HomeMy WebLinkAbout22322-205WMain-ServiceResidential Calculation - 205 W. MAIN
2020 NFPA 70 ART. 220 PART IV
2020 NEC 220.84(C)
1200 SQFT Main Level
1200 SQFT General Lighting Load 3600 VA
2 CCT Small Appliance 3000 VA
1 CCT Laundry Circuit 1500 VA
Total General Load: 8100 VA General Lighting Load: 8100 VA
Appliance Loads:
1 Refrigerator 600 VA
1 Dishwasher 1200 VA
1 Disposal 900 VA
1 Microwave 1200 VA
3900 VA Appliance Load: 3900 VA
Dryer Loads:
1 Electric Dryer 5000 VA Electric Dryer Load: 5000 VA
Oven loads:
1 Electric Range 9600 VA Electric Oven Load: 9600 VA
Other Loads:
0 VA Other Load: 0 VA
125% LARGEST MOTOR: 300 VA
Subtotal General Loads: 26900 VA
2020 NEC 220.84(C)
Cooling Loads
Unit Power Power
Baseboard Heat 3000 VA
Baseboard Heat 3000 VA 9000 VA Heating Loads
Baseboard Heat 3000 VA 0 VA Cooling Loads
Connected: 9000 VA Greater of Noncoincidental Loads: 9000 VA
208 V CONNECTED: 35900 VA
1 Ø 172.6 A
Table 220.84 - Number of Dwelling Units
9 Number of Units
208 V CONNECTED: 323100 VA DEMAND: 138933 VA
3 Ø 896.8 A 43 % 385.6 A
2020 NEC 220.84(B)
House Loads:
1 Elevator 6000 VA
1 Lighting 3000 VA
1 General Outlets 3000 VA
12000 VA
Total Service Size:
208 V CONNECTED: 335100 VA DEMAND: 150933 VA
3 Ø 930.1 A 418.9 A
Heating Loads