Subject: PlanCheck
Page Label: 1
Author: linzhid
Color:
File Name: 90. 1265 Red Butte_Plans_STAMPED.pdf
Window spec sheets do not meet U-factor 0.28
requirement because it only provides the U-factor
of the glass.
Please provide new spec sheet of entire window
assembly that has a U-factor of 0.28 or better.
90. 1265 Red Butte_Plans_STAMPED.pdf (2)
Subject: PlanCheck
Page Label: 3
Author: linzhid
Color:
File Name: 90. 1265 Red Butte_Plans_STAMPED.pdf
Provide new detail to meet prescriptive table per
2015 IECC 402.1.2 stating R-49 insulation
requirement for ceilings
Window spec sheets
do not meet U-factor
0.28 requirement
because it only
provides the U-factor
of the glass.
Please provide new
spec sheet of entire
window assembly that
has a U-factor of 0.28
or better.
Provide new detail to meet prescriptive table
per 2015 IECC 402.1.2 stating R-49 insulation
requirement for ceilings