HomeMy WebLinkAbout22322-205WMain-ServiceResidential Calculation - 205 W. MAIN 2020 NFPA 70 ART. 220 PART IV 2020 NEC 220.84(C) 1200 SQFT Main Level 1200 SQFT General Lighting Load 3600 VA 2 CCT Small Appliance 3000 VA 1 CCT Laundry Circuit 1500 VA Total General Load: 8100 VA General Lighting Load: 8100 VA Appliance Loads: 1 Refrigerator 600 VA 1 Dishwasher 1200 VA 1 Disposal 900 VA 1 Microwave 1200 VA 3900 VA Appliance Load: 3900 VA Dryer Loads: 1 Electric Dryer 5000 VA Electric Dryer Load: 5000 VA Oven loads: 1 Electric Range 9600 VA Electric Oven Load: 9600 VA Other Loads: 0 VA Other Load: 0 VA 125% LARGEST MOTOR: 300 VA Subtotal General Loads: 26900 VA 2020 NEC 220.84(C) Cooling Loads Unit Power Power Baseboard Heat 3000 VA Baseboard Heat 3000 VA 9000 VA Heating Loads Baseboard Heat 3000 VA 0 VA Cooling Loads Connected: 9000 VA Greater of Noncoincidental Loads: 9000 VA 208 V CONNECTED: 35900 VA 1 Ø 172.6 A Table 220.84 - Number of Dwelling Units 9 Number of Units 208 V CONNECTED: 323100 VA DEMAND: 138933 VA 3 Ø 896.8 A 43 % 385.6 A 2020 NEC 220.84(B) House Loads: 1 Elevator 6000 VA 1 Lighting 3000 VA 1 General Outlets 3000 VA 12000 VA Total Service Size: 208 V CONNECTED: 335100 VA DEMAND: 150933 VA 3 Ø 930.1 A 418.9 A Heating Loads