 24 GUAGE METAL (16 OZ.) SHEETING (TO MATCH) FOR ALL EXTERIOR FLASHING & WEATHERSTRIPPING APPLICATIONS. VERIFY W/. ARCHITECT ANY UNCONVENTIONAL ENVELOPE WATERPROOFING AREAS PRIOR TO INSTALLATION. FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' CARRIAGE HOUSE F.F. 7893.50' 39 47 49 63 60 62 5421 6 7 2 9 13 70 6.8 12: 12 12 :12 12: 12 12: 1212 :12 12: 12 12 :12 7913.53' 7917.50' 7919.57' 7914.60' 7917.45' 1/ 3 P O I N T F R O M E A V E T O R I D G E 19 ' - 1 " 1/ 3 P O I N T F R O M E A V E T O R I D G E 17 ' - 9 7 / 8 " 1/ 3 P O I N T F R O M E A V E T O R I D G E 14 ' - 5 1 / 8 " 8 4 7 7 6 7 5 4 HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. 7921.27' HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. 1 A-5.1 ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. 25 ' - 0 " 25 ' - 0 " 1/ 2 P O I N T F R O M E A V E T O R I D G E 23 ' - 8 1 / 8 " FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' 12 3 12 47 46 55 7913.53' 7917.50' 7921.92'7921.27'7921.92' 7919.57' 12: 1212 :12 12: 1212 :12 1/ 3 D I S T A N C E U P P E R A P S E N M U N I . C O D E 14 ' - 5 1 / 8 " HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. 1/ 3 P O I N T F R O M E A V E T O R I D G E 19 ' - 1 " 8 4 7 77 4 8 1 A-5.1 25 ' - 0 " ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7.ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. 25 ' - 0 " 1/ 3 P O I N T F R O M E A V E T O R I D G E 18 ' - 6 1 / 8 " 1/ 3 P O I N T F R O M E A V E T O R I D G E 17 ' - 9 7 / 8 " 1/ 2 P O I N T F R O M E A V E T O R I D G E 23 ' - 8 1 / 8 " DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXTERIOR ELEVATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-4.0 TBD RYAN McDANIEL, AIA 3/16" = 1'-0"1 NORTH ELEVATION 3/16" = 1'-0"2 WEST ELEVATION 1 T&G PANELING, REVEAL AS SEL. FINISH AS SELECTED - REF. MATERIAL SCHEDULE SHT. A-4.0 2 ACM PANEL - REF. MAT. SCHEDULE A-4.0 3 STANDING SEAM METAL ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 4 WOOD SHINGLE ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 5 WOOD HALF-MOON SHINGLE SIDING, FINISH AS SELECTED - REF. MATERIAL SCHEDULE SHT. A-4.0" 6 WOOD SHINGLE SIDING - REF. MATERIAL SCHEDULE SHT. A-4.0 7 CLAPBOARD SIDING, REVEAL AS SEL., PRIMED, CAULKED & SEALED, PAINT TO MATCH, ARCH. TO APPV. REF. MAT. SCHEDULE A-4.0 8 BRICK VENEER - REF. MAT. SCHEDULE SHT. A-4.0 MATERIAL SPECIFICATIONSA GENERAL NOTESB KEYNOTESC 1. FENESTRATIONS MUST HAVE TEMPORARY AND PERMANENT LABELS. 2. REF. ROOF PLAN (A-3.0) FOR ALL PLATE HTS. & RIDGE HTS. 3. ALL OUDOOR LIGHTING MUST COMPLY WITH THE CITY OF ASPEN LIGHTING CODE SECTION 26.575.150. NO. REVISION DATE 3/16" = 1'-0"3 EAST ELEVATION -HISTORIC & CARRAIGE HOUSE FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' CARRIAGE HOUSE F.F. 7893.50' 6 6.1 G I 2 3 7922.36' 7924.91' 7916.91' 7910.82' 7913.53'7913.53' 6 :1 2 6:12 12: 12 7 :1 2 1/ 2 D I S T A N C E U P P E R A P S E N M U N I . C O D E 13 ' - 1 7 / 8 " 4 5 1/ 3 D I S T A N C E U P P E R A P S E N M U N I . C O D E 24 ' - 0 1 / 2 " 1/ 3 D I S T A N C E U P P E R A S P E N M U N . C O D E 14 ' - 5 1 / 8 " 1 A-5.0 ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. 25 ' - 0 " 25 ' - 0 " FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' SECOND FLOOR F.F. 7904.91' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' SECOND FLOOR PLATE 7903.83' LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' 7 11 H J D 44 8 12 1 2 3 1 2 23 ' - 1 0 7 / 8 " 1 3 7910.83' 7916.91' 7922.36'7922.34' 7916.91' 1 A-5.1 29 ' - 3 3 / 4 " ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. 25 ' - 0 " 25 ' - 0 " WINDOWS & DOORS: AUTHORIZED DEALER (PRODUCTS LISTED BELOW) SUPPLIER:ASSOCIATED BUILDING SUPPLY ADDRESS:STONE MILL DESIGN CENTER 2915 RED HILL AVE., SUITE F104, COSTA MESA, CA 92626 CONTACT:JOE YOUNAN PHONE:949-872-3319 FAX:206-666-2150 EMAIL:JYOUNAN@ABSSOCAL.COM WEB:WWW.ASSOCIATEDBUILDINGSUPPLY.COM ALUMINUM CLAD WINDOWS & PATIO DOORS MANUFACTURER: JELD-WEN WINDOWS & DOORS PRODUCT:CUSTOM COLLECTION ADDRESS:3250 LAKEPORT BLVD. P.O. BOX 1329; KLAMATH FALLS, OREGON 97601 PHONE:541-885-7412 OR 800-535-3936 FAX:541-884-3331 WEB:WWW.JELD-WEN.COM MULTI SLIDE DOORS & STOREFRONT MANUFACTURER:WESTERN WINDOW SYSTEMS PRODUCT: SERIES 600 & STOREFRONT SYSTEMS ADDRESS: 5621 S. 25TH ST., PHOENIX, AZ 85040 PHONE: 877.268.1300 WEB: WWW.WESTERNWINDOWSYSTEMS.COM WOOD SIDING: MANUFACTURER: TBD COLOR: TBD APPLICATION: TBD CODE: TBD ROOFING: PRODUCT: TBD MFGR:TBD COLOR: TO BE APPROVED BY ARCH. & OWNER APPLICATION: TBD CODE:ICC # ESR-_____ WEIGHT: ???? LBS./S.F. GUTTERS: MATERIAL: METAL -COPPER/ALUM. PAINTED KYNAR SHAPE: HALF ROUND/SQUARE (5") (VERIFY W/. ARCH.) GARAGE DOORS: SUPPLIER:RANCH HOUSE DOORS WEB:WWW.RANCHHOUSEDOORS.COM STYLE: CUSTOM MATERIAL: CUSTOM BUILT, WOOD & GLASS WATERPROOF DECK MEMBRANE: MFGR:TUFFLEX POLYMERS ADDRESS:10880 POPLAR AVE., FONTANA, CA PHONE: 909.349.2016 WEB:WWW.TUFFLEXPOLYMERS.COM CODE:ICC # ESR-2505 FLASHING & WEATHERSTRIPPING PROVIDE MIN. 24 GUAGE METAL (16 OZ.) SHEETING (TO MATCH) FOR ALL EXTERIOR FLASHING & WEATHERSTRIPPING APPLICATIONS. VERIFY W/. ARCHITECT ANY UNCONVENTIONAL ENVELOPE WATERPROOFING AREAS PRIOR TO INSTALLATION. LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' CARRIAGE HOUSE F.F. 7893.50' CARRIAGE HOUSE F.F. 7893.50' 11 14 5 7913.53'7913.53' 1/ 3 D I S T A N C E U P P E R A S P E N M U N . C O D E 14 ' - 5 1 / 8 " 1 A-5.0 25 ' - 0 " ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7.ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' 76 77 85.5 12: 1212 :12 6:126:1 2 7917.50' 7921.92' 1/ 3 D I S T A N C E U P P E R A P S E N M U N I . C O D E 17 ' - 7 1 / 2 " 6 5 5 7 HISTORIC CHIMNEY TO BE RESTORED. IN ASSSUMED LOCATION BASEDON HISTORIC PHOTOS. HISTORIC IRON RIDGE ORNAMENT IN ASSSUMED LOCATION BASED ON HISTORIC PHOTOS. 1 A-5.0 25 ' - 0 " ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. ZONE DISTRICT HEIGHT LIMIT PER 26.710.060.D.7. DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 EXTERIOR ELEVATIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-4.1 TBD RYAN McDANIEL, AIA 1 STANDING SEAM METAL ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 2 ACM PANEL - REF. MAT. SCHEDULE A-4.0 3 T&G PANELING, REVEAL AS SEL. FINISH AS SELECTED - REF. MATERIAL SCHEDULE SHT. A-4.0 4 WOOD SHINGLE SIDING - REF. MATERIAL SCHEDULE SHT. A-4.0 5 CLAPBOARD SIDING, REVEAL AS SEL., PRIMED, CAULKED & SEALED, PAINT TO MATCH, ARCH. TO APPV. REF. MAT. SCHEDULE A-4.0 6 WOOD SHINGLE ROOFING - REF. MAT. SCHEDULE SHT. A-4.0 7 WOOD HALF-MOON SHINGLE SIDING, FINISH AS SELECTED - REF. MATERIAL SCHEDULE SHT. A-4.0" 3/16" = 1'-0"1 SOUTH ELEVATION 3/16" = 1'-0"2 EAST ELEVATION MATERIAL SPECIFICATIONSA GENERAL NOTESB KEYNOTESC NO. REVISION DATE 3/16" = 1'-0"3 NORTH ELEVATION -BARN 3/16" = 1'-0"4 SOUTH ELEVATION -HISTORIC 1. FENESTRATIONS MUST HAVE TEMPORARY AND PERMANENT LABELS. 2. REF. ROOF PLAN (A-3.0) FOR ALL PLATE HTS. & RIDGE HTS. 3. ALL OUDOOR LIGHTING MUST COMPLY WITH THE CITY OF ASPEN LIGHTING CODE SECTION 26.575.150. EXTERIOR WALL: 2 x 4 CONST.:R-13 MIN. 2 x 6 CONST. OR LARGER:R-20 MIN. RAISED FLOOR:R-30 MIN. ROOF:R-30 NOTES: 1. REF. RESCHECK FOR MORE INFORMATION 2. PROVIDE BID FOR INSULATION OF ENTIRE HOME *TOTAL R-VALUE INCLUDING THE RIDGID AND SPRAYED AIR-IMPERMEABLE INSULATION WHERE OCCURS FOR UNVENTED ASSEMBLY FIREBLOCKING AND DRAFTSTOPPING SHALL BE INSTALLED TO CUT OFF ALL CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND SHALL FORM AN EFFECTIVE BARRIER BETWEEN FLOORS, BETWEEN A TOP STORY AND A ROOF OR ATTIC SPACE, AND SHALL SUBDIVIDE ATTIC SPACES, CONCEALED ROOF SPACES AND FLOOR-CEILING ASSEMBLIES. THE INTEGRITY OF ALL FIRE BLOCKS AND DRAFT STOPS SHALL BE MAINTAINED. FIRE BLOCKS FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES, AT THE CEILING AND FLOOR LEVELS AND AT 10-FOOT INTERVALS BOTH VERTICAL AND HORIZONTAL. FIRE BLOCK CONSTRUCTION FIREBLOCKING SHALL CONSIST OF 2 INCHES NOMINAL LUMBER. FIRE BLOCKS MAY ALSO BE OF GYPSUM BOARD, CEMENT FIBER BOARD, BATTS OR BLANKETS OF MINERAL OR GLASS FIBER, OR OTHER APPROVED MATERIALS INSTALLED IN SUCH A MANNER AS TO BE SECURELY RETAINED IN PLACE. LOOSE-FILL INSULATION MATERIAL SHALL NOT BE USED. WALLS HAVING PARALLEL OR STAGGERED STUDS FOR SOUND-TRANSMISSION CONTROL SHALL HAVE FIRE BLOCKS OF BATTS OR BLANKETS OF MINERAL OR GLASS FIBER OR OTHER APPROVED FLEXIBLE MATERIALS. DRAFT STOPS DRAFTSTOPPING SHALL BE PROVIDED IN THE LOCATIONS SET FORTH IN THIS SECTION. FLOOR-CEILING ASSEMBLIES DRAFT STOPS SHALL BE INSTALLED IN FLOOR-CEILING ASSEMBLIES OF THE BUILDING. SUCH DRAFT STOPS SHALL BE IN LINE WITH WALLS SEPARATING INDIVIDUAL DWELLING UNITS FROM EACH OTHER AND FROM OTHER AREAS. ATTICS DRAFT STOPS SHALL BE INSTALLED IN THE ATTICS, MANSARDS, OVERHANGS, FALSE FRONTS SET OUT FROM WALLS AND SIMILAR CONCEALED SPACES OF THIS BUILDING. SUCH DRAFT STOPS SHALL BE ABOVE AND IN LINE WITH THE WALLS SEPARATING INDIVIDUAL DWELLING UNITS FROM EACH OTHER AND FROM OTHER USES. DRAFT STOP CONSTRUCTION DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN ½-INCH GYPSUM BOARD, 3/8-INCH WOOD STRUCTURAL PANEL, 3/8-INCH TYPE 2-M PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY SUPPORTED. OPENINGS IN THE PARTITIONS SHALL BE PROTECTED BY SELF-CLOSING DOORS WITH AUTOMATIC LATCHES CONSTRUCTED AS REQUIRED FOR THE PARTITIONS. ROOM TAGROOM NAME 1 A-5.0 1 1 ? 1 1 ELEVATION / SECTION INDICATOR AD-1.0 1 CALL-OUT TAG 10.00' SPOT ELEVATION KEYNOTE TAG REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG FIRE RATED CEILING ASS'Y -REF. DTLS. 7/AD-1.0 1-HR RATED INT CONDITION -REF. DTLS. 7/AD-1.0 1-HR RATED EXT CONDITION -REF. DTLS. 7/AD-1.0 CONCRETE WALL/PODIUM DECK -PER STRUCT. REF. STRUCT DWGS. –FOR SLAB ON GRADE PROVIDE BASE PER R506.2.2 AND VAPOR RETARDER PER R506.2.3 W/. CAPILLARY BREAK INSULATED BUILDING ENVELOPE -2X STUDS PER PLANS, SEE DIMENSION PLANS FOR MORE INFO –INSULATION PER INSULATION SCHEDULE AND T-24 ENERGY REPORTS FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' BASEMENT F.F. 7882.75' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83' LOWEST EXISTING GRADE 7893.00' CARRIAGE HOUSE F.F. 7893.50' 1 A-5.1 12 3 96 BEDROOM #2 BATH #2 W/D.BEROOM #3 ATTIC OFFICE PWDR. W.I.C.BUNK ROOM MECH. KITCHEN DIRTY KITCHEN CARRIAGE HOUSE 1' - 1 " 9' - 0 " 1' - 3 1 / 8 " 10 ' - 9 7 / 8 " 10 ' - 1 " 12 ' - 1 " 75 12 8' - 1 1 1 / 8 " DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 BUILDING SECTIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-5.0 TBD RYAN McDANIEL, AIA 1/4" = 1'-0"1 LONGITUDINAL SECTION 1 NO. REVISION DATE KEYNOTESD FIRE-BLOCKING & DRAFT STOP NOTESA INSULATION SCHEDULEB ANNOTATION LEGENDC FIREBLOCKING AND DRAFTSTOPPING SHALL BE INSTALLED TO CUT OFF ALL CONCEALED DRAFT OPENINGS (BOTH VERTICAL AND HORIZONTAL) AND SHALL FORM AN EFFECTIVE BARRIER BETWEEN FLOORS, BETWEEN A TOP STORY AND A ROOF OR ATTIC SPACE, AND SHALL SUBDIVIDE ATTIC SPACES, CONCEALED ROOF SPACES AND FLOOR-CEILING ASSEMBLIES. THE INTEGRITY OF ALL FIRE BLOCKS AND DRAFT STOPS SHALL BE MAINTAINED. FIRE BLOCKS FIREBLOCKING SHALL BE PROVIDED IN CONCEALED SPACES OF STUD WALLS AND PARTITIONS, INCLUDING FURRED SPACES, AT THE CEILING AND FLOOR LEVELS AND AT 10-FOOT INTERVALS BOTH VERTICAL AND HORIZONTAL. FIRE BLOCK CONSTRUCTION FIREBLOCKING SHALL CONSIST OF 2 INCHES NOMINAL LUMBER. FIRE BLOCKS MAY ALSO BE OF GYPSUM BOARD, CEMENT FIBER BOARD, BATTS OR BLANKETS OF MINERAL OR GLASS FIBER, OR OTHER APPROVED MATERIALS INSTALLED IN SUCH A MANNER AS TO BE SECURELY RETAINED IN PLACE. LOOSE-FILL INSULATION MATERIAL SHALL NOT BE USED. WALLS HAVING PARALLEL OR STAGGERED STUDS FOR SOUND-TRANSMISSION CONTROL SHALL HAVE FIRE BLOCKS OF BATTS OR BLANKETS OF MINERAL OR GLASS FIBER OR OTHER APPROVED FLEXIBLE MATERIALS. DRAFT STOPS DRAFTSTOPPING SHALL BE PROVIDED IN THE LOCATIONS SET FORTH IN THIS SECTION. FLOOR-CEILING ASSEMBLIES DRAFT STOPS SHALL BE INSTALLED IN FLOOR-CEILING ASSEMBLIES OF THE BUILDING. SUCH DRAFT STOPS SHALL BE IN LINE WITH WALLS SEPARATING INDIVIDUAL DWELLING UNITS FROM EACH OTHER AND FROM OTHER AREAS. ATTICS DRAFT STOPS SHALL BE INSTALLED IN THE ATTICS, MANSARDS, OVERHANGS, FALSE FRONTS SET OUT FROM WALLS AND SIMILAR CONCEALED SPACES OF THIS BUILDING. SUCH DRAFT STOPS SHALL BE ABOVE AND IN LINE WITH THE WALLS SEPARATING INDIVIDUAL DWELLING UNITS FROM EACH OTHER AND FROM OTHER USES. DRAFT STOP CONSTRUCTION DRAFTSTOPPING MATERIALS SHALL NOT BE LESS THAN ½-INCH GYPSUM BOARD, 3/8-INCH WOOD STRUCTURAL PANEL, 3/8-INCH TYPE 2-M PARTICLEBOARD OR OTHER APPROVED MATERIALS ADEQUATELY SUPPORTED. OPENINGS IN THE PARTITIONS SHALL BE PROTECTED BY SELF-CLOSING DOORS WITH AUTOMATIC LATCHES CONSTRUCTED AS REQUIRED FOR THE PARTITIONS. EXTERIOR WALL: 2 x 4 CONST.:R-13 MIN. 2 x 6 CONST. OR LARGER:R-20 MIN. RAISED FLOOR:R-30 MIN. ROOF:R-30 NOTES: 1. REF. RESCHECK FOR MORE INFORMATION 2. PROVIDE BID FOR INSULATION OF ENTIRE HOME *TOTAL R-VALUE INCLUDING THE RIDGID AND SPRAYED AIR-IMPERMEABLE INSULATION WHERE OCCURS FOR UNVENTED ASSEMBLY ROOM TAGROOM NAME 1 A-5.0 1 1 ? 1 1 ELEVATION / SECTION INDICATOR AD-1.0 1 CALL-OUT TAG 10.00' SPOT ELEVATION KEYNOTE TAG REVISION TAG DOOR TAG WINDOW WALL TAG WINDOW TAG FIRE RATED CEILING ASS'Y -REF. DTLS. 7/AD-1.0 1-HR RATED INT CONDITION -REF. DTLS. 7/AD-1.0 1-HR RATED EXT CONDITION -REF. DTLS. 7/AD-1.0 CONCRETE WALL/PODIUM DECK -PER STRUCT. REF. STRUCT DWGS. –FOR SLAB ON GRADE PROVIDE BASE PER R506.2.2 AND VAPOR RETARDER PER R506.2.3 W/. CAPILLARY BREAK INSULATED BUILDING ENVELOPE -2X STUDS PER PLANS, SEE DIMENSION PLANS FOR MORE INFO –INSULATION PER INSULATION SCHEDULE AND T-24 ENERGY REPORTS FIRST FLOOR F.F. 7894.83' FIRST FLOOR F.F. 7894.83' SECOND FLOOR F.F. 7904.91' SECOND FLOOR F.F. 7904.91' BASEMENT F.F. 7882.75' BASEMENT F.F. 7882.75' FIRST FLOOR PLATE 7893.57' FIRST FLOOR PLATE 7893.57' SECOND FLOOR PLATE 7903.83'SECOND FLOOR PLATE 7903.83' LOWEST EXISTING GRADE 7893.00' LOWEST EXISTING GRADE 7893.00' A-0.2 1 1 A-5.0 MASTER BEDROOMMA. BATH GREAT ROOM BUNK ROOM KITCHEN BEROOM #3 BATH #3 ?ATTIC MEDIA ROOMGAME ROOM 94 6.9 73 10 9 79 101E A ATTIC 3' - 6 " BATH #5 SPOOL 1' - 1 " 9' - 0 " 1' - 3 1 / 8 " 10 ' - 9 7 / 8 " 10 ' - 1 " 12 ' - 1 " 5.5 DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 01.10.22 BUILDING SECTIONS KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-5.1 TBD RYAN McDANIEL, AIA NO. REVISION DATE 1/4" = 1'-0"1 TRANSVERSE SECTION 1 KEYNOTESD FIRE-BLOCKING & DRAFT STOP NOTESA INSULATION SCHEDULEB ANNOTATION LEGENDC DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 09/27/21 REALISTIC PERSPECTIVE VIEW KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-8.0 TBD RYAN McDANIEL, AIA NO. REVISION DATE DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 09/27/21 REALISTIC PERSPECTIVE VIEW KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-8.1 TBD RYAN McDANIEL, AIA NO. REVISION DATE DATE REVISIONS OWNER INFORMATION: PROJECT STATUS PLAN CHECK NO. 151 KALMUS DRIVE, SUITE G-1 COSTA MESA, CA 92626 714.754.4040 WWW.BRANDONARCHITECTS.COM PROJECT CONTACT THESE DOCUMENTS ARE THE PROPERTY OF BRANDON ARCHITECTS INC., AND ARE NOT TO BE DUPLICATED, ALTERED OR UTILIZED IN ANY WAY BY ANY OTHER PARTY WITHOUT THE EXPRESSED AUTHORIZATION OF BRANDON ARCHITECTS. ANY UNAUTHORIZED DUPLICATION OR ALTERATION OF THESE DOCUMENTS BY ANY PARTY IS A VIOLATION OF BRANDON ARCHITECTS EXPRESSED COMMON LAW COPYRIGHT AND OTHER PROPERTY RIGHTS THERETO, AND IS SUBJECT TO FULL CIVIL LIABILITIES AND PENALTIES. THESE PLANS ARE ALSO NOT TO BE ASSIGNED TO ANY THIRD PARTY WITHOUT OBTAINING WRITTEN AUTHORIZATION AND EXPRESSED PERMISSION BY BRANDON ARCHITECTS, WHO SHALL THEN BE HELD HARMLESS AND ABSOLVED OF ANY LIABILITY REGARDING ANY USE OF THESE DOCUMENTS BY SUCH THIRD PARTY WHETHER DEPICTED OR IMPLIED HERON. PROJECT ADDRESS: BRANDON ARCHITECTS 09/27/21 REALISTIC PERSPECTIVE VIEW KA O R E S I D E N C E LOT D, LLC. "CUSTOM" -C/O JOHN KAO 312 ASPEN AIRPORT BUSINESS CENTER, STE. D, ASPEN, CO, 81611 HPC FIRST CHECK 233 W. BLEEKER ST., ASPEN, CO, 81611 A-8.2 TBD RYAN McDANIEL, AIA NO. REVISION DATE SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 SITE PLAN C1 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 OVERALL GRADING PLAN C2 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 OVERALL UTILITY PLAN C3 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.1 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.2 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.3 SHEET NO. SHEET TITLE NO . NA M E YA R N E L L C O N S U L T I N G & CI V I L D E S I G N , L L C P. O . B O X 3 9 0 1 , E A G L E , C O L O R A D O 8 1 6 3 1 (9 7 0 ) 3 2 3 - 7 0 0 8 IS S U E / R E V I S I O N DA T E : DA T E TH E D E S I G N S S H O W N H E R E I N I N C L U D I N G AL L T E C H N I C A L D R A W I N G S , G R A P H I C RE P R E S E N T A T I O N & M O D E L S T H E R E O F , A R E PR O P R I E T A R Y & C A N N O T B E C O P I E D , DU P L I C A T E D , O R C O M M E R C I A L L Y E X P L O I T E D IN W H O L E O R I N P A R T W I T H O U T T H E S O L E AN D E X P R E S S W R I T T E N P E R M I S S I O N F R O M YA R N E L L C O N S U L T I N G & C I V I L D E S I G N , L L C . DE S I G N B Y : DR A W N B Y : RE V I E W E D B Y : PR O J E C T N O . : SI N G L E - F A M I L Y R E S I D E N C E 23 3 W E S T B L E E K E R S T R E E T LO T S A , B , & C , B L O C K 5 1 , C I T Y O F AS P E N , C O L O R A D O J. Y A R N E L L J. Y A R N E L L J. Y A R N E L L 21 . 0 1 8 1/ 7 / 2 0 2 2 811 DETAILED GRADING & UTILITY PLAN C4.4 From:Ryan McDaniel To:Sara Adams Subject:Fwd: 233 W. Bleeker Street & 219 W. Bleeker St. Date:Monday, January 10, 2022 9:02:48 AM ---------- Forwarded message --------- From: Ron Christian <ron.christian@cityofaspen.com> Date: Mon, Jun 14, 2021 at 2:28 PM Subject: RE: 233 W. Bleeker Street & 219 W. Bleeker St. To: Ryan McDaniel <ryan@brandonarchitects.com> CC: Brian Jowett <brian@brandonarchitects.com>, Sara Adams <sara@bendonadams.com> There is a 3 phase transformer on the south side of that alley, on the west end of the alley that could accommodate 1 run of 500 copper for each unit which would give you a 400 amp three phase service for both 219 and 233. Thanks, Ron From: Ryan McDaniel <ryan@brandonarchitects.com> Sent: Monday, June 14, 2021 2:24 PM To: Ron Christian <ron.christian@cityofaspen.com> Cc: Brian Jowett <brian@brandonarchitects.com>; Sara Adams <sara@bendonadams.com> Subject: Re: 233 W. Bleeker Street & 219 W. Bleeker St. It is still early on as we have not developed the schematics, but would plan for the following: 219 W. Bleeker - 400 amp 233 W. Bleeker - not certain of demand at this time, but this will be appx. 8,000 s.f. so may need 600 amp or 400 amp + 150 amp sub-panel if that is an option. Thank you! Best Regards, Ryan McDaniel, AIA, LEED AP BD+C Jr. Principal Architect BRANDON ARCHITECTS (O) 714.754.4040 (C) 949.394.8670 151 Kalmus Dr. G-1, Costa Mesa, CA 92626 www.BrandonArchitects.com On Mon, Jun 14, 2021 at 1:00 PM Ron Christian <ron.christian@cityofaspen.com> wrote: Hey Ryan, any idea what size amperage the mains will be on those 2 houses? Thanks, Ron From: Ryan McDaniel <ryan@brandonarchitects.com> Sent: Monday, June 14, 2021 1:35 PM To: Ron Christian <ron.christian@cityofaspen.com> Cc: Brian Jowett <brian@brandonarchitects.com>; Sara Adams <sara@bendonadams.com> Subject: 233 W. Bleeker Street & 219 W. Bleeker St. Hi Ron, I received your contact information from Sara Adams. We are working on a shared project on 233 & 219 W. Bleeker St. We will be constructing two (2) separate single family residences on the two lots (90' and 30' configurations). Can you help us determine whether we need to plan for a new transformer or if there is adequate service in this area? Thank you! Best Regards, Ryan McDaniel, AIA, LEED AP BD+C Jr. Principal Architect BRANDON ARCHITECTS (O) 714.754.4040 (C) 949.394.8670 151 Kalmus Dr. G-1, Costa Mesa, CA 92626 www.BrandonArchitects.com -- Best Regards, Ryan McDaniel, AIA, LEED AP BD+C Jr. Principal Architect BRANDON ARCHITECTS (O) 714.754.4040 (C) 949.394.8670 151 Kalmus Dr. G-1, Costa Mesa, CA 92626 www.BrandonArchitects.com (Sent from mobile phone) From:Sara Adams To:Sarah Yoon Subject:RE: site coverage question Date:Monday, August 2, 2021 2:06:00 PM Attachments:image002.png image003.png Thanks! I can’t believe you are POD today with such a full plate!! From: Sarah Yoon <sarah.yoon@cityofaspen.com> Sent: Monday, August 2, 2021 2:01 PM To: Sara Adams <sara@bendonadams.com> Subject: RE: site coverage question Hi Sara, Zoning confirmed that lightwells, patios and decks are not part of the site coverage. Thank you, -Sarah- Sarah Yoon (She/Her/Hers) Historic Preservation Planner | Community Development (O): 970.920.5144 | (C): 970.319.0720 www.cityofaspen.com My typical in-office hours are Tuesday-Thursday, 9 a.m.-5 p.m. I work remotely Monday & Friday, 9 a.m.-5 p.m. Our Values: Stewardship | Partnership | Service | Innovation www.cityofaspen.com www.aspencommunityvoice.com www.aspenvictorian.com www.aspenmod.com Notice and Disclaimer: This message is intended only for the individual or entity to which it is addressed and may contain information that is confidential and exempt from disclosure pursuant to applicable law. If you are not the intended recipient, please reply to the sender that you have received the message in error and then delete it. Further, the information or opinions contained in this email are advisory in nature only and are not binding on the City of Aspen. If applicable, the information and opinions contained in the email are based on current zoning, which is subject to change in the future, and upon factual representations that may or may not be accurate. The opinions and information contained herein do not create a legal or vested right or any claim of detrimental reliance. From: Sarah Yoon Sent: Monday, August 2, 2021 1:51 PM To: Sara Adams <sara@bendonadams.com> Subject: RE: site coverage question Hi Sara, I will check in with Zoning this afternoon to get you some direction. Thank you, -Sarah- Sarah Yoon (She/Her/Hers) Historic Preservation Planner | Community Development (O): 970.920.5144 | (C): 970.319.0720 www.cityofaspen.com My typical in-office hours are Tuesday-Thursday, 9 a.m.-5 p.m. I work remotely Monday & Friday, 9 a.m.-5 p.m. Our Values: Stewardship | Partnership | Service | Innovation www.cityofaspen.com www.aspencommunityvoice.com www.aspenvictorian.com www.aspenmod.com Notice and Disclaimer: This message is intended only for the individual or entity to which it is addressed and may contain information that is confidential and exempt from disclosure pursuant to applicable law. If you are not the intended recipient, please reply to the sender that you have received the message in error and then delete it. Further, the information or opinions contained in this email are advisory in nature only and are not binding on the City of Aspen. If applicable, the information and opinions contained in the email are based on current zoning, which is subject to change in the future, and upon factual representations that may or may not be accurate. The opinions and information contained herein do not create a legal or vested right or any claim of detrimental reliance. From: Community Development <planneroftheday@gmail.com> Sent: Monday, August 2, 2021 12:57 PM To: Sarah Yoon <sarah.yoon@cityofaspen.com> Subject: Fwd: site coverage question ---------- Forwarded message --------- From: Sara Adams <sara@bendonadams.com> Date: Mon, Aug 2, 2021 at 12:52 PM Subject: site coverage question To: Community Development <planneroftheday@gmail.com> Hi POD, Does site coverage measurement includes lightwells, patios and decks? Here is the Code section for easy reference. Thanks! Sara (g)Measuring Site coverage. Site coverage is typically expressed as a percentage. When calculating site coverage of a structure or building, the exterior walls of the structure or building at ground level should be used. When measuring to the exterior walls, the measurement shall be taken from the exterior face of framing, exterior face of structural block, or similar exterior surface of the nominal structure excluding sheathing, vapor barrier, weatherproofing membrane, exterior-mounted insulation systems, and excluding all exterior veneer and surface treatments such as stone, stucco, bricks, shingles, clapboards or other similar exterior veneer treatments. Porches, roofs or balcony overhangs, cantilevered building elements and similar features extending directly over grade shall be excluded from maximum allowable site coverage calculations. Sara Adams, AICP www.bendonadams.com (o) 970.925.2855 x2 (m) 610.246.3236 -- Notice and Disclaimer: This message is intended only for the individual or entity to which it is addressed and may contain information that is confidential and exempt from disclosure pursuant to applicable law. If you are not the intended recipient, please reply to the sender that you have received the message in error and then delete it. Further, the information or opinions contained in this email are advisory in nature only and are not binding on the City of Aspen. If applicable, the information and opinions contain in the email are based on current zoning, which is subject to change in the future, and upon factual representations that may or may not be accurate. The opinions and information contained herein do not create a legal or vested right or any claim of detrimental reliance.