HomeMy WebLinkAboutFile Documents.901 E Hyman Ave.0009-2022-BRES (6)
Property Address
901 E Hyman Ave. #5
Aspen, CO 81611
Element Environmental Project#:
SH Built 110121 Hyman
Client Job Name
Hyman Ave.
TABLE OF CONTENTS
1.0 - Scope of Work
2.0 - Sampling Requirements
3.0 - Sampling Methodology
4.0 - Laboratory
5.0 - Suspect Materials Sampled
6.0 - Table of Results
7.0 - Description of Sampling Area
8.0 - Conclusion
9.0 - Lab Report
10.0 - Certificates
Asbestos Samples Analyzed: 20
Positive Asbestos Samples: 9
___________________________________________________
AS
B
E
S
T
O
S
L
E
A
D
HA
Z
M
A
T
RE
S
T
O
R
A
T
I
O
N
ww
w
.
e
l
e
m
e
n
t
co
n
s
u
l
t
s
.c
o
m
Asbestos Sampling Report
Date: 11/03/2021
Date of Inspection: 11/01/2021
Client:
SH Built
314 AABC Suite B
Aspen, CO 81611
Attn:
Tom Sherlock
Building Inspector:
Ellen Johnson
CDPHE #23799
Joshua Johnson
CDPHE #18401
189 County Rd. 135
Glenwood Springs, CO 81601
josh@elementconsults.com
(970) 274-3139
01/20/2022
Project #-SH Built 110121 Hyman
2
1.0- This was an inspection for suspect ACM (Asbestos Containing Material) for a remodel.
Element Environmental conducted a visible inspection for visible materials that would
be impacted during the remodel. This inspection was limited to the areas found in the
Description of the Sampling Area 7.0. Although sampling is destructive in nature, this
was a non-invasive inspection. It was of materials that were accessible. If other suspect
materials become visible/apparent during demolition or construction activities, work in
that area should be halted and more sampling/testing must take place, per Colorado
regulations. Any suspect materials that were not tested are to be assumed to contain
asbestos.
2.0- A limited bulk sampling of from all suspect materials was conducted in accordance with
Colorado State Requirements. The minimum number of samples per homogenous areas
are as follows:
2.1- Surfacing Materials- <1,000 sq.ft.- Minimum of 3 samples
1,000 sq.ft.- 5,000sq.ft.- Minimum of 5 samples
>5,000 sq.ft. Minimum of 7 samples
2.2- Miscellaneous materials- Minimum of 2 samples
2.3- Thermal Systems Insulation (TSI)- Minimum of 3 samples
3.0- The purpose of the inspection is to identify materials that are homogenous. A
homogeneous area is defined as one which shares suspect material, texture, color,
location, and/or apparent time of construction. The materials are touched to determine
friability. Friable ACM is material that can be crushed or reduced to powder by hand
pressure. The friable materials are segregated into separate homogenous areas. The size
of the sampling area is determined. Samples are taken according to a random numerical
sequence of the subareas, following guidelines per the EPA Pink Book: Asbestos in
Buildings: Simplified Sampling Scheme for Friable Surfacing Materials.
4.0- Ellen Johnson, a Colorado Department of Public Health & Environment certified building
inspector, certification number: 23799, performed the inspection. The findings were
reviewed by Josh Johnson, a Colorado Department of Public Health & Environment
certified building inspector, certification number: 18401. Samples taken were sent to
CEI Labs in Cary, North Carolina. The samples were analyzed by PLM (Polarized Light
Microscopy) analysis. Per the CDPHE Regulation any sample that is found by a lab to be
trace, or <1% asbestos, is considered to be ACM material. This material would still be a
regulated material by CDPHE. The sample must have an additional “point count”
performed to be considered less than 1% and not be regulated by the CDPHE. The lab’s
documents with analyses and findings are found below.
01/20/2022
Project #-SH Built 110121 Hyman
3
5.0- SUSPECT MATERIALS SAMPLES
• Texture
• Drywall System
• Joint Compound
• Tape
• Carpet and Pad
• Tile Grout
• 12 x 12 Floor Tile and Mastic
6.0- TABLE OF RESULTS
HOMOGENOUS
AREA
DESCRIPTION OF AREA ACM CATEGORY NUMBER
OF
SAMPLES
APPROXIMATE
SQ.FT.*
ACM ASSESSMENT CATEGORIES
% AND TYPE OF
ASBESTOS FOUND
(A) Skip Trowel Texture in Bath Surfacing
3 ~600 sq.ft. Friable Non-ACM No Asbestos Detected
(B) Drywall System in Bath Miscellaneous 2 ~600 sq.ft. Friable Non-ACM No Asbestos Detected
(C) Light Roll Texture throughout
unit except bath
Surfacing 5 ~1,680 sq.ft. No. 5 – ACM with potential for
damage
2% Chrysotile in 5 of 5
Samples
(D) Drywall System for Light Roll
Texture
Miscellaneous 2 ~1,680 sq.ft. No. 5 – ACM with potential for
damage
2% Chrysotile in 2 of 2
Samples
(E) 12 x 12 Tile and Mastic in Hall
Closet
Miscellaneous 2 ~120 sq.ft. Non- Friable Class 1 OSHA material 2%-3% Chrysotile in 2 of 2
Samples
(F) Carpet Miscellaneous 2 ~400 sq.ft. Non-Friable Non-ACM No Asbestos Detected
(G) Carpet Pad Miscellaneous 2 ~400 sq.ft. Non-Friable Non-ACM No Asbestos Detected
Key:
ACM Assessment Categories:
1- Damaged or significantly damaged Thermal Systems Insulation
(TSI) ACM
2- Damaged friable surfacing ACM
3- Significantly damaged friable Surfacing ACM
4- Damaged or significantly damaged friable Miscellaneous ACM
5- ACM with potential for damage
6- ACM with potential for significant damage
7- Friable ACM with low potential for damage
Other- ACM not classified in the above Assessment Categories
N/A- Not Applicable
* Square footage is estimated and not for bidding purposes
01/20/2022
Project #-SH Built 110121 Hyman
4
7.0- DESCRIPTION OF SAMPLING AREA
• Skip Trowel Texture in Bath
• Drywall System for skip trowel texture in bath
• Light Roll Texture throughout the unit except for bath
• Drywall System for the light roll texture
• 12 x 12 Tile and Mastic in Hall Closet and possibly under the cork floor in kitchen and
entry. We were unable to sample under the cork floor without causing damage but
could see edge of what appeared to be tile.
• Carpet and Pad in bedroom and living room
01/20/2022
Project #-SH Built 110121 Hyman
5
Sampling Locations
N
NTS
01/20/2022
Project #-SH Built 110121 Hyman
6
8.0- CONCLUSION
The areas on the Table of Results in Black did not contain asbestos.
The areas on the Table of Results in Red contains asbestos:
• The Light Roll Texture throughout the unit except for the bath
• The Drywall System of the Light Roll Texture
These materials become friable when they are removed. If these materials are to be disturbed or removed, the
materials MUST be remediated in accordance with the CDPHE Regulation No. 8 by a licensed abatement
contractor. For residential projects over 32 square feet of surfacing material, 50 linear feet of pipe insulation, or 55
gallon drum of waste; and for commercial projects with 160 square feet of surfacing material, 260 linear feet of
pipe insulation, or a 55 gallon drum of waste, a permit is required. The permit is through the CDPHE. Along with
the permit, a final air clearance is required by a certified Air Monitoring Specialist. For projects over 3,000 square
feet, a Project Design and Project Manager is required. Element Environmental is certified and can perform Final
Clearances, Project Design, and Project Management if required. All work performed MUST follow all EPA, State
Regulation 8, and OSHA regulations to protect the general public, the client, and the workers.
• The 12 x 12 Tile and Mastic in the entry closet and possibly under the cork floor in the
entry and kitchen
These materials are considered non-friable. If the tile and mastic will be rendered friable by mechanical means,
then the removal of them is regulated by the CDPHE. If not, then the removal of them is regulated by OSHA. You
must consult your landfill to see if they will accept them and how they must be prepared. They may need to be
segregated from the other materials so that the landfill may accept them. Element Environmental recommends
that an abatement contractor remove these materials to ensure that the workers are trained and that the
materials are handled correctly.
Sincerely,
Ellen Johnson
01/20/2022
Project #-SH Built 110121 Hyman
7
9.0- LAB REPORT
01/20/2022
Project #-SH Built 110121 Hyman
8
01/20/2022
Project #-SH Built 110121 Hyman
9
01/20/2022
Project #-SH Built 110121 Hyman
10
01/20/2022
Project #-SH Built 110121 Hyman
11
01/20/2022
Project #-SH Built 110121 Hyman
12
01/20/2022
Project #-SH Built 110121 Hyman
13
01/20/2022
Project #-SH Built 110121 Hyman
14
01/20/2022
Project #-SH Built 110121 Hyman
15
10.0- CERTIFICATES
01/20/2022