HomeMy WebLinkAboutGorsuchHaus DRC_BuildingComments_2.1GorsuchHaus DRC_BuildingComments_2draft Subject: PlanCheck Page: G0 Page Index: 1 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Wood is not permitted for use in Type I construction except as allowed by 603.1. Fire-retardant-treated wood is not permitted for balconies, porches, decks and exterior stairways for Type I buildings that are greater than 3 stories above grade plane (1406.3). Heavy timber may only be used as a substitute for a 1 hour fire rating but Type I requires 2 hour (601). Wood appears to be a significant design element for this project; clearly demonstrate compliance. 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf (35) Subject: PlanCheck Page: G0 Page Index: 1 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf As discussed later, over 500 occupants exit from this narrow, covered, below grade location. Over 200 occupants use it as their single exit. It is to be shared with the public as a public amenity. Subject: PlanCheck Page: G021 Page Index: 4 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Not IRC Subject: PlanCheck Page: G021 Page Index: 4 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Van accessible parking requires 98" of headroom. ICC/A117.1-2009 section 502.6 Subject: PlanCheck Page: G021 Page Index: 4 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf 2020 NEC Wood is not permitted for use in Type I construction except as allowed by 603.1. Fire-retardant-treated wood is not permitted for balconies, porches, decks and exterior stairways for Type I buildings that are greater than 3 stories above grade plane (1406.3). Heavy timber may only be used as a substitute for a 1 hour fire rating but Type I requires 2 hour (601). Wood appears to be a significant design element for this project; clearly demonstrate compliance. As discussed later, over 500 occupants exit from this narrow, covered, below grade location. Over 200 occupants use it as their single exit. It is to be shared with the public as a public amenity. GOVERNING CODES ARCHITECTURAL DESIGN:2015 INTERNATIONAL BUILDING CODE (IBC) 2015 INTERNATIONAL RESIDENTIAL CODE (IRC) STRUCTURAL DESIGN:2015 INTERNATIONAL BUILDING CODE (IBC) MECHANICAL, PLUMBING, AND FIRE PROTECTION DESIGN: 2015 INTERNATIONAL MECHANICAL CODE (IMC) 2015 INTERNATIONAL PLUMBING CODE (IPC) 2015 INTERNATIONAL FIRE CODE, AS REFEREED BY IBC (IFC) 2015 INTERNATIONAL FUEL GAS CODE (IFGC) ELECTRICAL DESIGN:2017 NATIONAL ELECTRICAL CODE (NEC) ENERGY CONSERVATION DESIGN:2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2015 SOLAR ENERGY PROVISIONS POOL AND SPA DESIGN:2015 INTERNATIONAL SWIMMING POOL AND SPA CODE ACCESSIBILITY DESIGN: ICC/ANSI A117.1 -2009 CODE SUMMARY BUILDING ADDRESS: ASPEN, CO 81611 USE AND OCCUPANCY CLASSIFICATIONS -CHAPTER 3 • R-1 (HOTEL ROOMS) PER SECTION 310.3 TABLE 601 FIRE-RESISTANCE RAT TYPES OF CONSTRUCTION BUILDING ELEMENT PRIMARY STRUCTURAL FRAME f( BEARING WALLS EXTERIOR INTERIOR NONBEARING WALLS AND PARTIT EXTERIOR NONBEARING WALLS AND PARTIT INTERIOR FLOOR CONSTRUCTION AND ASS ROOF CONSTRUCTION AND ASSO TABLE 602 FIRE-RESISTANCE RAT FIRE SEPARATION DISTANCE = X (feet) X < 5b 5 ≤ X < 10 Not IRC L ROOMS) PER SECTION 310.3 DOS) PER SECTION 310.4 ATE GARAGE) PER SECTION 311.3 AURANTS AND BARS) PER SECTION 303.3 ITY SPACES AND FITNESS) PER SECTION 303.4 S AND SPA) PER SECTION 304.1 - BUILDING HEIGHT AND NUMBER OF STORIES: GHT: ALLOWABLE BUILDING HEIGHT OF R-OCCUPANCY TYPE IB SPRINKLERED BUILDING IS 180 FEET. THIS ED THE AVERAGE ROOF HEIGHT TO THE GRADE PLANE. THE RESULTING BUILDING HEIGHT IS CALCULATED XIMATELY 43 FEET. EL 03 AND ABOVE QUALIFY AS STORIES ABOVE GRADE PLANE RESULTING IN THE BUILDING BEING S A 7-STORY BUILDING. PER TABLE 504.4 A R-1 OCCUPANCY TYPE IB SPRINKLERED BUILDING HAS AN NUMBER OF STORIES OF 12. TABLE 705.8 MAX AREA OF EXTERIOR WALL OPENING PROTECTION REFER SHEET G099 0' TO LESS THAN 3' FIRE SEPARATION DISTAN 3' TO LESS THAN 5' FIRE SEPARATION DISTAN 5' TO LESS THAN 10' FIRE SEPARATION DISTA 10' TO LESS THAN 15' FIRE SEPARATION DIST 15' TO LESS THAN 20' FIRE SEPARATION DIST 20' TO LESS THAN 25' FIRE SEPARATION DIST 25' TO LESS THAN 30' FIRE SEPARATION DIST 30' OR GREATER FIRE SEPARATION DISTANC * UNPROTECTED OPENINGS IN A BUILDING W CAN UTILIZE THE ALLOWANCES OF PROTECT SECTION 708 FIRE PARTITIONS FIRE PARTITIONS SHALL HAVE A FIRE-RESIST SECTION 711 HORIZONTAL ASSEMBLIES THE SUPPORTING CONSTRUCTION SHALL BE THE HORIZONTAL ASSEMBLY SUPPORTED. (I WHERE HORIZONTAL ASSEMBLIES SEPARAT RATING OF NOT LESS THAN THAT REQUIRED R OCCUPANCIES FROM ADJACENT OCCUPAN INTERIOR WALL AND CEILING FINISH REQUIR PROVIDE FLAMESPREAD CERTIFICATION OF -HIGH-RISE BUILDINGS WITH ALL BUILDING CODE HIGH RISE PROVISIONS WAS DEMONSTRATED EITHER BY PRESCRIPTION OR Y WITH THE FOLLOWING ITEMS DEEMED NOT APPLICABLE: QUIREMENT FOR ENHANCED SFRM BONDING STRENGTH DEEMED NOT APPLICABLE AS THE HAZARDS ADDRESSED BY THE PROVISION DO NOT EXIT FOR THIS PROJECT/DESIGN. ONDARY WATER SUPPLY -DETERMINATION OF THE APPLICABLE SEISMIC DESIGN CATEGORY PENDING. E COMMAND CENTER -FORM OF FCC AND CONTENTS TBD IN CONCERT WITH ASPEN FIRE. NDBY POWER FOR ELEVATORS -DEEMED NOT APPLICABLE AS HAZARDS ADDRESSED BY THE PROVISION NOT EXIST FOR THIS PROJECT/DESIGN. OKEPROOF EXIT ENCLOSURES -DEEMED NO APPLICABLE AS HAZARDS ADDRESSED BY THE PROVISION DO T EXIST FOR THIS PROJECT/DESIGN -MOTOR-VEHICLE-RELATED OCCUPANCIES T IN VEHICLE AND PEDESTRIAN TRAFFIC AREA IS NOT TO BE LESS THAN 7'-0". VEHICLE AND PEDESTRIAN MMODATING VAN-ACCESSIBLE PARKING SHALL COMPLY WITH SECTION 1106.5 (IBC 406.3.2) L VENTILATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL 6.6.2). C SPRINKLER SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 903.2.10 (IBC 406.6.3). -GROUPS R-1 & R-2: RATING UNITS IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE N 708 (IBC 420.2). G ASSEMBLIES SEPARATING UNITS IN THE SAME BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL N ACCORDANCE WITH SECTION 711 (IBC 420.3). AND DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY -CHAPTER 4 BUILDING HEIGHTS AND AREAS -CHAPTER 5 - BUILDING AREA: 10 ≤ X < 30 X ≥ 30 FIRE AND SMOKE PROTECTION FE INTERIOR FINISHES -CHAPTER 8 GROUP R-2 S-2 A-2 A-3f B, R-1 INTERIOR EXIT STAIRWAYS A RAMP AND EXIT PASSAGEWAY C C B B B Van accessible parking requires 98" of headroom. ICC/A117.1-2009 section 502.6 GOVERNING CODES ARCHITECTURAL DESIGN:2015 INTERNATIONAL BUILDING CODE (IBC) 2015 INTERNATIONAL RESIDENTIAL CODE (IRC) STRUCTURAL DESIGN:2015 INTERNATIONAL BUILDING CODE (IBC) MECHANICAL, PLUMBING, AND FIRE PROTECTION DESIGN: 2015 INTERNATIONAL MECHANICAL CODE (IMC) 2015 INTERNATIONAL PLUMBING CODE (IPC) 2015 INTERNATIONAL FIRE CODE, AS REFEREED BY IBC (IFC) 2015 INTERNATIONAL FUEL GAS CODE (IFGC) ELECTRICAL DESIGN:2017 NATIONAL ELECTRICAL CODE (NEC) ENERGY CONSERVATION DESIGN:2015 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2015 SOLAR ENERGY PROVISIONS POOL AND SPA DESIGN:2015 INTERNATIONAL SWIMMING POOL AND SPA CODE ACCESSIBILITY DESIGN: ICC/ANSI A117.1 -2009 CODE SUMMARY BUILDING ADDRESS: ASPEN, CO 81611 USE AND OCCUPANCY CLASSIFICATIONS -CHAPTER 3 • R-1 (HOTEL ROOMS) PER SECTION 310.3 • R-2 (CONDOS) PER SECTION 310.4 • S-2 (PRIVATE GARAGE) PER SECTION 311.3 • A-2 (RESTAURANTS AND BARS) PER SECTION 303.3 • A-3 (AMENITY SPACES AND FITNESS) PER SECTION 303.4 • B (OFFICES AND SPA) PER SECTION 304.1 SPECIAL AND DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY -CHAPTER 4 TABLE 601 FIRE-RESISTANCE TYPES OF CONSTRUCT BUILDING ELEMENT PRIMARY STRUCTURAL FRAM BEARING WALLS EXTERIOR INTERIOR NONBEARING WALLS AND PA EXTERIOR NONBEARING WALLS AND PA INTERIOR FLOOR CONSTRUCTION AND ROOF CONSTRUCTION AND A TABLE 602 FIRE-RESISTANCE FIRE SEPARATION DISTANCE = X (feet X < 5b 5 ≤ X < 10 10 ≤ X < 30 X ≥ 30 FIRE AND SMOKE PROT 2020 NEC Subject: PlanCheck Page: G021 Page Index: 4 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Need to be seismic design category B to be exempt from secondary water supply. Subject: PlanCheck Page: G021 Page Index: 4 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf We need to have a letter requesting exemption/alternate method and detailing how your design has equivalent safety. Subject: PlanCheck Page: G022 Page Index: 5 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Class A required by Ordinance 40, 2016 Subject: PlanCheck Page: G023 Page Index: 6 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf 2015 IBC 403.2.4 requires a SFRM minimum bond strength of 430 psf for buildings under 421 feet, which includes this building. Subject: PlanCheck Page: G023 Page Index: 6 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Have a structural engineer determine your seismic design category. 2015 SOLAR ENERGY PROVISIONS POOL AND SPA DESIGN:2015 INTERNATIONAL SWIMMING POOL AND SPA CODE ACCESSIBILITY DESIGN: ICC/ANSI A117.1 -2009 CODE SUMMARY BUILDING ADDRESS: ASPEN, CO 81611 USE AND OCCUPANCY CLASSIFICATIONS -CHAPTER 3 • R-1 (HOTEL ROOMS) PER SECTION 310.3 • R-2 (CONDOS) PER SECTION 310.4 • S-2 (PRIVATE GARAGE) PER SECTION 311.3 • A-2 (RESTAURANTS AND BARS) PER SECTION 303.3 • A-3 (AMENITY SPACES AND FITNESS) PER SECTION 303.4 • B (OFFICES AND SPA) PER SECTION 304.1 TABLE 705.8 MAX AR OPENING PROTECTI REFER SHEET G099 0' TO LESS THAN 3' F 3' TO LESS THAN 5' F 5' TO LESS THAN 10' 10' TO LESS THAN 15 15' TO LESS THAN 20 20' TO LESS THAN 25 25' TO LESS THAN 30 30' OR GREATER FIR * UNPROTECTED OP CAN UTILIZE THE ALL SECTION 708 FIRE PA FIRE PARTITIONS SH SECTION 711 HORIZO THE SUPPORTING C THE HORIZONTAL AS WHERE HORIZONTA RATING OF NOT LES R OCCUPANCIES FR SECTION 403 -HIGH-RISE BUILDINGS COMPLIANCE WITH ALL BUILDING CODE HIGH RISE PROVISIONS WAS DEMONSTRATED EITHER BY PRESCRIPTION OR EQUIVALENCY WITH THE FOLLOWING ITEMS DEEMED NOT APPLICABLE: 1. REQUIREMENT FOR ENHANCED SFRM BONDING STRENGTH DEEMED NOT APPLICABLE AS THE HAZARDS ADDRESSED BY THE PROVISION DO NOT EXIT FOR THIS PROJECT/DESIGN. 2. SECONDARY WATER SUPPLY -DETERMINATION OF THE APPLICABLE SEISMIC DESIGN CATEGORY PENDING. 3. FIRE COMMAND CENTER -FORM OF FCC AND CONTENTS TBD IN CONCERT WITH ASPEN FIRE. 4. STANDBY POWER FOR ELEVATORS -DEEMED NOT APPLICABLE AS HAZARDS ADDRESSED BY THE PROVISION DO NOT EXIST FOR THIS PROJECT/DESIGN. 5. SMOKEPROOF EXIT ENCLOSURES -DEEMED NO APPLICABLE AS HAZARDS ADDRESSED BY THE PROVISION DO NOT EXIST FOR THIS PROJECT/DESIGN SECTION 406 -MOTOR-VEHICLE-RELATED OCCUPANCIES CLEAR HEIGHT IN VEHICLE AND PEDESTRIAN TRAFFIC AREA IS NOT TO BE LESS THAN 7'-0". VEHICLE AND PEDESTRIAN AREAS ACCOMMODATING VAN-ACCESSIBLE PARKING SHALL COMPLY WITH SECTION 1106.5 (IBC 406.3.2) A MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH THE INTERNATIONAL MECHANICAL CODE (IBC 406.6.2). AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 903.2.10 (IBC 406.6.3). SECTION 420 -GROUPS R-1 & R-2: WALLS SEPARATING UNITS IN THE SAME BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN ACCORDANCE WITH SECTION 708 (IBC 420.2). FLOOR/CEILING ASSEMBLIES SEPARATING UNITS IN THE SAME BUILDING SHALL BE CONSTRUCTED AS HORIZONTAL SPECIAL AND DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY -CHAPTER 4 NONBEARING WALL INTERIOR FLOOR CONSTRUC ROOF CONSTRUCT TABLE 602 FIRE-RES FIRE SEP DISTANC X 5 ≤ X 10 ≤ X FIRE AND SMOK Need to be seismic design category B to be exempt from secondary water supply. SECTION 403 -HIGH-RISE B COMPLIANCE WITH ALL BUI EQUIVALENCY WITH THE FO 1. REQUIREMENT FO ADDRESS 2. SECONDARY WAT 3. FIRE COMMAND C 4. STANDBY POWER DO NOT EXIST FO 5. SMOKEPROOF EX NOT EXIST FOR T SECTION 406 -MOTOR-VEH CLEAR HEIGHT IN VEHICLE AREAS ACCOMMODATING V A MECHANICAL VENTILATIO CODE (IBC 406.6.2). AN AUTOMATIC SPRINKLER SECTION 420 -GROUPS R-1 SPECIAL AND DETAIL We need to have a letter requesting exemption/alternate method and detailing how your design has equivalent safety. E 2902.1 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES MBING SYSTEMS -CHAPTER 29 OCCUPANCY WATER CLOSET DRINKING FOUNTAINMALE A-2 A-3 B FEMALE LAVATORY M 1 per 75 1 per 75 1 per 200 1 per 500 1 per 125 1 per 65 1 per 200 1 per 500 1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50 1 per 40 for the first 80 and 1 per 80 for the remainder exceeding 80 1 per 100 1 per 500 1 per 750 1 per 1,000 1505.1 MINIMUM ROOF COVERING CLASSIFICATION: TRUCTION TYPE IB:CLASS B F ASSEMBLIES AND ROOFTOP STRUCTURES -CHAPTER 15 RINGS ARE REQUIRED TO BE NON-COMBUSTIBLE. (IBC 1406.2.1) RIOR BALCONIES MADE OF COMBUSTIBLE CONSTRUCTION ARE REQUIRED TO BE TYPE IV, Y TIMBER CONSTRUCTION OR HAVE A MINIMUM 2 HOUR FRR (IBC 1406.3) DS, PICKETS, RAILS AND SIMILAR GUARDRAIL DEVICES ARE PERMITTED TO BE OF UNTREATED D. (IBC 1406.3 EX. 2) RIOR BALCONIES ARE LIMITED TO A MAXIMUM OF 50 PERCENT OF THE BUILDINGS PERIMETER CH FLOOR UNLESS SRINKLERED PROTECTION IS EXTENDED TO THE BALCONY AREAS. (IBC EX. 3) Class A required by Ordinance 40, 2016 2015 IBC 403.2.4 requires a SFRM minimum bond strength of 430 psf for buildings under 421 feet, which includes this building. Have a structural engineer determine your seismic design category. Subject: PlanCheck Page: G023 Page Index: 6 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Provide duct smoke detection as required by 907.2.13.1.2. Subject: PlanCheck Page: G090 Page Index: 16 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf This exterior exit stair on the east side must be 10' from the property line or abut permanent open space, which must be documented. 2015 IBC 1027 Subject: PlanCheck Page: G090 Page Index: 16 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf In many cases the west stair is right up against the setback; 5' from the property line. Provide documentation demonstrating that the adjacent property is permanent open space or provide protection from the property line in the form of 10' of separation distance or a rated wall. 2015 IBC 1027 Provide duct smoke detection as required by 907.2.13.1.2. 46' - 1" This exterior exit stair on the east side must be 10' from the property line or abut permanent open space, which must be documented. 2015 IBC 1027 12' - 10" 19' - 2" 41 R.O.W. CENTERLINE > 20' MIN > 1 8 EAS 54' - 6" PROPERTY LINE SET BACK EXTENTS OF PUBLIC SKIWAY > 20' MIN. (IBC 705.2) 41' - 8" > 20' MIN.(IBC 705.2) CENT PROPERTY LINE 20' - 11" 19' - 6" SCALE: 1/32" = 1'-0"2 FIRE SEPARATION D L 05 In many cases the west stair is right up against the setback; 5' from the property line. Provide documentation demonstrating that the adjacent property is permanent open space or provide protection from the property line in the form of 10' of separation distance or a rated wall. 2015 IBC 1027 Subject: Group Page: G091 Page Index: 17 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf I have marked up this elevation to show the approximate location of the west stair in red. This shows that the stair is not on grade but is substantially below grade and not open to the side. Exit discharge must be at grade and open to the sky (202, 1028). Exterior exit stairs must be open to one side (1027). The portions of the building highlighted in yellow overhang the stair, making it not open to the sky. Exit discharge may not reenter the building but at this location it essentially does. The portion of stair where over 500 occupants converge to egress is in front of the bottom green highlighted door, which is covered on all sides creating a tunnel. This location also marks the convergence of all exiting for the R-1 occupancies on stories 4 through 9, creating a single exit. Converging exits and single exits are not permitted for buildings of this size (1006, 1007.1). Exterior exit stairs must be 10' from the property line and are not permitted in high rise buildings or buildings six stories or greater above grade plane. This stair cannot be considered as exit discharge or as a protected exit stair. Subject: PlanCheck Page: G091 Page Index: 17 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Revise these elevations and provide elevations of other aspects to show the mud flow free board line. The Tetratech report calls for 3' above grade on uphill sides (South and West) and 2' everywhere else. Exit components may not be within these zones. Windows must be hurricane resistant. Subject: PlanCheck Page: G100 Page Index: 18 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Revise to show accessible parking, including a van accessible space (verify height requirement). Accessible parking may not be double parked. UNPROTECTED, SPRINKLERED (UP,S) UNPROTECTED, SPRINKLERED (UP,S) UNPROTECTED, SPRINKLERED (UP,S) 45% 75% NO LIMIT EXTERIOR WALL 10' TO LESS THAN 15' EXTERIOR WALL15' TO LESS THAN 20' EXTERIOR WALL20' TO LESS THAN 30' EXTERIOR WALL OPENING PROTECTION LEGEND WALL OPENING AREAS WALL OPENING AREAS -PROTECTED 45 MIN. WALL OPENING AREAS -PROTECTED 90 MIN. NOTE: AREAS LEFT UN-HATCHED AREA BEYOND 20' FROM ZONE LOT LINE OR CL OF R.O.W. AND HAVE NO LIMIT ON OPENINGS FIRE SEPARATION DISTANCE. The distance measured from the building face to one of the following:1. The closest interior lot line.2. To the centerline of a street, an alley or public way.3. To an assumed line between two buildings on the lot.The distance shall be measured at right angles from the face of the wall. WALL AREAS WITHIN NOTED DISTANCE TO R.O.W. LEVEL 01 (7999')78' - 6" LEVEL 02 (8009'-6")89' - 0" LEVEL 03 (8020'-6")100' - 0" LEVEL 04 (8031')110' - 6" LEVEL 05 (8041'-6")121' - 0" LEVEL 06 (8052')131' - 6" LEVEL 07 (8062'-6")142' - 0" LEVEL 08 (8073')152' - 6" LEVEL 09 (8082')162' - 6" ROOF (8098'-6")178' - 0" THIS AREA IS BETWEEN 15'-20' AWAY FROM CL OF R.O.W. PER IBC TABLE 705.8, UNPROTECTED, SPRINKLERED OPENINGS = MAX 75% OPENINGS IN FACADE LEVEL 05: TOTAL FACADE AREA: =210.57 SFMAX 75% OPEN:=157.93 SFACTUAL:=56.00 SF LEVEL 06: TOTAL FACADE AREA: =661.63 SFMAX 75% OPEN:=496.22 SFACTUAL:=293.77 SF LEVEL 07: TOTAL FACADE AREA: =370.91 SFMAX 75% OPEN:=278.18 SFACTUAL:=145.62 SF LEVEL 07 (8062'-6")142' - 0" LEVEL 08 (8073')152' - 6" LEVEL 09 (8082')162' - 6" ROOF (8098'-6")178' - 0" FIRE SEPARATION DISTANCE = 13'-1" FIRE SEPARATION DISTANCE = 17'-8" THIS AREA IS BETWEEN 15'-20' AWAY FROM CL OF R.O.W. PER IBC TABLE 705.8, UNPROTECTED, SPRINKLERED OPENINGS = MAX 75% OPENINGS IN FACADE LEVEL 08: TOTAL FACADE AREA: =391.88 SFMAX 75% OPEN:=293.91 SFACTUAL:=144.33 SF LEVEL 09: TOTAL FACADE AREA: =426.65 SFMAX 75% OPEN:=319.99 SFACTUAL:=261.33 SF THIS AREA IS BETWEEN 10'-15' AWAY FROM CL OF R.O.W. PER IBC TABLE 705.8, UNPROTECTED, SPRINKLERED OPENINGS = MAX 45% OPENINGS IN FACADE LEVEL 07: TOTAL FACADE AREA: =126.48 SFMAX 45% OPEN:=268.28 SFACTUAL:=14.41 SF LEVEL 08: TOTAL FACADE AREA: =314.37 SFMAX 45% OPEN:=141.47 SFACTUAL:=37.00 SF LEVEL 09: TOTAL FACADE AREA: =426.60 SFMAX 45% OPEN:=191.97 SFACTUAL:=147.00 SF LEVEL 01 (7999')78' - 6" LEVEL 02 (8009'-6")89' - 0" THIS AREA IS BETWEEN 10'-15' AWAY FROM CL OF R.O.W. PER IBC TABLE 705.8, UNPROTECTED, SPRINKLERED OPENINGS = MAX 45% OPENINGS IN FACADE LEVEL 01: TOTAL FACADE AREA: =141.63 SFMAX 45% OPEN:=63.73 SFACTUAL:=25.38 SF FIRE SEPARATION DISTANCE=12'-10". LEVEL 01: TOTAL FACADE AREA: =347.43 SFMAX 75% OPEN:=260.57 SFACTUAL:=97.78 SF FIRE SEPARATION DISTANCE = 19'-3" THIS AREA IS BETWEEN 15'-20' AWAY FROM CL OF R.O.W. PER IBC TABLE 705.8, UNPROTECTED, SPRINKLERED OPENINGS = MAX 75% OPENINGS IN FACADE ISS. # 4240 Architecture Inc. copyright 2019 ARCHITECT'S PROJECT NO. :DESIGNER:DRAFTER:CHECKER:APPROVED BY: DESCRIPTION DATE OWNER G091 CODE ANALYSIS - FIRE SEPARATIONDISTANCE 21222.00DesignerAuthorCheckerApprover AS P E N , C O 8 1 6 1 1 GO R S U C H H A U S NORWAY ISLAND, LLCASPEN, CO 81611 STUDIO NYL2995 BASELINE RD., SUITE 314BOULDER, CO STRUCTURALENGINEER BG BUILDINGWORKS1626 COLE BLVD. SUITE 300LAKEWOOD, CO 80401 MEPENGINEER INTEGRAL GROUP3000 LAWRENCE STREETDENVER, CO 80216 SUSTAINABILITY GEILER & ASSOCIATES12355 E. CORNELL AVENUEAURORA, CO 80014 ACOUSTICALENGINEER 186 LIGHTING DESIGN GROUP1200 BANNOCK STREETDENVER, CO 80204 LIGHTING SCALE: 1/16" = 1'-0"1FIRE SEPARATION DISTANCE - WEST ELEVATION SCALE: 1/16" = 1'-0"2 FIRE SEPARATION DISTANCE - SOUTH ELEVATIONSCALE: 1/16" = 1'-0"3FIRE SEPARATION DISTANCE - NW ELEVATION 25% DESIGN DEVELOPMENT 15 JAN 2020 I have marked up this elevation to show the approximate location of thewest stair in red. This shows that the stair is not on grade but issubstantially below grade and not open to the side. Exit discharge must beat grade and open to the sky (202, 1028). Exterior exit stairs must be opento one side (1027). The portions of the building highlighted in yellowoverhang the stair, making it not open to the sky. Exit discharge may notreenter the building but at this location it essentially does. The portion ofstair where over 500 occupants converge to egress is in front of thebottom green highlighted door, which is covered on all sides creating atunnel. This location also marks the convergence of all exiting for the R-1occupancies on stories 4 through 9, creating a single exit. Convergingexits and single exits are not permitted for buildings of this size (1006,1007.1). Exterior exit stairs must be 10' from the property line and are notpermitted in high rise buildings or buildings six stories or greater abovegrade plane. This stair cannot be considered as exit discharge or as aprotected exit stair. LEVEL 02 (8009'-6") LEVEL 03 (8020'-6") 100' - 0" LEVEL 04 (8031') 110' - 6" LEVEL 05 (8041'-6") 121' - 0" LEVEL 06 (8052') 131' - 6" LEVEL 07 (8062'-6") 142' - 0" LEVEL 08 (8073') 152' - 6" LEVEL 09 (8082') 162' - 6" ROOF (8098'-6") 178' - 0" THIS AREA IS BETWEEN 15'-20' AWAY FROM CL OF R.O.W. PER IBC TABLE 705.8, UNPROTECTED, SPRINKLERED OPENINGS = MAX 75% OPENINGS IN FACADE LEVEL 05: TOTAL FACADE AREA: =210.57 SF MAX 75% OPEN:=157.93 SF ACTUAL:=56.00 SF LEVEL 06: TOTAL FACADE AREA: =661.63 SF MAX 75% OPEN:=496.22 SF ACTUAL:=293.77 SF LEVEL 07: TOTAL FACADE AREA: =370.91 SF MAX 75% OPEN:=278.18 SF ACTUAL:=145.62 SF LEVEL 07 (8062'-6") 142' - 0" LEVEL 08 (8073') 152' - 6" LEVEL 09 (8082') 162' - 6" ROOF (8098'-6") 178' - 0" FIRE SEPARATION DISTANCE = 13'-1" FIRE SEPARATION DISTANCE = 17'-8" THIS AREA IS BETWEEN 15'-20' AWAY FROM CL OF R.O.W. PER IBC TABLE 705.8, UNPROTECTED, SPRINKLERED OPENINGS = MAX 75% OPENINGS IN FACADE LEVEL 08: TOTAL FACADE AREA: =391.88 SF MAX 75% OPEN:=293.91 SF ACTUAL:=144.33 SF LEVEL 09: TOTAL FACADE AREA: =426.65 SF MAX 75% OPEN:=319.99 SF ACTUAL:=261.33 SF REA IS BETWEEN 10'-15' AWAY F R.O.W. PER IBC TABLE 705.8, TED, SPRINKLERED OPENINGS AX 45% OPENINGS IN FACADE A: =126.48 SF =268.28 SF =14.41 SF A: =314.37 SF =141.47 SF =37.00 SF A: =426.60 SF =191.97 SF =147.00 SF ISS. # ARCHITECT'S PROJECT NO. : DESIGNER: DRAFTER: CHECKER: APPROVED BY: DESCRIPTION AS P E N , C O 8 1 6 1 1 GO R S U C H H A U S " = 1'-0" SEPARATION DISTANCE - SOUTH ELEVATION 25% DESIGN DEVELOPMENT 15 Revise these elevations and provide elevations of other aspects to show the mud flow free board line. The Tetratech report calls for 3' above grade on uphill sides (South and West) and 2' everywhere else. Exit components may not be within these zones. Windows must be hurricane resistant. UP STAIR 01 OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 598 SF 2 BOILER ROOM 300 SF GROSS MECH. MECH. Revise to show accessible parking, including a van accessible space (verify height requirement). Accessible parking may not be double parked. Subject: PlanCheck Page: G101 Page Index: 19 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Doors in a series need 48" between door swings. 2015 IBC 1010.1.8 Subject: Group Page: G102 Page Index: 20 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf The eastern three King units on level 2 have a common path travel distance exceeding 75'. This distance must be measured from the furthest location inside the unit, including balconies. 1006.2.1 Subject: PlanCheck Page: G102 Page Index: 20 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Area of assisted rescue required at exit discharge that does not have an accessible route to grade must have sides that are at least 50% open. This area may not decrease the required width. 1009.7 Subject: PlanCheck Page: G102 Page Index: 20 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf High rise buildings and buildings more than 6 stories above grade plane may not use exterior exit stairs. 2015 IBC 1027.2 Exterior exit stairs must be 10' from property line and be protected from the building. Only openings used for egress from normally occupied spaces are allowed, no windows permitted (within 10'). 2015 IBC 1027. ELEVATOR 2 EMERGENCY GENERATOR ELEV. LOBBY STAIR 02 TELECOM OCCUPANCY: AREA SUBTOT LOAD FACTOR OCCUPANT LO OCCUPANCY: AREA SUBTOT LOAD FACTOR OCCUPANT LO USE (FUNCTION TELECOM REQ'D DOOR W TOTAL EGRESS REQ'D STAIR W STAIR 02 .20"/OCC = 3.8" .30"/OCC = 5.7" 2 1 2 17 Doors in a series need 48" between door swings. 2015 IBC 1010.1.8 5T72 24 5T72 24 5T 6024 5T 60 24 5T 6024 5T 60 24 5T 36 24 5T66 24 5T 7224 5T 7224 BEV/SERVICE DISH ASSEMBLYPLATING STOR. HOTHOLDING REF. REF. FR.FR. STORAGE ICE DC WINSTO N C A C - 5 2 2 DC WINSTON C A C - 5 2 2 DC WINSTON CA C - 5 2 2 DBL TRUE T- 4 9 F TRUE T-49F TRUE T-49F TRUE T-49F UNIVERSAL MOP 20-8 FISHER2445 133 1N EW A GE 133 1N EW A GE 133 1N EW A GE AIRIN DD C AIROUT HOSHIZAKI K M - 1 3 0 1 S A H 3 D 133 1N EW A GE AFFORDABLE HOUSING UNIT MEN MTG STORAGE MEETING / BANQUET STORAGE KING KING KING KING WARMING KITCHEN ELEVATOR 2 SERVICE STAIR 02 HOUSEKEEPING ELECTRICAL KING KING ELEVATOR 1 PRE-FUNCTION CORRIDORSTORAGE CORRIDOR CO R R I D O R WOMEN F&B OFFICE F&B SALES EMPL. TOILET JAN. MECHANICAL BAR FILL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 503 SF 3 SIM @ ALL KING SUITES 200 SF GROSS R-1 TEMP. RESIDENTIAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 174 SF 1 TERRACE 200 SF GROSS R-1 ACCESSORY OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 101 SF 1 BALCONY 200 SF GROSS R-1 ACCESSORY 1 64 64 64 64 3 10 6 2 2 2 1 1 3 14 4 31 4 3 4 31 3 1 4 3 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: EXIT DOOR 64 .20"/OCC =12.8" < 36" ACTUAL 3 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: EXTERIOR EGRESS STAIR 128 .30"/OCC = 38.4" < 85" ACTUAL128165 2 154 12 95 DO LO UP STA CO STA STA ST 95 AREA OF RESCUE AREA OF RESCUE 255 The eastern three King units on level 2 have a common path travel distance exceeding 75'. This distance must be measured from the furthest location inside the unit, including balconies. 1006.2.1 99 ' - 0 " 99 ' - 2 " 99 ' - 2 " DN UP AFFORDABLE HOUSING UNIT ELECTRICAL KING OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 777 SF 4 AFFORDABLE HOUSING UNIT 200 SF GROSS R-2 RESIDENTIAL 14 4 31 165 95 AREA OF RESCUE SCALE:1" = 10'-0"1 OCCUPANCY & FIRE RA Area of assisted rescue required at exit discharge that does not have an accessible route to grade must have sides that are at least 50% open. This area may not decrease the required width. 1009.7 DN UPDN * AFFORDABLE HOUSING UNIT KING STAIR 02 ELECTRICAL KING KING MECHANICAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 406 SF 2 MECHANICAL 300 SF GROSS MECH. MECH. OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 198 SF 1 ELECTRICAL 300 SF GROSS MECH. MECH. OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 777 SF 4 AFFORDABLE HOUSING UNIT 200 SF GROSS R-2 RESIDENTIAL 3 14 4 31 4 3 165 2 95 DOOR = UPPER OCCUPANT LOAD: STAIR = COMBINED OCC LOAD AT EXIT DISCHARGE: STAIR LANDING = STAIR = .2"/OCC = 18" < 36" ACTUAL .3"/OCC = 13.8" < 48" ACTUAL .3"/OCC = 27" < 48" ACTUAL LEVEL 04 = 46 90 .3"/OCC = 13.2" < 48" ACTUAL 95 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: EXTERIOR STAIR 165 .20"/OCC = 33" < 36" .30"/OCC = 49.5" < 72" ACTUAL AREA OF RESCUE SCALE:1" = 10'-0"1 OCCUPANCY & FIRE RATED WALLS - LEVEL 02 High rise buildings and buildings more than 6 stories above grade plane may not use exterior exit stairs. 2015 IBC 1027.2 Exterior exit stairs must be 10' from property line and be protected from the building. Only openings used for egress from normally occupied spaces are allowed, no windows permitted (within 10'). 2015 IBC 1027. Subject: PlanCheck Page: G102 Page Index: 20 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf All exits serving the R-1 occupancies on stories 4-9 converge at this location on the exterior western stair. In addition, the second exit from all of the commercial spaces also exits here. A quick occupant load calculation: 95 beds x 2 pillows = 190. + 29 from the spa = 219 occupants using this stair as a single exit. Then add half of the occupant loads from the lobby (31), banquet (255), restaurant (126), library (115), and world cup bar (58) and you have an occupant load of roughly 512. This does not include the additional load from the public using this "public amenity" during an event such as the world cup. Stair width needed for 512 occupants x 0.3”/occupant = 153” at the bottom per 2015 IBC 1005.3.1. Doors swinging into the egress path of this stair may not block the required width by more than one half. At this location the stair is essentially a tunnel enclosed on each side and above. Elsewhere where open above it is below grade. Subject: PlanCheck Page: G102 Page Index: 20 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf The six King units on level 2 have access to only one exit. Table 1006.3.2(2) does not permit a single exit for R-1 units on the second story above grade plane. Egress through the banquet pre-function room requires travel through an intervening space which is not permitted by 1016.2. Subject: PlanCheck Page: G102 Page Index: 20 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Large electrical equipment may require a second exit. DN UPDN AFFORDABLE HOUSING UNIT KING KING OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 777 SF 4 AFFORDABLE HOUSING UN 200 SF GROSS R-2 RESIDENTIAL CY: TOTAL: TOR: T LOAD: TION): 503 SF 3 LL KING SUITES 200 SF GROSS R-1 TEMP. RESIDENTIAL CY: TOTAL: TOR: T LOAD: 174 SF 1 200 SF GROSS R-1 4 4 31 165 95 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: EXTERIOR STAIR 165 .20"/OCC = 33" < 36" .30"/OCC = 49.5" < 72" ACTUAL AREA OF RESCUE All exits serving the R-1 occupancies on stories 4-9 converge at this location on the exterior western stair. In addition, the second exit from all of the commercial spaces also exits here. A quick occupant load calculation: 95 beds x 2 pillows = 190. + 29 from the spa = 219 occupants using this stair as a single exit. Then add half of the occupant loads from the lobby (31), banquet (255), restaurant (126), library (115), and world cup bar (58) and you have an occupant load of roughly 512. This does not include the additional load from the public using this "public amenity" during an event such as the world cup. Stair width needed for 512 occupants x 0.3”/occupant = 153” at the bottom per 2015 IBC 1005.3.1. Doors swinging into the egress path of this stair may not block the required width by more than one half. At this location the stair is essentially a tunnel enclosed on each side and above. Elsewhere where open above it is below grade. 5T72 24 5T72 24 5T 6024 5T 60 24 5T 6024 5T 60 24 5T 36 24 5T66 24 5T 7224 5T 7224 BEV/SERVICE DISH ASSEMBLYPLATING STOR. HOTHOLDING REF. REF. FR.FR. STORAGE ICE DC WINSTON CAC - 5 2 2 DCWINSTON CAC-52 2 DC WINSTON CA C - 5 2 2 DBL RACK TRUE T-49F TRUE T-49F TRUE T-49F TRUE T-49F UNIVERSAL MOP 20-8 FISHER2445 133 1N EW A GE 133 1N EW A GE 133 1N EW A GE AIRIN DD C AIROUT HOSHIZAKI KM- 1 3 0 1 S A H 3 D 133 1N EW A GE DN UPDN AFFORDABLE HOUSING UNIT MEN MTG STORAGE MEETING /BANQUET STORAGE KING KING KING KING WARMINGKITCHEN ELEVATOR 2 SERVICE STAIR 02 HOUSEKEEPING ELECTRICAL KING KING ELEVATOR 1 PRE-FUNCTION SERVICECORRIDORSTORAGE CORRIDOR CO R R I D O R WOMEN F&B OFFICE F&B SALES EMPL. TOILET JAN. MECHANICAL BAR FILL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 777 SF 4 AFFORDABLE HOUSING UNIT 200 SF GROSS R-2 RESIDENTIAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 503 SF 3 SIM @ ALL KING SUITES 200 SF GROSS R-1 TEMP. RESIDENTIAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 174 SF 1 TERRACE 200 SF GROSS R-1 ACCESSORY OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 101 SF 1 BALCONY 200 SF GROSS R-1 ACCESSORY 1 64 64 64 64 3 10 6 2 2 2 1 1 3 14 4 31 4 3 4 31 3 1 4 3 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: EXIT DOOR 64 .20"/OCC =12.8" < 36" ACTUAL 3 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: EXTERIOR EGRESS STAIR 128 .30"/OCC = 38.4" < 85" ACTUAL128165 2 154 12 95 95 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: EXTERIOR STAIR 165 .20"/OCC = 33" < 36" .30"/OCC = 49.5" < 72" ACTUAL AREA OF RESCUE AREA OF RESCUE AREA OF RESCUE 255 SCALE:1" = 10'-0"1 OCCUPANCY & FIR The six King units onlevel 2 have access to only one exit. Table 1006.3.2(2) does not permit a single exit for R-1 units on the second story above grade plane. Egressthrough the banquet pre-function roomrequires travel through an intervening spacewhich is not permitted by 1016.2. ELECTRICAL MECHANICAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 406 SF 2 MECHANICAL 300 SF GROSS MECH. MECH. OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 198 SF 1 ELECTRICAL 300 SF GROSS MECH. MECH. 3 1 2 DOOR = UPPER OCCUPANT LOAD: STAIR = COMBINED OCC LOAD AT EXIT DISCHARGE: STAIR LANDING = STAIR = .2"/OCC = 18" < 36" ACTUAL .3"/OCC = 13.8" < 48" ACTUAL .3"/OCC = 27" < 48" ACTUAL LEVEL 04 = 46 90 .3"/OCC = 13.2" < 48" ACTUAL Large electrical equipment may require a second exit. Subject: PlanCheck Page: G102 Page Index: 20 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf The hallway from stair 2 to the exterior on level 2 appears to be intended to be an exit passageway, is this correct? Subject: PlanCheck Page: G103 Page Index: 21 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf The second exit for the R-1 units on level 3 require traversing a dead end egress balcony (requires fire protection of walls and openings, and through the intervening spaces of the restaurant and library decks. (1016.2, 1021.2) Subject: PlanCheck Page: G103 Page Index: 21 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf These stairs must be considered as exterior exit stairs as path of travel to an exit may not traverse more than 2 stories. Demonstrate adequate separation from the building and property line in plan and elevation. 1027 Subject: Group Page: G104 Page Index: 22 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf The four northernmost R-1 units on level 4 have a common path travel distance exceeding 75'. This distance must be measured from the furthest location inside the unit, including balconies. 1006.2.1 Subject: PlanCheck Page: G104 Page Index: 22 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf This stair may not count as an exit access stair because it requires egressing through the intervening space of the library. 1016.2 DN UP AFFORDABLE HOUSING UNIT MEN KING KING ELEVATOR 2 STAIR 02 ELECTRICAL KING KING MECHANICAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 40 2 MECHANICAL 30 ME ME OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 19 1 ELECTRICAL 30 ME ME OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 777 SF 4 AFFORDABLE HOUSING UNIT 200 SF GROSS R-2 RESIDENTIAL 3 14 4 3 4 3 165 2 154 95 DOOR = LOWER OCCUPANT LOAD: UPPER OCCUPANT LOAD: STAIR = COMBINED OCC LOAD AT EXIT DIS (EGRESS C STAIR LANDING = STAIR = STAIR 02 .2"/OCC = 18" < 36" ACTUA .3"/OCC = 13.8" < 48" ACTU .3"/OCC = 27" < 4 LEVEL LEVEL .3"/OCC = 13.2" < 48" ACTU 95 AREA OF RESCUE 1 OCCUPANCY & FIRE RATED WALLS The hallway from stair 2 to the exterior on level 2 appears to be intended to be an exit passageway, is this correct? HSK 3 10 ANCY: UBTOTAL: ACTOR: ANT LOAD: NCTION): 47 SF 1 EKEEPING 200 SF GROSS R-1 ACCESSORY ANCY: UBTOTAL: ACTOR: ANT LOAD: NCTION): 594 SF 40 RY PATIO 15 SF NET A-2 LOUNGE/BAR ANCY: UBTOTAL: ACTOR: ANT LOAD: NCTION): 1722 SF 115 RY 15 SF NET A-2 LOUNGE/BAR 1 40 DOOR WIDTH: EGRESS LOAD: IT DOOR 29 C =5.8" < 36" ACTUAL 29 29 The second exit for the R-1 units on level 3 require traversing a dead end egress balcony (requires fire protection of walls and openings, and through the intervening spaces of the restaurant and library decks. (1016.2, 1021.2) COO EXPO SERVICE ADA SERVICE HOST HOST SERV. VESTIBULE BAR RESTAURANT LIB OUTD ST OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 1882 SF 126 RESTAURANT 15 SF NET A-2 RESTAURANT OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 1073 SF 72 RESTAURANT PATIO 15 SF NET A-2 RESTAURANT OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 316 SF 22 EXTERIOR TERRACE 15 SF NET A-2 ASSEMBLY USE (FUNCTION): LIBRARY LOUNGE/BAR 108 126 6763 370 241 REQ'D DOOR WIDTH TOTAL EGRESS LO EXIT DOOR .20"/OCC =13.4" < 72 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: EXIT DOOR 63 .20"/OCC =12.6" < 36" ACTUAL REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: EXTERIOR EGRESS STAIR 241 .30"/OCC = 72.3" < 84" ACTUAL AREA OF RESCUE AREA OF RESCUE 29 These stairs must be considered as exterior exit stairs as path of travel to an exit may not traverse more than 2 stories. Demonstrate adequate separation from the building and property line in plan and elevation. 1027 PASTRY /CARVERY BAR PICK UP POS SERVICE DN OPEN TOBELOW KING KING KING EXT. Q/Q BOOT ROOM KING Q/Q ELEVATOR 2 VEST KING KING KING CORRIDOR SERVICE STAIR 02 FITNESS KING ELEVATOR 4 ELEVATOR 1 WORLD CUP BAR KING Q/Q HSK STAIR 03 GREAT ROOM AHU MECH OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 371 SF 2 SIM @ ALL KING 200 SF GROSS R-1 TEMP. RESIDENTIAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 484 SF 3 SIM @ ALL Q/Q 200 SF GROSS R-1 TEMP. RESIDENTIAL OCCUPANCY: AREA SUBTOTAL:LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 347 SF 7 BOOT ROOM 50 SF NET A-2 ASSEMBLY OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 128 SF 1 GREAT ROOM AHU 300 SF GROSS MECH. MECH. OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 37 SF 1 HOUSEKEEPING 200 SF GROSS R-1ACCESSORY 4 3 1 433 3 1 46 1 1 1 1 3 3 3 3 4 4 4 41 18 111 3 3 4 4 7 34 29 2 3 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: STAIR 02 46 .20"/OCC = 9.2" < 36" ACTUAL .30"/OCC = 13.8" <48" ACTUAL 34 REQ'D DOOR WIDTH: REQ'D STAIR WIDTH:.30"/OCC = 10.2" < 78" ACTUAL REQ'D DOOR WIDTH:TOTAL EGRESS LOAD: EXIT DOOR 7 .20"/OCC =1.4" < 36" ACTUAL REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: EXIT DOOR 34 .20"/OCC =6.8" < 36" ACTUAL AREA OF RESCUE AREA WELL 5 1 SCALE:1" = 10'-0"1 OCCUPANCY & FIRE RATED WALLS - LEVEL The four northernmostR-1 units on level 4have a common pathtravel distanceexceeding 75'. This distance must be measured from the furthest location inside the unit, including balconies. 1006.2.1 97 ' - 6 " 83 ' - 6 " 86' - 2 " 81 ' - 6 " DN OPEN TO BELOW ELEVATOR 2 VEST ELEVATOR 1 HSK GREAT ROOM AHU 46 1 3 5 1 This stair may not count as an exit access stair because it requires egressing through the intervening space of the library. 1016.2 Subject: PlanCheck Page: G104 Page Index: 22 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf R1 rooms may not egress through the intervening space of A2 world cup bar. 1016.2 Subject: PlanCheck Page: G104 Page Index: 22 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Chiller yard is not a normally occupied space so may not open into an exit. 2015 IBC 1026,6, 1027.6 Subject: Group Page: G105 Page Index: 23 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Five of the R-1 units on level 5 have a common path travel distance exceeding 75' (two in NE corner, two in SE corner, one in NW corner). This distance must be measured from the furthest location inside the unit, including balconies. 1006.2.1 Subject: Group Page: G105 Page Index: 23 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf The common path travel distance from the most remote point within the spa (group B occupancy) exceeds 100'. 1006.2.1 Subject: PlanCheck Page: G106 Page Index: 24 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf A door is required to separate the exit passageway from the exit stair. PASTRY /CARVERY BAR PICK UP POS SERVICE BOOT ROOM KING VEST SERVICE ELEVATOR 1 WORLD CUP BAR Q/Q TAL: R: OAD: ON): 371 SF 2 L KING 200 SF GROSS R-1 TEMP. RESIDENTIAL TAL: R: OAD: ON): 484 SF 3 L Q/Q 200 SF GROSS R-1 TEMP. RESIDENTIAL 7 34 29 2 3 34 REQ'D STAIR WIDTH: .30"/OCC = 10.2" < 78" ACTUAL AREA OF RESCUE 5 R1 rooms may not egress through the intervening space of A2 world cup bar. 1016.2 DN KING KING EXT. Q/Q Q/Q ELEVATOR 2 KING STAIR 02 KING ELEVATOR 4 STAIR 03 OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 454 SF 3 SIM @ ALL Q/Q 200 SF GROSS R-1 TEMP. RESIDENTIAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 453 SF 3 SIM @ ALL KING EXT. 200 SF GROSS R-1 TEMP. RESIDENTIAL OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 137 SF 1 TERRACE 200 SF GROSS R-1 ACCESSORY 4 3 1 4 3 1 46 1 1 1 3 3 3 3 4 4 4 SCALE:1" = 10'-0"1 OCCUPANCY & FIRE RATED WALLS - LEVEL 04 Chiller yard is not a normally occupied space so may not open into an exit. 2015 IBC 1026,6, 1027.6 DN DN DN DN DN UP DN SHEET NOTES: SEE A500 SERIES 1. ALL FIRE RATED WILL EXTEND TO FACE OF ALL WA 2. ALL RATED WALL DOOR OPENING, FRAMES 3. ALL INTERIOR SH AND ELEVATORS RATED UNLESS B 4. ALL NON-RATED ASSEMBLIES ARE STC RATING ONL 5. REFER G110 FOR STAIR PROTECTI 6. FIRE RESISTANCE -RATED WALL LEGEND (IBC 708) WALL SYMBOL DESCRIPTION LOCATION / PURPOSE FIRE RESISTIVE RATING NOTES: (1) THE FIRE-RESISTANCE RATING OF EXTERIOR WALLS WITH A FIRE SEPARATION DISTAN FEET SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE INSIDE; FOR A FIRE SEPARATI DISTANCE < OR = 5 FEET, SUCH WALLS SHALL BE RATED FOR EXPOSURE TO FIRE FROM SIDES.(2) SEE MECHANICAL DOCUMENTATION FOR LOCATIONS OF FIRE DAMPERS.(3) SEE MECHANICAL DOCUMENTATION FOR LOCATIONS OF SMOKE DAMPERS.(4) SEE ARCHITECTURAL DOCUMENTATION FOR LOCATIONS OF FIRE DOORS AND FIRE SH (5) NOT REQUIRED AT PENETRATION OF EXHAUST OR SUPPLY SHAFTS IN PARKING GARA ARE SEPARATED FROM OTHER BUILDING SHAFTS BY NOT LESS THAN 2 HR FIRE RESISTA CONSTRUCTION. NON-BEARING WALLS SEPARATING DWELLING UNITS OR SLEEPING UNITS, AND OCCUPANCY SEPARATIONS PER IBC 302. 1 HR DESIGN OCCUPANCY LOAD FIRE PARTITIONS CORRIDORS PER IBC 1018.1..5 HR @ R OCC. FIRE PARTITION INT / EXTERIOR WALLS INTERIOR AND EXTERIOR NON-RATED WALLS (PER OCCUPANCY -IBC 302)NR EXIT OCCUPANT LOAD X Z FIRE BARRIERS (IBC 707) TYPE HR RATING (SPRINKLERED) < 4 STORIES 1HR (2HR*)STAIRWAYS HR RATIN > 1HR (2HR*)SHAFTS 2HRHOR. EXIT 1HREXIT PASSAGEWAY 1HR OR SPRINKLERINCIDENTAL USES 1HR * FIRE HR RATING IS NOT TO BE LESS THEN FLOOR ASSEMBLY PENETRATED BUT NEED NO (IBC 2012 SECTION 713.4) OCCUPANCY SYMBOLS LEGEND EXIT ENCLOSURES, ALL SHAFT WALLS, AND EXIT PASSAGE WALLS 2 HRFIRE BARRIER NON BEARING WALLS AT TRANSFORMER AND GENERATOR 3 HRFIRE WALL RATED EXTERIOR WALLS 1 HREXTERIOR WALL RATED EXTERIOR WALLS 2 HREXTERIOR WALL STAIR WALLS CONNECTING LESS THAN 4 STORIES; NON BEARING WALLS AT TRANSFORMER, GENERATOR AND BOILER 1 HRFIRE BARRIER KING KING KING Q/QQ/QKING EXT. Q/Q KING KING EXT.ELEVATOR 2 BOHQ/Q SERVICE STAIR 02 SPA KING KING ADA KING KING ELEVATOR 4 KING EXT. ELEVATOR 1 CORRIDOR Q/Q KING KING STAIR 03 OCCUPANCY:AREA SUBTOTAL: LOAD FACTOR:OCCUPANT LOAD: USE (FUNCTION): 2848 SF 29 SPA 100 SF GROSS BSPAOCCUPANCY:AREA SUBTOTAL: LOAD FACTOR:OCCUPANT LOAD: USE (FUNCTION): 433 SF 3 SIM @ ALL ADA KING 200 SF GROSS R-1TEMP. RESIDENTIAL OCCUPANCY:AREA SUBTOTAL:LOAD FACTOR:OCCUPANT LOAD: USE (FUNCTION): 525 SF 3 KING 200 SF GROSS R-1TEMP. RESIDENTIAL 29 4 3443 11 11 1 1 1 1 1 1 1 1 1 3 3 4 4 4 4 4 4 4 4 3 4 4 33 33 3 3 3 3 3 3 3 3 3 27 69 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: STAIR 02 27 .20"/OCC = 5.4" < 36" ACTUAL .30"/OCC = 8.1" <48" ACTUAL 69 DOOR = LOWER OCCUPANT LOAD: UPPER OCCUPANT LOAD:STAIR =COMBINED OCC LOAD AT EXIT DISCHARGE: (EGRESS CONVERGENCE) STAIR LANDING = STAIR = STAIR 03 .2"/OCC = 11.6" < 36" ACTUAL .3"/OCC = 5.1" < 48" ACTUAL .3"/OCC = 17.4" < 48" ACTUAL LEVEL 04 = 41 LEVEL 06 = 17 58 .3"/OCC = 12.3" < 48" ACTUAL REQ'D DOOR WIDTH:TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: EXTERIOR STAIR 69 .20"/OCC = 13.8" < 36" ACTUAL .30"/OCC = 20.7" < 44" ACTUAL REQ'D DOOR WIDTH:TOTAL EGRESS LOAD: EXIT DOOR 69 .20"/OCC =13.8" < 36" ACTUAL FLAT GREEN ROOF(BELOW) SCALE:1" = 10'-0"1OCCUPANCY & FIRE RATED WALLS - LEVEL 05 Five of the R-1 unitson level 5 have acommon path traveldistance exceeding 75'(two in NE corner, twoin SE corner, one inNW corner). Thisdistance must bemeasured from thefurthest location insidethe unit, includingbalconies. 1006.2.1 77 ' - 1 " 79 ' - 1 1 " 82 ' - 4 " 80'- 0 " 77 ' - 1 " WALL SYMBOL DESCRIPTION LOCATION / PURPOSE NOTES: (1) THE FIRE-RESISTANCE RATING OF EXTERIOR WALLS W FEET SHALL BE RATED FOR EXPOSURE TO FIRE FROM THE DISTANCE < OR = 5 FEET, SUCH WALLS SHALL BE RATED F SIDES. (2) SEE MECHANICAL DOCUMENTATION FOR LOCATIONS O (3) SEE MECHANICAL DOCUMENTATION FOR LOCATIONS O (4) SEE ARCHITECTURAL DOCUMENTATION FOR LOCATION (5) NOT REQUIRED AT PENETRATION OF EXHAUST OR SUP ARE SEPARATED FROM OTHER BUILDING SHAFTS BY NOT CONSTRUCTION. NON-BEARING WALLS S DWELLING UNITS OR SL UNITS, AND OCCUPANC SEPARATIONS PER IBC DESIG FIRE PARTITIONS CORRIDORS PER IBC 10 FIRE PARTITION INT / EXTERIOR WALLS INTERIOR AND EXTERIO WALLS (PER OCCUPANC X FIRE BARRIERS (IBC 707) TYPE HR RATING (SPRI < 4 STORI 1HR (2HR STAIRWAYS 1HR (2HR SHAFTS 2HRHOR. EXIT 1HREXIT PASSAGEWAY 1HR OR SPRIN INCIDENTAL USES * FIRE HR RATING IS NOT TO BE LESS THEN FLOOR ASSEMB (IBC 2012 SECTION 713.4) OCCUPANCY SY EXIT ENCLOSURES, ALL WALLS, AND EXIT PASSA FIRE BARRIER NON BEARING WALLS A TRANSFORMER AND GE FIRE WALL RATED EXTERIOR WALL EXTERIOR WALL RATED EXTERIOR WALL EXTERIOR WALL STAIR WALLS CONNECT THAN 4 STORIES; NON B WALLS AT TRANSFORME GENERATOR AND BOILE FIRE BARRIER KING KING Q/QQ/QT.KING SPA KING KING ADA KING KING ELEVATOR 4 CORRIDOR STAIR 03 OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 2848 SF 29 SPA 100 SF GROSS B SPA OCCUPANCY: AREA SUBTOTAL: LOAD FACTOR: OCCUPANT LOAD: USE (FUNCTION): 433 SF 3 SIM @ ALL ADA KING 200 SF GROSS R-1 TEMP. RESIDENTIAL 29 4 3443 1 1 1 1 1 3 4 4 3 4 4 33 33 3 3 3 69 69 The common path travel distance from the most remote point within the spa (group B occupancy) exceeds 100'. 1006.2.1 10 7 ' - 9 " NOTES: (1) THE FIRE-RES FEET SHALL BE DISTANCE < OR SIDES. (2) SEE MECHAN (3) SEE MECHAN (4) SEE ARCHITE (5) NOT REQUIRE ARE SEPARATED CONSTRUCTION FIRE BARRIER TY STAIR SHA HOR. EXIT PASS KING STAIR 04 4 4 3 31 157 A door is required to separate the exit passageway from the exit stair. Subject: PlanCheck Page: G108 Page Index: 26 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf This stairway serves an uppermost level at 8074'. Lowest level of fire department vehicle access is ground floor at 7999'. This is exactly 75' and thus does not require the stairway to be a smoke proof enclosure per 2015 IBC 403.5.3.1 Subject: PlanCheck Page: G110 Page Index: 28 Author: nickt Color: File Name: 20200115_Gorsuch Haus - 25% DD_CODE SHEETS ONLY.pdf Dash in the stairway walking surface and accurately dimension 10' above it. The shading appears to be incorrect in some locations. Every wall within 10' of the stair horizontally must be 2 hour rated up to 10' in height above the stairway with no windows. The 1 hour/ 3/4 hr opening requirement only applies to walls that are 180 degrees to the exterior exit stairway. 1027.6 CONDO LODGE ELEVATOR 4 ROOF TERRACE LOBBY CONDO LODGE VESTIBULE STAIR 03 1949 102 2 7 REQ'D DOOR WIDTH: TOTAL EGRESS LOAD: REQ'D STAIR WIDTH: STAIR 03 102 .20"/OCC = 20.4" < 36" ACTUAL .30"/OCC =30.6" < 48" ACTUAL SCALE:1" = 1 1 OCCUP This stairway serves an uppermost level at 8074'. Lowest level of fire department vehicle access is ground floor at 7999'. This is exactly 75' and thus does not require the stairway to be a smoke proof enclosure per 2015 IBC 403.5.3.1 DNDN DN DN DN UP DN DN DN DN UP DNDN DN DN DN DN DN DN DN DN DNDN EASEMENT CENTERLINE 11' - 6 5 / 8 " 10' - 0 " LEVEL 01 (7999')78' - 6" LEVEL 02 (8009'-6")89' - 0" LEVEL 03 (8020'-6")100' - 0" LEVEL 04 (8031')110' - 6" LEVEL 05 (8041'-6")121' - 0" LEVEL 06 (8052')131' - 6" 1 HOUR PROTECTION WITH 3/4 HOUR OPENING PROTECTIVE 2 HOUR PROTECTION WITH NO WINDOWS PERMITTED WINDOWS AND DOORS BEYOND 10'-0" MIN. REQUIRED SEPARATION; RE: PLANS 10' - 0" 10' - 0 " 10' - 0"10' - 0" WINDOWS AND DOORS BEYOND 10'-0" MIN. REQUIRED SEPARATION; RE: PLANS SCALE: 1/16" = 1'-0"3 EXTERIOR STAIRWAY PROTECTION - LEVEL 03 SCALE: 1/16" = 1'-0"4 EXTERIOR STAIRWAY PROTECTION - LEVEL 04 SCALE: 1/16" = 1'-0"5 EXTERIOR STAIRWAY PROTECTION - LEVEL 05 SCALE: 1/16" = 1'-0"1 EXTERIOR STAIRWAY PROTECTION - LEVEL 01 SCALE: 1/16" = 1'-0"2 EXTERIOR STAIRWAY PROTECTION - LEVEL 02 SCALE: 1/16" = 1'-0"6 EXTERIOR STAIRWAY PROTECTION - LEVEL 06 SCALE: 1/16" = 1'-0"7 EXTERIOR STAIRWAY PROTECTION - WEST ELEVATION Dash in the stairway walkingsurface and accurately dimension10' above it. The shading appearsto be incorrect in some locations.Every wall within 10' of the stairhorizontally must be 2 hour rated up to 10' in height above thestairway with no windows. The 1hour/ 3/4 hr opening requirementonly applies to walls that are 180degrees to the exterior exitstairway. 1027.6