HomeMy WebLinkAboutSnowmelt Plans.508 E Cooper Ave199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Project: 508 East Cooper Location: Aspen, Co Coverage area: 992 ft² Function: Snow & Ice Management Panels: ThermaPANEL by Therma-HEXX Snow & Ice Melting Summary: Supply glycol temperature = 140°F with a 20°F delta T Glycol Percentage = 50% Estimated Volume: 83 Gal Snow Melt Load = 202 BTU/ft² Net BTU requirement = 200,384 BTU/hr Max Required Head (at manifolds): 30.0 ft System Flow: 21.4 GPM Components Provided By Therma-HEXX: Snowmelt Panels: -LD Pedestal Mount ThermaPANEL, ½ “ PE-RT distribution tubing, Copper PEX Crimp Fittings, Paver Alignment and Spacer Disk Manifolds: - Zone 1 5-Port 1” Legend Stainless Steel Manifold - Zone 2 8-Port 1” Legend Stainless Steel Manifold -Zone 3 12-Port 1” Legend Stainless Steel Manifold Glycol Feeder: -Axiom DMF300-17 Gal Controls: - Tekmar 680 Controller, 090 Sensor, 091 Housing 508 East Cooper Date: 7/06/2021 Section Zone Circuits Flow GPM Per Circuit 1 1 4 2.6 0.7 1 2 7 6.7 1.0 1 3 11 9.4 0.9 992 ft² 140 °F 20 °F 202 BTU/hr/ft²Section Zone 50 %1 1 83 gal 1 2 21.4 GPM 1 3 25.7 ft 1.2 30 ft 16 Panels 200,384 BTU/hr Max Row Length: Max Pressure Loss: Total System Flow: *Based on nominal Copper Tube Size. Differences in diameter assume reducing from primary mains to feed individual manifolds. 2" 2" 2" Area (ft²) 310 121 *All numbers are best estimates at this stage of design. For pipe sizing, please round up to allow for error of margin. All manifolds have an extra port for PRV valve assembly. Values represent at the manifold and does not include pressure loss for main piping. 22.6 30 Max Pressure Loss (ft) Area Primary 28.4 436 Total Load Uncorrected Sytem Head: Safety Factor: Total Area *Pipe Sizing Requirements Pipe Diameter (CTS)Supply: 2" Glycol Dilution: ΔT: Load per ft²: System Volume: TRIM AREA 50 P S I P R V TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA 1 3B 3A 3B 1 2A 2B 2B 4 3A4 THIRD LEVEL TERRACE ACTUAL PAVER SIZE: PANEL SPACING: NOTE: PAVERS AND PEDESTALS BY OTHERS 23.5" X 23.5" X .78" 3/16" NOTES: DO NOT LEAVE PANELS & TUBING IN SUN FOR EXTENDED PERIODS OF TIME. DO NOT EXCEED 37 PSI IN SYSTEM. ROUTE TUBING AS SHOWN ON PLANS. SHOP DRAWING / SUBMITTAL REVIEW REVISE & RESUBMIT APPROVED WITH NOTED CHANGES ENTIRE SUBMITTAL WAS REVIEWED FOR DESIGN CONFORMITY & GENERAL CONFORMANCE TO CONTRACT DOCUMENTS. SUBCONTRACTOR IS RESPONSIBLE FOR CONFIRMING DIMENSIONS AT JOBSITE FOR TOLERANCE, CLEARANCE & UNDOCUMENTED SCOPE CHANGES AND PAVER PENETRATIONS. APPROVED FOR SHIPMENT BY:DATE: DRAWING LEGEND FULL PANEL HALF PANEL TRIM PANEL SUPPLY MANIFOLD RETURN MANIFOLD MANIFOLD SUPPLY LINE PANEL SUPPLY LINES MANIFOLD RETURN LINE PANEL RETURN LINES FILLER PANEL F CRIMP CONNECTION TRIM AREA SCAN TO DOWNLOAD INSTALLATION MANUAL FOURTH LEVEL TERRACE TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A 50 P S I P R V TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A 1A 1C 1B1B 2A 2A 2B2B 3A 3B 7C7C 4A7A 7D7B 7A 6A 3A 3B 7D 1C 4A 4B 4B 5 5 6A 6B ROOF TERRACE TRIM AREA TRIM AREA TRIM AREA TRIM AREA 1 4 8 7 6 3 10A 5 2 3 4 8 7 6 10B 5 10A 11A 11A 11B11B11C11C11D11D11E TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A 1 2 9 9 DATE:SCALE: PR O J E C T : TITLE: SHEET: DRAWN BY:CHECKED BY: REV DESCRIPTION DATE BY 199 CONSTITUTION AVE. SUITE 7 PORTSMOUTH, NH 03801 (603) 319-8815 PROJECT OVERVIEW 50 8 E A S T C O O P E R N/A07/01/2021 EB 1.0 AS P E N , C O TRIM AREA 50 P S I P R V SECTION 1 ZONE 1 4+1 PRV - MANIFOLD 121 SQ FT LONGEST EQ ROW = 12 LONGEST SUPPLY + RETURN = 56' TOTAL TUBING LENGTH = 164' THIRD LEVEL TERRACE F F FF F F TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREA TRIM AREAF FF 1 3B 3A 3B 1 2A 2B 2B 4 3A4 DATE:SCALE: PR O J E C T : TITLE: SHEET: DRAWN BY:CHECKED BY: REV DESCRIPTION DATE BY 199 CONSTITUTION AVE. SUITE 7 PORTSMOUTH, NH 03801 (603) 319-8815 ZONE 1 50 8 E A S T C O O P E R N/A07/01/2021 EB 1.1 AS P E N , C O FOURTH LEVEL TERRACE TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A F F 50 P S I P R V SECTION 1 ZONE 2 7+1 PRV - MANIFOLD 310 SQ FT LONGEST EQ ROW = 16 LONGEST SUPPLY + RETURN = 52' TOTAL TUBING LENGTH = 234' F F TR I M AR E A F TR I M AR E A TR I M AR E A TR I M AR E A F F F F TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A 1A 1C 1B1B 2A 2A 2B2B 3A 3B 7C7C 4A7A 7D7B 7A 6A 3A 3B 7D 1C 4A 4B 4B 5 5 6A 6B 2'-9" DATE:SCALE: PR O J E C T : TITLE: SHEET: DRAWN BY:CHECKED BY: REV DESCRIPTION DATE BY 199 CONSTITUTION AVE. SUITE 7 PORTSMOUTH, NH 03801 (603) 319-8815 ZONE 2 50 8 E A S T C O O P E R N/A07/01/2021 EB 1.2 AS P E N , C O ROOF TERRACESECTION 1 ZONE 3 11+1 PRV - MANIFOLD 436 SQ FT LONGEST EQ ROW = 15 LONGEST SUPPLY + RETURN = 66' TOTAL TUBING LENGTH = 464' F TRIM AREA TRIM AREA 22'-4" 22'-5" F F F F F F F F F F F F F F F F F F F FF F F TRIM AREA TRIM AREA UMBRELLA BASE LOCATION UMBRELLA BASE LOCATION GAS LINE LOCATION 1 4 8 7 6 3 10A 5 2 3 4 8 7 6 10B 5 10A 11A 11A 11B11B11C11C11D11D11E TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A TR I M AR E A 50 PSI PRV 1 2 9 9 DATE:SCALE: PR O J E C T : TITLE: SHEET: DRAWN BY:CHECKED BY: REV DESCRIPTION DATE BY 199 CONSTITUTION AVE. SUITE 7 PORTSMOUTH, NH 03801 (603) 319-8815 ZONE 3 50 8 E A S T C O O P E R N/A07/01/2021 EB 1.3 AS P E N , C O T 4"Ø HOLE FOR SOCKET Therma-HEXX TRIMMABLE PANEL PEDESTAL PAVER SENSOR INSTALL CAP TO BE SET FLUSH WITH TOP OF PAVER. MORTAR BRASS HOUSING INTO PAVER WITH CEMENT FOR THERMAL CONDUCTIVITY BETWEEN HOUSING AND PAVER. 7 8" ELECTRICAL CONDUIT CONNECTION 31 2" 4" HOLE SUPPORT HOUSING WITH PEDESTAL Maximum Wire Lengths for Snow / Ice Sensor 090 The following table shows the maximum wire length for the Snow / Ice Sensor 090. The “Max Added Length” column shows the additional length of wire that can be added to the 090's existing 65'. All splices must be: • soldered individually • heat shrinked individually • located in a dry junction box, preferably inside the building For a more robust connection and long term signal quality, it is recommended to heat shrink the cable jacket. Maximum wire length for 090 AWG (solid copper wire) 10 12 14 16 18 20 Max. Added Length (feet) 2787 1760 1103 692 435 276 Total combined feet, including factory 65’ 2852 1825 1168 757 500 341 Tekmar Submittal Snow / Ice Sensor Socket 091 The Snow/Ice Sensor Socket 091 is designed to provide a mounting solution for the Automatic Snow/Ice Sensor 090 or 094. It is intended to be installed directly into a concrete slab when the slab is poured, so that the 090 or 094 can be installed into it once dry. Front View Top View Snow / Ice Sensor Socket 091 Literature D090 Packaged weight Dimensions Approvals Warranty 1.5 lb (670 g), silicon brass 3-13/16” H x 3-1/2 O.D. (97 x 89 O.D. mm) CSA C US with tekmar Snow / Ice Sensor 090 Limited 3 Year (See D090 for full warranty) Special Requirements Must be mounted on a level slope, so that 090/094 sensor is flush with slab surface. 090 / 091 TEKMAR SENSOR 3" x 3" x 3 8" SS / Aluminum / Galvinized Steel angle iron or recessed pedestal at perimeter by others Facade overhang Paver High density EPS insulation at perimeter if required SS lag bolts for steel angle by others Low density 1 lb EPS insulation at field Therma-HEXX 1 8" spacer disks w / optional screw hold down. Screw by others Adustable pedestals (no spacer tabs) by others 1 4" ss perforated plate for pedestal support at roof drains as needed. 1 8" rubber spacers at paver perimeter. By others Perimeter detail may differ DATE:SCALE: PR O J E C T : TITLE: SHEET: DRAWN BY:CHECKED BY: REV DESCRIPTION DATE BY 199 CONSTITUTION AVE. SUITE 7 PORTSMOUTH, NH 03801 (603) 319-8815 DETAILS 50 8 E A S T C O O P E R N/A07/01/2021 EB 2.0 AS P E N , C O Outdoor Air Temperature Sensor Snow Melt Control Panel variable Speed Pump Low Pressure Shut Off Switch Boiler or Heat Exchanger Spirovent Air Separator Glycol Makeup Package Expansion Tank 50 PSI pressure relief valve Return Manifold Supply Manifold PP-R Blue Pipe, PEX, PE-RT or Copper Main supply and return pipe to be PP-R, PEX, PE-RT or Copper. Y-Strainer on supply of each manifold. 1 2" PE-RT Interconnect Tubing Typical ThermaPANEL Snow Melt Schematic Snow & Ice Sensor ThermaPANEL rows beneath Pavers DATE:SCALE: PR O J E C T : TITLE: SHEET: DRAWN BY:CHECKED BY: REV DESCRIPTION DATE BY 199 CONSTITUTION AVE. SUITE 7 PORTSMOUTH, NH 03801 (603) 319-8815 MECHANICAL SCHEMATIC 50 8 E A S T C O O P E R N/A07/01/2021 EB 3.0 AS P E N , C O R4.00 .63 PANELS CAN BE INSTALLED ON 23 9/16" - 24" CENTERS WITH 1/8" ALIGNMENT TABS ON THE PEDESTALS. THE STANDARD CONFIGURATION FOR USE WITH 23 15/16" PAVERS IS 24" CENTERS. ALL CONFIGURATIONS ARE SHIPPED IN 6' LONG BANDED BUNDLES. ROWS CAN BE ASSEMBLED UP TO 48' LONG (24 PANELS). FINISHED SIZE 23.5" x 23.5" x 1.41" INTERCONNECT TUBES ARE FUSION WELDED TO THE PANEL PEDESTAL VERSION: 1 LB DENSITY EPS INSULATION IS REMOVED TO ACCOMODATES AN 8" DIAMETER PEDESTAL POCKET. GROUND MOUNT VERSION: 1LB OR 3 LB DENSITY (OPTIONAL) EPS INSULATION EXTENDS TO THE CORNERS. 1.41 1.00 FINISHED SIZE 23.5" x 23.5" x 1.41" PE-RT RPB 1-30-15 DIMENSIONS ARE IN INCHES D C B AA B C D 12345678 8 7 6 5 4 3 2 1 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF THERMA-HEXX CORPORATION. ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF THERMA-HEXX IS PROHIBITED. PROPRIETARY AND CONFIDENTIAL MATERIAL DRAWN COMMENTS: DATENAMEUNLESS OTHERWISE SPECIFIED: SHEET 1 OF 1 1-30-15 THERMAPANEL ASSEMBLY DO NOT SCALE DRAWING DWG. NO. (603) 319-8815 www.therma-hexx.com Therma- HEXX Product Specifications Dimensions:Dimensions: 23.375” x 23.375” x 1.375” Full Panel 23.375“ x 23.375” x 1.375“ Trimmable Panel (Trimmable to 23.375” x 12.75” x 1.375“) 23.5” x 11.5” x 1.375” Half Panel 23.5” x 23.5” x 1.375” Filler Panel Panels are 3/8” thick when mounted on pedestals. 1” EPS insulaƟon extends beneath top of pedestal. Ground mounted Panels are 1.375” thick, edge to edge. Material:Material: Bimodal Copolymer of LLDPE and HDPE PE-RT 2499 ASTM F2623 Fluid capacity:Fluid capacity: Approximately 0.26 US gallons / full panel Amount varies with interconnect configuraƟon Maximum operaƟng temperature / pressure:Maximum operaƟng temperature / pressure: 30 PSI @ 140 degrees F (or as marked on panels) Recommended system staƟc (resƟng) pressure: Recommended system staƟc (resƟng) pressure: 10-15 psi Maximum panels per row:Maximum panels per row: 24 (48 lineal Ō / 96 sq Ō) ConnecƟons:ConnecƟons: Socket Fusion, Push on connectors, Crimp, Compression ASTM F1807 - F2159 - D2683 25 year limited warranty 25 year limited warranty 100% made in the U.S.A. 100% made in the U.S.A. RecyclableRecyclable Master Spec SecƟon 32-17-43 Pavement Snow MelƟng SystemsMaster Spec SecƟon 32-17-43 Pavement Snow MelƟng Systems Full / Trimmable Panel Half Panel Permeable Protective Panel 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Panels: LD Pedestal Mount ThermaPANEL - No Oxygen Barrier 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Manifolds: Legend 1” Stainless Steel Manifold w/ Iso and Fill/Purge) 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Fittings: Sioux Chief ½” Copper PEX Crimp ASTM F1807 Crimp™ American Society for Testing and Materials (ASTM) Standard Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing. F1807 Installation 3. Install PEX fitting into tube end. 5. Compress tool perpendicular to tubing run. Compress only once. Remove defective connections. Use a gauge to assure a proper joint. Test completed joint. 1. Cut tube at 90-degrees. Do not crush OD of tubing with cutters. Hint: Slightly rotate cutter during blade engagement. 2. Install PEX Crimp Ring onto OD of tubing. 4. Position ring over sealing barbs of the fitting. The ring should be positioned approximately 1/8" to 1/4" from the end of the tube. F1807 fittings can be made from various listed materials. See ASTM standard for acceptable brass alloys. Assure your fitting is made from a listed material. F1807 systems use a copper crimp ring to compress around a fitting. Connection is made by positioning a crimp ring over a fitting’s sealing barbs and compressing it into position. Fittings are reusable if barbs remain undamaged. ASTM F1807 Crimp Installations & Application Problems 13 www.siouxchief.com F1807 Application Problems Crimp joint made with an improperly calibrated tool - not providing enough compression to joint. Ring compressed multiple times possibly developing a leak path. Crimp Tool did not engage the Crimp Ring over the entire surface of the ring. Tube not cut squarely – ring not compressing tube for a secure seal. Fitting not inserted completely into tube end. Ring not placed over sealing barbs of fitting. Ring too far forward or too far back & not fully over sealing barbs. ASTM F1807 Crimp Installations & Application Problems PowerPEX ASTM F1807 Crimp fittings are made for use with a copper crimp ring or Sioux Chief's ASTM F877 V-Sleeve ONLY. Cinch type or pinch type clamps and rings, hose clamps or other proprietary clamps are not covered by Sioux Chief's Warranty. www.siouxchief.com 14 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Glycol Feeder: Axiom DMF300 17 Gal 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Controller: Tekmar 680 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Sensor Socket: Tekmar 091 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Snow and Slab Sensor: Tekmar 090 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 T 4"Ø HOLE FOR SOCKET Therma-HEXX TRIMMABLE PANEL PEDESTAL PAVER SENSOR INSTALL CAP TO BE SET FLUSH WITH TOP OF PAVER. MORTAR BRASS HOUSING INTO PAVER WITH CEMENT FOR THERMAL CONDUCTIVITY BETWEEN HOUSING AND PAVER. 7 8" ELECTRICAL CONDUIT CONNECTION 31 2" 4" HOLE SUPPORT HOUSING WITH PEDESTAL DATE:SCALE: PR O J E C T : TITLE: SHEET: DRAWN BY:CHECKED BY: REV DESCRIPTION DATE BY 199 CONSTITUTION AVE. SUITE 7 PORTSMOUTH, NH 03801 (603) 319-8815 SNOWMELT SENSOR INSTALL DETAIL RE F E R E N C E N/A7/22/20 RPB 1 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 Tubing: ThermaTUBE PE-RT Tubing ½” x 300’ – No Oxygen Barrier 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815 199 Constitution Ave., Suite 7 Portsmouth, New Hampshire 03801 www.thermahexx.com 603.319.8815