- 1 -
Testing, Adjusting and Balancing
Project Gucci- Aspen
Address 204 S. Galena St. Aspen, CO 81611
Architect Callisonrtkl Inc.
Mechanical Engineer Rosini Engineering
Contractor Climate Control
Balancing Supervisors Greg Barnes
Date October 18, 2023
Job Number 4931
2
(E): Existing
Actual D.P.: Recorded Differential Pressure
AHU: Air Handling Unit
AK: Area Correction
BV: Balance Valve
CD: Ceiling Diffuser
CFM: Cubic Feet Per Minute
CHW: Chilled Water
CRAC: Computer Room Air Conditioning Unit
CUH: Cabinet Unit Heater
CW: Condenser Water
D.P. (Pump): Discharge Pressure
Design D.P.: Design Differential Pressure
Diff.: Differential
DX: Direct Expansion
EAT: Entering Air Temperature
EF: Exhaust Fan
EG: Exhaust Grille
ERU: Energy Recovery Unit
ERV: Energy Recovery Ventilator
EWT: Entering Water Temperature
FCU: Fan Coil Unit
FPB: Fan Powered Box
FPM: Feet Per Minute
HW: Heating Water
HX: Heat Exchanger
IN.WC.: Inches of Water Column
ESP: External Static Pressure
Ind.Imp.Dia.: Indicated Impeller Diameter
K Factor: Correction/Calibration Factor
KEF: Kitchen Exhaust Fan
CS: Circuit Setter
LAT: Leaving Air Temperature
LD: Linear Diffuser
LWT: Leaving Water Temperature
MA: Mixed Air
MAU: Make Up Air Unit
Motor FLA: Full Load Amperage
MVD: Manual Volume Damper
NAC: No Access
NG: Not Given
NIC: Not in Contract
Nom. Eff.: Nominal Efficiency
OA/OSA: Outside Air
OA: Outside Air
OBD: Opposed Blade Damper
OD: Outside Diameter
P.F.: Power Factor
PSI: Pounds per Square Inch
RA: Return Air
RF: Return Fan
RG: Return Grille
RPM: Revolutions per Minute
RTU: Roof Top Unit
S.F.: Service Factor
S.P. (Pump): Suction Pressure
SA: Supply Air
SD: Supply Diffuser
SEF: Smoke Exhaust Fan
SF: Supply Fan
SP: Static Pressure
SPF: Stairwell Pressurization Fan
SWD: Sidewall Diffuser
T1: Terminal 1
T2: Terminal 2
T3: Terminal 3
TDH: Total Dynamic Head
TF: Transfer Fan
TSP: Total Static Pressure
UH: Unit Heater
VAV: Variable Air Volume
VP: Velocity Pressure
III
Method of Balancing:
Supply, Return and Exhaust diffusers, grilles and registers were measured with an
Alnor Balometer EBT-721, which includes the flow hood, velgrid, pitot tube and
airfoil. Heating and Chilled water flow rates were measured with an Alnor Hydronic
Manometer HM-680 by obtaining pressure measurements. RPM was measured with a
Shimpo tachometer. Amperage and Voltage readings were taken with a Fluke 930
meter.
Instrumentation:
Digital Manometer Alnor Balometer EBT-721
Flow hood Alnor Balometer EBT-721
Digital Pressure Gage Alnor Hydronic Manometer HM-680
Tachometer Shimpo
Digital Volt-Amp Meter Fluke 930
Thermometer Alnor Balometer EBT-721
Warranty Information:
This project was completed per TABB & NEBB Procedural Standards.
The data presented in this report is a record of system measurements and final adjustments
that have been obtained in accordance with the current edition of the TABB & NEBB
Procedural Standards for Testing, Adjusting, and Balancing Environmental Systems. Any
variances from design quantities, which exceed TABB & NEBB tolerances, are noted in
the Test-Adjust-Balance Report Project Summary. If a Test-Adjust-Balance Report
Project Summary is not issued directly following this cover page, all measurements met
the design requirements as specified by the design mechanical engineer.
This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date
listed on this cover page.
Greg Barnes
Owner / Supervisor
greg@certtab.com
IV
720-201-6274
Project Summary
1. Individual Notes, Explanations, and Deficiencies, if applicable, are shown
underneath the associated equipment.
Cover PagePROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
FIRM:PHONE:
FAX:
PROJECT:
CONTACT:
10/18/2023DATE:
PROJECT #:
NOTES:
4931
Barnes, Soun
(720) 201-6274Certified Balancing and Commissioning
PO Box 620547
Littleton, CO 80162
GUCCI-ASPEN
ASPEN, CO 81611
204 S. GALENA STREET
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Table Of ContentsPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
Table Of Contents
1 Air Handling Unit......................................................................................................................................................3
1.1 AC-1....................................................................................................................................................................3
1.2 AC-1/SPP-01......................................................................................................................................................4
1.3 AC-1/Main Pitot (Total).......................................................................................................................................5
1.4 AC-2....................................................................................................................................................................7
1.5 AC-2/SPP-01......................................................................................................................................................8
2 Fan Unit....................................................................................................................................................................10
2.1 EF-1....................................................................................................................................................................10
2.2 TEF-1..................................................................................................................................................................10
3 4931 GUCCIASPEN REPORT DWGS..pdf............................................................................................................11
3.1 M-100 Mechanical General Notes, Symbol & Abbreviation List 24x36-144 (1)..................................................11
3.2 M-101 Mechanical Schedules 24x36-144 (1).....................................................................................................11
3.3 M-102 Mechanical Specifications 24x36-144 (1)................................................................................................11
3.4 M-103 Mechanical Specifications 24x36-144 (1)................................................................................................11
3.5 M-200 Basement Mechanical Demolition Plan 24x36-144 (1)...........................................................................11
3.6 M-201 First Floor Mechanical Demolition Plan 24x36-144 (1)...........................................................................11
3.7 M-202 Roof Mechanical Demolition Plan 24x36-144 (1)....................................................................................11
3.8 M-300 Basement Mechanical Plan 24x36-144 (1).............................................................................................11
3.9 M-301 First Floor Mechanical Plan 24x36-144 (1).............................................................................................11
3.10 M-302 Mechanical Roof Plan 24x36-144 (1)....................................................................................................11
3.11 M-400 Mechanical Piping Plans 24x36-144 (1)................................................................................................11
3.12 M-500 Mechanical Details 24x36-144 (1).........................................................................................................11
3.13 M-501 Mechanical Details 24x36-144 (1).........................................................................................................11
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 3 of 23
Air Handling UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
Tested By:Greg Barnes
Date:10/13/2023
SYSTEM/UNIT: AC-1
Log:AC-1 10/17/2023 Greg Barnes FAN MIN SET AT 25 HZ MAX SET AT 51.8 HZ
AC-1 10/13/2023 Greg Barnes ALL DIFFUSERS THAT COULD BE READ WITH VELGRID OR HOOD. ANY
ONES NOT ABLE TO BE READ WERE CHECKED FOR DISCHARGE TEMP,
DAMPERS WERE WIDE OPEN AND CFM WAS TAKEN FROM THE PITOT
MINUS THE READABLE OUTLETS.
Unit Data
Unit Manufacturer TRANE
Unit Model Number TWE09043BAA
Unit Serial Number 22321946BA
Design Airflow 3110 CFM
Test Data
Actual Airflow 3240 CFM
Design Outside Airflow 500 CFM
Actual Outside Airflow 530 CFM
Test Pressures
RF SP In 0.50 in. wc
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 4 of 23
Air Handling UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
Tested By:Greg Barnes
Date:10/12/2023
SYSTEM/UNIT: AC-1/SPP-01
Test Pressures
Supply Fan SP In -0.63 in. w.c.
Supply Fan SP Out 0.58 in. w.c.
DX Coil SP In NAC in. w.c.
DX Coil SP Out -0.63 in. w.c.
Filter SP In -0.33 in. w.c.
Filter SP Out NAC in. w.c.
Heating Coil SP In 0.58 in. w.c.
Heating Coil SP Out 0.37 in. w.c.
Static Pressure Profile
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 5 of 23
Air Handling UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
Tested By:Greg Barnes
Date:10/12/2023
SYSTEM/UNIT: AC-1/Main Pitot (Total)
Log:AC-1/Main Pitot (Total)10/11/2023 Greg Barnes FAN LAW 1 (1200 RPM @ 40 HZ) X 1.26 = 51.8 HZ
AC-1/Main Pitot (Total)10/11/2023 Greg Barnes READING TAKEN @40 HZ
Traverse Data Points
Unit Data
Type of Traverse Rectangular
Duct Height 12.00 in.
Duct Width 32.00 in.
Insulation Width 1.00 in.
Duct SQ. FT 2.67 sq. ft.
Number Of Rows 4
Readings Per Row 8
Total Readings 32
Location of Holes 1 Top
Location of Holes 2 Left
Final Data
Sum of Readings 30363
Average Reading 949 FPM
Reading Std. Dev.238 FPM
Design Total Flow 3200 CFM
Actual Total Flow 2534 CFM
Duct Static Press.0.43 in. wc
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 6 of 23
Air Handling UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
System/Unit Outlet Type Size LxW / D AK Factor Design
Airflow
Prelim
Airflow
% Prelim
Diff.
Final
Airflow
% Final
Diff.
Outlet-01 SR 8X6 1 150 350 233 155 103
Outlet-02 SR 8X6 1 200 420 210 210 105
Outlet-03 SG 48 1 200 280 140 210 105
Outlet-04 SG 48 1 200 230 115 215 108
Outlet-05 SG 24 1 100 105 105
Outlet-06 SG 24 1 100 105 105
Outlet-07 SG 24 1 100 105 105
Outlet-08 SG 24 1 100 105 105
Outlet-09 SG 24 1 100 105 105
Outlet-10 SG 42 1 190 195 103
Outlet-11 SG 42 1 190 195 103
Outlet-12 SG 42 1 190 195 103
Outlet-13 SG 24 1 100 105 105
Outlet-14 SG 24 1 100 105 105
Outlet-15 SG 36 1 250 230 92 255 102
Outlet-16 SG 24 1 110 120 109
Outlet-17 SG 36 1 250 245 98 250 100
Outlet-18 SG 24 1 120 130 108
Outlet-19 SG 36 1 250 255 102 255 102
Outlet-20 SG 24 1 110 120 109
Totals:---3110 2010 65 3240 104
AC-1 Supply Outlet Summary
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 7 of 23
Air Handling UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
Tested By:Greg Barnes
Date:10/17/2023
SYSTEM/UNIT: AC-2
Log:AC-2 10/17/2023 Greg Barnes FAN MIN SET AT 25 HZ MAX SET AT 49.6 HZ
AC-2 10/17/2023 Greg Barnes ALL DIFFUSERS THAT COULD BE READ WITH VELGRID OR HOOD. ANY
ONES NOT ABLE TO BE READ WERE CHECKED FOR DISCHARGE TEMP,
DAMPERS WERE WIDE OPEN AND CFM WAS TAKEN FROM THE PITOT
MINUS THE READABLE OUTLETS.
Unit Data
Unit Manufacturer TRANE
Unit Model Number TWE09043BAA
Unit Serial Number 22321946BA
Design Airflow 3284 CFM
Test Data
Actual Airflow 3450 CFM
Design Outside Airflow 800 CFM
Actual Outside Airflow 845 CFM
Test Pressures
RF SP In 0.50 in. wc
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 8 of 23
Air Handling UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
Tested By:Greg Barnes
Date:10/17/2023
SYSTEM/UNIT: AC-2/SPP-01
Test Pressures
Supply Fan SP In -0.58 in. w.c.
Supply Fan SP Out 0.44 in. w.c.
DX Coil SP In NAC in. w.c.
DX Coil SP Out -0.58 in. w.c.
Filter SP In -0.36 in. w.c.
Filter SP Out NAC in. w.c.
Heating Coil SP In 0.44 in. w.c.
Heating Coil SP Out 0.33 in. w.c.
Static Pressure Profile
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 9 of 23
Air Handling UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
System/Unit Outlet Type Size LxW / D AK Factor Design
Airflow
Prelim
Airflow
% Prelim
Diff.
Final
Airflow
% Final
Diff.
Outlet-01 SG 24 1 90 95 106
Outlet-02 SG 24 1 80 85 106
Outlet-03 SG 24 1 87 90 103
Outlet-04 SG 30 1 100 105 105
Outlet-05 SG 30 1 80 85 106
Outlet-06 SG 30 1 80 85 106
Outlet-07 SG 30 1 80 85 106
Outlet-08 SG 30 1 80 85 106
Outlet-09 SG 30 1 80 85 106
Outlet-10 CD 24X24 1 100 95 95
Outlet-11 CD 24X24 1 150 155 103
Outlet-12 CD 24X24 1 70 65 93
Outlet-13 CD 24X24 1 150 165 110
Outlet-14 CD 24X24 1 150 145 97
Outlet-15 CD 24X24 1 50 50 100
Outlet-16 SG 30 1 180 190 106
Outlet-17 SG 24 1 70 75 107
Outlet-18 CD 24X24 1 120 125 104
Outlet-19 SG 1 70 75 107
Outlet-20 SG 1 87 95 109
Outlet-21 SG 1 87 95 109
Outlet-22 SG 1 87 95 109
Outlet-23 SG 1 87 95 109
Outlet-24 SG 30 1 70 75 107
Outlet-25 SG 30 1 70 75 107
Outlet-26 SG 36 1 260 270 104
Outlet-27 SG 30 1 70 75 107
Outlet-28 SG 36 1 260 270 104
Outlet-29 SG 30 1 70 75 107
Outlet-30 SG 24 1 112 120 107
Outlet-31 87 95 109
Outlet-32 70 75 107
Totals:---3284 0 0 3450 105
AC-2 Supply Outlet Summary
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 10 of 23
Fan UnitPROJECT:
LOCATION:
GUCCI-ASPEN
ASPEN, CO
4931PROJECT #:
DATE:
CONTACT:
AUTHOR:
10/18/2023
Soun Barnes
CBC REPORT DEPT.
SYSTEM/UNIT: EF-1
Log:EF-1 10/17/2023 Greg Barnes TESTED ON TEMP POWER
Unit Data
Fan Manufacturer Greenheck
Fan Model Number CSP-A700-VG
Test Data
Design ESP 0.20 in. wc
Motor Data
Rated Design Airflow 400 CFM
Motor Hertz 60 Hz
SYSTEM/UNIT: TEF-1
Log:TEF-1 10/17/2023 Greg Barnes TESTED ON TEMP POWER
Unit Data
Fan Manufacturer Greenheck
Fan Model Number CSP-A390-VG
Test Data
Design ESP 0.80 in. wc
Motor Data
Rated Design Airflow 200 CFM
Motor Hertz 60 Hz
Certified Balancing and Commissioning
“All I have in this world is my faith and my word, I don’t break them for anyone”
Page 11 of 23
Page 12 of 23
Page 13 of 23
Page 14 of 23
Page 15 of 23
Page 16 of 23
Page 17 of 23
Page 18 of 23
10
11
12
13
14
15
2
Page 19 of 23
?
1
2
3
4
5
6 7
8
9
16
17
18
19 20
21
22
23
24
25
26
27
28
29
30
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16 17
18
19
1
2
1
20
Page 20 of 23
Page 21 of 23
Page 22 of 23
Page 23 of 23