HomeMy WebLinkAboutExhibitB Referral Comments.121 W Bleeker.2021.03.24121 W Bleeker – HPC Conceptual Review
Engineering Comments
Carly McGowan
March 11th, 2021
Comments to be resolved prior to HPC approval:
1.The proposed water service line is shown to go through the drip line of a large tree, with
excavation likely required into the drip lines of two other large trees. Applicant shall work with
the Parks Dept to resolve this issue and coordinate water line placement prior to HPC approval.
2.Per the CoA Urban Runoff Management Plan (URMP), drywells must be located a minimum of
10’ away from property lines and structures. The plans show the water quality drywell located
less than 10’ away from the property line. A variance will not be granted for the distance
between the drywell and the property line. If a variance is requested for the distance between
the drywell and the structure, applicant must submit a variance request and a letter from a
geotechnical engineer that the building foundation will not be compromised. This shall be
resolved before HPC approval.
3.What transformer serves the property and does the existing transformer have capacity for the
increased use? Will this property require a new transformer? Work with the City Electric
Department to determine available capacity. A Load Calc Form will be required at time of
building permit. Hotel Aspen is planning on upgrading transformers on their property. Verify
that the proposed work aligns with the planned transformer work at Hotel Aspen. This shall be
resolved before HPC approval.
Other Comments:
1.At building permit, plans shall show how the water service line ties into the structure. An
unrestrained service line through the house is not recommended. Instead, plans should include
a small mechanical room at the front of the house to switch to internal plumbing.
2.Since this property is in the Aspen Mountain Drainage Basin, detention is not required.
However, it needs to be clearly shown how runoff above the WQCV leaves the site. With the
proposed drywell the overflow route is not clear. At building permit, applicant will need to show
how additional runoff is routed to the City’s storm system without impacting neighboring
properties. If this can’t be accomplished, detention will need to be provided.
3.Stormwater from all impervious areas on the property must be treated for water quality.
4.Only one drywell is proposed on the planset, but the detail calls out the connection to a second
drywell. If two drywells are proposed, both must meet the 10' setback from all structures and
property lines.
5.Clarify the purpose of the filter fabric around the drywell. Studies show that filter fabric is the
first thing to clog, and removing or repairing the filter fabric would require excavating the entire
drywell.
6.Clarify what the 8.5’x24’ dotted line around the drywell represents.
7.This property is in a sidewalk deferred zone. A sidewalk will not be required at this time.
EXHIBIT B - REFERRAL COMMENTS
From:Bonnie Muhigirwa
To:Sarah Yoon
Cc:Denis Murray; Nick Thompson
Subject:RE: HPC Referral: 121 W. Bleeker
Date:Friday, March 12, 2021 2:59:46 PM
Attachments:image003.png
image004.png
image005.png
image002.png
image007.jpg
image008.jpg
image009.jpg
image010.jpg
image011.png
Hi Sarah,
Building Comments:
Fire sprinklers will be required because the fire area exceeds 5,000 sf.
Exterior stair to the roof deck does not meet fire separation distance requirements per 2015
IRC Table 302.1(2). Projections need to be at least 2 feet from the property line and have a 1
hour fire-resistance rating if less than 3 feet from the property line.
Window well can not be located in a patio without guard protection per city policy
https://www.cityofaspen.com/DocumentCenter/View/6195/Emergency-Escape-and-Rescue-
Window-Wells
The guest mater suite located in the historic resource needs a compliant emergency escape
and rescue opening per R310.2.1
Hot tub at the roof deck will need to be located at least 18” from the deck edge or the guard
height will need to extend 18” above the top of the hot tub per city policy
https://www.cityofaspen.com/DocumentCenter/View/6202/Hot-Tub-and-Spa-Safety-Railings
Snow fencing is required on the historic roof where snow sheds into the window well on the
east side.
Thanks,
Bonnie Muhigirwa
Plans Examiner / Building Inspector III
Community Development
130 S Galena St.
Aspen, CO 81611
p: 970.429.2787
c: 970.309.5119
www.cityofaspen.com
From:Jim Pomeroy
To:Sarah Yoon
Subject:Zoning notes for 121 W. Bleeker
Date:Saturday, March 13, 2021 1:54:32 PM
Attachments:image009.png
image010.jpg
image011.jpg
image012.jpg
Here are zoning notes for 121 W. Bleeker.
1. Yard exceptions needed: Fire feature, and possibly a built in barbeque (it only shows on a
couple of sheets) that are placed between a street and structure.
2. The exterior stairs in the west side yard setback need an exception.
3. The rear basement and second floor deck need a 5’ rear setback variance
4. The east side yard has AC units taller than allowed. If those can be set lower into the ground
in some sort of “vault” so they are no more than 30” above the surrounding grade, then no
setback variance to the east will be required. If they cannot be lowered the applicant will
need an east side yard setback variance for the higher than 30” AC units.
5. Combined side yard setback – the combined side yards are supposed to be 14.94’. If the
stairs and the AC units receive a variance, then the combined side yard will be reduced to 10’.
6. There are height challenges for the rear, non-historical, section of the project. Because the
areaway/lightwell is larger than 100 sq. ft., height for all of the rear element on the property
will be counted from the bottom of the areaway per 26.575.020.F.4, Allowed Exceptions to
Height. Currently as drawn, the entire rear (new) section of the house does not meet height.
The applicant will either need to reduce the size of the areaway to 100 sq. ft. or less or ask
HPC for a variance. There are currently no height points being shown on the plans. Without
these height points being added, there is no guarantee that the applicant meets height even
without the areaway. Please review section 26.575.020.F.2.c) for how to measure height
when there are multiple pitches within one vertical plane.
To promote the health and safety of our staff and community and to minimize the spread of
COVID-19, Community Development staff are conducting business by email and phone and are
only available in person by appointment. Contact information for our entire staff and how best to
get the services you need can be found on our website: cityofaspen.com/177/Community-
Development. Thank you for your understanding.
Cheers,
Jim Pomeroy
Zoning Enforcement Officer
130 S. Galena St.
Aspen, CO 81611
p 970.429.2745
c 970.319.2565
www.cityofaspen.com
www.aspencommunityvoice.com
Notice and Disclaimer:
This message is intended only for the individual or entity to which it is addressed and may contain information that is
confidential and exempt from disclosure pursuant to applicable law. If you are not the intended recipient, please reply to the
sender that you have received the message in error and then delete it. Further, the information or opinions contained in this
email are advisory in nature only and are not binding on the City of Aspen. If applicable, the information and opinions
contained in the email are based on current zoning, which is subject to change in the future, and upon factual
representations that may or may not be accurate. The opinions and information contained herein do not create a legal or
vested right or any claim of detrimental reliance.