Subject: PlanCheck
Page Index: 2
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 2
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:29:06 AM
Creation Date: 2/3/2021 11:28:04 AM
X: 23.1658 in
Y: 1.6616 in
Document Width: 2.5402 in
Document Height: 15.6930 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
It appears that this dwelling
separation wall could be
impacted. Provide a listed 1 hour
fire and STC 50 sound rated
assembly on the plans for use in
patching/replacing the
membrane on the unit side of the
wall. 2015 IBC 420
90.Architectural Plans.20201104.pdf (8)
Subject: PlanCheck
Page Index: 2
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 2
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:31:42 AM
Creation Date: 2/3/2021 11:30:36 AM
X: 16.5940 in
Y: 15.0720 in
Document Width: 1.7500 in
Document Height: 2.1181 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
New plumbing penetrations must
be protected where they
penetrate the membrane (gyp or
floor sheathing) of the fire rated
dwelling separation wall or floor
per 2015 IBC 714. Note this
requirement on the plans.
It appears that thisdwelling separationwall could beimpacted. Provide alisted 1 hour fire andSTC 50 sound ratedassembly on the plansfor use inpatching/replacing themembrane on the unitside of the wall. 2015IBC 420
New plumbing
penetrations must be
protected where they
penetrate the
membrane (gyp or
floor sheathing) of the
fire rated dwelling
separation wall or floor
per 2015 IBC 714.
Note this requirement
on the plans.
Subject: PlanCheck
Page Index: 3
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 3
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:33:11 AM
Creation Date: 2/3/2021 11:32:11 AM
X: 23.2036 in
Y: 2.4369 in
Document Width: 1.7500 in
Document Height: 1.5431 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
Exhaust fan required to be
provided in the bathroom. Show
on the plans and indicate
termination location dimensioned
from openings (if new).
Ordinance 40, 2016
Subject: Smoke Alarms
Page Index: 3
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 3
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:39:38 AM
Creation Date: 2/3/2021 11:39:12 AM
X: 20.1189 in
Y: 16.8375 in
Document Width: 4.7404 in
Document Height: 0.2014 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
Provide a carbon monoxide
detector per Municipal Code
Title 8.
Exhaust fan required
to be provided in the
bathroom. Show on
the plans and indicate
termination location
dimensioned from
openings (if new).
Ordinance 40, 2016
Provide a carbon monoxide detector per Municipal Code Title 8.
Subject: PlanCheck
Page Index: 4
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 4
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:29:26 AM
Creation Date: 2/3/2021 11:24:10 AM
X: 23.6545 in
Y: 6.3431 in
Document Width: 8.1269 in
Document Height: 3.5212 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
New floor/ceiling assembly must
be 1 hour fire rated as this
building is of type VA
construction. 2015 IBC 601. The
hatch does not require a fire
rating. Provide a listed 1 hour
fire rated assembly printed on
the plans.
Subject: PlanCheck
Page Index: 4
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 4
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:29:42 AM
Creation Date: 2/3/2021 11:19:25 AM
X: 3.1214 in
Y: 3.0316 in
Document Width: 10.2609 in
Document Height: 2.1772 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
Flooring underlayment providing
an IIC sound rating of 50 or
greater required by 2015 IBC
1207. Note this and provide a
spec.
New floor/ceiling
assembly must be 1
hour fire rated as this
building is of type VA
construction. 2015 IBC
601. The hatch does
not require a fire
rating. Provide a listed
1 hour fire rated
assembly printed on
the plans.
Flooring underlayment
providing an IIC sound
rating of 50 or greater
required by 2015 IBC
1207. Note this andprovide a spec.
Subject: PlanCheck
Page Index: 4
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 4
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:35:36 AM
Creation Date: 2/3/2021 11:33:26 AM
X: 15.8596 in
Y: 2.1814 in
Document Width: 1.7500 in
Document Height: 2.1181 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
Exposed roof framing cavity
must be filled with insulation or
insulated to R49. If the roof is
vented, maintain venting. If
unvented, insulation should be
vapor impermeable. Indicate on
the plans. 2015 IECC R503.1.1
Subject: PlanCheck
Page Index: 4
Author: nickt
Color:
File Name: 90.Architectural Plans.20201104.pdf
Page Label: 4
Lock: Unlocked
Checkmark: Unchecked
Date: 2/3/2021 11:38:37 AM
Creation Date: 2/3/2021 11:37:51 AM
X: 26.0594 in
Y: 2.9738 in
Document Width: 4.1183 in
Document Height: 3.1273 in
Length: 0
Width: 0
Height: 0
Rise/Drop: 0
Unit: Count
Area: 0
Wall Area: 0
Volume: 0
Count: 0
Measurement: 1
Capture: No
Indicate the location of exhaust
and combustion air venting
termination(s) for the new water
heater. Dimension termination
from openings and property
lines. 2015 IMC 501.3.1
Exposed roof framing
cavity must be filled
with insulation or
insulated to R49. If the
roof is vented,
maintain venting. If
unvented, insulation
should be vapor
impermeable. Indicate
on the plans. 2015
IECC R503.1.1
Indicate the location of
exhaust and
combustion air venting
termination(s) for the
new water heater.
Dimension termination
from openings and
property lines. 2015
IMC 501.3.1