Loading...
HomeMy WebLinkAboutFile Documents.1012 E Cooper Ave.0131-2020-BRES (4)Ernest Kollar Engineers, Inc. 320 Main St., Suite 203 Carbondale, CO 81623 Phone (970) 963-3223 erniekollar@gmail.com September 17, 2021 To: Simon Bentley Crawford Design and Build Re: 1012 E Cooper, Unit 4, Aspen, CO Simon: It appears from the photos you submitted the three issues mentioned in the September 9th letter to the building department have been adequately addressed. They are copied below for reference: 1. The loft framing and header over the pocket door is adequate as framed assuming there are at least (4) 16d nails at 16” o.c. attaching the ledger to the stud framing at the north and south sides of the loft. 2. The new window on the north wall will need a new header, (2-2x6 minimum – oriented vertically) at or below the loft height. Fasten the existing loft ledger to the header with 4-16d nails at 16” o.c. or (2) Ledger-lok screws at 16” o.c.. Provide at least one trimmer for each end of the header. 3. Along the south wall, where the existing door was replaced, the left header support appears questionable. There should be a header between the upper window and new glass door to resist lateral wind loads. As a minimum, the header should be at least 2-2x4 oriented flat or 2-2x6’s oriented vertically. Each end of the header should be supported with at least one trimmer nailed to the king studs. The king studs should be continuous to the roof. Additional observation holes may be required to verify this condition. Thank you, Ernest Kollar Ernest Kollar, PE Ernest Kollar Engineers, Inc. O LIDCAERNOSL EO DC P R R E O E F N E ISGSNIOE N LA UL A K OP LT LS AE RN R IIE27036 Ernest Koll a r 09/17/202 1