Loading...
HomeMy WebLinkAboutInspection.204 S Galena St.0030-2022-BCOM - 1 - Testing, Adjusting and Balancing Project Gucci- Aspen Address 204 S. Galena St. Aspen, CO 81611 Architect Callisonrtkl Inc. Mechanical Engineer Rosini Engineering Contractor Climate Control Balancing Supervisors Greg Barnes Date October 18, 2023 Job Number 4931 2 (E): Existing Actual D.P.: Recorded Differential Pressure AHU: Air Handling Unit AK: Area Correction BV: Balance Valve CD: Ceiling Diffuser CFM: Cubic Feet Per Minute CHW: Chilled Water CRAC: Computer Room Air Conditioning Unit CUH: Cabinet Unit Heater CW: Condenser Water D.P. (Pump): Discharge Pressure Design D.P.: Design Differential Pressure Diff.: Differential DX: Direct Expansion EAT: Entering Air Temperature EF: Exhaust Fan EG: Exhaust Grille ERU: Energy Recovery Unit ERV: Energy Recovery Ventilator EWT: Entering Water Temperature FCU: Fan Coil Unit FPB: Fan Powered Box FPM: Feet Per Minute HW: Heating Water HX: Heat Exchanger IN.WC.: Inches of Water Column ESP: External Static Pressure Ind.Imp.Dia.: Indicated Impeller Diameter K Factor: Correction/Calibration Factor KEF: Kitchen Exhaust Fan CS: Circuit Setter LAT: Leaving Air Temperature LD: Linear Diffuser LWT: Leaving Water Temperature MA: Mixed Air MAU: Make Up Air Unit Motor FLA: Full Load Amperage MVD: Manual Volume Damper NAC: No Access NG: Not Given NIC: Not in Contract Nom. Eff.: Nominal Efficiency OA/OSA: Outside Air OA: Outside Air OBD: Opposed Blade Damper OD: Outside Diameter P.F.: Power Factor PSI: Pounds per Square Inch RA: Return Air RF: Return Fan RG: Return Grille RPM: Revolutions per Minute RTU: Roof Top Unit S.F.: Service Factor S.P. (Pump): Suction Pressure SA: Supply Air SD: Supply Diffuser SEF: Smoke Exhaust Fan SF: Supply Fan SP: Static Pressure SPF: Stairwell Pressurization Fan SWD: Sidewall Diffuser T1: Terminal 1 T2: Terminal 2 T3: Terminal 3 TDH: Total Dynamic Head TF: Transfer Fan TSP: Total Static Pressure UH: Unit Heater VAV: Variable Air Volume VP: Velocity Pressure III Method of Balancing: Supply, Return and Exhaust diffusers, grilles and registers were measured with an Alnor Balometer EBT-721, which includes the flow hood, velgrid, pitot tube and airfoil. Heating and Chilled water flow rates were measured with an Alnor Hydronic Manometer HM-680 by obtaining pressure measurements. RPM was measured with a Shimpo tachometer. Amperage and Voltage readings were taken with a Fluke 930 meter. Instrumentation: Digital Manometer Alnor Balometer EBT-721 Flow hood Alnor Balometer EBT-721 Digital Pressure Gage Alnor Hydronic Manometer HM-680 Tachometer Shimpo Digital Volt-Amp Meter Fluke 930 Thermometer Alnor Balometer EBT-721 Warranty Information: This project was completed per TABB & NEBB Procedural Standards. The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB & NEBB Procedural Standards for Testing, Adjusting, and Balancing Environmental Systems. Any variances from design quantities, which exceed TABB & NEBB tolerances, are noted in the Test-Adjust-Balance Report Project Summary. If a Test-Adjust-Balance Report Project Summary is not issued directly following this cover page, all measurements met the design requirements as specified by the design mechanical engineer. This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date listed on this cover page. Greg Barnes Owner / Supervisor greg@certtab.com IV 720-201-6274 Project Summary 1. Individual Notes, Explanations, and Deficiencies, if applicable, are shown underneath the associated equipment. Cover PagePROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. FIRM:PHONE: FAX: PROJECT: CONTACT: 10/18/2023DATE: PROJECT #: NOTES: 4931 Barnes, Soun (720) 201-6274Certified Balancing and Commissioning PO Box 620547 Littleton, CO 80162 GUCCI-ASPEN ASPEN, CO 81611 204 S. GALENA STREET Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Table Of ContentsPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. Table Of Contents 1 Air Handling Unit......................................................................................................................................................3 1.1 AC-1....................................................................................................................................................................3 1.2 AC-1/SPP-01......................................................................................................................................................4 1.3 AC-1/Main Pitot (Total).......................................................................................................................................5 1.4 AC-2....................................................................................................................................................................7 1.5 AC-2/SPP-01......................................................................................................................................................8 2 Fan Unit....................................................................................................................................................................10 2.1 EF-1....................................................................................................................................................................10 2.2 TEF-1..................................................................................................................................................................10 3 4931 GUCCIASPEN REPORT DWGS..pdf............................................................................................................11 3.1 M-100 Mechanical General Notes, Symbol & Abbreviation List 24x36-144 (1)..................................................11 3.2 M-101 Mechanical Schedules 24x36-144 (1).....................................................................................................11 3.3 M-102 Mechanical Specifications 24x36-144 (1)................................................................................................11 3.4 M-103 Mechanical Specifications 24x36-144 (1)................................................................................................11 3.5 M-200 Basement Mechanical Demolition Plan 24x36-144 (1)...........................................................................11 3.6 M-201 First Floor Mechanical Demolition Plan 24x36-144 (1)...........................................................................11 3.7 M-202 Roof Mechanical Demolition Plan 24x36-144 (1)....................................................................................11 3.8 M-300 Basement Mechanical Plan 24x36-144 (1).............................................................................................11 3.9 M-301 First Floor Mechanical Plan 24x36-144 (1).............................................................................................11 3.10 M-302 Mechanical Roof Plan 24x36-144 (1)....................................................................................................11 3.11 M-400 Mechanical Piping Plans 24x36-144 (1)................................................................................................11 3.12 M-500 Mechanical Details 24x36-144 (1).........................................................................................................11 3.13 M-501 Mechanical Details 24x36-144 (1).........................................................................................................11 Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 3 of 23 Air Handling UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. Tested By:Greg Barnes Date:10/13/2023 SYSTEM/UNIT: AC-1 Log:AC-1 10/17/2023 Greg Barnes FAN MIN SET AT 25 HZ MAX SET AT 51.8 HZ AC-1 10/13/2023 Greg Barnes ALL DIFFUSERS THAT COULD BE READ WITH VELGRID OR HOOD. ANY ONES NOT ABLE TO BE READ WERE CHECKED FOR DISCHARGE TEMP, DAMPERS WERE WIDE OPEN AND CFM WAS TAKEN FROM THE PITOT MINUS THE READABLE OUTLETS. Unit Data Unit Manufacturer TRANE Unit Model Number TWE09043BAA Unit Serial Number 22321946BA Design Airflow 3110 CFM Test Data Actual Airflow 3240 CFM Design Outside Airflow 500 CFM Actual Outside Airflow 530 CFM Test Pressures RF SP In 0.50 in. wc Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 4 of 23 Air Handling UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. Tested By:Greg Barnes Date:10/12/2023 SYSTEM/UNIT: AC-1/SPP-01 Test Pressures Supply Fan SP In -0.63 in. w.c. Supply Fan SP Out 0.58 in. w.c. DX Coil SP In NAC in. w.c. DX Coil SP Out -0.63 in. w.c. Filter SP In -0.33 in. w.c. Filter SP Out NAC in. w.c. Heating Coil SP In 0.58 in. w.c. Heating Coil SP Out 0.37 in. w.c. Static Pressure Profile Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 5 of 23 Air Handling UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. Tested By:Greg Barnes Date:10/12/2023 SYSTEM/UNIT: AC-1/Main Pitot (Total) Log:AC-1/Main Pitot (Total)10/11/2023 Greg Barnes FAN LAW 1 (1200 RPM @ 40 HZ) X 1.26 = 51.8 HZ AC-1/Main Pitot (Total)10/11/2023 Greg Barnes READING TAKEN @40 HZ Traverse Data Points Unit Data Type of Traverse Rectangular Duct Height 12.00 in. Duct Width 32.00 in. Insulation Width 1.00 in. Duct SQ. FT 2.67 sq. ft. Number Of Rows 4 Readings Per Row 8 Total Readings 32 Location of Holes 1 Top Location of Holes 2 Left Final Data Sum of Readings 30363 Average Reading 949 FPM Reading Std. Dev.238 FPM Design Total Flow 3200 CFM Actual Total Flow 2534 CFM Duct Static Press.0.43 in. wc Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 6 of 23 Air Handling UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. System/Unit Outlet Type Size LxW / D AK Factor Design Airflow Prelim Airflow % Prelim Diff. Final Airflow % Final Diff. Outlet-01 SR 8X6 1 150 350 233 155 103 Outlet-02 SR 8X6 1 200 420 210 210 105 Outlet-03 SG 48 1 200 280 140 210 105 Outlet-04 SG 48 1 200 230 115 215 108 Outlet-05 SG 24 1 100 105 105 Outlet-06 SG 24 1 100 105 105 Outlet-07 SG 24 1 100 105 105 Outlet-08 SG 24 1 100 105 105 Outlet-09 SG 24 1 100 105 105 Outlet-10 SG 42 1 190 195 103 Outlet-11 SG 42 1 190 195 103 Outlet-12 SG 42 1 190 195 103 Outlet-13 SG 24 1 100 105 105 Outlet-14 SG 24 1 100 105 105 Outlet-15 SG 36 1 250 230 92 255 102 Outlet-16 SG 24 1 110 120 109 Outlet-17 SG 36 1 250 245 98 250 100 Outlet-18 SG 24 1 120 130 108 Outlet-19 SG 36 1 250 255 102 255 102 Outlet-20 SG 24 1 110 120 109 Totals:---3110 2010 65 3240 104 AC-1 Supply Outlet Summary Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 7 of 23 Air Handling UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. Tested By:Greg Barnes Date:10/17/2023 SYSTEM/UNIT: AC-2 Log:AC-2 10/17/2023 Greg Barnes FAN MIN SET AT 25 HZ MAX SET AT 49.6 HZ AC-2 10/17/2023 Greg Barnes ALL DIFFUSERS THAT COULD BE READ WITH VELGRID OR HOOD. ANY ONES NOT ABLE TO BE READ WERE CHECKED FOR DISCHARGE TEMP, DAMPERS WERE WIDE OPEN AND CFM WAS TAKEN FROM THE PITOT MINUS THE READABLE OUTLETS. Unit Data Unit Manufacturer TRANE Unit Model Number TWE09043BAA Unit Serial Number 22321946BA Design Airflow 3284 CFM Test Data Actual Airflow 3450 CFM Design Outside Airflow 800 CFM Actual Outside Airflow 845 CFM Test Pressures RF SP In 0.50 in. wc Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 8 of 23 Air Handling UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. Tested By:Greg Barnes Date:10/17/2023 SYSTEM/UNIT: AC-2/SPP-01 Test Pressures Supply Fan SP In -0.58 in. w.c. Supply Fan SP Out 0.44 in. w.c. DX Coil SP In NAC in. w.c. DX Coil SP Out -0.58 in. w.c. Filter SP In -0.36 in. w.c. Filter SP Out NAC in. w.c. Heating Coil SP In 0.44 in. w.c. Heating Coil SP Out 0.33 in. w.c. Static Pressure Profile Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 9 of 23 Air Handling UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. System/Unit Outlet Type Size LxW / D AK Factor Design Airflow Prelim Airflow % Prelim Diff. Final Airflow % Final Diff. Outlet-01 SG 24 1 90 95 106 Outlet-02 SG 24 1 80 85 106 Outlet-03 SG 24 1 87 90 103 Outlet-04 SG 30 1 100 105 105 Outlet-05 SG 30 1 80 85 106 Outlet-06 SG 30 1 80 85 106 Outlet-07 SG 30 1 80 85 106 Outlet-08 SG 30 1 80 85 106 Outlet-09 SG 30 1 80 85 106 Outlet-10 CD 24X24 1 100 95 95 Outlet-11 CD 24X24 1 150 155 103 Outlet-12 CD 24X24 1 70 65 93 Outlet-13 CD 24X24 1 150 165 110 Outlet-14 CD 24X24 1 150 145 97 Outlet-15 CD 24X24 1 50 50 100 Outlet-16 SG 30 1 180 190 106 Outlet-17 SG 24 1 70 75 107 Outlet-18 CD 24X24 1 120 125 104 Outlet-19 SG 1 70 75 107 Outlet-20 SG 1 87 95 109 Outlet-21 SG 1 87 95 109 Outlet-22 SG 1 87 95 109 Outlet-23 SG 1 87 95 109 Outlet-24 SG 30 1 70 75 107 Outlet-25 SG 30 1 70 75 107 Outlet-26 SG 36 1 260 270 104 Outlet-27 SG 30 1 70 75 107 Outlet-28 SG 36 1 260 270 104 Outlet-29 SG 30 1 70 75 107 Outlet-30 SG 24 1 112 120 107 Outlet-31 87 95 109 Outlet-32 70 75 107 Totals:---3284 0 0 3450 105 AC-2 Supply Outlet Summary Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 10 of 23 Fan UnitPROJECT: LOCATION: GUCCI-ASPEN ASPEN, CO 4931PROJECT #: DATE: CONTACT: AUTHOR: 10/18/2023 Soun Barnes CBC REPORT DEPT. SYSTEM/UNIT: EF-1 Log:EF-1 10/17/2023 Greg Barnes TESTED ON TEMP POWER Unit Data Fan Manufacturer Greenheck Fan Model Number CSP-A700-VG Test Data Design ESP 0.20 in. wc Motor Data Rated Design Airflow 400 CFM Motor Hertz 60 Hz SYSTEM/UNIT: TEF-1 Log:TEF-1 10/17/2023 Greg Barnes TESTED ON TEMP POWER Unit Data Fan Manufacturer Greenheck Fan Model Number CSP-A390-VG Test Data Design ESP 0.80 in. wc Motor Data Rated Design Airflow 200 CFM Motor Hertz 60 Hz Certified Balancing and Commissioning “All I have in this world is my faith and my word, I don’t break them for anyone” Page 11 of 23 Page 12 of 23 Page 13 of 23 Page 14 of 23 Page 15 of 23 Page 16 of 23 Page 17 of 23 Page 18 of 23 10 11 12 13 14 15 2 Page 19 of 23 ? 1 2 3 4 5 6 7 8 9 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 1 2 1 20 Page 20 of 23 Page 21 of 23 Page 22 of 23 Page 23 of 23