Loading...
HomeMy WebLinkAboutEngineering_Comments_02From:Hailey Guglielmo To:Sarah Yoon Cc:Wyatt Young Subject:RE: HPC Referral Project: 227 E. Bleeker Street Date:Monday, November 30, 2020 12:39:48 PM Attachments:image001.png image002.png image003.png image006.png image007.png Sarah, Two additional comments to add based on this information. 1.The drainage letter states they intend to raise the existing first floor elevation to get positive drainage. If I recall correctly there was an HPC issue with 203 N Monarch that due to it’s historic nature the house could not be raised. I will defer to HPC on if altering the floor elevation is permitted. 2.StormTech is not an approved BMP in the URMP. It does not meet the ten foot depth requirement to get below frost depth. At building permit the applicability of this particular BMP will need to be further vetted. Thanks. Hailey