HomeMy WebLinkAbout1039 E Cooper_Mech RDS Exceptions Application and Exhibits_11.4.20 1 | Page 300 SO SPRING ST | 202 | ASPEN, CO 81611 970.925.2855 | BENDONADAMS.COM November 4, 2020 Garrett Larimer, Planner Community Development 130 S Galena Street Aspen CO 81611 RE: 1039 E Cooper AC Installation, Unit 30A Mr. Larimer: As requested, we have outlined the proposed scope of work for the installation of AC unit located at 1039 East Cooper Avenue Unit 30A. The applicant is proposing to install a wall mounted AC unit on the exterior of the building adjacent to the unit’s patio. The AC unit is a Mitsubishi M-Series and is approximately 42” x 37” x 13” – the unit is stereotypical for what you’d see in other Aspen homes. The applicant is also proposing to add three new skylights and an additional non-orthogonal window which are illustrated in Exhibit A: Exterior Elevations. In speaking with staff, we understand that both proposals qualify for exemptions and we have provided additional detail below illustrating compliance with the Land Use Code and regulations for AC units. As indicated in the images to the right, the unit is one of the furthest away from East Cooper Avenue and is located on the third floor of the building. 2 | Page 300 SO SPRING ST | 202 | ASPEN, CO 81611 970.925.2855 | BENDONADAMS.COM 1. 26.575.020.E.5.N Heating and air conditioning equipment and similar mechanical equipment shall have the following requirements: 1. Prohibited between any lot line adjacent to a street and any structure; and 2. Shall be located at least double the minimum setback for a primary structure from any lot line adjacent to a street; and 3. If visible from the street, these features shall be screened in accordance with Section 26.575.050, Fences; and 4. If located within a setback not adjacent to a street, these features shall not exceed thirty (30) inches above or below finished grade. These features may be up to thirty (30) inches above and below finished grade simultaneously. The Community Development Director may approve exceptions to the requirements of m) and n) above. The Community Development Director must first determine that the visual impact of the exemption is minimal and that no other reasonable option exists. Approval shall be in the form of a recordable administrative determination. Response: The proposed AC unit will be mounted on the exterior of the third story of the building facing towards the back of the property. Per the City’s regulations, the Community Development Director has the authority to approve exceptions to these regulations. The footprint of the AC unit is minimal, and due to the unit being located on the back of the building on the southern elevation hundreds of feet from East Cooper Street. The unit is not located within a setback. The location of the unit can be seen in aerial below in orange: While the applicant is subject to the Multi-Family Residential Design Standards, we believe that the standards are not applicable due to the location of the unit at the rear of the building, and due to the fact that it is not street facing. We have outlined our responses to the standards below and have also provided further explanation of the scope of work for your reference. 3 | Page 300 SO SPRING ST | 202 | ASPEN, CO 81611 970.925.2855 | BENDONADAMS.COM Standard Complies Alternative Compliance NA Notes B.1 Building Orientation (Flexible) X There are changes proposed to building orientation, therefore this standard does not apply. B.2 Garage Access (Non-Flexible) X The development has a parking lot for owners to use, therefore this standard does not apply. B.3 Garage Placement (Non-Flexible) X The development has a parking lot for owners to use, therefore this standard does not apply. B.4 Entry Connection (Non-Flexible) X There are no proposed changes to the entry of the unit, which is accessed via a shared interior stairwell, therefore this standard does not apply. B.5 Principle Window (Flexible) X The changes to windows within the unit are not street-facing, therefore this standard does not apply. The applicant is proposing an interior remodel which will include the three skylights mentioned above, illustrated in the roof plan in the drawings provided. Additionally, the applicant is proposing to add a window above the proposed AC unit which will match the existing. The AC unit and the new window will be the only elements of the renovation that will be visible form the exterior. Please see below for the existing and proposed conditions: 4 | Page 300 SO SPRING ST | 202 | ASPEN, CO 81611 970.925.2855 | BENDONADAMS.COM We believe this application contains the necessary information for a complete and competent review. Please let us know if additional information is needed. We look forward to your review and will make ourselves available for any questions or concerns you have. We can also arrange a site visit at your request. Kind Regards, Reilly Thimons, Planner BendonAdams LLC Attachments: 1. Land Use Application Packet 2. RDS Application Packet 3. Drawings CITY OF ASPEN COMMUNITY DEVELOPMENT DEPARTMENT City of Aspen|130 S. Galena St.|(970) 920 5090 April 2020 Agreement to Pay Application Fees Please type or print in all caps Representative Name (if different from Property Owner) Contact info for billing: e-mail: Phone: I understand that the City has adopted, via Ordinance No. 30, Series of 2017, review fees for Land Use applications and payment of these fees is a condition precedent to determining application completeness. I understand that as the property owner that I am responsible for paying all fees for this development application. For flat fees and referral fees: I agree to pay the following fees for the services indicated. I understand that these flat fees are non-refundable. $. flat fee for . $. flat fee for $. flat fee for . $. flat fee for For Deposit cases only: The City and I understand that because of the size, nature or scope of the proposed project, it is not possible at this time to know the full extent or total costs involved in processing the application. I understand that additional costs over and above the deposit may accrue. I understand and agree that it is impracticable for City staff to complete processing, review and presentation of sufficient information to enable legally required findings to be made for project consideration, unless invoices are paid in full. The City and I understand and agree that invoices mailed by the City to the above listed billing address and not returned to the City shall be considered by the City as being received by me. I agree to remit payment within 30 days of presentation of an invoice by the City for such services. I have read, understood, and agree to the Land Use Review Fee Policy including consequences for no-payment. I agree to pay the following initial deposit amounts for the specified hours of staff time. I understand that payment of a deposit does not render and application complete or compliant with approval criteria. If actual recorded costs exceed the initial deposit, I agree to pay additional monthly billings to the City to reimburse the City for the processing of my application at the hourly rates hereinafter stated. $ deposit for hours of Community Development Department staff time. Additional time above the deposit amount will be billed at $325.00 per hour. $ deposit for hours of Engineering Department staff time. Additional time above the deposit amount will be billed at $325.00 per hour. City of Aspen: Phillip Supino, AICP Community Development Director City Use: Fees Due: $ Received $ Case # Signature: PRINT Name: Title: An agreement between the City of Aspen (“City”) and Address of Property: 1039 E Cooper Unit 30A Property Owner Name: Billing Name and Address - Send Bills to: Reilly Thimons/BendonAdams Jim Baldwin, 1039 E Cooper, Unit 30A, Aspen CO 81611 jim.baldwin@kdrp.com 325.00 Planning Owner Huckelbutt House LLC c/o Jim Baldwin Huckelbutt House LLC c/o Jim Baldwin DocuSign Envelope ID: FFAD8AE8-0740-4DFB-8667-6C69F2C9F352 CITY OF ASPEN COMMUNITY DEVELOPMENT DEPARTMENT City of Aspen|130 S. Galena St.|(970) 920 5090 April 2020 LAND USE APPLICATION APPLICANT: REPRESENTIVATIVE: Review: Administrative or Board Review Required Land Use Review(s): Growth Management Quota System (GMQS) required fields: Net Leasable square footage Lodge Pillows Free Market dwelling units Affordable Housing dwelling units Essential Public Facility square footage Have you included the following? FEES DUE: $ Pre-Application Conference Summary Signed Fee Agreement HOA Compliance form All items listed in checklist on PreApplication Conference Summary Name: Address: Phone#: email: Address: Phone #: email: Name: Project Name and Address: Parcel ID # (REQUIRED) 1039 E Cooper, Unit 30A, Aspen, CO 81611 273707342035 Huckelbutt House LLC c/o Jim Baldwin 1039 E Cooper, Unit 30A, Aspen, CO 81611 jim.baldwin@kdrp.com Reilly Thimons 300 S Spring Street, Ste 202, Aspen, CO 81611 970.925.2855 Ext. 3 reilly@bendonadams.com Description: Existing and Proposed Conditions The applicant is proposing to install a wall mounted AC unit on the third story exterior of the building facing the back of the property, in addition to a new window. The project is also subject to Multi-Family Residential Design Standards. Staff review Stream Margin Exemption 325.00 XX NA NA DocuSign Envelope ID: FFAD8AE8-0740-4DFB-8667-6C69F2C9F352 CITY OF ASPEN COMMUNITY DEVELOPMENT DEPARTMENT April 2020 City of Aspen|130 S. Galena St.|(970) 920 5090 Homeowner Association Compliance Policy All land use applications within the City of Aspen are required to include a Homeowner Association Compliance Form (this form) certifying the scope of work included in the land use application complies with all applicable covenants and homeowner association policies. The certification must be signed by the property owner or Attorney representing the property owner. Property Owner (“I”): Name: Email: Phone No.: Address of Property: (subject of application) I certify as follows: (pick one) □This property is not subject to a homeowners association or other form of private covenant. □This property is subject to a homeowners association or private covenant and the improvementsproposed in this land use application do not require approval by the homeowners association orcovenant beneficiary. □This property is subject to a homeowners association or private covenant and the improvementsproposed in this land use application have been approved by the homeowners association or covenant beneficiary. I understand this policy and I understand the City of Aspen does not interpret, enforce, or manage the applicability, meaning or effect of private covenants or homeowner association rules or bylaws. I understand that this document is a public document. Owner signature: date: Owner printed name: or, Attorney signature: date: Attorney printed name: Huckelbutt House LLC c/o Jim Baldwin jim.baldwin@kdrp.com 1039 E Cooper, Unit 30A Aspen, CO 81611 Huckelbutt House LLC c/o Jim Baldwin 10.5.20 X DocuSign Envelope ID: FFAD8AE8-0740-4DFB-8667-6C69F2C9F352 Residential Design Standards Administrative Review Section 26.410.020.B. of the Land Use Code requires an Administrative Review for compliance with the Residential Design Standards (RDS) for all residential projects, unless otherwise exempted pursuant to Section 26.410.010.C. All residential projects affecting the exterior of the building shall submit for RDS Administrative Review prior to building permit submittal. If exterior work is proposed, and the scope of work meets one of the exemptions listed above, staff shall provide a signed exemption form to be included in the building permit application. Review Process: The Community Development Department staff shall review an application for applicability and compliance with Chapter 26.410, Residential Design Standards. If the application complies with all applicable standards as written, a signed Checklist and stamped plan set shall be provided to the applicant to be included with building permit submission. If the application does not comply with one or more applicable standards, an unsigned Checklist and redlined plan set shall be emailed to the applicant including comments from staff on which standard(s) the application does not comply with and a description of why the standard(s) is not compliant. The applicant shall be provided the opportunity to revise and resubmit the design in response to the comments. Staff will keep an application open for 30 days from the date an unsigned Checklist is emailed to the applicant. If after such time no revisions are submitted, the application will expire. Application for RDS Administrative Review: An application for RDS Administrative Review that DOES NOT require Alternative Compliance (see Page 2) shall be submitted to the Community Development front desk on a USB drive or emailed to planneroftheday@gmail.com. Applicants will be notified of received application by email and if additional documents are required. Certain application requirements may be waived by staff depending on the scope of work. An application for RDS Administrative Review shall include the following documents in digital format: • Site improvement survey certified by a registered land surveyor (no older than one year from submittal date) • Proposed Site plan (scaled 24”x36”) • Proposed Floor plans (scaled 24”x36”) • Proposed Elevations (scaled 24”x36”) • Existing Elevations if a remodel (scaled 24”x36”) • Complete scope of work noting all exterior areas affected by the proposed project • Complete RDS applicant checklist (attached) addressing how each standard is met with sheet references for each standard Page 1 of 2 Alternative Compliance or Variation: Pursuant to 26.410.020.C, projects that do not meet the criteria for Administrative Review or Alternative Compliance (as determined by staff) may be reviewed by the Planning & Zoning Commission, or HPC if appropriate, at the applicant’s request. An applicant may choose to apply directly for a Variation from the Planning & Zoning Commission or Historic Preservation Commission, pursuant to Chapter 26.410.020.C. A pre-application summary will be required for an Alternative Compliance or Variation request. Application for Alternative Compliance or Variation: An application for Alternative Compliance or a Variation will require a pre-application summary provided by Community Development staff, and shall be submitted as a Land Use Application. Required application submittal items shall be outlined in the pre-application summary. Page 2 of 2 Residential Design Standards Administrative Review Residential Design Standards Administrative Compliance Review Applicant Checklist - Multi-family Development Standard Complies Alternative Compliance N/A Sheet #(s)/Notes B.1.Building Orientation (Flexible) B.2.Garage Access (Non-flexible) B.3.Garage Placement (Non-flexible) B.4.Entry Connection (Non-flexible) B.5Principle Window (Flexible) Instructions: Please fill out the checklist below, marking whether the proposed design complies with the applicable standard as written or is requesting Alternative Compliance (only permitted for Flexible standards). Also include the sheet #(s) demonstrating the applicable standard. If a standard does not apply, please mark N/A and include in the Notes section why it does not apply. If Alternative Compliance is requested for a Flexible standard, include in the Notes section how the proposed design meets the intent of the standard(s). Additional sheets/graphics may be attached. Disclaimer: This application is only valid for the attached design. If any element of the design subject to Residential Design Standards changes prior to or during building permit review, the applicant shall be required to apply for a new Administrative Compliance Review. Address: Parcel ID: Zone District/PD: Representative: Email: Phone: Page 1 of 1 WP AR T AR T BE N C H MILLWORK CLOSET BAR K Q FFF 104 MAIN BEDROOM 106 BEDROOM 107 BUNK ROOM 103 SHARED BATHROOM 105 MAIN BATHROOM 102 LIVING ROOM / FAMILY ROOM 101 KITCHEN 100 ENTRY HALL 108 LAUNDRY 1 A5.1 DW DESK FO L D D O W N W A L L S T O R A G E DE S K NOT IN SCOPE STAIR HALL AND NEIGHBOR UNITS 2' - 6" TWIN ABOVEDE S K MINI-SPLIT A/C UNIT NEW CLERESTORY WINDOW rowland+broughton architecture / urban design / interior design 500 w. main st. aspen, co 81611 970.544.9006 1830 blake st. denver, co 80202 303.308.1373 Consultants: Issuances and Revisions: COPYRIGHT 2020 ROWLAND + BROUGHTON ARCHITECTURE AND URBAN DESIGN THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. SCALE: SHEET TITLE: PROJECT NO: Fi l e P a t h : Pl o t D a t e :NOT FOR CONSTRUCTIONC: \ U s e r s \ a c o o k \ D o c u m e n t s \ 2 2 0 2 5 . 0 0 _ B A L D W I N _ a d a m . c o o k C C P 4 E . r v t 9/ 1 7 / 2 0 2 0 4 : 3 2 : 1 7 P M 1/4" = 1'-0" A2.1 22025.00 BALDWIN 1039 E COOPER AVE, UNIT 30A ASPEN, CO 81611 PROPOSED MAIN LEVEL FLOOR PLAN SCALE: PLAN NORTH TRUE NORTH A2.1 1/4" = 1'-0" 1 MAIN LEVEL FLOOR PLAN TBD PERMIT W/D M M L L 17 17 13 13 15 15 EXISTING ELECTRIC PANEL NICHE WITH COUNTERTOP AND LIGHTS STACKED WASHER AND DRYER HOT WATER TANK 1 PRIMARY BEDROOM 2 BEDROOM 3 BUNK ROOM 4 LAUNDRY 1a OPEN CLOSET 1b PRIMARY BATHROOM 5 SHARED BATHROOM 6a CLOSET 7a PANTRY 7 KITCHEN 8 LIVING ROOM / FAMILY ROOM 2a CLOSET 6 HALL 6b CLOSET RE F NOT IN SCOPE STAIR HALL AND NEIGHBOR UNITS EXISTING DECK NOT IN SCOPE EXISTING FP A4.1 1 M M L L 17 17 13 13 15 15 H.P. DN DN B.O. CLG 8' - 4" B.O. CLG 11' - 4" B.O. CLG 7' - 7" B.O. CLG 8' - 0" B.O. CLG 8' - 0" EXISTING BEAMS, TYP. A4.1 1 rowland+broughton architecture / urban design / interior design 500 w. main st. aspen, co 81611 970.544.9006 1830 blake st. denver, co 80202 303.308.1373 Consultants: Issuances and Revisions: COPYRIGHT 2020 ROWLAND + BROUGHTON ARCHITECTURE AND URBAN DESIGN THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. SCALE: SHEET TITLE: PROJECT NO: Fi l e P a t h : Pl o t D a t e :NOT FOR CONSTRUCTIONC: \ U s e r s \ a c o o k \ D o c u m e n t s \ 2 2 0 2 5 . 0 0 _ B A L D W I N _ a d a m . c o o k C C P 4 E . r v t 9/ 1 7 / 2 0 2 0 4 : 3 2 : 1 9 P M 1/4" = 1'-0" A2.1e 22025.00 BALDWIN 1039 E COOPER AVE, UNIT 30A ASPEN, CO 81611 EXISTING LEVEL 1 PLANS SCALE: PLAN NORTH TRUE NORTH A2.1e 1/4" = 1'-0" 1 EXISTING LEVEL 1 PLAN SCALE: PLAN NORTH TRUE NORTH A2.1e 1/4" = 1'-0" 2 EXISTING LEVEL 1 RCP TBD PERMIT 1 A5.1 PROPOSED SKYLIGHTS PROPOSED SKYLIGHTS M M L L 17 17 13 13 15 15 A4.1 1 rowland+broughton architecture / urban design / interior design 500 w. main st. aspen, co 81611 970.544.9006 1830 blake st. denver, co 80202 303.308.1373 Consultants: Issuances and Revisions: COPYRIGHT 2020 ROWLAND + BROUGHTON ARCHITECTURE AND URBAN DESIGN THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. SCALE: SHEET TITLE: PROJECT NO: Fi l e P a t h : Pl o t D a t e :NOT FOR CONSTRUCTIONC: \ U s e r s \ a c o o k \ D o c u m e n t s \ 2 2 0 2 5 . 0 0 _ B A L D W I N _ a d a m . c o o k C C P 4 E . r v t 9/ 1 7 / 2 0 2 0 4 : 3 2 : 2 0 P M 1/4" = 1'-0" A2.3 22025.00 BALDWIN 1039 E COOPER AVE, UNIT 30A ASPEN, CO 81611 ROOF LEVEL PLANS SCALE: PLAN NORTH TRUE NORTH A2.3 1/4" = 1'-0" 2 ROOF LEVEL PLAN TBD PERMIT SCALE: PLAN NORTH TRUE NORTH A2.3 1/4" = 1'-0" 1 EXISTING ROOF PLAN LEVEL 3 7895' -0" T.O. PLY NEW WINDOW TO MATCH EXISTING NEW SLIDING DOOR TO MATCH EXISTING NEW WINDOW NEW MINI-SPLIT A/C UNIT. WALL MOUNT. NO CHANGE ± 7 ' - 5 1 / 2 " NO CH A N G E ± 1 2 ' - 5 5 / 8 " LEVEL 3 7895' -0" T.O. PLY EXISTING WINDOW EXISTING SLIDING DOOR rowland+broughton architecture / urban design / interior design 500 w. main st. aspen, co 81611 970.544.9006 1830 blake st. denver, co 80202 303.308.1373 Consultants: Issuances and Revisions: COPYRIGHT 2020 ROWLAND + BROUGHTON ARCHITECTURE AND URBAN DESIGN THE INFORMATION AND DESIGN INTENT CONTAINED ON THIS DOCUMENT IS THE PROPERTY OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. NO PART OF THIS INFORMATION MAY BE USED WITHOUT THE PRIOR WRITTEN PERMISSION OF ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN. ROWLAND+BROUGHTON ARCHITECTURE AND URBAN DESIGN SHALL RETAIN ALL COMMON LAW STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING COPYRIGHT THERETO. SCALE: SHEET TITLE: PROJECT NO: Fi l e P a t h : Pl o t D a t e :NOT FOR CONSTRUCTIONC: \ U s e r s \ a c o o k \ D o c u m e n t s \ 2 2 0 2 5 . 0 0 _ B A L D W I N _ a d a m . c o o k C C P 4 E . r v t 9/ 1 7 / 2 0 2 0 4 : 3 2 : 2 0 P M 1/4" = 1'-0" A4.1 22025.00 BALDWIN 1039 E COOPER AVE, UNIT 30A ASPEN, CO 81611 EXTERIOR ELEVATIONS TBD PERMIT SCALE:A4.1 1/4" = 1'-0" 2 PROPOSED EXTERIOR ELEVATION SCALE:A4.1 1/4" = 1'-0" 1 EXISTING EXTERIOR ELEVATION